Loading...
Specifications • TES Z o1? - OOoR3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 7/15/2013 C: \HASS74\ARLINGTON119 . SDF JOB TITLE: Arlington Heights Lot # 119 k2(01_{ 1 C -io , r d� WATER SUPPLY DATA w�� (( , SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ' D RECEIVED NODE PRESS . PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) JUL 16 2013 8 118 . 0 54 . 0 12 3 0.0 117 . 9 27 . 2 6 0 . 3 Crty oFTIGARD BUILDING DIVISION AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 27 . 2 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0. 0 GPM OTHER HOSE STREAM ALLOWANCES 0. 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 27 .2 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 9 . 0 K= 4 . 90 7 . 0 13. 0 2 9 . 0 K= 4 . 90 8 . 4 14 . 2 3 9 . 5 - - - - 10 . 2 - - - 4 19 . 0 - - - - 29 . 2 - - - 5 8 . 0 - - - - 40 . 1 - - - 6 1 . 0 - - - - 44 . 5 - - - 7 1 . 0 - - - - 48 . 5 - - - - 8 0 . 0 SOURCE 60. 3 27 . 2 • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 7/15/2013 C: \HASS74\ARLINGTON119. SDF JOB TITLE: Arlington Heights Lot # 119 PIPE DATA • PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL (FPS) HW (C) (FT) SUM. • NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13 . 0 0 . 874 PL 11 . 00 PF 1 . 4 1 9 . 0 4 . 9 7 . 0 13 . 0 6. 9 150 FTG ET PE 0. 0 2 9. 0 4 . 9 8 . 4 14 .2 0. 094 TL 15 . 35 PV Pipe: 2 -27 . 2 0 . 874 PL 4 . 00 PF 1 . 9 2 9 . 0 4 . 9 8 . 4 14 .2 14 . 5 150 FTG E PE -0 . 2 3 9 . 5 0 . 0 10.2 0 .0 0 . 370 TL 5 . 24 PV Pipe: 3 -27 . 2 0 . 874 PL 49 . 00 PF 23.2 3 9. 5 0 . 0 10.2 0 .0 14 . 5 150 FTG E4T PE -4 . 1 4 19.0 0 . 0 29. 2 0 . 0 0. 370 TL 62 . 67 PV Pipe: 4 -27 . 2 0 . 874 PL 14 . 00 PF 6. 1 4 19 . 0 0. 0 29. 2 0.0 14 . 5 150 FTG 2E PE 4 . 8 5 8 . 0 0 . 0 40. 1 0 . 0 0 . 370 TL 16. 49 PV Pipe: 5 -27 .2 1 . 080 PL 7 . 00 PF 1 . 4 5 8 . 0 0 . 0 40. 1 0. 0 9. 5 120 FTG ---- PE 3 . 0 6 1 . 0 0. 0 44 . 5 0. 0 0 . 199 TL 7 . 00 PV Pipe: 6 FIXED PRESSURE LOSS DEVICE 7 1 . 0 0 . 0 48 . 5 0 .0 4 . 0 psi, 27 . 2 gpm 6 1 . 0 0 . 0 44 . 5 0 . 0 • Pipe: 7 -27 . 2 1 . 101 PL 94 . 00 PF 11 . 3 7 1 . 0 0. 0 48 . 5 0. 0 9 . 2 150 FTG ---- PE 0 . 4 8 0 . 0 SRCE 60. 3 (N/A) 0 . 120 TL 94 . 00 PV NOTES : (1) Calculations were performed by the HASS 7 . 4 computer program under license no. 5010113212 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0. 001 gpm and a maximum imbalance at any node of 0. 006 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14 . 5 ft/sec at pipe 3 . - (4) PIPE FITTINGS TABLE Pipe Table Name : STANDARD. PIP • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 7/15/2013 C: \HASS74\ARLINGTON119 . SDF JOB TITLE: Arlington Heights Lot # 119 PAGE: * MATERIAL: S40 HWC: 120 . Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NPTee 0 . 874 0 . 82 2 . 06 0 . 82 2 . 06 2 . 47 0 . 41 4 . 11 4 . 11 2 . 06 1 . 080 2 . 30 5 . 76 2 . 30 5 . 76 6. 91 1 . 15 11 . 52 11 . 52 5 . 76 1 . 101 2 . 53 6. 33 2 . 53 6. 33 7 . 59 1 . 27 12 . 66 12 . 66 6. 33 • O CU H ti WATER SUPPLY ANALYSIS t-3 140.0 Static: 118.00 psi Resid: 54 .00 psi Flow: 1230. 0 gpm y m .. (-„ LEGEND > 1\) 1-i 1--■ 1 1 Available pressure 117.94 psi @ 27.2 gpm �* G112.0 _ 2 Required pressure 0 A 60.26 psi @ 27.2 gpm x ro m U r H G Z rt� x E r u r' p o to R 84.0 * H E t.1 S x S w x K U 0 R 2 j c E 56.0 • P - 2 s x �•�t i m Ul ) U] U1 28.0 _ H z G) O z 0.0 ro t.0 a cnm O ro � -14.7 f i 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) Fire Suppression 8r Bud ding Products • tLJCO rapid response Technical Services 800-381-9312 I+1-401-781-8220 HOME FIRE SPRINKLER SYSTEM www.tyco-fire.com Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General The Series LFII Residential Flat-Plate Concealed Pendent Sprinkler has a 4.9 Description (60,5)K-factor that provides the required residential flow rates at reduced pres- - The TYCO RAPID RESPONSE Series sures,enabling smaller pipe sizes and .. ..,4••,,,,,_ LFII Residential Flat-Plate Concealed water supply requirements. '. 5, ° Pendent Sprinklers(TY2524)are decora- This sprinkler has been designed with "' tive,fast response,fusible solder sprin- heat sensitivity and water distribution „, °” '-,,,,, klers designed for use in residential oc- characteristics proven to help in the con- . °4 cupancies such as homes, apartments, __ =-';=' dormitories,and hotels. trot of residential fires and to improve ~ �:": the chance for occupants to escape or The Cover Plate/Retainer Assembly con- be evacuated. ' ' t^ ''.,. ceals the sprinkler operating compo- F ,. ;`.' ;iii '•;. r.A.i'' ' ' The Series LFII Residential Flat-Plate � � •4 nents above the ceiling.The flat profile Concealed Pendent Sprinklers are of the Cover Plate provides the optimum shipped with a Disposable Protective aesthetically appealing sprinkler design. Cap.The Protective Cap protects the Additionally,the concealed design of the sprinkler during ceiling installation or _=Series_LFU Residential-Flat-Plate Con-.—finish:=After ceiling°installation=is corn-`__- Technical-- --- cealed Pendent Sprinklers provides 1/2 plete, the Protective Cap is removed inch(12,8 mm)vertical adjustment.This and the Cover Plate/Retainer Assem- Data adjustment provides a measure of flex- bly is installed. Removing the Protec- ibility when cutting fixed pipe drops. tive Cap is required for proper sprinkler Approvals • The Series LFiI Residential Flat-Plate performance. UL and C-UL Listed Concealed Pendent Sprinklers are in- NSF-61 Certified tended for use in the following systems: NOTICE The Series LFII Residential Flat-Plate • per NFPA 13D, wet pipe residential The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only sprinkler systems for one- and two- Concealed Pendent Sprinklers(TY2524) listed with the Series LFII Concealed family dwellings and mobile homes; described herein must be installed and Cover Plates having a factory-applied • per NFPA 13R, wet pipe residential maintained in compliance with this doc- finish. ument and with th sprinkler systems for residential oc- the applicable standards cupnkler s up to and including four of the National Fire Protection Associa- Maximum Working Pressure stories in height;and tion,in addition to the standards of any 175 psi(12,1 bar) authorities having jurisdiction. Failure Discharge Coefficient •per NFPA 13,wet pipe sprinkler sys- to do so may impair the performance K=4.9 GPM/psi''(70,6 LPM/bar1'2) tems for the residential portions of of these devices. any occupancy. Owners are responsible for maintaining Temperature Rating their fire protection system and devices Sprinkler: 160°F(71°C) in proper operating condition. The in- Cover Plate: 139°F(59°C) IMPORTANT stalling contractor or sprinkler manu- Vertical Adjustment Always refer to Technical Data facturer should be contacted with any 1/2 inch (12,7 mm) Sheet TFP700 for the 'INSTALLER questions. WARNING" that provides cautions Finishes with respect to handling and instal- Model/Sprinkler Refer to the Ordering Procedure lation of sprinkler systems and corn- section. ponents. Improper handling and in- Identification Ph si stallation can permanently damage y 'cal Characteristics a sprinkler system or its components • Cover Plate/Retainer Assembly: • and cause the sprinkler to fail to Number (SIN) • Cover Plate Copper operate in a fire situation or cause it TY2524 Ejection Spring . . . . Stainless Steel to operate prematurely. Retainer Brass Page 1 of 6 OCTOBER 2010 TFP443 TFP443 Page 2 of 6 Horizontal Ceiling Sloped Ceiling Sloped Ceiling Minimum Flowrbrand Minimum Flowrbrand Minimum Flowrbrand Residual Pressure Residual Pressure Residual Pressure Maximum Maximum (Maximum 2-inch rise (Greater than 2-inch rise (Greater than 4-inch rise Coverage Spacing for 12-inch run) up to maximum 4-inch up to maximum 8-inch Area nr rise for 12-inch run) rise for 12-inch run) 160°F(71°C) 160°F(71°C) 160°F(71°C) Sprinkler Sprinkler Sprinkler 12'x 12' 12' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (3,7 m x 3,7 m) (3,7 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 14'x 14' 14' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,3 m x 4,3 m) (4,3 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 16'x 16' 16' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,9 m x 4,9 m) (4,9 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 18'x 18' 18' 17 GPM(64,3 LPM) 22 GPM(83,3 LPM) 22 GPM(83,3 LPM) (5,5 m x 5,5 m) (5,5 m) 12.0 psi(0,83 bar) 20.2 psi(1,39 bar) 20.2 psi(1,39 bar) 20'x 20' 20' 20 GPM(75,7 LPM) 24 GPM(90,8 LPM) 24 GPM(90,8 LPM) (6,1 m x 6,1 m) (6,1 m) 16.7 psi(1,15 bar) 24.0 psi(1,65 bar) 24.0 psi(1,65 bar) (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b)The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler,The associated residual pressures_ are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. TABLE A SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS • Sprinkler/Support Cup Assembly: Design For systems designed to NFPA 13, the Body Brass ______number of design sp r1[]kleCS_is_to_be_____ .. _. _ Cap Bronze------ - -the four most hydraulically demandin Saddle Brass Criteria y y g"-- - - Saddl Assembly sprinklers.The minimum required dis- Sealing y • .. .. . .Beryllium The TYCO RAPID RESPONSE Series charge from each of the four sprinklers Nickel w/Teflon' LFII Residential Flat-Plate Concealed is to be the greater of the following: • • Soldered Link Halves Bronze Pendent Sprinklers (TY2524) are UL •flow rates given in Table A for NFPA Lever and C-UL Listed for installation in ac- Compression Screw Brass cordance with the following criteria. er and 13R as a f o - Deflector Bronze pature rating and thhe e maximum maximuu m a all- Guide Pin Housing Bronze NOTICE towable coverage area Guide Pins Bronze • minimum discharge of 0.1 GPM/ Support Cup Steel When conditions exist that are outside sq. ft. over the "design area" corn- the scope of the provided criteria, re- prised of the four most hydraulically fer to the Residential Sprinkler Design demanding sprinklers for actual cov- Operation Guide TFP490 for the manufacturer's erage areas protected by the four recommendations that may be accept- sprinklers When exposed to heat from a fire,the able to the Authority Having Jurisdiction. Cover Plate, which is normally soldered The Series LFII Residential Flat-Plate Obstruction To Water Distribution to the Retainer at three points,falls away Concealed Pendent Sprinklers must Locate sprinklers in accordance with the to expose the Sprinkler/Support Cup As- obstruction rules of NFPA for residential to expo.At this point,the Deflector,sup- not be used in applications where the p- sprinklers as well as obstruction criteria air pressure above the ceiling is greater ported by the Guide Pins, drops down than that below. Down drafts through described within TYCO technical data to its operated position. g sheet TFP490. the Support Cup can delay sprinkler op- The Solder Link Element of the Sprinkler/ eration in a fire situation. Operational Sensitivity Support Cup Assembly is comprised of Install sprinklers relative to the ceilin two link halves that are soldered togeth- System Type g er with a thin layer of solder. When the Only wet pipe systems may be utilized, mounting surface as shown in Figure 3. rated temperature is reached, the sot- Sprinkler Spacing der melts and the two link halves se a- Hydraulic Design p Table A provides the minimum required The minimum spacing between sprin- rate, allowing the sprinkler to activate klers is 8 feet(2,4 m). and flow water. sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R as a function The maximum spacing between sprin- • of temperature rating and the maximum klers cannot exceed the length of the allowable coverage areas.The sprinkler coverage area(Table A) being hydrau- flow rate is the minimum required dis- lically calculated;for example, a maxi- charge from each of the total number of mum of 12 feet for a 12 ft.x 12 ft. coy- 1 Registered trademark of Dupont "design sprinklers"as specified in NFPA erage area or 20 feet for a 20 ft.x 20 ft. 13D or NFPA 13R. coverage area. TFP443 Page 3 of 6 BODY 7 /` SEALING (1/2' NPT) /r ASSEMBLY CAP I //�' ��I/�I� l'i/ i��. SPRINKLER F r�-viir- j WRENCHING SADDLE 1 If ,?`` '; I AREA a' ;: `W; SUPPORT JIiIIiiI COMPRESSION ROLL FORMED THREADS I �_ LEVER WRENCH c Lt, ,, „ � RECESS GUIDE 1 'r_�' t SOLDER LINK 1�� ou"1 II ELEMENT �� HOUSING I i 1 1 I ...1 - i DEFLECTOR ' -`� I (OPERATED PUSH WRENCH DEFLECTOR 1 --z---- - -1 I POSITION) IN TO ENSURE I SPRINKLER/SUPPORT CUP ENGAGEMENT ASSEMBLY I WITH SPRINKLER I I WRENCHING AREA THREAD INTO I I RETAINER SUPPORT CUP I ) WITH THREAD UNTIL MOUNTING J 1 DIMPLES FIGURE 2 SURFACE IS , 0 O I, W-TYPE 18 FLUSH WITH J EJECTION SPRINKLER WRENCH - -- ------- - - —CEILING-- __ -- ---------------- ----- ----—... _..-- SPRING--------- ---- - - - SOLDER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE • FIGURE 1 . FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) ASSEMBLY 2-1/2'DIA. SPRINKLER- (63,5 mm) 1/2"(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING / OPERATED a �L__ �� SPRINKLER COVER • =it �� 1-7/8't1/8' PLATE (47,6 mm _ IS 1/8'GAP t3,2 mm) RETAINER I, (3.2 mm) !fl!_ ill I111. _.11 j 1 MEE M I_ =r COVER- SPRINKLER- 7/8"(22,2 mm) I 3/16' RETAINER SUPPORT CUP J MOUNTING SURFACE ING 1-1/8"(28,6 mm) ASSEMBLY ASSEMBLY (4,8 mm) - 3-3/16"DIA. DISPOSABLE DEFLECTOR IN • (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 PROTECTIVE CAP AND ACTIVATED DEFLECTOR INSTALLATION DIMENSIONS TFP443 Page 4 of 6 Installation 6. Screw on the Cover Plate/Retainer Replace sprinklers that: Assembly until its flange contacts The TYCO RAPID RESPONSE Series the ceiling. •were damaged by dropping, striking, • LFII Residential Flat-Plate Concealed Do not continue to screw on the wrench twisting, wrench slippage, or Pendent Sprinklers must be installed Cover Plate/Retainer Assembly such the like. in accordance with the following that it lifts a ceiling panel out of its • were modified or over-heated. instructions. normal position. • are leaking or exhibiting visible signs NOTICE If the Cover Plate/Retainer Assembly of corrosion. cannot be engaged with the Mounting Responsibility lies with owners for the Damage to the Solder Link Element dur- Cup or the Cover Plate/Retainer As- inspection,testing, and maintenance of ing installation can be avoided by han- sembly cannot be engaged sufficiently their fire protection system and devices dling the sprinkler by the Support Cup to contact the ceiling,the Sprinkler in compliance with this document, as only,•that is, do not apply pressure to the Fitting must be repositioned. well as with the applicable standards of Solder Link Element(Figure V. the National Fire Protection Association Obtain a leak-tight 1/2 inch NPTsprinkler Care and (for example, NFPA 25), in addition to joint by applying a minimum-to-maxi- the standards of any other authorities mum torque of 7 to.14 ft.-lbs. (9,5 to 19,0 Maintenance having jurisdiction.Contact the install- Nm). Higher levels of torque can distort ing contractor or sprinkler manufacturer the sprinkler inlet with consequent leak- The TYCO RAPID RESPONSE Series regarding any questions. age or impairment of the sprinkler. LFII Residential Flat-Plate Concealed Automatic sprinkler systems are rec- Pendent not attempt to compensate for in- Pendent Sprinkler (TY2524) must be p p maintained and serviced in accordance o and maintained to be inspected, tested, sufficient adjustment in the Cover Plate/ and maintained by a qualified - Retainer Assembly by under-or over- with the following instructions. tion Service in accordance with th local tightening the sprinkler.Re-adjust the requirements and/or national codes. position of the sprinkler fitting to suit. NOTICE 1. Install pendent sprinklers in the Before closing a fire protection system pendent position, with the center- main control valve for maintenance work line of the sprinkler perpendicular on the fire protection system that it con- to the mounting surface. trols,obtain permission to shut down the affected fire protection system from the 2. Remove the Protective Cap. proper authorities and notify all person- 3. With pipe-thread sealant applied nel who may be affected by this action. • _ _ _ to the_pipe_tbreads,__and_using the___SNhenprnperlylnstalled,-there-is-a-nomi-•--- _-------___._ _ ..._______... W-Type 18 Wrench shown in Figure nal 1/8 inch(3,2 mm)air gap between - -- - - -' - - -- - 2, install and tighten the Sprinkler/ the lip of the Cover Plate and the cell- - Support Cup Assembly into the fit- ing,as shown in Figure 3.This air gap ting. The W-Type 18 Wrench ac- is necessary for proper operation of the • cepts a 1/2 inch ratchet drive. sprinkler by allowing heat flow from a 4. Replace the Protective Cap by fire to pass below and above the Cover pushing It upwards until it bottoms Plate to help assure appropriate release • out against the Support Cup. The of the Cover Plate in a fire situation.If the Protective Cap helps prevent dam- ceiling needs repainting after sprinkler age to the Deflector and Guide installation,exercise care to ensure that Pins during ceiling installation and/ the new paint does NOT seal off any of or during application of the finish the air gap. Failure to do so may impair ' coating of the ceiling. sprinkler operation. Absence of a Cover Plate can delay the NOTICE sprinkler operation in a fire situation. As long as the protective Cap re- Do not pull the Cover Plate relative to mains in place, the system is con- the Enclosure.Separation may result. sidered"Out Of Service". Exercise care to avoid damage to sprin- 5. After the ceiling has been corn- klers before, during,and after installa- pleted with the 2-1/2 inch (63 mm) tion.Never paint, plate, coat, or other- diameter clearance hole and in wise alter automatic sprinklers after they preparation for installing the Cover leave the factory. Plate/Retainer Assembly, remove Never repaint factory-painted Cover and discard the Protective Cap, Plates.When necessary,replace cover and verify that the Deflector moves plates with factory-painted units. Non- up and down freely. factory applied paint can adversely de- If the Sprinkler has been damaged lay or prevent sprinkler operation in the and the Deflector does not move up event of a fire. and down freely, replace the entire • Sprinkler assembly.Do not attempt to modify or repair a damaged sprinkler. • • TFP443 Page 5 of 6 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression & Building Products ability. When placing an order, indicate (TFSBP)are warranted solely to the orig- the full product description and Part inal Buyer for ten(10)years against de- Number(P/N). fects in material and workmanship when paid for and properly installed and main- Sprinkler/Support Cup Assembly tained under normal use and service. Specify: Series LFII Residential Flat- This warranty will expire ten (10)years Plate Concealed Pendent Sprinkler from date of shipment by TFSBP. No (TY2524), K=4.9,without Cover Plate/ warranty is given for products or com- Retainer Assembly,P/N 51-114-1-160. ponents manufactured by companies Cover Plate/Retainer Assembly • not affiliated by ownership with TFSBP Specify: Cover Plate/Retainer Assem- or for products and components which bly with finish (below) for the Series have been subject to misuse, improper LFII Residential Flat-Plate Concealed installation,corrosion,or which have not Pendent Sprinkler(TY2524),K=4.9, P/N been installed,maintained, modified or (below): repaired in accordance with applicable Standards of the National Fire Protection Chrome P/N 56-201-9-135 Association,and/or the standards of any Custom P/N 56-201-X-135 other Authorities Having Jurisdiction. Off white Materials found by TFSBP to be defec- tive shall be either repaired or replaced, Pure White' at TFSBP's sole option. TFSBP neither (RAL 9010) P/N 56-201-3-135 assumes, nor authorizes any person to Signal White" assume for it, any other obligation in • (RAL 9003) P/N 56-201-4-135 connection with the sale of products or Standard White(Grey White) • parts of products.TFSBP shall not be (RAL9002) P/N 56-201-5-135 responsible for sprinkler system design errors or inaccurate or incomplete in- • Eastern known as Bright only. formation supplied by Buyer or Buyer's Previously known as Bright White. representatives. Note: A!I Custom Cover Plates are painted=using Sherwrn L1TiTliams Interior— - --- -- - - In no event shall TFSBP be liable,in con- Latex Paint. Contact TYCO Customer tract,tort,strict liability or under any oth- Service with any questions related to er legal theory,for incidental, indirect, custom orders. special or consequential damages,in- cluding but not limited to labor charg- Sprinkler Wrench • es, regardless of whether TFSBP was Specify W-Type 18 Sprinkler Wrench, informed about the possibility of such P/N 56-000-1-265. damages,and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied, including warranties of mer- chantability and fitness for a Particular • purpose. This limited warranty sets forth the ex- clusive remedy for claims based on fail- ure of or defect in products,materials or components, whether the claim is made in contract,tort,strict liability or any oth- er legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. • ttjco Flow Tyco Fire Control Products .:.•--.: :-.7 BlazeMaster° FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 www.tyco-fire.com TECHNICAL SERVICES - _ _ — -_ - • TEL (800) 381-9312 • FAX: (800) 791-5500 E-MAIL techserv@tycofp..com a ,it tl wx' Rey ,''i iraa.�s't'.r..j.`: . . ti. _ ._:,: r I �a 0, rOtg Vin No. 19-1.5 TD91 5 4-1.1.20 9/2001 • s Introduction Tyco Fire Products (TFP) BlazeMaster('CPVC pipe and the same time, they provide superior heat resistance and fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping - automatic fire sprinkler systems. They are made from a materials used in the plumbing trade. Various adapters are specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability. • the art additives. TFP BlazeMaster'CPVC products are Grooved adapters connect directly to grooved end valves easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings. Technical Data Sizes: 1/4"-3" Manufacture Source: U.S.A. Maximum Working Pressure: 175 psi Material: Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDF 13.5 MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and Note: See current TFP BlazeMaster Installation Instructions and ASTM F439 (Sch. 80) Technical Manual,for exact listing/approval information Color: Orange Pipe Nom.Pipe Size Avg. 0.0. Inches Avg. I.U. Inches Wt. Lbs./Ft. Wt.1420 filled Pipe Lbs./Ft. Ft. of Pipe per Lift Wt.per Lift Lbs. 3/4" 1.050 0.874 0.17 0.43 7875 1413 1" 1.315 1.101 0.26 0.67 5040 1320 11/." 1.660 1.394 0.42 1.07 IMMEMENIN 1191 11/2" 1.900 1.598 0.55 1.40 2205 1136 2" 2.375 2.003 0.86 2.20 1260 1063 2 '/2' 2.875 2.423 1.26 3.22 1215 1531 3" 3.500 2.952 1.87 4.79 720 1344 - Fittings T° IN rro' rio mg 45° Elbow _ �� Tro Reducing ucing 2j. 90° Elbow 90 Elbow _ Tro= -- - - -- - T/° lit ---1 I Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O' Wt. 80050 '/." 40 '/e" 0.08Ib. No. Size Sch. 1 2 Ib 80025 3/4" 9 40 /+6" 0.09 lb. 80051 1" 40 '/e" 0.11 lb. 80032 1"x 3/4" 40 "/+e" "/+e" 0.16 80026 1" 40 3/+" 0.14 lb. 80052 1'/4" 40 3/4" 0.20 lb. 80053 11/2" 80 '/,fi" 0.31 lb. 80027 1'/4" 40 '/e" 0.21 lb. 80028 1'/2" 80 13/46" 0.40 lb. 80054 2" 80 3/4' 0.56 lb. 80029 2" 80 1/4" 0.79 lb. 80055 21/2" 80 3/4' 0.89 lb. 80030 2'/:" 80 172" 1.14 lb. 80056 3" 80 1" 1.19 lb. 80031 3" 80 1"/+6" 1.82 lb. + 1 1 I T/O' ti ! , T/O i Tee NV T/° Reducing ! Crass �; _NMI_ �Cross a ,�� rro I no rro' I 1 rro 11 T/O' I T/O' T/O T/O Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt. 80000 3/4" 5 Size Sch. 40 /e" 0.11 Ib. No. 1 2 lb. 80009 '/." 40 9/,6' 0.13 lb. - 80001 1" 40 3/4" 0.19 lb. 80015 1"x 3/4" 40 "/,e" "/+e" 0.28 80010 1" 40 5/+6" 0.23 lb. 80002 1'/4" 40 '/e" 0.26 lb. 80011 11/4" 40 15/1e" 0.34 lb. 80003 1'/2" 80 1" 0.51 lb. 80012 1'/2" 80 11/,6" 0.67 lb. - 80004 2" 80 1'/e" 0.90 lb. 80013 2" 80 1'/e" 1.00 lb. 80005 2'/2" 80 19/,6" 1.59 lb. 80014 2'/2" 80 19/■e" 1.91 lb. 80006 3" 80 1"/,6" 2.41 lb. 80008 3" 80 1'3/,6" 2.89 lb. „4- • IS U Soon --1r-T/0 T/O --i T/O Coupling _ __ _. Cap Reducer _. 1�� to ._ Bushing 4Z Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. 80200 1"x'/4" 40 '/1s" 0.04 Ib. 80075 '/�" 40 '/e" 0.07 Ib. 80100 '/" 40 5/1e" 0.04 Ib. 80201 1'/4"x'/4' 40 '/,a" 0.11 lb. 80076 1" 40 '/s" 0.11 lb. 80101 1" 40 3/e" 0.06 lb. 80202 1'/4"x 1" 40 5/16" 0.12 Ib. 80077 1'/." 40 3/,6" 0.12 lb. 80102 11/4" 40 '/2" 0.10 lb. 888000222000320 0203 1'/:"x 3/ 844000 0 5/a" 000:0824 .16 Ib. 80078 1'/z" 80 3/,." 0.25 lb. 80103 1'/z" 80 5/8" 0.20 lb. 80204 11/2"x 1" 80 '/z" 0.14 lb. 80079 2" 80 '/1a" 0.38 lb. 80104 2" 80 ./e" 0.31 lb. 80205 1'/2"x 1'/4" 80 3/s" 0.17 lb. 80080 21/2" 80 '/,a" 0.67 lb. 80105 2'/" 80 '/s" 0.58 lb. 80206 2"x'/4" 80 3/4" 0.27 lb. 80081 3" 80 3/,." 0.91 lb. 80106 3" 80 1" 0.88 lb. 80207 2"x 1" 80 "A." 0.26 lb. 80208 2"x 1'/4" 80 9/1s" 0.24 lb. rio 80209 2"x 1'/2" 80 '/,." 0.19 lb. Grooved 80215 2'/:"x 1" 80 1 t5/,s" 0.42 lb. Coupling Po.o. 80214 2'/z"x 11/4" 80 1'/4" 0.45 lb. Adapter 80213 2'/z"X 11/2" 80 11/4" 0.46 lb. 80211 2'/2"x 2" 80 1'/,s" 0.29 lb. Part No. Size Sch. T/O Wt. Pipe OD 80210 3"x 2" 80 2 3/,a" 0.72 lb. 80160 1'/4"x 1'/4" Grooved 40 2 s/,s" 0.78 Ib. 1'/4"(1.660") 80212 3"x 2'/z" 80 1 f5/,e" 0.47 lb. 80161 1'/2"x 1'/2" Grooved 80 2 5/,e" 0.95 lb. 1'/2"(1.900") 80162 2"x 2" Grooved 80 2 5/15" 1.42 lb. 2" (2.375") i 80163 2'/z"x 272" Grooved 80 2 5/16" 2.28 lb. 2'/z"(2.875") w III'3"x 3" Grooved 80 2'/4" 3.00 lb. 3" (3.500") Reducing IVA' �' 80168 3"x 76.1mm Grooved 80 21/4" 2.72 lb. 76.1mm (3.000") Tee rt To' .. T/0' - - - Size Sch. 1 2 3 lb. Female _ 80132 3/4"x'/4"x 1" 40 '/4" 3/4" 5/5" 0.14 Adapter 11-.1-1111111 80133 1 X'/4"x3/4" 40 'x" " 3 4" -�r / /+a / 0.14 80134 1"x 3/4"x 1" 40 5/5" 3/4" 3/4" 0.17 Part No. Size Sch. T/O Wt. 80260 1"x l"x 3/." 40 3/+" 3/4" "/,5" 0.16 80142 3/4"x'/4"NPT 40 5/a" 0.41 lb. 80135 1'/4"x 1"X'/4w 40 '/,5" 3/4" 'S/1a" 0.21 80145 1"x 1" NPT 40 3/4" 0.63 lb. 80136 1'/4"x 1"x 1" 40 "/,a" 3/." 15/16" 0.22 80146 l'/+"x 1'/4" NPT 40 '/5" 1.03 lb. 80137 1'/4"x 1"x 1'/+" 40 13/5" 1S/,e" "/,a" 0.26 80147 1'/2"x 1'/2" NPT 80 1" 1.42 lb. 80261 1'/4"X 1'/4"X 3/4" 40 5/e 5/e" '/5" 0.23 80148 2"x 2" NPT 80 1'/e" 2.66 lb. 80262 1'/4"x 1'/4"x 1" 40 3/4" 3/4" '/s" 0.26 80138 1'/4"X 11/4"X 1'/2" 80 1" 1" 1" 0.43 rro 80140 11/2"X 11/4"X 3/4" 80 '/z" 5/6" 1" 0.36 80141 11/2"x 11/4"x 1" 80 1/2" 5/a" 1'/4" 0.38 Male __ __ 80263 11/2"x 1'/2"x 3/4" 80 9/18" 5/15" 1" 0.36 Adapter 80264 1'/2"x 11/2"x 1" 80 5/1s" '/1s" 1" 0.38 80275 1'/2"X 11/2"x 1'/4" 80 '/s" '/e" 1" 0.45 Part No. Size Sch. T/O i Wt. 80265 2"x 2"x 3/4" 80 3/4" 3/4" 13/a" 0.61 80157 3/4"x'/4" NPT 40 15/1." 0.33 lb. 80266 2"x 2"x 1" 80 '/s" '/5" 1'/5" 0.66 80158 1"x 1" NPT 40 1'/e" 0.56 Ib. 80274 2"x 2"x 1'/4" 80 1" 1" 1'/e" 0.74 80267 2"x 2"x 1'/2" 80 1'/a" 1'/s" 13/5" 0.78 T/O 80271 2'/2"x 2'/:"X 1" 80 1"/1e" 1"/16"" 19/16" 1.43 80272 2'/z"x 2'/2" X 1'/4" 80 111/18" 1"/,s" .19/16" 1.46 Reducing _�__ _ _ 80273 2'/2"x 2'/2" x 11/3" 80 1"A." 1"/16" 19/1s" 1.48 Coupling 80276 2'/2"X 2'/s"X 2" 80 1"/1s" 1'1/44" 19/1s" 1.50 80270 3"x 3"x 1'/z" 80 13/4" 13/4' 113/1." 2.28 Part No. Size Sch. T/O Wt. 80268 3"x 3"x 2" 80 13/4" 13/4" 13/4" 2.25 80220 1" x 3/4" 40 '/a" 0.08 lb._ 80269 3"x 3"x 2'/2" 80 13/4" 13/4" 115/,6" 2.44 • X00....,. r_T/O T/0 Sprinkler Head Adapter 1111 _ Sprinkler Head Adapter _ I r_ with Brass Threaded Insert with Brass Threaded Insert i�� Part No. Size Sch. T/O Wt. Part No. Size f Sch. T/0 1 Wt. 80175E 3/4"X '/2" NPT 80 7/16" 0.20 lb. 80175W 3/4"x '/2" NPT 40 1/46" 0.19 lb. 80176E 1"x '/2" NPT 80 7/,6" 0.22 lb. 80176W 1"x 1/2" NPT 40 7,6" 0.18 lb. 80177WL 3/4'x'/2" NPT 40 e/16" 0.16 lb. , 80179 1 x 3/4" NPT 40 3/4" 0.43 lb. IB- M' Back-to-Back Cross I _ Sprinkler Head Adapter iiiir: � !!� .+� with Brass Threaded Insert .� (Spigot) T,O' with Brass Threaded Insert I T/o' T/O' Part No. Size Sch.I T/0 I Wt. Part T/O Wt. 80177L 3/4"x 1/2" NPT 40 '/z" 0.16 lb. No. Size Sch. 1 2 lb. 80178 1"x '/2"NPT 40 '/2" 0.20 lb. 80462 1"x 1"x1/2"NPT x1/2"NPT 40 5/e" 1'/e" 0.46 80463 1"x 1"x 1/2"NPT x1/2"NPT 40 5/e" 15/16' 0.47 T/o' Sprinkler Head Adapter 90° Elbow Mr. - I 4- 6r 4� with Brass Threaded Insert �, T'O' Back-to-Back Tee Tro.__�CQ' �� III with Brass Threaded Insert I — i T/O 2 T/O' Part T/0 Wt. Part Size Sch. T/O Wt. Size Sch. if No. 1 --2=- -_lb. _ - _ - --..No. — -- - -- ._._1 _ _2-- - lb. - 80199 3/4" x '12" NPT 40 5/6" 15/,6" 0.20 80459 1"x '/2" NPT x 1/2"NPT 40 "/,e" 15/,e" 0.48 80189 1"x'/2" NPT 40 13/,6" 13/1e" 0.26 80460 1"x 1/2" NPT x'/2"NPT 40 "/,e" 1'/e" 0.46 Part No. Size Sch. 1 2 3 lb. 80250 3/4"X 1/4"X'/2"NPT 40 6/6" 5/e" 1" 0.22 1 80251 1"x 1"x 1/2"NPT 40 "/,e" "/16" 13/,e" 0.29 I ' f 80249 1"X 1"X 1"NPT 40 15/,e" 15/,e" 17/,6" 0.73 Sprinkler Head Adapter a ""` T/O' 80256 11/4"x 1"x'/2"NPT 40 716" ' e/16" 11/6" 0.30 Tee ----- ,------- 80252 11/4" x 1'/4"x '/2"NPT 40 7/,e" 'be 1'/e" 0.31 with Brass Threaded Insert = ' 80257 11/2" x 1'/4"x 1/2"NPT 80 5/1e" 5/e" 1'/,e" 0.43 v0' I _.) I Tbd 80254 1'/2" X 11/2"X '/2"NPT 80 a/,6" 9/,6" 17/,4" 0.46 80258 2"x 1'/2"x '/2"NPT 80 1/2" 5/6" 15/6" 0.56 80253 2" x 2"x'/2"NPT 80 '/2" '/2" 15/e" 0.62 Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse,improper installation,corrosion,or which have not been installed.maintained,modified or repaired in accordance with applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced,at Tyco Fire Products sole • option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it,any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE,IN CONTRACT,TORT.STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY.FOR INCIDENTAL,INDIRECT,SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LThUTED TO LABOR CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES. AND IN NO EVENT SHALL TYCO FIRE PRODUCTS LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. 1 THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED.INCLUDING V:: WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, tggCO/F/ow Control/Tyco Fire Products 0 DynaffiThread Full Line Sch 4Q Replacement Dyne-Thread• offers the life expectancy of Sch4O with superior hydraulics and greater glue. Dyne-Thread sprinkler pipe represents an engineerins advancement for the sprinkler pine industry.It combines the safety and Iongevity of traditional Soh-40 pipe with quality and superior hydraulic advantages. Comparison to Schedule 40 • Dyna-Thread's inside rnarneter is UP • With its increased strength and lighter - More wall thickness at the thread to 3.5%larger than Sch-40 giving it weigh;Dyna-Thread reduces (CRR=1-00)gives D Thread superior hydraulics.And,when used 3�" installation fatigue and is ideal far better life expectancy than ligImvsll in oombination with Dyna-Flow pipe, retro-fit applications. threadebic pipe joints. down sizing often occurs, Corrosion Resistance Ratio (CRR)is a • Unlike lightwall threadable pipe, • Dyne-Thread is fully listed and UL(Underwriters Laboratory)term for Dyna-Thread has no thread gauge approved by UL,ULC,and FM far the estimated life expectancy of a pipe warning fire sprinkler applications. joint.This is based on the calculated •• The life expectancy of Dyna-Thread wall thickness at the base of the first Dyaa Thread is approved for and Sch-40 arc equal based on the exposed thread,assumed to be the standard hanger spacing(15 fr calculated wall thicknesses per UL. "ta Pow of the pipe length"Dyne- 0.C.),can be used as earthquake Thread and 9th-40 have the same sway tracing, and is safe to use as • The consistent quality of steel used to calculated wall thicknesses at this point cli.°Ps' make Dyne-Thread facilitates smooth and are bath assigned the same CRR of • Dyna-Thread is safer to weld on, threading and lower maintenance 1,00, casts, • Dyne-Thread is more widely The internal surPsoe of all black Allied accepted than lightwall ihreadahie • The exterior of Dyna-Thread is where Sch-40 is specified. protected by a clean,durable mill Tuba&Conduit Fire Sprinkler pipe coating for extended shelf life and Products up to 4.5000"in diameter is easy paint application. coated with our now Anta3aaterial Formula,"ABF",In scientific laboratory test,ABS proved to have superior SpecificatitpnS-& Ap}i ovals resistance to microbial colonization of (Di GO pipe walls,thereby delaying or possibly Super 40/Dyne Thread pipe is preventing the onset of manufactured to meet:ASTM A-135, Listed Approved Listed Microbielogi❑ally Influenced corrosion Grade A and is in compliance with (MIC)when the First Sprinkler System 1VFPA-l3.All sizes of Super 40/Dyna- is Bret installed. Thread are rated at 300 psi working pressure.Super 40/Dyna-Throad is UL Specifications and UT-C Listed for veer,dry deluge and . pre-notion sprinkler systems and FM NP8 Naming/I,D, Wt, WI.(1120 F1lfed) Pct/ WI/LIft(21') W!/Lilt(24') WI/LIIt(25') Approved for use in wet systems.Super In;mm In;mm Lbs/Ft;Kgmi LIzirt Kg/m Lift Lbs;Kg Les;Kg Lbs;Kg 40/Dyna-Thread can be"hot-dip" 1° 1,080 1.330 1,75 70 1855 2234 2327 galvanized to moot FM requirement for 25 27.4 2.0 2.80 70 857 1013 1056 dry systems, Super 40/Dyna-Thread is 1 Ye" 1,408 1,870 2.54 51 2002 2288 2984 approved fbr all threaded couplings and 32 95,8 2.8 3.78 51 908 1035 1D8t welded outlets and is suitable for all 1 W 1.838 2.290 3.22 44 2115 2410 251 g roll-grooved,and plain-end fittings. 40 41.6' 3,4 4,79 44 959 1097 1143 (See listing information), 2" 2.104 3.050 4.57 30 1921 2195 2287 50 53.4 4.5 0,80 30 871 996 1007 dies/Flowtoms'' allied 16100 S. Lathrop • Harvey, IL 60428 Customer Service: l (�J 11350 Norcom Rd.•Philadelphia, PA 19154 (800)882-5543 ruse a aoN❑uir 2525 N,27 th Ave.•Phoenix,AZ 85009 Fax 708-339-1805 S3 -3 • Submittal Data Sheet Dyna-Thread° Sump Here Full Line Sch-40 Replacement Dyna•Thread sprinkle pine repres=sts an engineering advimeemeal for the sprinkler pipe industry.It combines the safety and longevity of traditional Soh-40 pipe with quality and sup ice hydraulic advantages, Comparison to Schedule 40 Dyne-Threodi inaide diamcr~is up to 3.6%large than Sch-40 giving it anperior hydraulics.Also,when used in combination with Dyne,-Flow pipe, dawn sing oiteo.occurs.Dytut-Thread is fully list-„d and approved UL, ULC, .,_1 t-:‘:: ..: �r.:•-: and FM for fire sprinkler lcr applications.The life expectancy of Dyna•Thread and Sch-40 - • '` :•' , `" 1 s are equal based cm the calculated c - . �"�_ ., ..:..:, � , .- wall thicknesses per UL,The consistent quality of :-;k :!_: " •_ - z -- ' I used to make Dyne-Thread fecilirates smooth threading and lower mamranance •r'• -t:'•1-e-- - - a,':q,a .- costs. The exterior ofDyna-Thread is paotcetcd by a cl n, `'� "4: '3~~x~ durable mill bearing 4a V. :.:-; extended shelf life and cagy paint application.with its increased strength and lighter • : ;. `�-` :'_ ••S° "�-, s , 4 ' wei�.t,Dyne-Thread arced reduces installation fatigue and is ideal for retro-fit applications. =>°`• fir;.-L 'rr• %.�J. _.��'4 F:::., Corrosion Resistance Ratio(CRR)is a UL(Underwriters Laboratory)term for the b`3, ::~ °°" i kgp,- estimated life joint.This is hexed the calculated •`' e.'i•, .,, ..� actancy of a pipe l wall thialcaesa "�: "s .:• • ='.!r *.:7'... at the base of the firer exposed[bread,sasumed to be the weakest paint of the pipe :: -*,• -t`•- ..F."-'" i3 length.Dyne-Thread and Seh-40 have the game calculated wall thiakneasea at this i. .. a.t; ? ?;e '' and are both assigned the same CRR of 1.00. .2.. S11,-'s'y - `l: .. `. ,, _t, r: point r' 4 ` -.A� r r' #'1 v yet Comparison to L.W.T.Pipe More well thickness at the thread(CRR=1.00)gives � e.;-:...r �" ` Dyne-Thread better life expectancy than lightwall threadablc pipe jointa. Unh7ra :;1.. .:,; _•_ .;<°. • 4• lightwall threadablc pipe Dyna-T mead bas no thread gauge warning.Dyna-Thread is !is ' '' approved for standard banger spacing(15 ft.O.C.),can be used as earthquake away °-0e°, °k� `* bracing, and is safe to us:as drop[.D Thread is safer in weld on zinc- ,'.' }�na" than many ..^;� , b �ia::.:.:;:iE":; coated li :wall thrcadeble rods "$' i .b;lOi; � pipe products.Dyna•Threed is more widely accepted the .� l `17y%�: '1'� ... ... lightwall threadable where Soh-40 is specified, •••'`i . . +. ..:p liIlli Specification&Approval* Super 40/ Dyne-Thread pipe is manufactured to Specifications meet:ASTM A 135,Crradc A and is is NP8 Natntoal 1.0• Wt. Wt.(H20 Filled) Pes/ Wttfft(21') WVLill(24') WWfl(25') compliance with NFPA-13.All sizes of !n;mm ix mm Left Ka v CUR:Kg(n Ltd Lbs;Kg Lbs,Kg [be;Kg Super 40/Dyna-Thread are rated at 300 1' 1.080 1.330 1.75 70 1855 2234 2327 psi working pressure. Suupc:40/Dyne- Y5 27.4 2.0 2.50 70 887 1019 1056 Thread is UL and ULC Listed for wet, 13/4' 1.408 1.870 2.54 51 2002 2288 238 dry and pro-action sprinkle:systems and 97 35.8 £8 8.78 51 908 7098 1061 FM Approved for use in wet systems. Super 401Dyaa•Thread can be"hot-dip" 1W 1.639 2.290 2.22 44 2115 2418 2519 galvanized to meet FM requirement for 40 41.6 3.4 4.79 44 959 1097 114,9 dry syateans. Super 40/Dyne-Thread is 2' 2,104 3,050 4,67 JO 1821 2196 2287 approved for all threaded couplings and 50 59.4 4,5 B.80 30 871 808 1032 welded outlets and is suitable for all roll- grooved,and plain-end fittings. (Sco American Tube and Pipe was acquired by Allied Tube and Condtat on February 1, hating information), 1997.The engineered lightwall and anmderd wall family of products although they The internal surface of all black Fire have differelt names arc the same in all respects with regard to strength,weight, Sprinkler pipe up to 4.5000"in diameter bundle count listings and approvals.For=ample, shall be coated with Allied Tube& Dyns-Flow and Super Flo arc the same product as 4111 4reo. OD Conduit Antibacterial Formula"ABF" ern Dyne Thread and Super 40.XL is manefeottrred with Exterior galvanized coating.BLT is manufactured with Black lacquer rluting. tinted Approved Listed Project: Sorinkler Contractor; new Eng near: Specification Reference' s;_ern Type: Locations: Comments: S3 -4 Kati ��� vs R.D ®��- VANE TYPE WATERFLOW APPROVED SWITCH WITH RETARD Potter Electric Signal Company 2081 Craig Rd., / St. Louis, MO 63146 / (800)325-3936 / (314)878-4321 • SERVICE PRESSURE UP TO 450 PSI CHARACTERISTICS FOR 2" TO S" PIPE SIZES 250 PSI FOR 10" PIPE SIZE U.L. LISTED AND F.M. APPROVED MINIMUM FLOW RATE FOR ALARM-10 GPM DIMENSIONS & WEIGHTS: See Fig. 2 ENCLOSURE: Cast Aluminum Finished: Red Enamel • CONTACT RATINGS: Two sets of S.P.D.T. (Form C) 15.00 Amp. @ 125/250V. AC 0.50 Amp. @ 125V. DC 0.25 Amp. @ 250V. DC 2.50 Amp. @ 0-30V. DC Resistive ENVIRONMENTAL LIMITATIONS: 40°F/120°F 4.5°C/49°C General Purpose for Indoor Use CAUTION: This device is not intended for applications outdoors or in explosive environments. SIZES AVAILABLE: U.L. - For Schedule 40 Pipe: 2" thru 10" • For Schedule 30 Pipe: 8" F.M.= For Schedule 40 Pie 2"thru 6" For Schedule 30 Pipe: 8" and 10" SERVICE USE: Automatic Sprinkler 't r~ NFPA-13 One or Two Family Dwelling NFPA-13D Central Station NFPA-71 Local NFPA-72A Auxiliary NFPA-72B Remote Station NFPA-72C Proprietary NFPA-72D U.S. Pat. Nos. 3,912,247 OPTIONAL: Cover Tamper Switch 4,062,377 Order Stk. No. 5420220 The Model VSR-D is a vane type waterflow switch for The flow condition must exist for a period of time necessary use on wet sprinkler systems. It is UL Listed for use on to overcome the selected retard period. steel pipe;schedule 40 sizes 2"thru 10"and schedule ENCLOSURE:The unit is enclosed in a general purpose, 30 size 8" and has FM approvals for schedule 40 steel pipe in sizes 2" thru 6" and schedule 30 pipe in sizes indoor use, cast aluminum housing. The cover is held in 8" and 10", place with two tamper resistant screws which require a spe- cial key for removal.A field installable cover tamper switch • The unit may also be used as a sectional waterflow is available as an option which may be used to indicate detector on large systems. unauthorized removal of the cover. See Bulletin 751 for installation instructions of this switch. The unit contains two single pole, double throw, snap RETARD ADJUSTMENT: The unit has an adjustable action switches and an adjustable pneumatic retard. pneumatic retard to prevent false alarms due to water The switches are actuated when a flow of 10 gallons surges.The retard is adjustable from 0 to approximately 75 per minute or more occurs downstream of the device. seconds. 2-88 CAT.#A010 PAGE 1 . :... p .. ,.t porrER a:,.iiitu-•..'may?+.,,-. 'ai.4.ea: a-sd':i.W.Wif :z-.v4Flof. $ Potter Electric Signal Company 2081 Craig Rd., / P.O.Box 28480 / St. Louis, MO 63146 / FAX: 314 878 7264 • VSR-D INSTALLATION FACTORY ADJUSTED FIG. 1 SENSITIVITY SPRING. DO NOT ADJUST RETARD ADJUSTMENT TO CHANGE TIME TURN ?NOG '' IEtTHER DIRECTION)FOR DESIRED TIME DELAY. I�r� TIGHTEN NUTS USE THE MINIMUM AMOUNT ' o/ ALTERNATELY TO AN OF RETARD NECESSARY TO ...k11) EVENTUAL PREVENT FALSE ALARMS. -'�`\ I OF TORpUEs A 'B" SETTING IS USUALLY ADEQUATE FOR THIS. �� ;� MOUNT ON PIPE SO 401' ARROW ON SADDLE POINTS IN DIRECTION 1 i OF WATERFLOW. ROLL PADDLE IN COI TO INSTALL: �4 ,�/ OPPOSITE DIRECTION FOR 2 V SIZES OF WATERFLOW. DRILL ILL I I/4 I/4-HOLE. ' FOR ALL OTHER SIZES , RILL 2-HOLE a �I ii APPROX. RETARD SETTING ON SEC.) 0 A e C 0 e 1 I) r `I 0 10-25 20-40 35-55 50-70 50-90 I �` y OPTIONAL: Corr Tamper Switch I Ordx Stt. No. 5420420 if DIRECTION OF /' WATERFLOW -.. /�J DWG. 5400710-309 SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL CAUTION: \ AN UNINSULATED SECTION OF A SINGLE CONDUCTOR IS NOT PERMIT- - I TED TO BE LOOPED AROUND THE TERMINAL AND SERVE AS TWO I ---— SEPARATE CONNECTIONS.THE WIRE MUST BE SEVERED TO SERVE ....,___ 1NC()MING AS TWO SEPARATE CONNECTIONS, THEREBY PROVIDING SUPERVI- SION OF THE CONNECTION IN THE EVENT THAT THE WIRE BECOMES DISLODGED FROM UNDER TERMINAL. NG� DWG.5400710-31 OUT pI INSTALLATION INSTRUCTIONS: These devices may Clean the inside of the pipe of all growth or other mate- be mounted in a horizontal or vertical pipe. On horizon- rial for a distance equal to the pipe diameter on either tal pipe they should be installed on the top side of the side of the hole. pipe where they will be accessible.The units should not Roll the vane so that it may be inserted into the hole;do be installed within 6 inches of a fitting which chances the not bend or crease it. Insert the vane so that the arrow direction of the waterflow or within 24 inches of a valve on the saddle points in the direction of the waterflow. or drain. Install the saddle strap and tighten nuts alternately to an Drain the system and drill a hole in the pipe using a cir- eventual 50 FT.-LBS. of torque. See Fig. 1 above. cular saw in a slow speed drill.The 2" and 21/2"devices The vane must not rub the inside of the pipe or bind in 'require a 11/4" hole; all other sizes require a 2" hole. any way. TESTING I The frequency of testing for the model VSR-D and its associated protective monitoring system should be in accordance with applicable NFPA Standards and/or the authority having jurisdiction,but under no circumstances less than bi-monthly. :AT. #A010 PAGE 2 2-88 AN • G - . , . _, . . ._. . . - - ,.,44 ... ...,..„ . • • . . . _ , . . . . . . , . . , Any r.-, ‘ , . , C x - s c w ,ar e h +.f^'h x i ii F ",. k � . .'•••4 x. QF me+ �' . 0 t _. S ..1;',L-,„,,,,,, ,c, C u r S11 P P• r4*"�'�jh,,d Jr %ift Jr: 4 t7:FSll�ecYfU �i ... � .F a �i�ti �. -- 11 E F ilk.Co..SraLlIt film•U ,; g ..1-.-f R net �°t , U L..°Plori 1W 47 l pr a atr P.4'0*,Pnn�"g %' _F aV r: , �,gf� aA N T r.-, • • The AGF Manufacturing Co., Inc. Model 1000 has been designed to provide both the Test Function and the Express Drain Function in a multi story installation. • Complies with all requirements of NFPA-13, and NFPA-13R • Complies with all requirements of NFPA-13D (HOUSING) • Positive Shut Off • Single Locking Handle • Tapped 1/2" for Pressure Gauge • Tamper Resistant Orifice permanently installed • Available with all required Orifices __ • Orifice size noted on Indicator Plate • Lightweight and compact (11/4" weighs 5 lbs.) ■ 300 PSI Rating • Fused, tempered, tamper resistant Sight Glasses • AD- 0 MODEL 1000 300 PSI 0 F _ TESTANDRAIR 3 ,/41r • . 1 r1 1 1/4 'r ' 1 1/2r` m 21r *3/.-NOT FM APPROVED PLAN VIEW FRONT VIEW j A f FROM I BRANCH GAUGE OUTLET ��� PROVIDED Ell sm III < TO DRAIN ° � �� \lin� � �IIII�I� � ��� S ingF1 o . = �' - �� STREET EL off) FRONT VIEW/HORIZONTAL INSTALLATION, STREET EL TO DAMN OR PIPE I 11,I -� E I 0 NM .y F , TO DRAIN FOR RIGHT HAND/STRAIGHT INSTALLATION ns; 111`øIit1T,,TO DRAIN . an APPROVALS • UL and ULC Listed • FM Approved except 3/4" 1 • NYC BD. of S&A CAL. NO. 720-87-SM • CA. State Fire Marshall ORIFICE SIZE • PROVIDED-3/8-7/16• 1/2— 17/32—5/8't*--.3/4** DIMENSIONS—INCHES MATERIAL LIST SIZE A B C D E F G H PART MATERIAL 3/4 51/16 13/4 23/a 4I/e 33/8 13/4 49/16 65/16 HANDLE STEEL STEM BALL ROD BRASS C.P. BRONZE 1 51/16 13/4 23/a 41/a 33/a 13/4 49/16 65/16 1 'A 57/16 13/4 27/a 45/e 35/Is 1'S/I6 5I/2 77/16 BODY BRONZE VALVE SEAT GLASS INPREGNATED TEFLON 1 '/z 67/I6 13/4 3"/16 57/16 372 23/a 8'/16 10 /16 INDICATOR PLATE STEEL 2 67/16 13/4 3'1/Ib 57/16 3'/2 23/a 8'/16 1077/16 HANDLE LOCK SPRING STEEL SIGHT GLASS (2) FUSED TEMPERED GLASS ** Available on 1 I/," to 2"size units only. ' AGF MFG. CO. JOB NAME: ( Box 4437, 150 Mt. Bethel Rd. ARCHITECT: Warren, N.J. 07059-0437 MADE INU.SA. Telephone (908) 604-6471 ENGINEER: Fax (908) 604-6501 CONTRACTOR: 1000 8/94 • • - OLCO INCORPORATED CORONA,CA (909)737-5599 • 1 0 u� Fig. 27 & 27A "Stand-Off" Hanger/Restrainer for CPVC Plastic Pipe Size Range—3/4" & 1" CPVC Plastic Pipe*. - 0 Material— Carbon Steel, Pre-Galvanized. Function—Designed to be used as a hanger/restrainer**for CPVC piping where the "stand-off" design will ease installation by eliminating the need for ` �'\ wood blocking. Features: .": • Flared edge design protects CPVC from any rough or abrasive surfaces. I• Snap-in retainers hold pipe firmly in place during installation. • The "Stand-Off"design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting Fig. 27 surface orientation. • Attaches easily to wood structure with 2 hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16"sockets, c eliminating impact tool damage to pipe Approvals- Underwriters Laboratories Listed in the U.S. (UL) and Canada ' o (cUL) to support automatic fire sprinkler systems. Meets and exceeds the V'irequirements of NFPA 13, 13R, and 13D. Fig. 27A **Important Note—When installed in slot op_ening on Fig_27, Fig.27A- _ _ '�\ _ _ provides additional stability and satisfies the UL vertical restraint requirement where needed. ■ —.,\ Order By—Fig. 27: By figure number and CPVC pipe size. \�I Fig. 27A: By figure number and CPVC pipe size. i � ) , U.S. and International Patent application in process. I' , *for other sizes consult factory. I Fig. 27 and Fig. 27/27A have also been tested by U.L. mounted on 3/8" Fig, 27/Fig. 27A composite wood web material (such as TJI Series/Trus Joist MacMillan) without the use of back up wood blocking. When using Fig.27 & 27A in Combination combination on 3/8"web to satisfy the UL requirement for vertical restraint, FIG.27 install 2 reinforcing speed nuts (Fig. 27B). Fig.27B is UL Listed only when W/FIG.27A used with Tolco products. ■ FIG.27B � FIG.27 d - W/FIG.27A ■t 4 III - !I I n••■ I FIG.27 FIG.27 • FIG.27 FIG.27 W/FIG.27A FIG.27 _ — it - l MIL lipli 111 101 Typical Applications �'° (I�11 ES-A-2000B Series 2000B AS Double Check Valve Assemblies FIRE&WATERWORKS"' Sizes: 1/2" —2" (15-60mm) t-; Features ;, , '- • Ease of maintenance with only one cover 2"2000B HC • Top entry (50mm) • Replaceable seats and seat discs • Modular construction • ,:Compact design • 1/z 2" (15 50mm)Cast bronze body construction 3/4"2000B.... • Top mounted ball valve test cocks (20mm) • Low pressure drop • No special tools required Series 2000B Double Check Valve Assemblies shall be installed at referenced cross-con- • '/z"—1"(15—25 mm)have nections to prevent the backflow of polluted water into the potable water supply.Only tee handles those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation,frequency of Available Models testing or other installation requirements. Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are __B--Quarter_turn ball_valves__ _approved_bythe_Foun_dation_for Cross_ConnectionControl_and_Hydraulic Research_at_the LBV- less ball valves -University of Southern California. LH- locking handle ball valves(open position) Specifications SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly HC- 2W inlet outlet fire hydrant fitting shall consist of two positive seating check modules with captured springs and rubber seat discs.The check module seats and seat discs shall be replaceable.Service of all internal Prefix: components shall be through a single access cover secured with stainless steel bolts.The U- union connections assembly shall also include two resilient seated isolation valves and four top mounted, re- silient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Pressure —Temperature Hydraulic Research at the University of Southern California.Assembly shall be an Ames Temperature Range:33°F—140°F Company Series 2000B (5°C—60°C) Approvals Maximum Working Pressure: 175psi t ASSE,IAPMO,CSA,UPC (12 bars) • Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Standards • Model LBV is not listed. ASSE Std. 1015,AWWA Std. C510 u UL Classified(LBV models only)3/4"—2"(19—50mm) e ® .� IAPMO PS31, CSA B64.5 • Horizontal and vertical"flow up"approval on all sizes. ID) dP © Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Dimensions - Weights A IN c I �� . ,._..filMi■- 1 Illrr'- ,1, B , �I, F H -■ 4-I G Suffix HC-Fire Hydrant Fittings dimension"A"=231/2"(594mm) Size(DN) A B Dimensions Model in. mm in. mm in. mm in. mm in. F mm in. G mm in. H mm in. I mm lbs. k's. 20006 1/2 15 10 254 4% 117 2'/6 62 5 127 3% 85 25/i6 59 2'/e 52 4.5 2 20008 M3 % 20 11'% 282 4 102 3'%e 79 63/i6 157 3745e 87 2'% 54 15/6 33 5 2.3 20008 1 25 131/4 337 5% 130 4 102 7%z 191 3% 85 11%6 43 1 1/6 43 12 5.4 20008 11/4 32 16% 416 5 127 35/6 84 9'%z 241 5 127 3 76 2 50 15 6.8 20008 1'% 40 163/4 425 4% 124 3'% 89 93/4 248 51316 148 3'%e 79 21%6 68 15.86 7.2 20008 2 50 19'% 495 61/4 159 4 102 13% 340 6% 156 3%6 87 2 1%e 68 25.75 11.7 Strainer sold separately Capacities bars psi 11/4"(32mm) As compiled from documented Foundation for Cross-Connection Control 1 14 and Hydraulic Research at the University of Southern California lab tests. y .8 12 'Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) .7.5 5 8 -r ba i %"(15mm) * co .3 4 N s ps 0 .7 10 . .1 2 .5 8 n m 0 0 3 4 Ap 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm ,--., w 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm t H a '�0 5 7.5 10. 15 0 2 4 1.5 2.3 3.0 ---- 4.6 mps --------- mps AP 0 7.6 15.2 22.8 30.4 38 45.6 gpm Flow Rate 5 7.5 10 fps bars psi 11h"(40mm) 1.5 2.3 3.0 mps H • bars psi 3/a"(20mm) Flow Rate .7 12 * 0 . y 1.5 22 7 10 m .5 8 3 1.2 18 H .4 6 _ .96 14 m .3 4 T H .69 10 0. .12 CD .41 6 APO 10 20 30 40 50 60 70 80 90 100 110 120 gpm a 1^� 0 38 76 114 152 190 228 266 304 342 380 418 456 1pm f` .14 2 5 7.5 10 15 fps AP 0 5 10 15 20 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps 0 19 30 57 76 95 114 133 152 171 190 1pm Flow Rate 7.5 15 2.3 4.6 imps bars psi 2"(50mm) m bars psi 1„(25mm) * Flow Rate m .8 12 m 1.1 16, o .7 10 0 .8 12 .5 8 41 .7 10 .4 6 5 8 H .3 4 m .3 4 a 1 2 o. .1 2 0 0 - . 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 1pm 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm AP 1.5 2.3 3.0 19 38 57 76 95 114 133 152 171 190 209 228 1pm 5 7.5 . 15 fps 5 7.5 10 15 0 4.6 mps 1.5 2.3 3.0 4.6 fps Flow Rate mps Flow Rate A I IMPORTANT In with governing authorities for local quire installation requirements. I A M E S A Division of Watts Industries ISO 9001 & FIRE WATERWORKS f es www.amesfirewater.com CERTIFIED �,._; 875 National Drive • Suite #107 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 ES-A-2000B 0313 ©Ames Co.2003 Printed in U.S.A.