Loading...
Report American Security Alarms, Inc. 5411 SE McLoughlin Blvd., Portland, OR. 97202(503)231-0303 RECEIVED FEB 172015 CITY OF TIGARD Attn: Dan Nelson BUILDING DIVISION . 2/17/15 1. We are installing a 5104B Silent Knight Fire alarm control and a dual path DSC cell phone dialer.l Each is powered by 120vac with its own battery backup. There is no current draw to speak of so no need for batt calc. (just monitoring relay outputs.) We will hood the 5104B into the DSC with phone cords. The DSC will give full data output when the 5104B is set on contact ID format. 2. In the mechanical room are one flow and two tamper switches. We will hook the flow up to zone 1 and the two tampers to zone 2. Then we will hook the hood suppression relay up to zone 3. 3. • Ther• ' an- ng existi 120vac bell that will ring upon watero .. .r \ Rich Miller 503-706-1605 richCasalarms.com • CITY OF TIGARD REVIEWED FOR CODE COMPLIANCE Approved: f it Permit 2C 5 5 Address: i 3 Z-'i.)' C(-P � Suite#: By: ,-- 1110111 Dater 2-1, rt"( � OFFICE COPY THE SECURITY PROFESSIONALS...SINCE 1970 .,/caln Security Alarms Inc ,5E McLoughl n Blvd., Portland, OR. 97202 (503)231-0303 PROPOSAL COMMERCIAL FIRE ALARM SYSTEM Attn: Wendy 541-829-3217 wens hendavid(a7gmail com Mizumi Buffet January 5, 2015 13500 SW Pacific Hwy, STE 17 Tigard, OR. 97223 Survey of Existing Fire Alarm System Fire Alarm System: • 1 — Fire Alarm Sprinkler Riser with (1) Flow Switch Device 2 —Water Wheel Tamper Devices Fire Alarm Control: 1 —AES Fire Alarm R/F Radio Transmitter I 4 • 1• Replace existing AES R/F Radio Transmitter with Honeywell Dual Cellular Transmitter Control Panel. 2. Reconnect existing Fire Alarm Sprinkler Sensors Flow& Tamper Devices. evices. 3. Check Fire Alarm Sensors for proper operation. • $395.00...!nstall Fire Rated Dual Path Cellular Transmitter $ 54.90...24-hour Monitoring Services via Cellular Transmission Per Requires standard American Security Alarms 36 month Monitoring Agreement o' Includes a one year warranty on all parts and labor Proposal is subject to approval of Authority having Jurisdiction. Customer requirements made by Authority having Jurisdiction upon plan review or inspection. 24-hour 120-Volt Direct AC Power to Fire Alarm Control Panel and Aux Power Supply o be provided responsible for additional P ded by customer or others Approved: 4/ 114 /1 0 I' l _ Date: r 24. /.3 503-231-0303 — Please call if you have any questions 503-230-1044— Fax— If you would like to proceed, please sign above to our office. Upon receipt, our scheduler: Ken Schwanderax contact you to set a time for the work x will • THE SECURITY PROFE SIONALS...SINCE 9 i; x� PROTECTED 7Y • CHANGE ORDER PA V% American SECURITY ALARMS Customer. vnn uvrr- T Date: * * * Address: 1.350 City: Tigard State:OR Zip:97223 5411 McLoughlin Blvd. Phone: 5411 S.E.S. .McLoughlin 54�-829 3217_��Email:_went jend3vidca gmail.com OR (503)231-0303 WA:(360)256-3783 Customer hereby authorizes American Security Alarms, Inc.to make the following additions and/or change(s) to the system. Required Upgrade&-Ad I Ions o cu n�FirE, Aidrrlr-Systern- A. Install Silent Knight 5104 Fire Alarm Panel $395.00 Installed * Reconnect cuitomer s USCCDual Path C 1fular Transmi g Srervices "ltegair-ed-for input-of lioadSuPPression-Relay *Special Price per Jim Liston Standard cost is $795.00 B. Corm{ fie-K O° F-i air into new_SK5109�.-` 225.00 installed fire alarm panel. Note: Final Connection to re ay o e prove e y oo up r Y`— Includes one year warr an y on a new a i - No warranty on Cutomers_existing_Controls_Devices Wirinq Etc Proposal is subject to approval of Authority having Jurisdiction. Customer is responsible for additional requiremen rity-traVing-dUrisdieticrn-tipon-pia}revi er-in6 pr ■24-hour 120-Volt Direct AC Power to Fire Alarm Control Panel and Aux Power Supply to be provided by customer or r others We agree to make the change(s) specified above fora total of: $ This Change Order shall be attached to and made a part of the terms and conditions of the original agreement between American Security Alarms, Inc. and Customer. J mes D. Liston Security/Fire Consultant �MERICAN SECURITY ALARMS, INC. ' M12UMI BUFFET N 921315 CUSTOMER By' By:— _ I -----.. Orticx oYMwrican 9�fy;.IncAluvbt ---- -_ Date' --_--- /� r - ��_.. .� -�i 1111_. © STORAGE - �__.:::. � 6 1::, GiR BRO°'iIp + MOVE EXIST HALF WALL� SS TIADgOYp Tw .if=i DROP COMB WALK IN COOLER ... • �/- .. CN RM/WH HOElo51BIK RESiMAHI 1DTN SEATWa RENAN SIC ISO ��I .. _ 2$SHEET 22 FOR EUPMCNT UST WAITING AREA R FIRE ALARM LEGEND BY RICH © C ELEC RAJ MILLER 1211 LEA AND MEET] 9'-8"FULL HIGH WALL I I I I • SJ-1p,DP ttlINL 1) CERT 1D21E1 W/METAL STUD SLND FREQMM CONTROL PANEL 5/8-GYPSUM BOKRD 0 _ O O SILENT KNIGHT SINS ON BOTH SIDE 1 RELOCATE 6' DOUBLE DOc1 REARANGE SEATING - N O O ©—o----Qz -o '-- _ - O I-i `UL PATHTRIAATMTE DUAL PATH TRANSMRTER W/PANIC HARDWARE S ET Ra°R 1 I ._._..........__._.._... `� e©i ss BAawsR° -• aa.HG �, S�MRCP FCon[TANS �� -� 1 - NE FLOOR t I in SMOOTH WWI CCaRL IppD HSUPPRESSION®4 O SYSIEAAHRU UP XERE TO C .J I'. I OOI THEIR ALARM WTPUT RELAY � STORAGE �� t S�vx I � O ' t8/1 FPL YINNRHM FIRE WRE -7 �-.6'HIGH WALL W/WOOD FINISH, TYP. r ' 1 1 .... g NOOK THE DSC TO THECCC WITH .I�I"I���,�� °" �R �°"° DATA BAR°a C> o ID ® --T----- R THE MECHANICAL ........ O K.AL ROOM ARE ONE .,'III„II�®�� T ,�'� 0� _ s Row AND TWO TAMPER SWITCHES �O y 1 0 I 1 NOOK THE ROW UP i0 LONE ONE OF L 14 THE 31040 AND THE TWO fLOW '�/ SNITCHES TO ZONE 2 OF THE 51049. S�wT� O 0�,, �r oL,E BACIIBD BTHEN MOiO THE IE 20E SUPPRESSION REARANGE SEATING ' ...._"-Z - ---i PLEASE NOTE THERE IS AN EXISTING OBOE CLANG�,. ._ .. • / 4 OUTSIDE 1211 VAC BELL THAT WEL RNG % • I IA[FLOOR Lib,FLAY. rro9,Al BOARD RN NOR CA DEVICE CRAWS P O W E R O l�©/ SuDOTN WHY.MLR. BAT'CALCS ROT NECESSARY AND OUTSDE BELL IS 1ZOVAC ./ ._..... ... ...._O WALK IN 9'-8-FULL HIGH WALL W/METAL STUD AND /�©� WALK IR • C tRt Flaw i! COOLER FREEZER $/8 GYPSUM BOARD ON BOTH SIDE )---DILw LFRnG 1� ros 11;� i I II E3 I ss I t(. WALK IN BLE FLOOR I ® COOLER , . .. THE NNE I9 BACKBOARD CARPET FLOOR OIFOr CLANG AV BOND r* SS _. G.PS oRaP aiRFG�,�. r I LOOKER 1 1 R zs Mr Cane E ORDP MARC I C RBOI I S BAgByRp 0.=, Ss• pa r / AM LADIES TXE Wi (f/�' BRw TR.[Bad i' + d+aP D[RII1B ( WFTL CUM ® I _ �_.. MEWS OFFICE •®' .........r.„,Y _ .,-.MOOR OBAR ...,,. a i! ii! -. aE.w bSH T _ ss s ,■ "" i ss BMx sowm 1 PLAN VIEW O Ho Dom By - RP.:Nw,F LMnq.eP 6P HL .y� Scow OmR By CONVERGENT PACIFIC AS NOTED MIZUMI BUFFET YR 0I75 02 CENTER STREET MIZUMI 9 A1 Gamed B' nDARa.oIQOR nze' `aA At.Dwc 1350 SW PACIFIC HWY .., ARR..e. TIGARD,OREGON Sher,NR: - ■ �M� °1a/3/14 FLOOR PLAN 2 OF 5 • • s.„?.. _...... .._ ._. ... ............................................._ .., if . 1 ss BACKBOARD TYP 1 i i ) : NO1E: 'I. STORAGE t ft ti WALK IN COOLER 1 IEH RM/WH 1. EXISTING RESTURANT. TOTAL BEATINGS REMAIN THE SAME I; I '' 2. SEE SHEET 62 F0113 EUIDAENT UST SS E\ .. 1 • i ' I''. ;.—.......A,, r. ..........1 ' I 1 I .-• 4d / SS S, 0 4•••••:-...----.-7".-7.•••-t-=.7-F'-"'7 FIRE ALARM LEGEND BY RICH ' , i "-**.-! ELEC RM MILLER 1211 LEA AND NICET 3 i Mk 4 CERT 102181 • I .• •4 0 .Yaree:4•Ci NE FLOOR •''''-nirdr,:m;''''''^ ------ im2 FIRE ALARM CONTROL PANEL ()••••••----DROP CEuNG------.() I 1 SILENT KNIGHT 510413 -. ....—_- ®. 1111.1111— a V.2•Y _ a =1_,-- MI CELL PHONE DIALER-DSC == .0 o i l 10'.. C51-I (:). 1 11K03 0 PR_ 0 1 7'ml — I NM i ,/, 72! Ka SS BACKBOARD . _ _ DUAL PATH TRANSMITTER 'I -21. ell TILE FLOOR `i 1 c)...------DROP CEILING----r) 'i 1 TILE FLOOR -- S1/00D-4 \ANTI. UJUNG E1202j HOOD SUPPRESSION ii SYSTEM-HOOK UP HERE TO 0 I .... T s't) THEIR ALARM OUTPUT RELAY / (i) 0 I \. •I s STORAGE tHOOD r4.• 0 I''''''1. -• ...;i1.0 18/2 FPL MINIMUM FIRE WIRE I u s, 0 '-• I i XI m .... J- Z0 5 ........-...-1....I HOOK THE DSC TO THE 5104B WITH 1 0 PHONE CORDS THE DSC CELL PHONE -',- t TILE FLOOR , WILL GIVE FUU.DATA TRANSMIT ON D (..)...„--DROP COUNG ...,0° CONTACT ID. D a...,a 0 5 IN THE MECHANICAL ROOM ARE ONE ,i ...... FLOW AND TWO TAMPER SWITCHES 7 .L.__....__......._........... -' ,..!_____1, ... ,iock,,• i ;pi,. , O G , ' --------._---4.------7 ..,,--.A.... .... ... c,),,., :„.... 1 : ,.., el ,...,...... t -SS DAMBOARD HOOK THE FLOW UP TO ZONE ONE OF THE 5104B AND THE TWO FLOW SWITCHES TO ZONE 2 OF THE 5104B. THEN HOOK THE HOOD SUPPRESSION SYSTEM TO THE ZONE 3 ',‘ I 0 0 / ; r....../ i PLEASE NOTE.THERE IS AN EXISTING a• .71 !;$.10 . OUTSIDE 120 VAC BELL THAT WILL RING UPON FLOW V 0 , ' '.' TILE FLOOR NO INPUT DEVICE DRAWS POWER SO I , '" GYPSUM BOARD WALL 1 9 ,, BATT CALCS NOT NECESSARY AND I 7 _ I , . . VI CEIUNG 1 . . i SMOOTH NYL , OUTSIDE BELL IS 120VAC .9 % g. ■ FIRE ALARM ACCESSORY 5104B Fire Control � Communicator ,, •a The speed, reliability and value •G• Al of digital communications munications from the company you can trust As pioneers in digital fire technology, Silent Knight delivers superior systems at an outstanding value. Our 5104B Fire Control Communicator has become the industry standard by proving itself in years of field-tested operation. This six-zone fire control communicator provides fast, reliable digital communication of fire and trouble conditions. It transmits via ordinary phone lines — eliminating the need for expensive leased line arrangements. Use it as a stand-alone, or incorporate it into your existing system. Why spec any other digital communicator? Go with the industry standard — the 5104B Fire Control Communicator from Silent Knight. For more information, please call 1-800-446-6444, or in Minnesota, call (763) 493-6435. Model 51048 the central station. If one of the Fire Control Communicator telephone lines faults for more than The Silent Knight Model 5104B is a 60 seconds, it will automatically six-zone fire control communicator switch to the other to report the ` providing digital fire reporting over failure. I ordinary telephone lines, The communicator will signal eliminating the need for costly activation, restoration and trouble leased lines. It's UL 864 and NFPA conditions on any of six inputs. If 72 approved for monitoring local an application requires a different evacuation controls. input configuration, the individual As a stand-alone unit, it can be input styles may be changed by used to monitor: using a Model 7181 Fire Zone Model 57046 • Sprinkler systems for waterflow, Converter Module. The 7181 also supervisory, and gate valve allows use of two-wire type smoke • Dual phone line interface Automatic tamper conditions. detectors, instead of the normal self tests every 24 hours with report • Automatic fire detection systems four-wire contact type, for sent to central station. for structures that are not automatic fire detection • Reports in SIA and most major required to have a fire alarm applications. communications formats. system but an property Features • 60 hours of standby power. • protection (e.g. to call the fire • UL 864 Listed as an NFPA 72 Operates on loop start phone lines department after hours). Central Station or Remote Station ahead of the building PBX system. • Monitors dry contact alarms, protected premise unit. A single, programmable output is trouble and supervisory outputs, • FM approved. provided for alarm or dialer failed then transmits a separate code • Can be used as a stand-alone or as conditions (cannot s) used for • for each. a Slave DACT. evacuation purposes). • Six fully supervised inputs:one The Model 5104B is fully supervised. Its microprocessor Class A(Style D) input, and five constantly runs programs to Class B(Style A) inputs. monitor AC, standby battery, zone • Downloadable for remote programming. SILENT inputs and telephone line connections. If a fault condition is • Fuseless overload protection with till I"` IGHT detected, it sounds a local trouble automatic reset circuitry and fault Indicators —audible and reports the condition to most field calsliminates the cause of by Honeywell 5104B Fire Control 2 Communicator Specifications Mechanical: Electrical Dimensions: 12.25"W x 14.5"H x 3.0"D Slave Applications-UL Listed (31.1cm W x 36.8 cm H x 7.6cm D) Input: 120 VAC 60 Hz 40 watts Weight: 15 lbs. (6.75 kg) Current: Standby 50 mA Color: Red Alarm 135 mA Optional Accessories: Stand Alone Applications 5230 Remote Annunciator/Programmer Input: 120 VAC 60 Hz 40 watts 5561 Download Package Standby: 12 volt 7 amp hour rechargeable battery 7181 Fire Zone Converter Module 7860 Telephone Connecting Cord for RJ31X Jack(2 required) 5230 Remote Annunciator(three maximum per system) Load: 60 mA standby 6712 12 volt,7AH rechargeable battery 120 mA alarm Communication Indicator Lights(LEDs): Formats: SIA,SK 3/1, Sescoa 3/1,Contact ID, Power On(Green) SK 4/2, Radionics BFSK Trouble Silenced(Yellow) Approvals: Until Trouble is Cleared/Flashing=Supervisory UL Listed-UL864/NFPA 72 Central and Remote Supervising Dialer Failure(Yellow) Station Fire Alarm System Service. FM Approved Telephone Line Fault(2 Red) Inside Cabinet at L1 and L2 Inputs CSFM Approved Telephone Requirements: MEA FCC Registration#:AC698R-17462-AL-E RINGER EQUIVALENCE 0.0B Type of Jack:RJ31 X(2 required) Model 5230 Remote The Model 5561 SKSS Alphanumeric Annunciator Downloading Package The 5104B can be programmed Allows for remote programming through the use of the optional and status checking of the 5104. Model 5230 Remote Alphanumeric Includes a 3 1/2-inch disk and Annunciator. Programming options Silent Knight proprietary modem. include: telephone numbers, reporting format, account number, Allows the installing company to loop response times (electronic view the default programming, modify it, and if necessary, retard), test time, output activation, troubleshoot the system. Designed fililigalleataM Ci user and installer codes. System to be used on an IBM or ef1®acy=, programming is stored in a non- compatible PC. The downloading volatile EEPROM chip which is software also contains programs reprogrammable hundreds of times. for other Silent Knight Model 5230 The 5104B accommodates up to downloadable products. 5 1/4-inch three remote annunciators via a disks available upon request. four-wire connection.A quick- connect plug allows temporary connection of the annunciator for programming. FIRE ALARM ACCESSOR 5104B Fire Control Communicator 120VAC 80 Hz UL-LISTED LOCAL F LOCAL FIRE SILENT KNIGHT IAO0EL 51048 6 Channel ileret 1 5230 C411inrvrricator --.-___ __ Model 5236 lopliunail Remote Annunciator Alarm t+�n1aCt 13.rl&k 11..3r 9y51€.nri 1N.O.Typlcall iv- 7r001t)1e gof1t,ct Tel. Line kF TypFcslr To p:ralx Tel. Line$7 MODEL 51046 BLOCK DIAGRAM Slave DACT Application SILENT KNIGHT MODEL 51048 120VAC 64 Hz Crass A Input 6 Channel Silent Knight {LUparvixadi —,( -- J'F—`-0—..�— Communicator Model 5231) Max 5 w$1e?lio (optional) rleYlses AP per NFs'A 72 Remote Annunciator (3 max per system) Clasp B In 0 pu (s�crrlsad} —� Wheelock Gals valve tamper or Phi MB-G1 d•12-R slpwW>,or-must rotocrel Tel. Line#1 —~ normally open rkrglal 6717 TO RJ 1X 12VDC 7.A,M Tel. Lima#2 MODEL 5104B BLOCK DIAGRAM Stand-alone Waterfiow Appiicatior) . Ds C A Tyco International Company HSPA Universal Wireless Commercial Fire Alarm Communicator 3G3O7OCF DSC Features That Make a Difference: • Uses HSPA(3G) network for high-speed, reliable and low- cost communications to an IP receiver • Automatically switches to 2G (EDGE/GPRS) if 3G service is not available 3G technology from DSC! • Compatible with control panels tha Cot communicate using the The 3G3070CF connects the alarm path shall be annunciated at the Contact ID format control panel to the HSPA network and reports alarm signals directly to supervising station and at the • Full event reporting y a protected premises within not more monitoring station receiver(Sur-Gard than 24 hours of the failure. • 4 on board inputs System 1/11/111/1V). The 3G3070CF uses `the HSPA network to ensure low- • 4 on-board outputs (open cost, high-speed and reliable alarm Now it Works collector) communications and is compatible The 3G3070CF can be used as • SIM card(included) with control panels that communicate either a Sole Communicator or as a • Activation and initialization via using the Contact ID format. Backup Communicator. When being automated telephone activation used as a Sole Communicator the The 3G3070CF is compliant 3G3070CF will replace the phone system automated tel web-user or with the latest requirements for line connection on the panel and mobile interface provided by Communications Methods as as soon as it detects that an alarm C24 Communications per UL864 and NFPA72 2010 needs to be transmitted it will send • PTM (Panel Transmission Edition. It can be used in Fire the alarm across the HSPA network Monitor)switches from PSTN Monitoring applications as a single immediately. When being used as a to Monitor)nitlor) wi unsuccessful communications technology, backup the communicator assesses in which case any failure of the the connection to the PSTN phone communication attempts communications path shall be line, and only in the event of a • Compatible with Sur-Gard® annunciated at the supervising station line failure will it send all alarm affice System I/II/III/IV monitoring within 5 minutes of the failure, or it station receivers can be used as part of a multiple across the HSPA network to the • Includes UL listed power communications technologies(for monitoring station. supply, transformer and 7 Ah example in conjunction with a DAM). In instances where the control panel rechargeable battery When used as a back-up provision does not support Contact ID, the shall be made to monitor the integrity 3G3070CF has inputs pre-set to • UL 864 listed of each communication path and transmit fire alarm, fire supervisory or • CSFM listed failure of any communications system trouble. Contact your DSC distributor. communications www.dsc.com 11-888-888-7838 • DB A Tyco International Company Alarm signals are transmitted directly without the need of a clearinghouse to the IP linecard of the monitoring station Specifications receiver(Sur-Gard®System 1/II/III/IV). Dimensions 11-1/2"x10"x3" Activating & initializing the unit (29.2 cm x 25.4 cm x 7.62 cm) Input Voltage Activating and initializing the 3G3070 can be done using Current Draw 120 VAC the automated telephone activation system(VRU), mobile 300 mA Operating Environment 32°to 120°F(0°to 48°C) interface or web-user interface provided by CONNECT 24. No special tools are required. Weight 12.8 lbs(5.8 kg) UL Listing The 3G3070CF is UL listed under File S4019, Listing guide UOXX, as a sole or backup communicator for Commercial Fire monitoring installations. When used as a sole communicator the 3G3070CF will send its heartbeat once every 97 seconds ensuring that three heartbeats will be received at the supervising station within the 300 second window. When used as a backup communicator the 3G3070CF will monitor the other communication method (DACT)and send a daily test transmission to the supervising station. CSFM Listing The 3G3070CF has been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code. Rate Plan Cost-effective rate plans have been negotiated and are available through authorized master resellers. Contact your monitoring station or visit www.connect24.com to find a master reseller. Ordering Information: 3G3070CF-USA.....Universal Wireless Commercial Fire Alarm Communicator(U.S. Model/SIM Card Included) a communications For product information www.dsc.coin �A 1' 2 )'2 NUT 7,_$• CORNER HANGING ANGLE 1-2e I4 & BOLT — TYP II • = • DA.HRED 2 EA 1/2X10 BOLTS W/ 8X8X1/4 X240 WASHERS AND NUTS, TI1 11 4 ' • o Q 0 0 0 0 1 -1 ZD • •• I_ o iu OPP' 1 1 1 MOM UNISTRUT 1 5/8 X 1 5/8 X 84 12 GAGE CHANNEL,TYP ATTACHING PLATE ISLAND HOOD TYP 16'-6• WALL OPENING ■o D PLAN VIEW - HOOD 1/2 X 14 BOLT TS UNISTRUT 1 5/8 X 1 5/8 X 84 1•_0• 4• SECTION CD TO CMU WALL,TYP �Y�" NUT & BOLT 12 GAGE CHANNEL,TYP� 20' 0' 1 • - to • \—TS 8X8X1/4 X240 51.. DIA. ALL THREAD ROD—\ • S VD \\ {-2 o ISLAND HOOD 1 2 izoi SECTION CII) rtl • T� 14'-0' 1 .i sp 16'-6• wpL,L nernUNG „, ,� `" ...) e.' '''91 ' Scar d. 3/a--1• MIZUMI BUFFET S1 .e.. 0 e. CONVERGENT PACIFIC Y ). 1350 SW PACIFIC HWY 181 ' em-7 mom sna) SLUNG y,,,,�.: 9]ea ,� C,.,.,... TIGARD,OREGON aw.a By 1,m-)�)-'�{9 r.se]-)4]-37n �`."r:e0 . o...: STRUCTUAL PLAN 5 OF •.n..ee!Y L..._�L&UA 10/21/1.