TEST • ADJUST • BALANCE REPORT
Project: Mizumi Buffet Island
Location: 13500 Pacific Highway - Tigard, OR.
Engineer: Captive Aire
HVAC Contractor: Bulldog Mechancial
;z, A # Lot
•
J
NEBB# 3177 • CCB# 6475 • ESB# 3866
PO Box 653 • BEAVERTON, OR 97075 • (503) 297-6594 • ABA @ABAINC.US • FAX (503) 292-4825
AACCURATE Table of Contents
BALANCING
. AGENCY INC
Project-Location: Mizumi Buffet Island- 13500 Pacific Highway-Tigard, OR.
Page #
Table of Contents 1
Certification 2
Terms and Abbreviations 3
Instrument Calibration 4
General Remarks and Summaries 5
Fan Test Reports 6
Air Outlet Test Report 8
Indexed Floor Plan
Accurate Balancing Agency, Inc. Page 1 of 8
ACCURATE Certification
BALANCING
. AGENCY INC
Project-Location: Mizumi Buffet Island- 13500 Pacific Highway-Tigard, OR.
The data presented in this report is a record of system measurements and final
adjustments that have been obtained in accordance with the current edition of the NEBB
Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems.
Any variances from design quantities, which exceed NEBB tolerances, are noted in the
Test-Adjust-Balance Report Project Summary.
Significant or noteworthy remarks are noted on the General Remarks or on individual
test reports.
Noted deficiencies are not the TAB firms responsibility to repair. Prior to issuance of this
report, Deficiency Reports are forwarded to our contracted agent.
Warranty is limited to one year from date of this report. Within that time, any
descrepancies, ambiguities, or omissions found in this report will be retested, adjusted,
or balanced as needed. A written notification will be required.
Submitted and Certified by
NEBB TAB Firm: Accurate Balancing Agency, Inc.
Certification: 3177
Expiration Date: March 31, 2015
Certification Date: March 3, 2015
Signed and Sealed by
NEBB Supervisor: Edward M. May Jr.
�
a\anoin. ,A
Cr t.o *71
,,. 3177
Exp.3131115
0,ty 5 s 0tC
drontc
Accurate Balancing Agency, Inc. Page 2 of 8
AACCURATE Terms and Abbreviations
BALANCING
. AGENCY INC
Project-Location: Mizumi Buffet Island - 13500 Pacific Highway -Tigard, OR.
AC Air Conditioning Unit
AH Air Handler
AHU Air Handling Unit
AK Area Factor or Flowhood Backpressure Compensation Factor
BHP Brake Horsepower
BMS Building Management System
BTUH British Thermal Units per Hour
CEF Ceiling Exhaust Fan
CFM Cubic Feet per Minute
CRU Computer Room Unit
DB Dry Bulb
DDC Direct Digital Control
EAT Entering Air Temperature
EWT Entering Water Temperature
EF Exhaust Fan
EG Exhaust Grille (Shown as Triangled number on indexed plans)
ERU Energy Recovery Unit
FPB Fan Powered Box (Terminal Unit which incorporates a fan)
FSD Fire/ Smoke Damper
GPM Gallons per Minute
Head Pressure Difference across the entering and leaving side of a pump
HRU Heat Recovery Unit
HVAC Heating Ventilation and Air Conditioning
HZ Hertz
Inches(") Inches of water gauge
K Correction factor to the free area needed to calculate CFM
LAT Leaving Air Temperature
LINT Leaving Water Temperature
N/A Not Applicable
N/L Not Listed
OBD Opposed Blade Damper
OAD Outside Air Damper
OD Outside Diameter
OSA Outside Air Damper
PSI Pounds per Square Inch
RA Return Air
RG Return Grille (Shown as a Circled number on indexed plans)
RPM Revolutions Per Minute
RTU Roof Top Unit
SA Supply Air
SG Supply Grille (Shown as a Standard number on indexed plans)
SFA Service Factor Amperage
TAB Test; Adjust; and Balance
VAV Variable Air Volume (Terminal Unit which regulates airflow)
VEL Velocity
WB Web Bulb
Accurate Balancing Agency, Inc. Page 3 of 8
ACCURATE Instrument Calibration Report
AA BALANCING
' AGENCY INC
Project-Location: Mizumi Buffet Island - 13500 Pacific Highway-Tigard, OR.
Manufacturer Mo.
Tachometer UE1 DPM S L420477 10/9/2014 I 10/9/2015 I
Rotation
Thermometer UEI PDT550 I N/A I 10/9/2014 I 10/9/2015 I
Immersion
Thermometer UEI I PDT550 N/A 10/9/2014 I 10/9/2015 I
Air Temp
Electrical UEI I DL389 140306812 10/9/2014 I 10/9/2015
Multimeter
Manometer Shortridge ADM-860 M91491 1/16/2014 1/16/2015
Air Pressure
Hygro-Thermometer Extech I RH490 10052806 10/6/2014 10/6/2015 I
Humidity
Anemometer UEI I DAFM3 9705374 4/23/2014 I 4/23/2015 I
Air Velocity
Flowhood Shortridge I ADM-860 M91491 1/16/2014 1/16/2015
Air Volume
Thermometer UEI ATT47 probe 140306812 10/9/2014 10/9/2015
Contact
Hydrometer Alnor/TSI HM680 70552168 3/26/2014 I 3/26/2015 I
Differential Pressure
I
Accurate Balancing Agency, Inc. Page 4 of 8
AACCURATE General Remarks and Summary
BALANCING
. AGENCY INC
Project-Location: Mizumi Buffet Island - 13500 Pacific Highway-Tigard,OR.
1) No remarks were noted.
Accurate Balancing Agency, Inc. Page 5 of 8
AACCURATE Fan Test Report
BALANCING (Belted)
AGENCY INC
Project-Location: Mizumi Buffet Island- 13500 Pacific Highway-Tigard, OR.
Technician: MS Test Date: Feb 2015
Unit Designation MAU-1
Service Kitchen
Manufacturer Captive Aire
Model Number A3-D.500-G18
Serial Number Job#2123914
Test Data
Total Airflow (CFM Design / Outlet) 4655/4655 4232
Total Static Pressure (Inches water gauge) Not Listed 1.28"
Motor Horsepower 3.0
Motor Manufacturer Weg
Motor Frame 56Hz
Motor Service Factor III 1.15
Full Load Amperage (T1 / T2 / T3) 9.5 6.8/6.3/6.2
Voltage (T1-T2 / Tl-T3 / T2-T3) 208-3-60 212/211/210
Operating Hz. 60 60
Motor(RPM) I 1725 1751
Fan (RPM) Not Listed 735
Motor Sheave 2VP42x7/8"
Fan Pulley 2BK90Hx1 3/16"
Belt(Number) Size (2)BX58
Sheave Centerline Distance 20.5"
Static Pressure Profile 1
Component In (Suction SP) Out(Discharge SP) DmeHr ,iral Pressure
Fan -0.51' U.i,' 1.28"
Remarks:,,
No Remarks were noted.
Accurate Balancing Agency, Inc. Page 6 of 8
ACCURATE Fan Test Report
BALANCING (Direct Drivel
•
. AGENCY INC
Project-Location: Mizumi Buffet Island- 13500 Pacific Highway -Tigard,OR.
Technician: MS Test Date: Feb 2015
Unit Designation EF-1
Service Kitchen Hood
Manufacturer Captive Aire
Model Number DU240HFA
Serial Number Job#2123914
Test Data
Design,
Total Airflow (CFM Design / Outlet) 4900/4900
Total Static Pressure (Inches water gauge) Not Listed N/A
Motor Horsepower 5.0
Motor Manufacturer Teco
Motor Frame 184T
Motor Service Factor 1.15
Full Load Amperage(Ti / T2 / T3) 13.6 14.5/14.3/14.4
Voltage (T1-T2 / T1-T3 / T2-T3) 208-3-60 212/211/212
Operating Hz. 60 39
Speed Setting VFD
Fan (RPM) N/A N/A
pressure Profile
Component In (Suction SP) Out(Discharge SP) Differeitial,;; ,essure
Fan IN A N/A N/A
No Remarks were noted.
Accurate Balancing Agency, Inc. Page 7 of 8
ACCURATE Air Outlet Test Report
BALANCING
AGENCY INC
Project-Location: Mizumi Buffet Island- 13500 Pacific Highway -Tigard,OR.
Technician: MS Test Date: Feb 2015
System / UAW Desig eliminarO _ .mai st .
Vy
-GAV g M
MAU-1 1 (6)18x14 Inlet 10.50 443 4655 403 4232 403 4232 91%
Kitchen
EF-1 1 155x18 Hood 18.84 260 4900 268 5049 268 5049 103%
Kitchen Hood
No remarks were noted.