Report (5) 20 1(4 (DD ACCURATE BALANCING AGENCY INC AIR AND WATER BALANCING • DUCT LEAKAGE TESTING CERTIFIED TEST • ADJUST • BALANCE REPORT Project: Mizumi Buffet Island Location: 13500 Pacific Highway - Tigard, OR. Engineer: Captive Aire HVAC Contractor: Bulldog Mechancial ;z, A # Lot • J NEBB# 3177 • CCB# 6475 • ESB# 3866 PO Box 653 • BEAVERTON, OR 97075 • (503) 297-6594 • ABA @ABAINC.US • FAX (503) 292-4825 AACCURATE Table of Contents BALANCING . AGENCY INC Project-Location: Mizumi Buffet Island- 13500 Pacific Highway-Tigard, OR. Page # Table of Contents 1 Certification 2 Terms and Abbreviations 3 Instrument Calibration 4 General Remarks and Summaries 5 Fan Test Reports 6 Air Outlet Test Report 8 Indexed Floor Plan Accurate Balancing Agency, Inc. Page 1 of 8 ACCURATE Certification BALANCING . AGENCY INC Project-Location: Mizumi Buffet Island- 13500 Pacific Highway-Tigard, OR. The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test-Adjust-Balance Report Project Summary. Significant or noteworthy remarks are noted on the General Remarks or on individual test reports. Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this report, Deficiency Reports are forwarded to our contracted agent. Warranty is limited to one year from date of this report. Within that time, any descrepancies, ambiguities, or omissions found in this report will be retested, adjusted, or balanced as needed. A written notification will be required. Submitted and Certified by NEBB TAB Firm: Accurate Balancing Agency, Inc. Certification: 3177 Expiration Date: March 31, 2015 Certification Date: March 3, 2015 Signed and Sealed by NEBB Supervisor: Edward M. May Jr. � a\anoin. ,A Cr t.o *71 ,,. 3177 Exp.3131115 0,ty 5 s 0tC drontc Accurate Balancing Agency, Inc. Page 2 of 8 AACCURATE Terms and Abbreviations BALANCING . AGENCY INC Project-Location: Mizumi Buffet Island - 13500 Pacific Highway -Tigard, OR. AC Air Conditioning Unit AH Air Handler AHU Air Handling Unit AK Area Factor or Flowhood Backpressure Compensation Factor BHP Brake Horsepower BMS Building Management System BTUH British Thermal Units per Hour CEF Ceiling Exhaust Fan CFM Cubic Feet per Minute CRU Computer Room Unit DB Dry Bulb DDC Direct Digital Control EAT Entering Air Temperature EWT Entering Water Temperature EF Exhaust Fan EG Exhaust Grille (Shown as Triangled number on indexed plans) ERU Energy Recovery Unit FPB Fan Powered Box (Terminal Unit which incorporates a fan) FSD Fire/ Smoke Damper GPM Gallons per Minute Head Pressure Difference across the entering and leaving side of a pump HRU Heat Recovery Unit HVAC Heating Ventilation and Air Conditioning HZ Hertz Inches(") Inches of water gauge K Correction factor to the free area needed to calculate CFM LAT Leaving Air Temperature LINT Leaving Water Temperature N/A Not Applicable N/L Not Listed OBD Opposed Blade Damper OAD Outside Air Damper OD Outside Diameter OSA Outside Air Damper PSI Pounds per Square Inch RA Return Air RG Return Grille (Shown as a Circled number on indexed plans) RPM Revolutions Per Minute RTU Roof Top Unit SA Supply Air SG Supply Grille (Shown as a Standard number on indexed plans) SFA Service Factor Amperage TAB Test; Adjust; and Balance VAV Variable Air Volume (Terminal Unit which regulates airflow) VEL Velocity WB Web Bulb Accurate Balancing Agency, Inc. Page 3 of 8 ACCURATE Instrument Calibration Report AA BALANCING ' AGENCY INC Project-Location: Mizumi Buffet Island - 13500 Pacific Highway-Tigard, OR. Manufacturer Mo. Tachometer UE1 DPM S L420477 10/9/2014 I 10/9/2015 I Rotation Thermometer UEI PDT550 I N/A I 10/9/2014 I 10/9/2015 I Immersion Thermometer UEI I PDT550 N/A 10/9/2014 I 10/9/2015 I Air Temp Electrical UEI I DL389 140306812 10/9/2014 I 10/9/2015 Multimeter Manometer Shortridge ADM-860 M91491 1/16/2014 1/16/2015 Air Pressure Hygro-Thermometer Extech I RH490 10052806 10/6/2014 10/6/2015 I Humidity Anemometer UEI I DAFM3 9705374 4/23/2014 I 4/23/2015 I Air Velocity Flowhood Shortridge I ADM-860 M91491 1/16/2014 1/16/2015 Air Volume Thermometer UEI ATT47 probe 140306812 10/9/2014 10/9/2015 Contact Hydrometer Alnor/TSI HM680 70552168 3/26/2014 I 3/26/2015 I Differential Pressure I Accurate Balancing Agency, Inc. Page 4 of 8 AACCURATE General Remarks and Summary BALANCING . AGENCY INC Project-Location: Mizumi Buffet Island - 13500 Pacific Highway-Tigard,OR. 1) No remarks were noted. Accurate Balancing Agency, Inc. Page 5 of 8 AACCURATE Fan Test Report BALANCING (Belted) AGENCY INC Project-Location: Mizumi Buffet Island- 13500 Pacific Highway-Tigard, OR. Technician: MS Test Date: Feb 2015 Unit Designation MAU-1 Service Kitchen Manufacturer Captive Aire Model Number A3-D.500-G18 Serial Number Job#2123914 Test Data Total Airflow (CFM Design / Outlet) 4655/4655 4232 Total Static Pressure (Inches water gauge) Not Listed 1.28" Motor Horsepower 3.0 Motor Manufacturer Weg Motor Frame 56Hz Motor Service Factor III 1.15 Full Load Amperage (T1 / T2 / T3) 9.5 6.8/6.3/6.2 Voltage (T1-T2 / Tl-T3 / T2-T3) 208-3-60 212/211/210 Operating Hz. 60 60 Motor(RPM) I 1725 1751 Fan (RPM) Not Listed 735 Motor Sheave 2VP42x7/8" Fan Pulley 2BK90Hx1 3/16" Belt(Number) Size (2)BX58 Sheave Centerline Distance 20.5" Static Pressure Profile 1 Component In (Suction SP) Out(Discharge SP) DmeHr ,iral Pressure Fan -0.51' U.i,' 1.28" Remarks:,, No Remarks were noted. Accurate Balancing Agency, Inc. Page 6 of 8 ACCURATE Fan Test Report BALANCING (Direct Drivel • . AGENCY INC Project-Location: Mizumi Buffet Island- 13500 Pacific Highway -Tigard,OR. Technician: MS Test Date: Feb 2015 Unit Designation EF-1 Service Kitchen Hood Manufacturer Captive Aire Model Number DU240HFA Serial Number Job#2123914 Test Data Design, Total Airflow (CFM Design / Outlet) 4900/4900 Total Static Pressure (Inches water gauge) Not Listed N/A Motor Horsepower 5.0 Motor Manufacturer Teco Motor Frame 184T Motor Service Factor 1.15 Full Load Amperage(Ti / T2 / T3) 13.6 14.5/14.3/14.4 Voltage (T1-T2 / T1-T3 / T2-T3) 208-3-60 212/211/212 Operating Hz. 60 39 Speed Setting VFD Fan (RPM) N/A N/A pressure Profile Component In (Suction SP) Out(Discharge SP) Differeitial,;; ,essure Fan IN A N/A N/A No Remarks were noted. Accurate Balancing Agency, Inc. Page 7 of 8 ACCURATE Air Outlet Test Report BALANCING AGENCY INC Project-Location: Mizumi Buffet Island- 13500 Pacific Highway -Tigard,OR. Technician: MS Test Date: Feb 2015 System / UAW Desig eliminarO _ .mai st . Vy -GAV g M MAU-1 1 (6)18x14 Inlet 10.50 443 4655 403 4232 403 4232 91% Kitchen EF-1 1 155x18 Hood 18.84 260 4900 268 5049 268 5049 103% Kitchen Hood No remarks were noted. Accurate Balancing Agency, Inc. Page 8 of 8