Specifications . 201a- coo v.1 f DATE: 4/30/2013 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 C: \HASS74\ARLINGTON77 . SDF , JOB TITLE: Arlington Heights Lot #77 te61410 IN.M1rre■teViCLU WATER SUPPLY DATA - SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ' D RECEIVED NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS . TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) APR 3 0 2013 8 118 . 0 54 . 0 12 3 0. 0 117 . 9 27 . 6 6 2 . 3 CITY OF TIGARD BUILDING DIVISION AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 27 . 6 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0. 0 GPM OTHER HOSE STREAM ALLOWANCES 0. 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 27 . 6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 9 . 0 K= 4 . 90 7 . 0 13 . 0 2 9 . 0 K= 4 . 90 8 . 8 14 . 6 3 9 . 5 - - - - 13 . 4 - - - . 4 18 . 5 - - - - 25 . 3 - - - 5 8 . 0 - - - - 38 . 0 - - - 6 1 . 0 - - - - 42 . 5 - - - - 7 1 . 0 - - - - 46. 5 - - - 8 0 . 0 SOURCE 62 . 3 27 . 6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 4/30/2013 C: \HASS74\ARLINGTON77 . SDF .JOB TITLE: Arlington Heights Lot #77 PIPE DATA - PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ . PT DISC. VEL (FPS) HW (C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13 . 0 0 . 874 PL 17 . 00 PF 1 . 8 1 9 . 0 4 . 9 7 . 0 13. 0 6. 9 150 FTG 2E PE 0. 0 2 9 . 0 4 . 9 8 . 8 14 . 6 0 . 094 TL 19 . 49 PV Pipe: 2 -27 . 5 0 . 874 PL 9. 50 PF 4 . 8 2 9 . 0 4 . 9 8 . 8 14 . 6 14 . 7 150 FTG T PE -0 . 2 3 9 . 5 0. 0 13. 4 0. 0 0 . 378 TL 12 . 61 PV Pipe: 3 -27 . 5 0 . 874 PL 30 . 00 PF 15 . 8 3 9. 5 0 . 0 13. 4 0.0 14 .7 150 FTG 2E3T PE -3. 9 4 18 .5 0 . 0 25 . 3 0. 0 0 . 378 TL 41 . 80 PV Pipe: 4 -27 . 5 0. 874 PL 16. 00 PF 8 .2 4 18 . 5 0 . 0 25. 3 0. 0 14 . 7 150 FTG 2ET PE 4 . 5 5 8 . 0 0 . 0 38 . 0 0.0 0 . 378 TL 21 . 59 PV Pipe: 5 -27 . 5 1 . 080 PL 7 . 00 PF 1 . 4 5 8 . 0 0. 0 38 . 0 0 . 0 9 . 6 120 FTG ---- PE 3 . 0 6 1 . 0 0 . 0 42 . 5 0. 0 0 . 204 TL 7 . 00 PV Pipe: 6 FIXED PRESSURE LOSS DEVICE 7 1 . 0 0 . 0 46. 5 0 .0 4 . 0 psi, 27 . 5 gpm 6 1 . 0 0. 0 42 . 5 0 . 0 Pipe : 7 -27 . 6 1 . 101 PL 125 . 00 PF 15 . 4 7 1 . 0 0 . 0 46. 5 0 .0 9 . 3 150 FTG ---- PE 0 . 4 8 0 . 0 SRCE 62 . 3 (N/A) 0 . 123 TL 125 . 00 PV NOTES: (1) Calculations were performed by the HASS 7 . 4 computer program under license no. 5010113212 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0. 024 gpm and a maximum imbalance at any node of 0. 166 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14 . 7 ft/sec at pipe 2 . (▪ 4) PIPE FITTINGS TABLE , Pipe Table Name : STANDARD. PIP SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 4/30/2013 C: \HASS74\ARLINGTON77 . SDF . JOB TITLE: Arlington Heights Lot #77 PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet - (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NPTee 0. 874 0 . 82 2 . 06 0. 82 2 . 06 2 . 47 0 . 41 4 . 11 4 . 11 2 . 06 1. 080 2 . 30 5 .76 2 . 30 5 . 76 6 . 91 1 . 15 11 . 52 11 . 52 5 . 76 1 . 101 2 . 53 6. 33 2 . 53 6. 33 7 . 59 1.27 12 . 66 12 . 66 6. 33 • O ' W C+7 WATER SUPPLY ANALYSIS H .. Static: 118.00 psi Resid: 54.00 psi Flow: 1230.0 gpm 1-1 A 140. 0 LTJ w LEGEND • N �t O H- w 1 \ 1 Available pressure 117. 94 psi @ 27. 6 gpm o G112.0 2 Required pressure A 62.27 psi @ 27.6 gpm x b m G • Z � x E rr r ( m p o m R 84.0 — `* * E m S X S x K U U R 2 ui C E 56.0 H n P •. zz s '' iK 1 > cn u) 28.0 r H z c) H 0 z 0.0 ro -J a • ,Q W co U -14 .7 1 I 1 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) ttjco /Fire & Building alft Products rapid response HOME FIRE SPRINKLER SYSTEM Technical Services:Tel: (800)381-9312/Fax:(800)791-5500 Series LFIi Residential Horizontal Sidewall Sprinklers 4.2 K-factor General adjustment or up to 1/2 inch(12,7 mm) of total adjustment from the flush mounting surface position.The adjust- Description ment provided by the Recessed Es- cutcheon reduces the accuracy to The Series LFII (TY1334) Residential which the pipe nipples to the sprinklers k" Horizontal Sidewall Sprinklers are must be cut. decorative, fast response, frangible )01 The Series LFII TY1334 has been bulb sprinklers designed for use in ( ) residential occupancies such as designed with heat sensitivity and • homes, apartments, dormitories, and water distribution characteristics Y F hotels.When aesthetics and optimized proven to help in the control of residen �it 11 flow characteristics are the major con- occupants to escape tial fires or be evacuated.res and to improve the chance for i I • sideration, the Series LFII (TY1334) P P should be the first choice. The Series LFII are to be used in wet WARNINGS pipe residential sprinkler systems for The Series LFii(TY1334)Residential one-and two-family dwellings and mo- Horizontal Sidewall Sprinklers de- bile homes per NFPA 13D; wet pipe scribed herein must be installed and residential sprinkler systems for resi- maintained in compliance with this dential occupancies up to and includ- document,as well as with the applica- ing four stories in height per NFPA ble standards of the National Fire Pro- '� 13R;or, wet pipe sprinkler systems for tection Association, in addition to the -,‘ the residential portions of any occu- standards of any other authorities hay- "*4 , pancy per NFPA 13. ing jurisdiction. Failure to do so may ' ,tx • The Series LFII (TY1334) has a 4.2 impair the performance of these de- )`ff (60,5) K-factor that provides the re- vices. quired residential flow rates at reduced The owner is responsible for maintain- P ressures,enabling smaller pipe sizes in g their fire s y stem and de- '" and water supply requirements. vices in proper operating condition. The installing contractor or sprinkler The recessed version of the Series g p LFII (TY1334) is intended for use in manufacturer should be contacted -R•:' `' areas with finished walls. It employs a with any questions. two-piece Style 20 Recessed Escutch- eon. The Recessed Escutcheon pro- vides 1/4 inch (6,4 mm) of recessed Sprinkler/it/lode! Identification IMPORTANT Number Always refer to Technical Data Sheet TFP700 for the "INSTALLER SIN TY1334 WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 JANUARY, 2006 TFP410 Page 2 of 8 TFP41O Components: 5 3 2 1 1 - Frame i 2 Button Assembly �tb.''�►�`a WRENCH I 3- Sealing Assembly 'i �f;' 0 e— pr Nit 4 Bulb 0 5- Compression Screw `AWNON 1 6- Deflector* DEFLECTOR-OF- 6* 4 —�{ 7/1NO(11,1 mm) ' A�1��III�IIIIIIl *Temperature rating MAKE-IN • ! 7380"DIA. is indicated on top �- of Deflector. II a CENTERLINE 7/16" I��° J. II OF WATERWAY Ih STYLE 20 (11,1 mm) ' 1/2"NPT RECESSED ��_ 1-5/8" ` ESCUTCHEON END-OF- (41,3 mm) ESCUTCHEON DEFLECTOR 2-1/4" -� PLATE SEATING BOSS F—(57,2 mm) SURFACE RECESSED FIGURE 1 SERIES LFII(TY1334)RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS y 7/16±1/8" le.; (11,1±3,2 mm) /"WRENCH MOUNTING FACE OF RECESS SURFACE - SPRINKLER (END"A"USED FITTING FOR TY1334) . 1 DEFOLECOTOR CLOSURE 111111 FIGURE 3 W-TYPE 6 SPRINKLER WRENCH TY1334 2-7/8"DIA. (73,0 mm) WRENCH ii���•F'III�I (57,2-1 "m DIA. RECESS 7/16" (11,1 mm) IMI Vt4r* MOUNTING IIA PLATE END-OF- DEFLECTOR t'" 1/8" BOSS (3,2 mm) PUSH WRENCH IN TO ENSURE 1-3/8"(34,9 mm) _ 1/2"(12,7 mm) ENGAGEMENT 1-1/8"(28,6 mm) 1/4"(6,4 mm) WRENCHING AREA > FIGURE 2 FIGURE 4 W-TYPE 7 RECESSED STYLE 20 RECESSED ESCUTCHEON SPRINKLER WRENCH FOR USE WITH THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER I 4. % • TFP41O Page 3 of 8 Technical total number of"design sprinklers" as Do not attempt to compensate for in- specified in NFPA 13D or NFPA 13R. sufficient adjustment in an Escutcheon Plate by under-or over-tightening the For systems designed to NFPA 13,the Data number of design sprinklers is to be Sprinkler. Readjust the position of the the four most hydraulically demanding sprinkler fitting to suit. Approvals: Y Y UL and C-UL Listed. NYC Approved sprinklers. The minimum required dis- The Series LFII Horizontal Sidewall under MEA 44-03-E. charge from each of the four sprinklers Sprinklers must be installed in ac- is to be the greater of the following: cordance with the following instruc- Maximum Working Pressure: tions. 175 psi (12,1 bar) • The flow rates given in Tables A, B, Discharge Coefficient: C, and D for NFPA 13D and 13R as Step 1. Horizontal sidewall sprinklers K=4.2 Gsi11z (60,5 LPM/bar��2) a function of temperature rating and are to be installed in the horizontal the maximum allowable coverage position with their centerline of water- Temperature Rating: area. way perpendicular to the back wall and 155°F/68°C or 175°F/79°C • A minimum discharge of 0.1 gpm/sq. parallel to the ceiling.The word"TOP" Finishes: ft. over the"design area"comprised on the with the is front face towards the De- White Polyester Coated, of the four most hydraulically de- ceiling with the front edge of the De Hector parallel to the ceiling. Chrome Plated, or Natural Brass manding sprinklers for the actual coverage areas being protected by Step 2. With pipe thread sealant ap- Physical Characteristics: the four sprinklers. plied to the pipe threads, hand tighten Frame Brass Obstruction To Water Distribution. the sprinkler into the sprinkler fitting. Button Bronze Locations of sprinklers are to be in Step 3. Tighten the sprinkler into the Sealing Assembly accordance with the obstruction rules sprinkler fitting using only the W-Type Beryllium Nickel of NFPA 13 for residential sprinklers. 6 Sprinkler Wrench (Ref. Figure 3). Bulb 3 mm dia.a. Glass lass With reference to Figure 1,the W-Type Compression Screw Bronze Operational Sensitivity. The sprin- 6 Sprinkler Wrench is to be applied to Deflector Copper klers are to be installed with an end-of- the wrench flats. deflector-boss to wall distance of 1- tDupont Registered Trademark 3/8 to 6 inches or in the recessed po- The Series LFII Recessed Horizontal sition using only the Style 20 Re- Sidewall Sprinklers must be installed cessed Escutcheon as shown in in accordance with the following in- Operation Figure 2. structions. The glass Bulb contains a fluid that In addition the top-of-deflector-to-cell- Step A. Recessed horizontal sidewall expands when exposed to heat.When ing distance is to be within the range sprinklers are to be installed in the the rated temperature is reached, the (Ref. Table A, B, C, or D) being hy- horizontal position with their centerline fluid expands sufficiently to shatter the draulically calculated. of waterway perpendicular to the back glass Bulb allowing the sprinkler to Sprinkler Spacing. The minimum wall and parallel to the ceiling. The activate and flow water. spacing between sprinklers is 8 feet word"TOP"on the Deflector is to face (2,4 m). The maximum spacing be- towards the ceiling. Design tween sprinklers cannot exceed the Step B. After installing the Style 20 width of the coverage area(Ref.Table Mounting Plate over the sprinkler Criteria A)being hydraulically calculated(e.g., threads and with pipe thread sealant maximum 12 feet for a 12 ft. x 12 ft. applied to the pipe threads, hand The Series LFII (TY1334) Residential coverage area,or 16 feet for a 16 ft. x tighten the sprinkler into the sprinkler Horizontal Sidewall Sprinklers are UL 20 ft.coverage area). fitting. and C-UL Listed for installation in ac- Step C. Tighten the sprinkler into the cordance with the following criteria. Installation sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. NOTE The Series LFII (TY1334) must be in- Figure 4). With reference to Figure 1, When conditions exist that are outside stalled in accordance with the follow the W-Type 7 Recessed Sprinkler the scope of the provided criteria,refer ing instructions: Wrench is to be applied to the sprinkler to the Residential Sprinkler Design NOTES wrench flats. Guide TFP490 for the manufacturer's Do not install any bulb type sprinkler if Step C. After the wall has been in- recommendations that may be accept- the bulb is cracked or there is a loss of stalled or the finish coat has been ap- able to the local Authority Having Ju- liquid from the bulb. With the sprinkler plied, slide on the Style 20 Closure risdiction. held horizontally, a small air bubble over the Series LFII Sprinkler and System Type. Only wet pipe systems should be present. The diameter of the push the Closure over the Mounting may be utilized. air bubble is approximately 1/16 inch Plate until its flange comes in contact (1,6 mm). with the wall. Hydraulic Design. The minimum re- quired sprinkler flow rate for systems A leak tight 1/2 inch NPTsprinklerjoint designed to NFPA 13D or NFPA 13R should be obtained with a torque of 7 are given in Table A, B, C,and D as a to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- , function of temperature rating and the mum of 21 ft.lbs. (28,5 Nm) of torque maximum allowable coverage areas. is to be used to install sprinklers. The sprinkler flow rate is the minimum Higher levels of torque may distort the required discharge from each of the sprinkler inlet with consequent leak- age or impairment of the sprinkler. (Continued on Page 8) Page 4 of 8 TFP41O ELEVATION Maximum Maximum Coverage Spacing Minimum Flow(C)and Residual Pressure Area(al Ft. Width x Length(b) (m) Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: Ft.x Ft. 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) (m x rn) 155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C 12 x 12 12 12 GPM(45,4 LPM) 12 GPM(45,4 LPM) 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) (3,7 x 3,7) (3,7) 8.2 psi(0,57 bar) 8.2 psi(0,57 bar) 9.6 psi(0,66 bar) 9.6 psi(0,66 bar) 14 x 14 14 14 GPM(53,0 LPM) 16 GPM(60,6 LPM) 17 GPM(64,3 LPM) 18 GPM(68,1 LPM) (4,3 x4,3) (4,3) 11.1 psi(0,77 bar) 14.5 psi(1,00 bar) 16.4 psi(1,13 bar) 18.4 psi(1,27 bar) 16 x 16 16 16 GPM(60,6 LPM) 16 GPM(60,6 LPM) 18 GPM(68,1 LPM) 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 16 19 GPM(71,9 LPM) 19 GPM(71,9 LPM) 21 GPM(79,5 LPM) 21 GPM(79,5 LPM) (4,9 x 5,5) (4,9) 20.5 psi(1,41 bar) 20.5 psi(1,41 bar) 25.0 psi(1,72 bar) 25.0 psi(1,72 bar) 16 x 20 16 23 GPM(87,1 LPM) 23 GPM(87,1 LPM) 26 GPM(98,4 LPM) 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 30.0 psi(2,07 bar) 30.0 psi(2,07 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Width (backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details. (d)Sidewall sprinklers,where installed under a ceiling with a slope greater than 0 inch rise for a 12 inch run to a slope up to 2 inch rise for 12 inch run, must be located per one of the following: • Locate the sprinklers at the high point of the slope and positioned to discharge down the slope. • Locate the sprinklers along the slope and positioned to discharge across the slope. TABLE A NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR HORIZONTAL CEILING(Maximum 2 Inch Rise for 12 Inch Run) • TFP41O Page 5 of 8 12" el 8" MAXIMUM ELEVATION Minimum Flow(c)and Residual Pressure (I)Two sprinkler design with the sprinklers at the high point of the slope and positioned to discharge down the slope. Maximum Maximum Coverage Spacing Area(a) Ft. Width x Length(b) (m) Ft.x Ft. Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: (m x m) 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) 155°FI68°C 175°F/79°C 155°F/68°C 175°F/79°C 12 x 12 12 I 12 GPM(45,4 LPM) I 12 GPM(45,4 LPM) I 13 GPM(49,2 LPM) I 13 GPM(49,2 LPM) (3,7 x 3,7) (3,7) 8.2 psi(0,57 bar) 8.2 psi(0,57 bar) 9.6 psi(0,66 bar) 9.6 psi(0,66 bar) 14 x 14 14 I 14 GPM(53,0 LPM) I 14 GPM(53,0 LPM) I 17 GPM(64.3 LPM) I 17 GPM(64.3 LPM) (4,3 x 4,3) (4,3) 11.1 psi(0,77 bar) 11.1 psi(0,77 bar) 16.4 psi(1,13 bar) 16.4 psi(1,13 bar) 16 x 16 16 I 16 GPM(60,6 LPM) I 16 GPM(60,6 LPM) I 18 GPM(68,1 LPM) I 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 16 I 19 GPM(71,9 LPM) I 19 GPM(71,9 LPM) I 21 GPM(79,5 LPM) I 21 GPM(79,5 LPM) (4,9 x 5,5) (4,9) 20.5 psi(1,41 bar) 20.5 psi(1,41 bar) 25.0 psi(1,72 bar) 25.0 psi(1,72 bar) 16 x 20 16 I 24 GPM(90,8 LPM) I 24 GPM(90,8 LPM) I 26 GPM(98,4 LPM) I 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 32.7 psi(2,25 bar) 32.7 psi(2,25 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a) For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE B NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS AT THE HIGH POINT OF THE SLOPE AND DISCHARGING DOWN THE SLOPE (Greater Than 2 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run) Page 6 of 8 TFP470 12" 4" MAXIMUM ELEVATION Minimum Flow lc)and Residual Pressure (II)Two sprinkler design with the sprinklers located along the slope and positioned to discharge across the slope. Maximum Maximum (III)Three sprinkler design when there are more than two sprinklers in a compartment and Coverage Spacing with the sprinklers located along the slope and positioned to discharge across the slope. Area(al Ft. Width x Length(b) (m) Ft.x Ft. Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: (m x m) 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) 155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C 12 x 12 12 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) 11 18 GPM(68,1 LPM) (3,7 x 3,7) (3,7) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 14 x 14 14 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) 11 18 GPM(68,1 LPM) (4,3 x 4,3) (4,3) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 16 16 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) II 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 16 II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) (4,9 x 5,5) (4,9) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 16 x 20 16 III 23 GPM(87,1 LPM) III 23 GPM(87,1 LPM) III 26 GPM(98,4 LPM) III 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 30.0 psi(2,07 bar) 30.0 psi(2,07 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a) For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE C NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFI1(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE (Greater Than 2 Inch Rise for 12 Inch Run Up To 4 Inch Rise for 12 Inch Run) TFP410 Page 7 of 8 12" 8" MAXIMUM ELEVATION Minimum Flow(C)and Residual Pressure (III)Three sprinkler design when there are more than two sprinklers in a compartment and with the sprinklers located along the slope and positioned to discharge across the slope. Maximum Maximum Coverage Spacing Area(a) Ft. Width x Length(b) (m) Ft.x Ft. Top-Of-Deflector-To-Ceiling: (m x m) 4 to 6 Inches(100 to 150 mm) 155°FI68°C l75F/79°C 12 x 12 12 111 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (3,7 x 3,7) (3,7) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 14 x 14 14 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (4,3 x 4,3) (4,3) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 16 x 16 16 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 16 x 18 16 N/A N/A (4,9 x 5,5) (4,9) 16 x 20 16 N/A N/A (4,9 x 6,1) (4,9) (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler)_ (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE D NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE (Greater Than 4 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run) Page 8 of 8 TFP41O Care and Limited Ordering Maintenance Warranty Procedure The Series LFII (TY1334) must be Products manufactured by Tyco Fire& When placing an order, indicate the maintained and serviced in accord- Building Products (TFBP) are war- full product name. Contact your local ance with the following instructions: ranted solely to the original Buyer for distributor for availability.. ten(10)years against defects in mate- Sprinkler Assembly: Absence of an Escutcheon Plate may rial and workmanship when paid for delay the sprinkler operation in a fire and properly installed and maintained Series LFII(TY1334),K=4.2,Residen- situation. under normal use and service. This tial Horizontal Sidewall Sprinkler with warranty will expire ten (10) years (specify) temperature rating and Before closing a fire protection system from date of shipment by TFBP. No (specify)finish, P/N (specify). main control valve for maintenance warranty is given for products or corn- work on the fire protection system ponents manufactured by companies 155°F/68°C or which it controls, permission to shut not affiliated by ownership with TFBP Chrome Plated P/N 51-211-9-155 down the affected fire protection sys- or for products and components which 155°F/68°C tern must be obtained from the proper p p White Polyester P/N 51-211-4-155 authorities and all personnel who may have been subject to misuse,improper 155°F/68°C be affected by this action must be no- installation, corrosion, or which have White y not been installed, maintained, modi- (RAL9010)' P/N 51-211-3-155 tified. fled or repaired in accordance with ap- 155°F/68°C l Sprinklers which are found to be leak- plicable Standards of the National Fire Natural Brass P/N 51-211-1-155 P p 17s°Fns°c or ing or exhibiting visible signs of corro- Protection Association, and/or the Chrome Plated P/N 51-211-9-175 sion must be replaced. standards of any other Authorities 175*F/79°C Automatic sprinklers must never be Having Jurisdiction. Materials found 175 Fite Polyester P/N 51-211-4-175 painted, plated, coated, or otherwise by TFBP to be defective shall be either White altered after leaving the factory. Modi- repaired or replaced, at TFBP's sole (RAL9010)° P/N 51-211-3-175 fied sprinklers must be replaced. option. TFBP neither assumes, nor 175°F/79°C Sprinklers that have been exposed to authorizes any person to assume for it, Natural Brass P/N 51-211-1-175 corrosive products of combustion, but any other obligation in connection with *Eastern Hemisphere sales only. have not operated,should be replaced the sale of products or parts of prod- if they cannot be completely cleaned ucts.TFBP shall not be responsible for Recessed Escutcheon: by wiping the sprinkler with a cloth or sprinkler system design errors or inac- . by brushing it with a soft bristle brush. curate or incomplete information sup- Specify: Style 20 Recessed Escutch- Care must be exercised to avoid dam- plied by Buyer or Buyer's repre- eon with (specify*) finish, P/N (spec- age to the sprinklers - before, during, sentatives. ify )• and after installation. Sprinklers dam- In no event shall TFBP be liable, in *Refer to Technical Data Sheet TFP770. aged by dropping, striking, wrench contract, tort, strict liability or under twist/slippage, or the like, must be re- any other legal theory, for incidental, placed.Also,replace any sprinkler that indirect,special or consequential dam- Sprinkler Wrench: has a cracked bulb or that has lost ages, including but not limited to labor Specify: W-Type 6 Sprinkler Wrench, liquid from its bulb. (Ref. Installation charges, regardless of whether TFBP P/N 56-000-6-387. Section). was informed about the possibility of Specify: W-Type 7 Sprinkler Wrench, The owner is responsible for the in- such damages, and in no event shall P/N 56-850-4-001. spection,testing, and maintenance of TFBP's liability exceed an amount their fire protection system and de- equal to the sales price. vices in compliance with this docu- The foregoing warranty is made in lieu ment, as well as with the applicable of any and all other warranties. ex- standards of the National Fire Protec- press or implied. including warranties tion Association (e.g., NFPA 25), in of merchantability and fitness fora par- addition to the standards of any other ticular purpose. authorities having jurisdiction. The in- stalling contractor or sprinkler manu- This limited warranty sets forth the ex- facturer should be contacted relative clusive remedy for claims based on to any questions. failure of or defect in products,materi- NOTE als or components, whether the claim The owner must assure that the sprin- is made in contract, tort, strict liability k/ers are not used for hanging of any or any other legal theory. objects and that the sprinklers are only This warranty will apply to the full ex- cleaned by means of gently dusting tent permitted by law.The invalidity,in . with a feather duster;otherwise, non- whole or part, of any portion of this operation in the event of a fire or inad- warranty will not affect the remainder. vertent operation may result. It is recommended that automatic ' sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 1-11CO Fire Suppression & Building Products rapid response• Technical Services 800-381-9312 +1-401-781-8220 HOME FIRE SPRINKLER SYSTEM www.tyco-fire.com 1 iff Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General The Series LFII Residential Flat-Plate Concealed Pendent Sprinkler has a 4.9 Description (60,5)K-factor that provides the required residential flow rates at reduced pres- _ The TYCO RAPID RESPONSE Series sures,enabling smaller pipe sizes and �,u'r. LFII Residential Flat-Plate Concealed water supply requirements. Pendent Sprinklers(TY2524)are decora- This sprinkler has been designed with '' '._7.'"' ' tive,fast response,fusible solder sprin- heat sensitivity and water distribution ____ klers designed for use in residential oc- characteristics proven to help in the con- cupancies such as homes, apartments, trol of residential fires and to improve , - -- dormitories,and hotels. - - the chance for occupants to escape or ..--. • The Cover Plate/Retainer Assembly con- be evacuated. rrt.:1 s, ceals the sprinkler operating compo- F-''` .">�;f;,,"n`w •" nents above the ceiling.The flat profile The Series LFII Residential Flat-Plate of the Cover Plate provides the optimum Concealed Pendent Sprinklers are shipped with a Disposable Protective aesthetically appealing sprinkler design. Cap.The Protective Cap protects the Additionally,the concealed design of the sprinkler during ceiling installation or _Series-LFII-Residential-Flat-Plate Con------— ------- ---------finish:=After-ceiling'iristallation=is com =---=Technical cealed Pendent Sprinklers provides 1/2 plete, the Protective Cap is removed inch(12,8 mm)vertical adjustment.This and the Cover Plate/Retainer Assem- Data adjustment provides a measure of flex- bly is installed. Removing the Protec- ibility when cutting fixed pipe drops. tive Cap is required for proper sprinkler Approvals The Series LFiI Residential Flat-Plate performance. UL and C-UL Listed Concealed Pendent Sprinklers are in- NSF-61 Certified tended for use in the following systems: NOTICE The Series LFII Residential Flat-Plate • per NFPA 13D, wet pipe residential The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only sprinkler systems for one- and two- Concealed Pendent Sprinklers(TY2524) listed with the Series LFII Concealed family dwellings and mobile homes; described herein must be installed and Cover Plates having a factory-applied •per NFPA 13R, wet pipe residential maintained in compliance with this doc- finish. sprinkler systems for pipe oc- ument and with the applicable standards cupnkler s up to and including four of the National Fire Protection Associa- Maximum Working Pressure Lion,in addition to the standards of any 175 psi(12,1 bar) stories in height;and authorities having jurisdiction. Failure •per NFPA 13,wet pipe sprinkler sys- to do so may impair the performance Discharge Coefficient K=4.9 GPM/psi' tems for the residential portions of of these devices. (70,6 LPM/bar's any occupancy. Owners are responsible for maintaining Temperature Rating their fire protection system and devices Sprinkler: 160°F(71°C) in proper operating condition. The in Cover Plate: 139°F(59°C) IMPORTANT stalling contractor or sprinkler manu- facturer Vertical Adjustment Always refer to Technical Data should be contacted with any 1/2 inch (12,7 mm) Sheet TFP700 for the "INSTALLER questions. WARNING" that provides cautions Finishes with respect to handling and instal- Model/Sprinkler Refer to the Ordering Procedure lation of sprinkler systems and corn- section. ponents. Improper handling and in- identification Physical Characteristics stallation can permanently damage a sprinkler system or its components �/ • Cover Plate/Retainer Assembly: and cause the sprinkler to fail to Number (SIN) • Cover Plate Copper operate in a fire situation or cause it TY2524 Ejection Spring . . . . Stainless Steel to operate prematurely. Retainer Brass Page 1 of 6 OCTOBER 2010 TFP443 • TFP443 Page 2 of 6 Horizontal Ceiling Sloped Ceiling Sloped Ceiling Minimum Flowoo and Minimum Floweland Minimum Flowwand Residual Pressure Residual Pressure Residual Pressure Maximum Maximum (Maximum 2-inch rise (Greater than 2-inch rise (Greater than 4-inch rise Coverage Spacing for 12-inch run) up to maximum 4-inch up to maximum 8-inch Area 0) rise for 12-inch run) rise for 12-inch run) 160°F(71°C) 160°F(71°C) 160°F(71°C) Sprinkler Sprinkler Sprinkler 12'x 12' 12' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (3,7 m x 3,7 m) (3,7 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 14'x 14' 14' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,3 m x 4,3 m) (4,3 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 16'x 16' 16' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,9 m x 4,9 m) (4,9 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) • 18'x 18' 18' 17 GPM(64,3 LPM) 22 GPM(83,3 LPM) 22 GPM(83,3 LPM) (5,5 m x 5,5 m) (5,5 m) 12.0 psi(0,83 bar) 20.2 psi(1,39 bar) 20.2 psi(1,39 bar) 20'x 20' 20' 20 GPM(75,7 LPM) 24 GPM(90,8 LPM) 24 GPM(90,8 LPM) (6,1 m x 6,1 m) (6,1 m) 16.7 psi(1,15 bar) 24.0 psi(1,65 bar) 24.0 psi(1,65 bar) (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b)The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each_sprinkler The associated residual pressures.are calculated using the nominal K-factor.Refer to"Hydraulic Design'in the Design Criteria section for details. TABLE A SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS • Body Cup Assembly: Design For systems designed to NFPA 13,the - -- ---- - y Brass _ ___ _number of design spdnklers_is_to_be__._ Cap�7.�-:.:--.-::_.-.-Bronze=--- __ _ '_ _ _ ___ _ _ __ - Saddle Brass Criteria - - -the four most hydraulically--demanding--- - - - Saddl Assembly sprinklers.The minimum required dis- Sealing y . . .. . . .Beryllium The TYCO RAPID RESPONSE Series charge from each of the four sprinklers Nickel w/Teflont LFII Residential Flat-Plate Concealed is to be the greater of the following: Soldered Link Halves Nickel Pendent Sprinklers (TY2524) are UL Bronze •flow rates given in Table A for NFPA Compression Screw Bras s e C-UL Listed for installation in ac- 13D and 13R as a function of tern- Deflector Bronze cordance with the following criteria. perature rating and the maximum al- Guide Pin Housing . Bronze towable coverage area Guide Pins Bronze NOTICE • minimum discharge of 0.1 GPM/ Support Cup Steel When conditions exist that are outside sq. ft. over the "design area" com- the scope of the provided criteria, re- prised of the four most hydraulically fer to the Residential Sprinkler Design demanding sprinklers for actual cov- Operation Guide TFP490 for the manufacturer's erage areas protected by the four recommendations that may be accept- sprinklers When exposed to heat from a fire,the able to the Authority Having Jurisdiction. Cover Plate,which is normally soldered The Series LFII Residential Flat Plate Obstruction To Water Distribution to the Retainer at three points,falls away Concealed Pendent Sprinklers must to expose the Sprinkler/Support Cup As- Locate sprinklers in accordance with the obstruction rules of NFPA for residential sembly.At this point,the Deflector,sup- not be used in app/ications where the sprinklers as well as obstruction criteria ported by the Guide Pins, drops down air pressure above the ceiling is greater p than that below. Down drafts through described within TYCO technical data to its operated position. sheet TFP490. the Support Cup can delay sprinkler op The Solder Link Element of the Sprinkler/ eration in a fire situation. Operational Sensitivity Support Cup Assembly is comprised of Install rinklers relative to the ceilin two link halves that are soldered togeth- System Type p g er with a thin layer of solder. When the Only wet pipe systems may be utilized. mounting surface as shown in Figure 3. • rated temperature is reached, the sot- Sprinkler Spacing Hydraulic Design der melts and the two link halves se a- p Table A provides the minimum required The minimum spacing between sprin- rate, allowing the sprinkler to activate klers is 8 feet(2,4 m). and flow water. sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R as a function The maximum spacing between sprin- of temperature rating and the maximum klers cannot exceed the length of the allowable coverage areas.The sprinkler coverage area(Table A)being hydrau- flow rate is the minimum required dis- lically calculated; for example, a maxi- charge from each of the total number of mum of 12 feet for a 12 ft.x 12 ft. cov- 1 Registered trademark of Dupont "design sprinklers"as specified in NFPA erage area or 20 feet for a 20 ft.x 20 ft. 13D or NFPA 13R. coverage area. TFP443 Page 3 of 6 • BODY /` SEALING (1/2 NPT) sr� ASSEMBLY CAP 4y i______ ��1 SPRINKLER i� �`I/� � WRENCHING SADDLE 1 �� `\7.3; �1 j AREA SUPPORT COMPRESSION CUP WITH r SCREW ROLL FORMED THREADS ;��II i LEVER WRENCH L`, „ „ �t RECESS GUIDE I '�_�' PIN ■,_.;....•.■...... I 1 SOLDER LINK (� °') I ELEMENT %Iiid i GUIDE PIN Mr HOUSING `J DEFLECTOR J -' I (OPERATED PUSH WRENCH DEFLECTOR r_ -z---- ---_�_7 I POSITION) IN TO ENSURE SPRINKLER/SUPPORT CUP ENGAGEMENT ASSEMBLY I WITH SPRINKLER I WRENCHING AREA THREAD INTO SUPPORT CUP I RETAINER UNTIL MOUNTING 1 WITH THREAD DIMPLES FIGURE SURFACE IS 0 O W-TYPE 18 FLUSH WITH ) EJECTION SPRINKLER WRENCH - -CEILING- - —-- - - SPRING- - - - _ -• '-I _ SOLDER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE • FIGURE 1 FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) ASSEMBLY 2-1/2'DIA. SPRINKLER- 1---- (63,5 mm) 1/2'(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING OPERATED 1.__ r SPRINKLER I �� ���Ilit3 1-7/8't1/8' COVER fl (47,6 mm PLATE iri I 1/8'GAP ±3,2 mm) RETAINER V 1J� w,„___ (3.2 mm) _ .„, _. : _._._.-_� liml COVER- SPRINKLER- MOUNTING 7/8'(22,2 mm) RETAINER SUPPORT CUP 3/16" SURFACE 1-1/8"(28,6 mm) -����� - ASSEMBLY ASSEMBLY (4,8 mm) M. • 3-3/16'DIA. _ DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 PROTECTIVE CAP AND ACTIVATED DEFLECTOR INSTALLATION DIMENSIONS ' TFP443 Page 4 of 6 Installation 6. Screw on the Cover Plate/Retainer Replace sprinklers that: Assembly until its flange contacts The TYCO RAPID RESPONSE Series the ceiling. • were damaged by dropping, striking, LFII Residential Flat-Plate Concealed Do not continue to screw on the wrench twisting, wrench slippage, or Pendent Sprinklers must be installed Cover Plate/Retainer Assembly such the like. in accordance with the following that it lifts a ceiling panel out of its • were modified or over-heated. instructions, normal position. • are leaking or exhibiting visible signs NOTICE If the Cover Plate/Retainer Assembly of corrosion. cannot be engaged with the Mounting Responsibility lies with owners for the Damage to the Solder Link Element dur- Cup or the Cover Plate/Retainer As- inspection,testing, and maintenance of ing installation can be avoided by han- sembly cannot be engaged sufficiently their fire protection system and devices dling the sprinkler by the Support Cup to contact the ceiling,the Sprinkler in compliance with this document, as only,-that is, do not apply pressure to the Fitting must be repositioned. well as with the applicable standards of Solder Link Element(Figure 1). the National Fire Protection Association Obtain a leak-tight 1/2 inch NPTsprinkler Care and (for example, NFPA 25),in addition to joint by applying a minimum-to-maxi- the standards of any other authorities mum torque of 7 to.14 ft.-lbs.(9,5 to 19,0 Maintenance having jurisdiction.Contact the install- Nm). Higher levels of torque can distort ing contractor or sprinkler manufacturer the sprinkler inlet with consequent leak- The TYCO RAPID RESPONSE Series regarding any questions. age or impairment of the sprinkler. LFII Residential Flat-Plate Concealed Automatic sprinkler systems are rec- Do not aftem t to com ensafe for in- Pendent Sprinkler(TY2524) must be p p maintained and serviced in accordance o d maim i to be inspected, tested, sufficient adjustment in the Cover Plate/ and maintained by a qualified th loc - Retainer Assembly by under-or over- with the following instructions. tion Service in accordance with local tightening the sprinkler. Re-adjust the requirements and/or national codes. position of the sprinkler fitting to suit. NOTICE �. Install pendent sprinklers in the Before closing a fire protection system pendent position, with the center- main control valve for maintenance work line of the sprinkler perpendicular on the fire protection system that it con- to the mounting surface. trols,obtain permission to shut down the affected fire protection system from the 2. Remove the Protective Cap. proper authorities and notify all person 3. With pipe-thread sealant applied nel who maybe affected by this action. __._. _________ to the_pipe_threads, and_.using the__JNhen:propedy_installed,-there-is-a-nomi-- _---_---- - - --.. —-.- WType 18 Wrench shown in Figure nal 1/8 inch (3,2 mm)air gap between - -- --- - - -- - '" 2, install and tighten the Sprinkler/ the lip of the Cover Plate and the ceil- - Support Cup Assembly into the fit- ing,as shown in Figure 3.This air gap ting. The W Type 18 Wrench ac- is necessary for proper operation of the cepts a 1/2 inch ratchet drive. sprinkler by allowing heat flow from a 4. Replace the Protective Cap by fire to pass below and above the Cover pushing it upwards until it bottoms Plate to help assure appropriate release out against the Support Cup. The of the Cover Plate in a fire situation.If the Protective Cap helps prevent dam- ceiling needs repainting after sprinkler age to the Deflector and Guide installation,exercise care to ensure that Pins during ceiling installation and/ the new paint does NOT seal off any of or during application of the finish the airgap. Failure to do so may impair coating of the ceiling. sprinkler operation. Absence of a Cover Plate can delay the NOTICE sprinkler operation in a fire situation. As long as the protective Cap re- Do not pull the Cover Plate relative to mains in place, the system is con- the Enclosure.Separation may result. sidered"Out Of Service" Exercise care to avoid damage to sprin- 5. After the ceiling has been com- klers before, during,and after installa- pleted with the 2-1/2 inch (63 mm) tion.Never paint, plate, coat, or other- diameter clearance hole and in wise alter automatic sprinklers after they preparation for installing the Cover leave the factory. Plate/Retainer Assembly, remove Never repaint factory-painted Cover and discard the Protective Cap, Plates.When necessary,replace cover and verify that the Deflector moves plates with factory-painted units. Non- ' up and down freely. factory applied paint can adversely de- li the Sprinkler has been damaged lay or prevent sprinkler operation in the and the Deflector does not move up event of a fire. . and down freely, replace the entire Sprinkler assembly.Do not attempt to modify or repair a damaged sprinkler. TFP443 Page 5 of 6 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression & Building Products ability. When placing an order, indicate (TFSBP)are warranted solely to the prig- the full product description and Part inal Buyer for ten(10)years against de- Number(P/N). fects in material and workmanship when paid for and properly installed and main- Sprinkler/Support Cup Assembly Specify: Series LFII Residential Flat tained under normal use and service. This warranty will expire ten (10)years Plate Concealed Pendent Sprinkler from date of shipment by TFSBP. No (TY2524), K=4.9,without Cover Plate/ warranty is given for products or com Retainer Assembly, P/N 51-114-1-160. ponents manufactured by companies Cover Plate/Retainer Assembly not affiliated by ownership with TFSBP Specify: Cover Plate/Retainer Assem- or for products and components which bly with finish (below) for the Series have been subject to misuse, improper LFII Residential Flat-Plate Concealed installation,corrosion,or which have not Pendent Sprinkler(TY2524),K=4.9, P/N been installed, maintained,modified or (below): repaired in accordance with applicable Standards of the National Fire Protection Chrome P/N 56-201-9-135 Association,and/or the standards of any Custom P/N 56-201-X-135 other Authorities Having Jurisdiction. Off White P/N 56-201-0-135 Materials found by TFSBP to be defec- tive shall be either repaired or replaced, Pure White. at TFSBP's sole option. TFSBP neither (RAL9010) P/N 56-201-3-135 assumes, nor authorizes any person to Signal white- assume for it, any other obligation in (RAL9003) P/N 56-201-4-135 connection with the sale of products or Standard White(Grey White) parts of products.TFSBP shall not be (RAL9002) P/N 56-201-5-135 responsible for sprinkler system design errors or inaccurate or incomplete in- • Eastern Hemisphere gles only. " formation supplied by Buyer or Buyer's Previously known as Bright White. representatives. Note: All Custom Cover Plates are _ —�---�—"- painted=using Sherwin i I-W7iams Interior— ---- - In no event shall TFSBP be liable,in con- Latex Paint. Contact TYCO Customer tract,tort,strict liability or under any oth- Service with any questions related to er legal theory,for incidental, indirect, custom orders. special or consequential damages,in- cluding but not limited to labor charg- Sprinkler Wrench • es, regardless of whether TFSBP was Specify W-Type 18 Sprinkler Wrench, informed about the possibility of such P/N 56-000-1-265. damages,and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties.express or implied,including warranties of mer- chantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on fail- ure of or defect in products,materials or components, whether the claim is made in contract,tort,strict liability or any oth- er legal theory. This warranty will apply to the full extent permitted by law.The invalidity,in whole or part, of any portion of this warranty will not affect the remainder. • ti/co tqCril Flow Tyco Pine Control Products Blaze) aster° FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 . www.tyco-fire.com TECHNICAL SERVICES • TEL' (800) 381-9312 • FAX: (800) 791-5500 • E-MAIL: techserv@tycofp.com ;,N NXM . ;),.?.4,:.i..:4:....1 1: CS No 19-1.5 TD915 4-1.1.20 9/2001 v • Introduction Tyco Fire Products (TFP) BlazeMaster4 CPVC pipe and the same time, they provide superior heat resistance and fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping . automatic fire sprinkler systems. They are made from a materials used in the plumbing trade. Various adapters are specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability. the art additives. TFP BlazeMaster)CPVC products are Grooved adapters connect directly to grooved end valves easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings. Technical Data Sizes: '/,"-3" Manufacture Source: U.S.A. Maximum Working Pressure: 175 psi Material: Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDR 13.5 MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and Note: See current TFP BlazeMaster Installation Instructions and ASTM F439 (Sch. 80) Technical Manual,for exact listing/approval information Color: Orange Pipe Nom.Pipe Size Avg. 0.0.Inches Avg. I.Q. Inches Wt. Lbs./Ft. Wt.1121)filled Pipe Lbs./Ft. Ft. of Pipe per Lift Wt.per Lift Lbs. 3.4" 1.050 0.874 0.17 0.43 7875 1413 1" 1.315 1.101 0.26 0.67 5040 1320 - 11/4" 1.660 1.394 0.42 1.07 2835 1191 172" 1.900 1.598 0.55 1.40 2205 1136 2" 111112E11. 2.003 0.86 2.20 1260 1063 2.875 2.423 1.26 1111.1118Miln 1215 1531 3" 3.500 2.952 1.87 4.79 720 1344 - Fittings T/O • IR Tro' no ''" �""�� Tro �;, 45° Elbow 11. Reducing 2j 90° Elbow ► {' 90° Elbow T/oz - -- - -- - T/O Al , Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt. 80050 3/4w Size Sch. 40 /6" 0.081b. No. 1 2 lb. 80025 '/," 40 6/,6" 0.09 lb. 80051 1" 40 3/6" 0.11 lb. 80032 1"X 3/4" 40 "3/46" 13/,6" 0.16 80026 1" 40 3/+" 0.14 lb. 80052 174" 40 1/4" 0.20 lb. 80027 1'/," 40 '/s" 0.21 lb. 80053 1'/z" 80 7/,6" 0.31 lb. 80028 1'12" 80 1''//,s" 0.40 lb. 80054 2" 80 3/4" 0.56 lb. 80029 2" 80 7'/ ," 0.79 lb. 80055 2'/2" 80 3/," 0.89 lb. 80030 2z" 80 �'/z" 1.14 lb. 80056 3" 80 1" 1.19 lb. 80031 3" 80 1 "/,6" 1.82 lb. 1 I . 1 I T/O ( T/02 ; I Tee T'° Reducing .p.� _ Cross �e���_ 7 Cross IIIINIAMI I T/O i I T/0 I/O' - 1 T/0 BE T/O' + T/0' T/O 1111111 T/O Pt No. Size Sch. O Wt. e Wt. 80000 ar '/," 40 T/5/6" 0.11 Ib. No,Part Size Sch. 1 T/O I 2 Wt.Ib. Part 80009 No. '/Siz," 40 Sch. 9/T/O,s" 0.13 Ib. 80001 1" 40 3/," 0.19 lb. 80015 1"x 3/4" 40 "/18" "/,s" 0.28 80010 1" 40 i5/is" 0.23 lb. 80002 1'/4" 40 7/6" 0.26 lb. 80003 1'/2" 80 1" 0.51 lb. 80011 1'14" 40 'S/,s" 0.34 lb. 80012 1'/z" 80 1'/,6" 0.67 lb. ' 80004 2" 80 1'/6" 0.90 lb. 80013 2" 80 1'/4" 1.00 lb. 80005 2'/2" 80 1'/,4" 1.59 lb. 80014 2'/2" 80 19/,6" 1.91 lb. 80006 3" 80 1"/,6" 2.41 lb. 80008 3" 80 1'3/,5" 2.89 lb. ' ISO a"v : Coupling _. _- _- Cap _ Reducer _,_ �� . Bushing Part No. Size Sch. T/0 Wt. Pe O O " '/4" ' . 80075 artNo. Siz 3/4" Sch.40 '/T/e" 0.07 Wt.Ib. Part 80100 No. 4"Size Sch. 3/ 40 T/5/,e" 0.04 Wt.Ib. 80201 80200 1'1/4"x x'/4" 40 40 77//1 6"" 00.11 04 Ib.lb. 80076 1" 40 1/8" 0.11 lb. 80101 1" 40 3/e" 0.06 lb. 80202 1'/4"x 1" 40 S/,s" 0.12 lb. 80077 13/4" 40 3/,e" 0.12 lb. 80102 13/4" 40 1/2" 0.10 Ib. 80203 1'/s"x3/4" 80 5/e" 0.16 lb. 80078 1'/s" 80 3/16" 0.25 lb. 80103 11/2" 80 5/e" 0.20 lb. 80204 11/z"x 1" 80 '/2" 0.14 lb. 80079 2" 80 '/,e" 0.38 lb. 80104 2" 80 5/e" 0.31 lb. 80205 1'/2"x 1'/4" 80 '/e" 0.17 lb. 80080 2'h" 80 3/,e" 0.67 lb. 80105 21/2" 80 '/e" 0.58 lb. 80206 2"x 3/4" 80 1/4" 0.27 lb. 80081 3" 80 3/18" 0.91 lb. 80106 3" 80 1" 0.88 lb. 80207 2"x 1" 80 "/,e" 0.26 lb. 80208 2"x 11/4" 80 '/,e" 0.24 lb. I r/O 80209 2"x 1'/2" 80 '/,8" 0.19 lb. Grooved 80215 2'/s"x 1" 80 115/1e" 0.42 lb. Coupling _ o.D. 80214 2'/:"x 1'/4" 80 1'/4" 0.45 lb. Adapter Ilin-Pipe _ I 80213 2'/2"x 1'2" 5 I . / 80 1 / 0.46 b 80211 2'/2"x 2" 80 13/4e" 0.29 lb. Part No. Size Sch. T/0 Wt. Pipe OD 80210 3"x 2" 80 2'/,e" 0.72 lb. 80160 1'/4"x 13/4" Grooved 40 2 5/1e" 0.78 lb. 174"(1.660") 80212 3"x 21/2" 80 115/18" 0.47 lb. 80161 1'/2"x 11/2" Grooved 80 2 5/1e" 0.95 lb. 11/2"(1.900") 80162 2"x 2" Grooved 80 2 5/1e" 1.42 lb. 2" (2.375") , 80163 2'/s"x 272" Grooved 80 2 5/,e" 2.28 lb. 2'/2"(2.875") ;�' - 80164 3"x 3" Grooved 80 21/4" Reducing - Tro' 3.00 lb. 3" (3.500") g _ 7 80168 3"x 76.1mm Grooved 80 2'/4" 2.72 ib. 76.1mm (3.000") Tee ,. U0' Tro' ..._.. - -- _-_ Part` = - -- - - - - - -T/O - -=-==Wt= -1- --No. Size Sch. 1 2 3 lb. Female _ 80132 3/4"x'/4"x 1" 40 3/4" 3/4" 5/e" 0.14 Adapter 111-471111111 80133 1"x 3/4"x 40 '2" "lie" 3 4" / / 0.14 80134 1"x 3/4"x 1" 40 5/e" 3/4" 3/4" 0.17 Part No. Size Sch. T/0 Wt. 80260 1"x 1"x 3/4" 40 3/." 3/4w "/,e" 0.16 80142 3/4"X'/4" NPT 40 5/e" 0.41 lb. 80135 1'/4"x 1"X'/4w 40 '/,e" 3/4" 'S/,e" 0.21 80145 1"X 1" NPT 40 3/4" 0.63 lb. 80136 1'/+"X 1"X 1" 40 "lie" 3/4" 'S/,s" 0.22 80146 174"x 1'/4" NPT 40 '/e" 1.03 lb. 80137 1'/4"X 1"X 1'/4" 40 "/,e" 15/,e" 13/,e" 0.26 80147 1'/2"x 172" NPT 80 1" 1.42 lb. 80261 1'/4"X 1'/4"X 3/4" 40 5/8 5/e" '/e" 0.23 80148 2"x 2" NPT 80 13/e" 2.66 lb. 80262 13/4"X 1'/4"x 1" 40 3/4" 3/4' '/e" 0.26 80138 1'/4"x 1'/4"x 172" 80 1" 1" 1" 0.43 80140 11/s"x 1'/4"x 3/4" 80 '/s" 5/e" 1" 0.36 80141 1'/s"X 1'/4"x 1" 80 '/s" a/e" 1'/8" 0.38 Male __ �__+:, -/c) L 80263 1'/2"x 11/2"x'/4" 80 9/,e" 9/1e" 1" 0.36 Adapter 80264 1'/s"X 172"x 1" 80 9/,e" 9/,e" 1" 0.38 80275 1'/s"x 1'/s"x 174" 80 '/e" '/e" 1" 0.45 Part No. Size I Sch. T/0 I Wt. 80265 2"x 2"x 3/4" 80 3/4" 3/4" 13/8" 0.61 80157 '/4"X 3/4" NPT 40 15/1e" 0.33 lb. 80266 2"x 2"x 1" 80 '/e" 78" 13/e" 0.66 80158 1"x 1" NPT 40 1'/e" 0.56 Ib_ 80274 2"x 2"X V/4" 80 1" 1" 13/e" 0.74 80267 2"x 2"x 11/2" 80 1'/8" 11/e" 1'/e" 0.78 1570 80271 2'/s"x 2'/s"X 1" 80 1"/,e" 1"/,e"" 19/,8" 1.43 80272 2'/s"X 2'/s"x 1'/4" 80 1"/,e" 1"/,e" -19/,e" 1.46 Reducing _ _ 80273 2'/s"x 2'/s"x 1'/s" 80 1"/,8" 1"/18" 19/,e" 1.48 Coupling 80276 2'/2"X 2'/2"x 2" 80 1"/,8" 1"/,8" 19/,8" 1.50 80270 3"x 3"x 1'/s" 80 13/4" 13/4" 113/18" 2.28 Part No. Size Sch. T/0 Wt. 80268 3"x 3"x 2" 80 13/4" 13/4" 13/4" 2.25 80220 1" x 3/4" 40 - '/e" 0.08 lb. 80269 3" x 3"x 21/2" 80 13/4" 13/4" 115/,8" 2.44 O I/O T/O . Sprinkler Head Adapter _ I`"'� Sprinkler Head Adapter _ iI o_ with Brass Threaded Insert il� y with Brass Threaded Insert ��wi Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. 80175E '/4"x1/2" NPT 80 7/,6" 0.20 lb. 80175W 314"x '/:" NPT 40 '/,6" 0.19 lb. 80176E 1"x '/2" NPT 80 '/,e" 0.22 lb. 80176W 1"x1/2" NPT 40 '/16" 0.18 lb. 80177WL '/4"x '/2" NPT 40 9/,6" 0.16 lb. 80179 1 x 3/." NPT 40 3/40 0.43 lb. j 1. T/O' ' it I/O , .:: Back-to-Back Cross �1 ��i ._ Sprinkler Head Adapter . . with Brass Threaded Insert = with Brass Threaded Insert Tro' Teo' Part No. Size Sch.i T/O I Wt. Part T/O Wt. 80177L 3/4"x 1/2" NPT 40 '/2" 0.16 lb. No. Size Sch. 1 2 lb. 80178 1"x 72" NPT 40 '/2" 0.20 lb. 80462 1"x 1"x '/2"NPT x 72"NPT 40 5/e" 1'/e" 0.46 80463 1"x 1"x '/2"NPT x '/2"NPT 40 5/e" 13/4a" 0.47 T/0' ; Sprinkler Head Adapter °°" MI 90 Elbow f " •��A T/o° Back-to-Back Tee T'°� `"t� with Brass Threaded Insert " ��i :MOM �� • with Brass Threaded Insert I ----4r = 77" T/O 2 T/0 2 - Part T/O Wt. Part Size Sch. T/O Wt. Size Sch. if No. 1 ? 1b, _ - - __ No. —— - _-1--:—.2 - lb. - 80199 3/4"x 1/2" NPT 40 5/e" 15/,e" 0.20 80459 1"x '/2"NPT X '/2"NPT 40 "/,s" 15/,e" 0.48 80189 1"x 72" NPT 40 "/,6" 1'/,6" 0.26 80460 1"x'/2"NPTx 1/2"NPT 40 "3/46" 1'/e" 0.46 Na Size Sch. 1 T/O 3 bt 80250 3/4"x 3/4"x'/2"NPT 40 5/6" 5/e" 1" 0.22 1 80251 1"x 1"x 72"NPT 40 "/,a" "/,e" 13/,6" 0.29 !!! f 80249 1"X 1"X 1"NPT 40 15/te" 15/1a" 171e" 0.73 Sprinkler Head Adapter v '' T/a' 80256 11/4"x 1"X'/2"NPT 40 '/,a" 8/Is" 1'/e" 0.30 Tee _____. tM.- 1 80252 11/4" x 174"X '12"NPT 40 7/,e" 7/le" 1'/a" 0.31 with Brass Threaded Insert - . 80257 1'/z" X 11/4"x '/2" NPT 80 5/le" 5/a" 1'/+e" 0.43 Tro' _1 I Tro' 80254 172" X 1'/2"X '/2"NPT 80 '/18" v.," 17/,6" 0.46 80258 2"x 172"X 72"NPT 80 '/2" 5/e" 15/a" 0.56 80253 2" x 2"x 72"NPT 80 72" '/2" 15/e" 0.62 Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse,improper installation,corrosion,or which have not been installed,maintained,modified or repaired in accordance with applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having . Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced,at Tyco Fire Products sole option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it,any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or - incomplete information supplied by Buyer or Buyer's representatives. • IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE.IN CONTRACT,TORT.STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY.FOR INCIDENTAL INDIRECT,SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LINI TED TO LABOR CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCT'S LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. 4 THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED,INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, tLjCO/Flow ContcotI P Tyco Fire r oducts DynaTh,ead Full. Line Sch-40 Replacement Dyna-ThrearP offors the life expectancy of Sch40 with superior hydraulics and greater vilue. Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages. Caparison to Schedule 40 .- • otlnparisini,f o�WWI;Pies'. • Dyna-Turead's inside diameter is up • With its incased strength and lighter • Marc wall thickness at the thread to 3.6%larger than Sch-40 giving it weight,Dyna-Thread reduces (CRR=1-00)givea D Thread superior hydraulics.And,when used }�" in oombinatfort with Dyna-Flow ( installation fntigu;,and is ideal for better life cxpeatanry than lig$twall 5m pipe, retro-fit applications. threadable pipe joints. down sizing often occurs, Corrosion Resistance Ratio (CRR)is a • Unlike lightwall threadable pipe, • Dyne-Thread is fully listed and UL(Underwriters Laboratory)term for Dyna-Thread has no thread gauge approved by UL,in-C,and FM for the estimated life expectancy of a pipe warning. fire sprinkler applications. joint.This is based on the calculated • The Iife expectancy Dyna-Thread of Dyna- read wall thiolcnass at the base of the first • Dyns-Thrad is approved for and Sch-40 are equal based on the exposed thread assumed to be the standard hangs spa❑irrg(15 ti calculated wall tlucIcnesses per UL. west point of the pipe length.Dyne.- D,C.)�can be used as safe to earthquake Thread and Seb-40 have the same sway bracing, is safe to use as • The consistent quality of steel used to calculated will thicimesses at this point mops' maim Dyna•Thread facilitates smooth and are bath assigned the same CRR of • Dyna-Thread is safer to weld on, threading and lower maintenance 1,00. costs, • Dyne-Thread is more widely The internal sur�ee of all black Allied accepted than ligtttwall threadable • The exterior of Dyna-Thread is where Soh-40 is specified. protected by a clean,durable mill Tube&Conduit Fire Sprinkler pipe coating for extended shelf life and products up to 4.5000•'in diameter is easy paint application. coated with our now Antibacterial Formula,"ABF",In scientific laboratory —.--_. -- test,ABS proved to have superior Specification'`& Approvals resistance to microbial colonization of ' ` 4, 1 GO pipe walls,thereby delaying or possibly Super 40/Dyne-Thread pipe is preventing the onset of manufactured to meet:AST1v1 A-135, Listed Approved Listed Microbiologioally Influenced corrosion Grade A and is in compliance with (MIC)when the First Sprinkler System tvFPA•13.All sizes of Super 40(Dyna- is fast installed. Thread are rated at 300 psi working pressure.Super 40/Dyne-Thread is UL Specifications • and ULC Listed for wet,dry deluge and . - . . pre-notion BF inkier ayatems and FM NPS Nrmtasl l.0, WI. WI,(1120 Fllladl Per/ Wy1.U11(21') Wt(LIIt(24) WUiIII(25') Approved for use in wet systems.Super In;mm In;mm Lba/F4'Kcmr 1.6a/Ft Kg/m L!r Lbs;Kg Ls,v K8 Lbs;Kg 40/Dyne-Thread can be"bet-dip" 1° 1.080 1.330 1,75 70 1855 2234 2327 galvanized to moot FM requirement for 25 27.4 2.0 2.80 70 957 7073 1056 dry syatoma. Super 40/Dyna-Thread is 1'/' 1,408 1,870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 35.8 2.8 3,78 51 908 7038 1087 welded outlets and is suitable for all 1 W 1.639 2.290 3.22 44 2115 2418 25519 roll-grooved,and plain cad fittings. 40 41.5 3.4 4,79 44 959 7097 1149 (See listing information), 2" 2.104 3.050 4.57 90 1921 2195 2287 50 53.4 4.5 8.80 30 877 986 1037 'f•JlrE913/How Control allied 16100 S. Lathrop •Harvey, IL 60428 Customer Service: [J' 11350 Norccm Rd.•Philadelphia, PA 19154 (800)882.5543 ruts a=Now- 2525 N,27 th Ave,•Phoenix,AZ 85009 Fax 708-339-1806 53-3 . Submittal Data Sheet - Dyna-Th eado stamp Hera Full Line Sch-40 Replacement Dyne-Thread sprinkler pipe repu-ea=ts an engineering advancement for the sprinkler ' pipe industry,It combines the safety and longevity of traditional Soh-40 pip:with 4uaiity and superior la,ydraulic edvsmrges, Comparison to Schedule 40 Dynes-Threads inside diamci~is up to 3.6%larger than Sch-40 rviug it superior hydraulics.Also, when used in combination with Dyne-Flow pipe, dawn siring often occurs.Dyna-Thread is fully listed and approved UL, ULC, -` '' =""w> and FM for fire sprinkler applications.The life expectancy of Dyna-Thread and Sch-40 - 7_�.. ::.. .r ; ti.-,;,,:-:,:-.:::•: are equal based on the calculated wall thicknesses per UL.The consistent quality of - :v - • '>^'- z s: - :; stxl used to make Dyne-Thread feciiirpraa smooth thr_ading and law=mainsaaanee ••• "A:!. :;::' r:^1i a c sear. The exterior of Dyne-Thread is protected a :.::..5...7:7—,:.'.::. . '.Y T a•4: 4•ay r Dyn by clean,durahlc mill coating for ` y '`,�... -` extended shelf life and easy paint application.With iris increased strength and lighter . wdeat,Dyna-Thread reduces installation fatigue and is ideal for retro- applications. = �,;.-a 'f r ":• • ,� fit pp ati0713. r' '1. •' Coerusion Resistance Ratio(CRR)is a UL(Underwriters Laboratory)term for the N•ai'.s. _ ,: .:4;;:a. 1i- "i"° estimated life=peotmny of a pipe joint.This is based r the calculated wall thickness '7°:j.4 '-Y'. '' ►'•I. sr.•! '�! f- at the base of the first exposed tad,Beaumod to be the weakest paint of the pipe '-4 4 .r:•; . ".f -� Thread the same calculated 1 thicicn.-s this f':: - ;.:a . ..:' '`:-1 length.Dyne- and Soh-40 have o culat wall sea et •• : r -;: t-•2 x,44 Dint and are both assigned the same ,•'"g. s'i ' ,F._ i �.iP P � CRR of 1.00. .�..r '(•-0 '��� :lt�-x Cornparieoa to L.W.T.Plpe More wall thickness at the thread(CRR=1.00)gives ' ."s':� N'1 r. _� Dyne-Thread better life expectancy than lightwaJl threadabL pipe joints. Unlr� '• . h x light-wall tlreadahlc pipe Dynes-Tread has no thread gauge warning.Dyns-Thread is c`1 " �+ approved for standard hanger spacing(15 it 0.C•),can be used as earthquake sway '�'� ..�k. `• W� bracing,and is safe to use as drops.D Thread is safer to weld - A,. P& }'�^ a w on than marry Ana- � ,;E •;:..•. coated li � f:,:,..r;:,..,. ghtwall thrcadable pipe products.Dyne-Thread is more widely accepted than lit& , 4_. . ,; 1.i�'�!;': it.. . Iightwall thtesdahk where �, . :: ,.• here Sah••40 is specified. i ` Specifications&Approvals Super 40/ Dyne-Thread pipe is manufactured to Specifications meet:ASTM A 135,Grade A and is in NPS Nsmlaaal I.D. Wt. Wt.(H20 Filled) Per/ Wtl1JtI(21') WI/1.i3(21') Mitt(23') cotnphance with NFPA-I 3.All sizes of In;mm kr mm Lta/Ft Kalm LGa/Ft;Kghrr Lilt Lu, Kit ibe,Kg Lys;Kg Super 40/Dyra-Thread are rated at 300 1' 1,090 1.330 1.75 70 1955 2234 2927 • psi working pressure. Super 40/Dyne- 25 27.4 2,0 250 70 887 1013 1056 Thread is UL and ULC Listed for we_t, 1W 1.405 1.873 2.64 61 2002 2288 239 dry and pro-acticu sprinkler systems and 32 35.8 ?.8 5.78 51 908 1098 1081 FM Approved for use in wet systems. Super 40/Dyaa-Thrersd can be'9aot-dip" 1W 1.639 2290 3,22 44 2115 2418 25t 9 galvanized to meet FM requirement for 40 41.6 3.4 4.79 44 959 1097 114,E dry systems. Super 40/Dyaa-Threads 2' 2,104 3.050 4.57 30 1921 2196 2287 approved for all threaded couplings and 50 59.4 9.5 8.90 30 871 995 1032 welded outlet&and is suitable for all roll- grooved,and plain-end fittings. (Sco Amenean 71tbc and Pipe was acquired by Allied Tube and Conduit on February I, listing information), 1997.The engineered lighrwall and standard wall!Emily of products although they The internal aur6oe of all black F rc have different names arc the same in all respects with regard to strength,wit, Sprinkler pipe up to 4.5000"in diameter bundles count,listings and approvals. For ezattrpk, Shall be coated with Allied Tube& Dyna-Flow and Super Flo arc the same product as is 40. 4110 Conduit Antibacterial Formula"A13F" are Dynes Thread and Super 40.XL is manufactured with Exterior galvanized coating.BLT is manufactured with Black flog=ro ring, Ltatsd Approved Listed Prue. Sprinkler Cunt-acor: Dater Engineer: Specification Reference: wn �: -• T/r_ . Locations: Comments: S3 -4 ® POTTER POTTER s U vs Ri.D • 4: • ® VANE TYPE WATERFLOW _POwo.EO SWITCH WITH RETARD • Potter Electric Signal Company 2081 Craig Rd., / St. Louis, MO 63146 / (800)325-3936 / (314)878-4321 SERVICE PRESSURE UP TO 450 PSI CHARACTERISTICS FOR 2" TO 5" PIPE SIZES 250 PSI FOR 10" PIPE SIZE U.L. LISTED AND F.M. APPROVED MINIMUM FLOW RATE FOR ALARM-10 GPM DIMENSIONS & WEIGHTS: See Fig. 2 ENCLOSURE: Cast Aluminum Finished: Red Enamel - °� CONTACT RATINGS: Two sets of S.P.D.T. (Form C) 15.00 Amp. C 125/250V. AC 0.50 Amp. @ 125V. DC 0.25 Amp. @ 250V. DC 2.50 Amp. 0 0-30V. DC Resistive ENVIRONMENTAL LIMITATIONS: 40°F/120°F 4.5°C/49°C General Purpose for Indoor Use • " CAUTION: This device is not intended for ' y applications outdoors or in explosive environments. . ' n- SIZES AVAILABLE: U.L. - For Schedule 40 Pipe: 2" thru 10" For Schedule 30 Pipe: 8" - - - ' F:M.== For Schedule 40 Pipe:2"thru 6" - „r For Schedule 30 Pipe: 8" and 10" • ri�1 SERVICE USE x r Automatic Sprinkler NFPA-13 One or Two Family Dwelling NFPA-13D Central Station NFPA-71 Local NFPA-72A Auxiliary NFPA-72B Remote Station NFPA-72C Proprietary NFPA-72D U.S. Pet. Nos. 3,912,247 OPTIONAL: Cover Tamper Switch 4,052,377 Order Stk. No. 5420220 The Model VSR-D is a vane type waterflow switch for The flow condition must exist for a period of time necessary use on wet sprinkler systems. It is UL Listed for use on to overcome the selected retard period. steel pipe;schedule 40 sizes 2"thru 10"and schedule ENCLOSURE:The unit is enclosed in a general purpose, 30 size 8" and has FM approvals for schedule 40 steel pipe in sizes 2" thru 6" and schedule 30 pipe in sizes indoor use, cast aluminum housing. The cover is held in 8" and 10", place with two tamper resistant screws which require a spe- cial key for removal.A field installable cover tamper switch The unit may also be used as a sectional waterflow is available as an option which may be used to. indicate detector on large systems. unauthorized removal of the cover. See Bulletin 751 for installation instructions of this switch. The unit contains two single pole, double throw, snap RETARD ADJUSTMENT: The unit has an adjustable action switches and an adjustable pneumatic retard. pneumatic retard to prevent false alarms due to water The switches are actuated when a flow of 10 gallons surges.The retard is adjustable from 0 to approximately 75 per minute or more occurs downstream of the device. seconds. 2-88 CAT.#A010 PAGE 1 . ill'''. '' P 0 TT ER • _,_.—.+. • -.w ..s<_f'.+.W-14,.r.�9_...!.MZKn,'.-.p...i:�.'A-.. qi_f A=?!ey:2:.gGS.w4F^4'+-. - r?a?M?si4,1%& .:'C.F.T.A*44.=a_.-c•i�1 !?3+:..449W:0,,aT, '.. .:i!>< 465"30F • Potter Electric Signal Company 2081 Craig Rd., / P.O. Box 28480 / St. Louis,MO 63146 / FAX: 314 878 7264 VSR-D INSTALLATION FACTORY ADJUSTED FIG. 1 SENSITIVITY SPRING. DO NOT ADJUST RETARD ADJUSTMENT TO CHANGE TIME TURN KNOB ' (EITHER DIRECTION)FOR ' DESIRED TIME DELAY. l�'1 O TIGHTEN NUTS USE THE MINIMUM AMOUNT ' TO A�lATELY OF RETARD NECESSARY TO EVENTUAL PREVENT FALSE ALARMS. 010104 50 FT-LBS.OF TORQUE.A 'B' SETTING IS USUALLY ADEQUATE FOR THIS. � MOUNT ON PIPE SO ARROW ON SADDLE • POINTS IN DIRECTION .► OF WATERFLOW, ROLL PADDLE IN TO INSTALL: 1 Ohm/ OPPOSITE DIRECTION FOR D 2 SIZES OF WATERFLOW. DRILL ILL I V I/4-HOLE. • FOR ALL OTHER SIZES DRILL 2 HOLE d it ■ APPROX. RETARD SETTING ON SEC.) 0 A e C 0 E , �t/ 4y 0 10-25 20-40 35-66 50-70 10-50 • OPTIONAL: CO r . Taxi pot S O Mar Stk. No.. 3120420 220 - DIRECTION OF 101:Z WATERF --. - . DWG. 5400710-305 SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL CAUTION: - AN UNINSULATED SECTION OF A SINGLE CONDUCTOR IS NOT PERMIT �... TED TO BE LOOPED AROUND THE TERMINAL AND SERVE AS TWO SEPARATE CONNECTIONS.THE WIRE MUST BE SEVERED TO SERVE J �INS pMIN� AS TWO SEPARATE CONNECTIONS, THEREBY PROVIDING SUPERVI- SION OF THE CONNECTION IN THE EVENT THAT THE WIRE BECOMES DISLODGED FROM UNDER TERMINAL. DUT6 p1NG' DWG.5-400710-31 INSTALLATION INSTRUCTIONS: These devices may Clean the inside of the pipe of all growth or other mate- be mounted in a horizontal or vertical pipe. On horizon- rial for a distance equal to the pipe diameter on either tal pipe they should be installed on the top side of the side of the hole. pipe where they will be accessible.The units should not Roll the vane so that it may be inserted into the hole;do be installed within 6 inches of a fitting which chances the not bend or crease it. Insert the vane so that the arrow direction of the waterflow or within 24 inches of a valve on the saddle points in the direction of the waterflow. or drain. Install the saddle strap and tighten nuts alternately to an Drain the system and drill a hole in the pipe using a cir- eventual 50 FT.-LBS. of torque. See Fig. 1 above. cular saw in a slow speed drill.The 2"and 21/2" devices The vane must not rub the inside of the pipe or bind in require a 11/4" hole; all other sizes require a 2" hole. any way. TESTING I The frequency of tasting for the model VSR-D and its associated protective monitoring system should be in accordance with applicable NFPA Standards and/or the authority having jurisdiction,but under no circumstances less than bi-monthly. „AT. #A010 PAGE 2 2-88 . r • . .:. • _ A ... . . . _ • - TES. ., . AN DRAI - -. .. • . _ . . • . .,• or,, ,, ,,,.---1-1.1,:tt r ,�.g G C. '! 4.�1 4i % r. ✓ � � 5.1�tr IVI r C`5404'i .4dY rr°r,�1t P14`i ,its _ 0^'Y .. ,t1 r it 1 ; �' r `x1r. 4 it, L�, tr 'w*... .iiA"°' r �,r ?h�a� �r n� 6 1�,,,,,MI .,,.rwm..+...ew.601.4';'.��,,,,t'P ?� ',raa,, •�V411;11'r t 0� t t 1 {j.pq���p,' p�py�qQ J� t tint .e4 C'.'�aA �'Y11d�'6f ' 11 1 r ''''. LOA Iii t.CO..SEt214 f1i4We U.J. . iiy Y ••w 1 4 as,�� L . v S 1� '. b1:.9 I I fia 5,7 i 7 plan a1�'r(Went:Peum�g:. "l r' I MI _ yp:f C 8511 , � 3I•e1-r Cg 1e^f 4 s 7 ":7- •k gyp '4 Z �'ti' .,ktt;- 1y r,i` � `'" i k {, wed Ie. ■ ' ., r C ' • z 3 „j,u•to r J P;� 4idY,.,..�,u `1 .e'a:'"T ` ■ The AGF Manufacturing Co., Inc. Model 1000 has been designed to provide both the Test Function and the Express Drain Function in a multistory installation. • Complies with all requirements of NFPA-13, and NFPA-13R • Complies with all requirements of NFPA-13D (HOUSING) • Positive Shut Off • Single Locking Handle • Tapped '/z" for Pressure Gauge • Tamper Resistant Orifice permanently installed • Available with all required Orifices __ • Orifice size noted on Indicator Plate • Lightweight and compact (1 '/4" weighs 5 lbs.) • 300 PSI Rating • Fused, tempered, tamper resistant Sight Glasses Afr: 0 MODEL 1000 300 PSI _ TESTANDRAION 3/4 « . 1 " 1 1 411 1 1/2 " N 2 !1 .'/..NOT FM APPROVED PLAN VIEW FRONT VIEW 4 I [ i O FROM BRANCH GAUGE OUTLET ■■� .. PROVIDED BRANCH`� TO DRAIN D 1 ligI:2 .■,MAIN ;lull OFF iToP-1 VI;c ill"CO� i 0 . 1 O t- STREET EL ^�� I WWM FRONT VIEW/HORIZONTAL INSTALLATION, STREET EL TO DRAIN OR PIPE �a 'l-, I -rrr"JJJ\ � � j iss1 -= y TO DRAIN F FOR RIGHT HAND/STRAIGHT INSTALLATION __i TO DRAIN - -.H_ - . ` 1W ID APPROVALS 0 • UL and ULC Listed 1 • FM Approved except 3/4" U • NYC BD. of SEA CAL. NO. 720-87-SM • CA. State Fire Marshall ORIFICE SIZE PROVIDED-3/8-7/16-1/2- 17/32—$/8**_3/4** DIMENSIONS—INCHES MATERIAL LIST SIZE A B C D E F G H PART MATERIAL 3/4 S'/iv 13/4 23/e 4'/a 33/a 13/4 49/16 65/16 HANDLE STEEL STEM ROD BRASS 1 51/16 13/4 23/a 41/8 33/a 13/4 49/16 65/16 BALL C.P. BRONZE 11/4 57/16 13/4 27/a 45/a 35/16 115/16 5'/2 77/16 BODY BRONZE VALVE SEAT GLASS INPREGNATED TEFLON 1 '/z 67/I6 13/4 3"/16 57/16 31/z 23/8 8IA16 10'/i 6 INDICATOR PLATE STEEL 2 6'/16 13/4 311/16 57/16 3'/z 23/8 $'/i6 10'/16 HANDLE LOCK SPRING STEEL SIGHT GLASS (2) FUSED TEMPERED GLASS ** Available on 1'/4 to 2"size units only. AGF MFG. CO. JOB NAME: Box 4437, 150 Mt. Bethel Rd. Warren, N.J. 07059-0437 ARCHITECT: MADE IN U.SA. Telephone (908) 604-6471 ENGINEER: Fax (908) 604-6501 CONTRACTOR: 1000 8/94 IOLCO INCORPORATED I CORONA,CA (909)737-5599 0G® Fig. 27 & 27A "Stand-Off" Hanger/Restrainer for CPVC Plastic Pipe Size Range—3/4" & 1" CPVC Plastic Pipe*. e Material— Carbon Steel, Pre-Galvanized. Function—Designed to be used as a hanger/restrainer**for CPVC piping • where the "stand-off' design will ease installation by eliminating the need for �'" wood blocking. Features: • Flared edge design protects CPVC from any rough or abrasive surfaces. � • Snap-in retainers hold pipe firmly in place during installation. • The "Stand-Off' design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting Fig. 27 surface orientation. • Attaches easily to wood structure with 2 hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16"sockets, o eliminating impact tool damage to pipe Approvals- Underwriters Laboratories Listed in the U.S. (UL) and Canada j 0 (cUL) to support automatic fire sprinkler systems. Meets and exceeds the way t,requirements of NFPA 13, 13R, and 13D. Fig. 27A **important Note—When installed in slot opening on Fig.27, Fig. 27A . _ 4'. _ - . provides additional stability and satisfies the UL vertical restraint requirement - -- where needed. I Order By—Fig. 27: By figure number and CPVC pipe size. Fig. 27A: By figure number and CPVC pipe size. - ) U.S. and International Patent application in process. I �=).-*for other sizes consult factory. Fig. 27 and Fig. 27/27A have also been tested by U.L. mounted on 3/8" composite wood web material (such as TJI Series/Trus Joist MacMillan) Fig. 27/ Fig. 27A without the use of back up wood blocking. When using Fig.27 & 27A in Combination combination on 3/8"web to satisfy the UL requirement for vertical restraint, FIG.27 install 2 reinforcing speed nuts (Fig. 27B). Fig. 27B is UL Listed only when W/FIG.27A used with Tolco products. 1114111111 FIG.27B � FIG.27 4 W/FIG.27A ■e I it r Ft Fp.■ II 1 FIG.27 • FIG.27 FIG.27 W/FIG.27A FIG.27 FIG.27 _ . 0 - 0 (t')1 Typical Applications � (0�) • ES-A-2000B • Sel'les 2000B 7 A M E S Double Check Valve Assemblies FIRE&WATERWORKS"' Sizes: 1/2" —2" (15— C.` 1. ,a Features _ _ - • Ease of maintenance with only one cover 2"20008 HC • Top entry (50mm) • Replaceable seats and seat discs • Modular construction • Compact design • ;'/z -2 (15 50mm)Cast bronze body construction: N"20006 • Top mounted ball valve test cocks (20mm) • Low pressure drop • No special tools required • Series 20006 Double Check Valve Assemblies shall be installed at referenced cross-con- • '/s"–1" (15–25 mm)have nections to prevent the backflow of polluted water into the potable water supply.Only tee handles those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation,frequency of Available Models testing or other installation requirements. Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are B=__Quarter_turn ball valves__ approved_bythe Foun_dation_for Cross onnection_ControLand_Hydraulic Researchat the LBV- less ball valves -University of Southern California.— LH- locking handle ball valves(open position) Specifications SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly HC- 21/2"inlet/outlet fire hydrant fitting shall consist of two positive seating check modules with captured springs and rubber seat (2" valve) discs.The check module seats and seat discs shall be replaceable.Service of all internal Prefix: components shall be through a single access cover secured with stainless steel bolts.The U union connections assembly shall also include two resilient seated isolation valves and four top mounted, re- silient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Pressure — Temperature Hydraulic Research at the University of Southern California.Assembly shall be an Ames Temperature Range:33°F–140°F Company Series 20006 (5°C–60°C) Approvals Maximum Working Pressure: 175psi t ASSE,IAPMO,CSA,UPC (12 bars) ♦ Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Standards • Model LBV is not listed. ASSE Std. 1015,AWWA Std. C510 u UL Classified(LBV models only)3/4"–2" (19–50mm) O ce N IAPMO PS31, CSA 864.5 " Horizontal and vertical "flow up"approval on all sizes. B" d P Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Dimensions - Weights A i •.._ MI ..-••=emirs- JI Iui >•.1■ 4' 4#0., i F H -► 4-I- I G Suffix HC-Fire Hydrant Fittings dimension"A"=231"(594mm) Size(DN) A B Dimensions Model in. mm in. mm in. mm in. mm in. F mm in. G mm in. H mm in. I mm lbs. ht Model 20008 1/2 15 10 254 4% 117 21/26 62 5 127 3% 85 25/,6 59 2'/6 52 4.5 2 20008 M3 % 20 11% 282 4 102 3% 79 6515 157 31/26 87 2% 54 15A6 33 5 2.3 20008 1 25 133/4 337 51/2 130 4 102 71h 191 3% 85 1"A6 43 1"/a 43 12 5.4 20008 13/4 32 16% 416 5 127 35/e 84 91/2 241 5 127 3 76 2 50 15 6.8 20008 11/2 40 16% 425 4% 124 31/2 89 93/4 248 513/6 148 31/2 79 2"A6 68 15.86 7.2 20008 2 50 191/2 495 63 159 4 102 13% 340 61/21 156 3/16 87 2"1/2a 68 25.75 11.7 Strainer sold separately Capacities bars psi 11/1"(32mm) As compiled from documented Foundation for Cross-Connection Control 1 14, and Hydraulic Research at the University of Southern California lab tests. rn .8 12 'Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) 0. 5• .5 bars psi 1"(75mm) * • .4 6 aa w .B 12 as .3 4 0 .7 10 ct .1 2 00°°'- .4 6 0 0 3 4 .- Ap 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm -, H 0 38 76 114 152 190 228 266 304 342 380 418 456 1pm P • a 0 0 , mps 1.5 2.3-3.0 4.6 AP 0 2 4 6 B 10 12 gpm mps 0 7.6 15.2 22.6 30.4 38 45.6 Ipm Flow Rate 5 7.5 10 fps bars psi 11/2"(40mm) * 1.5 2.3 3.0 mps m .8 12 bars psi 3/4"(20mm) Flow Rate N .7 10 y 1.5 22 * -3 .5 8 3 1.2 18 H .4 5 E .96 14 m .3 4 7�` y .69 10 a .1 Z �- .41 6 Apo 0 10 20 30 40 50 60 70 80 90 100 110 120 38 76 114 152 190 228 266 304 342 380 418 456 pm .14 2 5 7.5 10 15 fps AP 0 5 10 15 20 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps 0 19 38 57 76 95 114 133 152 171 190 Ipm Flow Rate 7.5 15 2.3 4.6 mps bars psi 2"(50mm) bars psi 1"(25mm) ,; Flow Rate m .8 12 - - vyi 1.1 16 0 7 10 -J .8 12 J 5 8 y .7 10 ' .4 6 .4 B H 12 3 4 60 4 6 ai 1 2 m .3 4 a 0 0 0• .1 2 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 fpm 0 5 10 15 28 25 30 35 40 45 50 55 60 gpm AP 1.5 2.3 3.0 19 38 57 76 95 114 133 152 171 190 209 228 Ipm 5 7.5 . 15 fps 5 7.5 10 15 0 4.6 mps 1.5 2.3 3.0 4.6 fps Flow Rate mps • Flow Rate IMPORTANT. Inq with inq local uire installaon governti reuirements.g authorities for I Q M E S 1S0 90011 FIRE&WATERWORKS A Division of Watts Industries www.amesfirewater.corn CERTIFIED I �:` ' 875 National Drive • Suite #107 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 ES-A-2000B 0313 ©Ames Co.2003 Printed in U.S.A.