Plans (3) RECEIVED
City of Tigard
1111 Building Division FEB 2 2015
' 13125 SW Hall Blvd,Tigard,OR 97223 FEB
Phone: 503.718.2439 Fax: 503.598.1960 BUILDING DIVISION
TI GA R D Inspection Line: 503.639.4175
www.tigard-or.gov
2010 Oregon Solar Installation Specialty Code
Check List for Prescriptive Installation of Roof-Mounted
PhotoVoltaic Solar Panel System
Property Information
Installation Address: 8900 SW Pippen Ln
City: Portland, OR Zip: 97224
Owner's Name: Willy Liang Date: 1/30/15
- Contractor's Name: Sunrun Installation Services CCB #: 180464
Inc.
Design Parameters of the Property/Structure
If"Yes", does not
Flood Hazard Is the installation ❑ Yes qualify for the
Area Located in a flood prescriptive path, follow
plain/flood way? ® No OSSC or ORSC for
design requirements.
Is the wind exposure ® Yes If"Yes", qualifies for
Wind Exposure "C"or less? ❑ No the prescriptive path.
Installations on detached Is the Ground Snow
single/two-family Load 70 psf or less?
dwelling/single/two- If"Yes", qualifies for
family townhomes ® Yes the prescriptive path.
and/or their accessory
Ground structures. ❑ No
Snow Load Is the Ground Snow
Installations on all Load 50 psf or less?
ID "Yes", qualifies for
structures other than
Yes the prescriptive path.
above
❑ No
1
I:Building/Forms/PhotoVoltaic-Checklist.docx
Is the construction
Type of material wood and does ® Yes If"Yes", qualifies for
the construction qualify
Construction as"conventional light ❑ No the prescriptive path.
frame"construction?
Is the spacing 24 inches
or less?
Pre-engineered trusses. ® Yes If"Yes", qualifies for
the prescriptive path.
❑ No
Roof framing
members Is the spacing 24 inches
or less?
Nominal lumber. ❑ If"Yes",qualifies for
Yes the prescriptive path.
❑ No
Is the combined weight ® Yes
of the PV modules and If"Yes", qualifies for
racking less than or ❑ No the prescriptive path.
Solar equal to 4.5 psf?
installation Is the solar installation
layout in accordance Yes If"Yes", qualifies for
with Section 305.4(3)of
the 2010 Oregon Solar ❑ No the prescriptive path.
Code?
❑ Metal
Single layer If roofing material is
Roofing Check the type of ❑ of wood one of the three types
material roofing material shingle/shake checked,qualifies for
Max.two layers the prescriptive path.
® of composition
shingle.
Is the roof mounted ® Yes
Connections of solar assembly If"Yes", qualifies for
the solar assembly connected to roof No
to the roof framing or blocking ❑ the prescriptive path.
directly?
2
I:Building/Fortes/PhotoVoltaic-Checklist.docx
❑ Yes If"Yes",qualifies for
Is the gauge 26 or less? ❑ No the prescriptive path.
115 lbs for 60 inch
spacing or less?
❑ If"Yes", qualifies for
Yes the prescriptive path.
❑ No
Minimum Uplift rating
of Clamps? 75 lbs for 48 inches
spacing or less?
If"Yes", qualifies for
❑ Yes the prescriptive path.
❑ No
Attachment of _
roof mounted Minimum 24 inches If the spacing falls
solar systems Spacing of clamps? within 24 inches and 60
directly to inches Maximum 60 inches inches, qualifies for the
standing seam prescriptive path.
metal panels Width of roofing If the width of the panel
panels? 18 inches or less is less than 18 inches,
inches qualifies for the
prescriptive path.
Minimum#10 at 24
inches o/c?
Size and spacing of If"Yes", qualifies for
fastener? ❑ Yes the prescriptive path.
❑ No
Is the roof decking of
WSP min. '/z"thickness, ❑ Yes
decking connected to If"Yes", qualifies for
framing members ❑ No the prescriptive path.
w/min. 8d nails @
6"/12"o/c?
Is the height less than or
Maximum 18 inches equal to 18 inches?
Height of the from the top of the If"Yes", qualifies for
solar modules module to the roof ® Yes the prescriptive path.
surface. ❑ No
I:Building/Forms/PhotoVoltaic-Checklist.docx
Submittal Documents required for Prescriptive Installations
Show the location of the PV system in relation to buildings, structures,
property lines, and, as applicable, flood hazard areas.
Site Plan Details must be clear and easy to read.
Minimum size of the plan is 8.5 x 11 inches.
Attach a simple structural plan showing the roof framing (rafter size, type, and
spacing)and PV module system racking attachment.
System must be shown in sufficient detail and clarity to assess whether it
Structural Plan meets the prescriptive construction requirements as listed earlier above in the
matrix.
Minimum size of the plan is 8.5 x 11 inches.
PV Modules
Manufacturer: REC Solar
Model Number: REC 260 PE (BLK)
Listing Agency: UL
4
(:Building/Forms/PhotoVoltaic-Checklist.docx
PROJECT NOTES: SYSTEM INFORMATION VICINITY MAP -SCALE: NTS MODULE NOTES: TABLE OF CONTENTS
1. 3640W DC, 3300W AC SOLAR PHOTOVOLTAIC SYSTEM. 1. REC SOLAR: REC260PE(BLK) DIMENSIONS:
2. (14) REC SOLAR: REC260PE(BLK) MODULES WITH (1)ABB: ARRAY PITCH MAGNETIC TRUE 65.55"x 39.02"x 1.5" PAGE DESCRIPTION
PVI-3.0-OUTD-S-US-A (240V) INVERTER. ORIENTATION ORIENTATION 2. PORTRAIT: CLAMP 8.2"-16.4" FROM EDGE #
3. TWO STORY COMP SHINGLE ROOF AT 34° PITCH. 3. LANDSCAPE: CLAMP 0"- 9.8" FROM EDGE
4. CONSTRUCTION FOREMAN TO CONFIRM FINAL CONDUIT AR-01 34° 164° 180° PV-01 SITE PLAN & MECHANICAL
RUN PLACEMENT WITH CUSTOMER. - - .. RACKING NOTES:
5. ROOF STRUCTURE: 2X4 PRE-FABRICATED TRUSSES 1. SNAPNRACK SERIES 100 OR S100 UL LISTED; "RECEIVE-PAL
24"OC. FLUSH MOUNT L-FOOT. SEE PEN D01. N
6. APN#: 2S111DA15200 2. LAG SCREWS: 5/16"X 3.5": 2.5" MIN EMBEDMENT
7. CONTACT: WILLY LIAG, 503-317-9798 _ _ _ 3. RAFTER AND PENETRATION LOCATIONS TO BE TB 2 2015 —
8. DESIGN CRITERIA: DETERMINED IN THE FIELD.
4. INSTALLER TO VERIFY RAFTER SIZE, SPACING,
8.1. SYSTEM WEIGHT: 3LBS/SQFT. AND UNSUPPORTED SPANS AND NOTIFY E.O.R
8.2. EFFECTIVE WIND SPEED: 95 MPH 3-SEC GUST.
8.3. EFFECTIVE SNOW LOAD: 25 LB/SQR FT. OF ANY DISCREPANCIES BEFORE PROCEEDING. BUILDING DIVISION
SITE PLAN -SCALE = 1/16" = 1' 46,N D1 -AR-01 -SCALE: 1/8" = 1-0" ,'
(N) SUN RUN METER • INDICATES TSRF VALUE AT MARKED LOCATION
(INTERIOR WALL)
(E) DRIVEWAY
(N) INVERTER WITH 6'-10" —13'-2" 11'
INTEGRATED DC DISCONNECT (E) MAIN PANEL
(INTERIOR WALL) (INTERIOR WALL) 1
SW PIPPEN LN
2'-3"
PL PL A _....._ /L\ �a\ /4\
/ 1
° t,, 1 99 Mo 100'/0 99% i 9(1% 99°A
(E) RESIDENCE T4'TYPy--- °- --
__ e ._.
,..
m—e 7 -9--
O - O-- -8
i 10' 11" A-6 D -6---
9— —e- —o— TT ---8 o— -0— —6 8, 9„
•
e 9-- -@--
i' 9i% 98%
L
23'
-0` (E) SKYLIGHT
(E) SERVICE ENTRANCE T 28'-4" CITY O TIGARD
Pli;., L1 �.
(EXTERIOR WALL) REVIEWED FOR CODE COMPLIANCE
O
I_ Approv dt i tom
(�/'/\ OTC: ' �]
/ 2� . • - ' •. `✓ C(� ��/ A
/ Address: r1 o kswi .
12" FIRE SETBACKS ---a -0
6„ t04
. Br i 40 Date: F15-1,i`_
PL PL 20'
(E) PROPERTY LINE ( OFFICE COPY
ROOF AREA: 1801 SQ.FT.
ARRAY AREA: 238 SQFT. (N)ARRAY AR-01
COVERAGE: 13%
SUNRUN,INC. 3380SE20TH,PORTLANO.0R9720s DESIGNER: SITE PLAN &
sunrun OR CL#180464 PHONE 5037664332 F. JAVIDKIA SUNRUN PROJECT NUMBER: LIAG RESIDENCE PV 01 REV: A
FAX 503.205.0748 LIAG (601 R-900LIAN) 8900 SW PIPPEN LN., PORTLAND, OR 97224-5238 MECHANICAL 1/14/2015
o DRAFTER: DV
LINE DIAGRAM:
120/240 VAC
SINGLE PHASE SERVICE
METER
C
D PGE 24522
2931
UTILITY
GRID
�
, EXISTING
C200A MAIN
q BREAKER
I EXISTING
< 200A MAIN ABB: PVI-3.0-OUTD-S-US-A JUNCTION BOX
FACILITY PANEL SUN RUN (240V) 3000 WATT INVERTER MIN RATED NEMA3R
METER (OR EQUIVALENT)
LOADS - PV MODULES
2 7-1
d- 3 3 o 0-----0 REC SOLAR: REC260PE(BLK)
(110 `� �- _�// (14) MODULES
o--e�o v + (1) STRING OF (14) MODULES
FACILITY
20A PV GROUND 250V METER SOCKET DUAL MPPT TRACKERS STRING
BREAKER AT 125A CONTINUOUS& COMBINER & LOAD RATED DC
OPPOSITE END 240V METER DISCONNECT AND AFC!
OF BUSBAR 200A, FORM 2S
NOTES TO INSTALLER: CONDUIT SCHEDULE SIGNAGE: WARNING
1. 529 VDC EXPECTED OPEN CIRCUIT STRING VOLTAGE.
2. REPLACE (2) EXISTING 15A-2P BREAKERS WITH (1) NEW 15/20/15A 1-2-1P # -Dual Power Sources ELECTRIC SHOCK HAZARD
# CONDUIT CONDUCTOR NEUTRAL GROUND Second source is photovoltaic system
QAUD BREAKER. CONNECT PV TO THE NEW 20A PORTION OF QAUD. , z DO NOT TOUCH TERMINALS
LABEL PLACEMENT.MAIN PANEL TERMINALS ON BOTH LINE AND
1 NONE (2) 10 AWG PV WIRE NONE (1)6 AWG BARE COPPER NEAR METER LOAD SIDES MAY BE ENERGIZED
WARNING IN THE OPEN POSITION
2 3/4" EMT OR EQUIV. (2) 10 AWG THHN/THWN-2 NONE (1)6 AWG THHN/THWN-2 __-,,,,• _,,
__,. ,,.,E DC VOLTAGE IS ALWAYS PRESENT
LABEL PLACEMENT:AC DISCONNECT, WHEN SOLAR MODULES
3 3/4" EMT OR EQUIV. (2) 10 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2 (1)8 AWG THHN/THWN-2 COMBINER BOX.INVERTER ARE EXPOSED TO SUNLIGHT
WARNING-Eloclnc Shock Ha¢ardo LABEL PLACEMENT:
No user ser�iceaole pr s inside /e DC DISCONNECTS
Cornacl aumorzed servcer for assslance
I
LABEL PLACEMENT.AC DISCONNECT, WARNING
COMBINER BOX,INVERTER
CAUTION:SOLAR ELECTRIC ELECTRIC SHOCK HAZARD
ELECTRICAL NOTES: SYSTEM CONNECTED IF A GROUND FAULT IS INDICATED
1. PHOTOVOLTAIC SYSTEM WILL LABEL PLACEMENT:
NORMALLY GROUNDED CONDUCTORS
COMPLY WITH 201 1 NEC. CONDUIT.JUNCTION BOXES
MAY BE UNGROUNDED AND ENERGIZED
2. ELECTRICAL SYSTEM GROUNDING PHOTOVOLTAIC POWER LABEL PLACEMENT:
WILL COMPLY WITH 2011 NEC. SOURCE
INVERTER
3. PHOTOVOLTAIC SYSTEM IS COND PLACEMENT
CONDUIT,JUNCTION BOXES WARNING
UNGROUNDED. NO CONDUCTORS
ARE SOLIDLY GROUNDED IN THE , .., rJU41.:. ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
INVERTER. SYSTEM COMPLIES LABEL PLACEMENT: TERMINALS ON BOTH LINE AND
ALL DISCONNECTS LOAD SIDES MAY BE ENERGIZED
WITH 690.35. MODULE CHARACTERISTICS SYSTEM CHARACTERISTICS -INVERTER 1 IN THE OPEN POSITION
4. MODULES CONFORM TO AND ARE LABEL PLACEMENT:
SOLAR: REC260PE(BLK) 260 W SYSTEM SIZE 3640 W AC DISCONNECTS
LISTED UNDER UL 1703. REC SOLA ,
5. INVERTER CONFORMS TO AND IS OPEN CIRCUIT VOLTAGE 37.8 V SYSTEM OPEN CIRCUIT VOLTAGE 576 V WARNING
LISTED UNDER UL 1741.
6. ARRAY DC CONDUCTORS ARE OPEN CIRCUIT VOLTAGE: (690.7) 41.1 V SYSTEM OPERATING VOLTAGE 429.8 V ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS
SIZED FOR DERATED CURRENT. MAX POWER VOLTAGE 30.7 V MAX ALLOWABLE DC VOLTAGE 600 V UNGROUNDED AND PHOTOVOLTAIC MAY B E ENER GIZED
E AY ENER
GIZED
9.01 AMPS MODULE SHORT BE
CIRCUIT CURRENT. SHORT CIRCUIT CURRENT 9.01 A SYSTEM OPERATING CURRENT 8.5 A LABEL PLACEMENT.
14.07 AMPS DERATED SHORT SHORT CIRCUIT CURRENT(690.8(A)(1)) 11.26 A SYSTEM SHORT CIRCUIT CURRENT 11.26 A JUNCTION INECTO COMBINER BOXES.
DISCONNECTS
CIRCUIT CIRCUIT(690.8 (a) &690.8
(b)) LABEL PLACEMENT:AC BREAKER
(INSIDE OR FRONT OF PANEL)
SUNRUN,INC. 3380SE20TH,PORTLAND,OR97202 DESIGNER:
sunrun OR CL#180464
PHONE 5037664332 F. JAVIDKIA SUNRUN PROJECT NUMBER: LIAG RESIDENCE REV A
FAX 503 205 0748
DRAFTER: DV LIAG (601R-900LIAN) 8900 SW PIPPEN LN., PORTLAND, OR 97224-5238 ELECTRICAL PV-02 1/14/2015
•
• NOTES: REVISION:
- 5/16" LAG BOLTS MUST EMBED
2.5" INTO ROOF STRUCTURAL MEMBERS/RAFTERS STEP 3: PLACE L FOOT
- TORQUE ALL 5/16" HARDWARE TO ON TOP OF FLASHING
SNAPNRACK THE FOLLOWING: AND TIGHTEN NUT
. COMPOSITION L FOOT - SILVER S.S. 10-16 FT-LBS
CAN BE MOUNTED IN 5 SS FLANGE NUT - BLACK S.S. 7-9 FT-LBS STEP 2: SLIP FLASHING OVER
ANY ORIENTATION . . - RAILS CAN MOUNT TO EITHER SIDE L FOOT BASE AND UNDER ROW
X 1" OR 1.25") OF L FOOT (UPSLOPE VS DOWNSLOPE) OF SHINGLES ABOVE
SNAPNRACK S.S. BOLT AND
4\••••,CHANNEL NUT SPLIT WASHER
'11-:---4.
''' <>; " S.S. LAG SCREW
�� N...10111°'.- pp WITH FLAT WASHER
SNAPNRACK i 2.5" MINIMUM EMBEDMENT
STANDARD RAIL IS STANDARD
SNAPNRACK COMPOSITION
11101.111 \
ROOF FLASHING STEP 1: BOLT L FOOT
BASE TO ROOF WITH
LAG BOLT
SNAPNRACK L FOOT BASE ROOF DECKING TYP.
4/0
• lip _ __ _ ____-------
ROOF DECKING TYP.
FLASHED L FOOT MOUNTING POINT FOR
USE ON COMPOSITION ROOF SURFACES
WITH LOW TO MODERATE TILT
RAILS CAN BE LEVELED UP TO 3" USING •
UP TO TWO LEVELING SPACERS AS
SHOWN IN "SERIES 100 RAIL LEVELING" COMPLETED INSTALLATION
RAFTER TYP.
MAINSTREAM ENERGY CORP. DESIGNER: G McPheeters SCALE: DNS PART NUMBER: DESCRIPTION: REV
S nan�f J ruQ[ -
PHONE(80552&8705•FN(805 52&97D1 DRAFTER: D Ryan ' S1 00 PEN DO1 PEN DETAIL 01 , FLASHED L FOOT TO F
ll" DATE: RAFTER
klOO unitI g en = . :=4- M°0.. APPROVED BY: 120113
ENERGIZING LIFE TOGETHER `•` REC
HIGH PERFORMANCE
SOLAR MODULES
REC PEAK
ENERGY BLK
REC Peak Energy BLK Series modules are
the perfect choice for building solar
systems that combine long lasting
product quality with reliable power
- output. REC combines high quality design
and manufacturing standards to produce
high-performance solar modules with
uncompromising quality.
I r"
410 t ' **4
MORE POWER ROBUST AND
PER FT' DURABLE DESIGN
40440?)."
kt., 44
C
E
tgA/V4
NERGY PAYBACK US-PRODUCED
TIME OF ONE YEAR SILICON
#t‘a V•14
1 I r A.' A 1, .
• REE PEAK ENER3Y BLK SERIES
65.55001 4.
.... ..1.1 . _.. ........ 3513._.._. �.. 1506
y
` r . Ifirarifig: EFFICIENCY
W. YEAR PRODUCT WARRANTY
. l
YEAR LINEAR POWER OUTPUT
WARRANTY
00
0.43 M Z
*008 . °P
j Mounting holes
a i, - Nominal Operating Cell Temperature Non 45.7°C(r2°C)
i
i a r° `" �'"" ' Temperature Coefficient of Pmcr, -0.40%/°C
Temperature Coefficient of V, -0.27%/°C
I
Temperature Coefficient of l:„ 0.024%/°C
ELECTRICAL DAV. .,it REC235PE REC240PE REC245PE REC250PE REC255PE REC260PE GENERAL DATA
BLK BLK BLK BLK BLK 8LK
Cell Type: 60 REC PE multi-crystalline
Nominal Power-P ,,(Wp) 235 240 245 250 255 260 3 strings of 20 cells
Watt Class Sorting-(W) 0/+5 0/+5 0/+5 0/+5 0/+5 0/+5 Glass: 1/8"mm solar glass with
Nominal Power Voltage-V (V) 29.5 29.7 30.1 30.2 30.5 30.7 anti-reflection surface treatment
Nominal Power Current-1,4,p(A) 8.06 817 8.23 8.30 8.42 8.50 Back Sheet: Double layer highly resistant polyester
Open Circuit Voltage-V„(V) 36.6 36.8 37.1 37.4 37.6 37.8 Frame: Anodized aluminium(black)
Short Circuit Current-l„(A) 8.66 8.75 8.80 8.86 8.95 9.01 Junction Box: IP67rated
4bypass diodes
Module Efficiency(%) 14.2 14.5 14.8 15.1 15.5 15.8 4 mm2 solar cable,35"+47"
Analysed data demonstrates that 99.7%of modules produced have current and voltage tolerance of t3%from nominal values. Hosiden 4 mm2 connectors,MC4 connectable
Values at standard test conditions STC(airmass AM 1.5,irradiance 1000 W/m',cell temperature 25°C).
At low irradiance of 200 W/m'(AM 1.5 and cell temperature 25°C)at least 97%of the STC module efficiency will be achieved.
ELECTRICAL DATA iv NULr REC235PE REC240PE REC245PE REC250PE REC255PE REC260PE
BLK BLK BLK BLK BLK BLK
Operational Temperature: -40...+80°C
Nominal Power-P,,„(Wp) 179 183 187 189 193 197
Maximum System Voltage: 600 V
Nominal PowerVoltage-V„,(V) 27.5 27.7 28.1 28.3 28.5 29.0 Design Load; 75.2lbs/ft2(3600Pa)r
Nominal Power Current-11,eP(A) 6.51 6.58 6.64 6.68 6.77 6.81 33.4lbs/ft2(1600Pa)*
Open Circuit Voltage-V„(V) 34.2 34.4 34.7 35.0 35.3 35.7 'Refer to installation manual
Short Circuit Current-It(A) 6.96 7.03 7.08 7.12 7,21 7.24 Max Series Fuse Rating: 15A
Nominal cell operating temperature NOCT(800 IN/m',AM 1.5,windspeed 1 m/s,ambient temperature 20°C). Max Reverse Current: 15 A
CERTIFICATION MECHANICAL DATA
10 year product warranty. Dimensions: 65.55 x 39.02 x1.5 in
CON IC E ❑ 25 year linear power output warranty Area: 17.76ft2
(max.degression in performance of 0.7%p.a.).
UL 1703,IEC 62716 iammoma resistance)&IEC 61701 Weight: 39.6 Ibs
(salt mist corrosion-severity level 61.
•
aiiiiiiiirs subject to change without notice.
REC is a leadingglobal provider of solar electricity solutions.With nearly two decades of expertise,we offer sustainable,high- n
- performing products, services and investment opportunities for the solar and electronics industries.Together with our I'(
partners,we create value by providing solutions that better meet the world's growing electricity needs.Our 2,400 employees
worldwide generated revenues of more than NOK13 billion in 2011,approximately USD 2.4 billion.To see more of what REC can www.recgroup.com
offer,visit www.recgroup.com
z, . .
efmtiOSA—r _fit ` f ,.- -
A MEMBER OF.THE ABB GROUP - " `.. i .t..
- 1, Y r;-..,,,..,,,,,. ,,,,, -u..r„m,,�ro++. ;i „ir-.j,, t4' ? .4%43 AA v$4t'A r F.:h? ,_. -vj.a{" au 30 ttl;Vf.,.: L 94wZ i 4,.„
' C
PVI-3• jx
PV1-3.13—IL
Plit— . -.a
__
,. a
::::°
... poi
The most common residential inverter is the ideal size for an average-
sized family home. This family of single-phase string inverter
complements the typical number of rooftop solar panels, allowing i,
home-owners to get the most efficient energy harvesting for the .,,
size of the property.This rugged outdoor inverter has been designed °'°� �'{' °� `
as a completely sealed unit to withstand the harshest environmental M -
conditions.
One of the key benefits of the Uno family of single-phase inverters ',
is the dual input section to process two strings with independent UN* �, ^
MPPT especially useful for rooftop installations with two different
orientations(ie East and West).The high speed MPPT offers real-time
NIIII---H
power tracking and improved energy harvesting.
The transformerless operation gives the highest efficiency of up to
97.0%. The wide input voltage range makes the inverter suitable to �`
low power installations with reduced string size.
' ..: -
Features ,,
• Each inverter is set on specific grid codes which can be selected in the field E.
• Single phase output
• Dual input sections with independent MPPT,allows optimal energy harvesting from two sub-arrays oriented
in different directions
• Wide input range
• High speed and precise MPPT algorithm for real time power tracking and improved energy harvesting
• Flat efficiency curves ensure high efficiency at all output levels ensuring consistent and stable performance
across the entire input voltage and output power range
• Outdoor NEMA 4X rated enclosure for unrestricted use under any environmental conditions
• Integrated DC disconnect switch in compliance with international Standards(-S Version)
• RS-485 communication interface(for connection to laptop or datalogger)
• Compatible with PVI-RADIOMODULE for wireless communication with Aurora PVI-DESKTOP
• Integrated Arc Fault Detection and Interruption(-A Version)
m.i.
BLOCK DIAGRAM OF PVI-3.0-OUTD,PVI-3.6-OUTD,PVI-3.8-OUTD AND PVI-4.2-OUTD FOR NORTH AMERICA
IN*18118
N1.11.1� I I I.,6 RUI6 CAP5 .DUACI
1�
141.71.11.7 0. • 0_ —0* 141.1016—-CI o—'� •O-
. .
YY
A ..b<
19$ N1I III :Ml 141: '
I 1 II LINE GRID PARALLEL
FILTER /� REI88
�NI.11I 4 141.11-) .— - • - .. -49-1A—
I ' I - 111.. ■ N
-1 1 a
T,.
1
1
1 T ^'
1 �� , 4K1
147.71.1C1 •a•a o- -1; ret.Io— ■ _ Y A`A�•,I167 917 t I 1 IN7 INF II ti RESIDUAL D CURRENT
CC008 NT 0
147.1119 u_ - 1942
9_ 147.11 9— '--9_ _■ L
14711-1
STANDARD VERSION -A VERSION -S VERSION 1'
. : ... _ isms
__
T/R
-. l a . RTN-lir-
IK/DC ''.,'1,‘,,t(
DSP
LISP REMOTE CONIIKKi1
_...
CON TN COMB.
f/IOIAO .L —j - R
rMAr P
OFRC1gR IJ ALARM
NC
� NO
I
CONTROL CIRCI•
•Remote 00nbN%melon nee+.Y37M 94,A venbl
Block Diagram and Efficiency Curves
- ---
PVI-4.2-OUTD-US PVI-4.2-OUTD-US
100-
> eo.00r 6 95.00%
99 i 90.00%
85.00% •96
80,00
97 75.0016 9A
_-_ 70.000 952
f 96 --- -_.. - ___ . 66.00%
1 60 wd
00%
3500A 932
� �`10.00%
940�Ca9 'N"++-�.«- -75.009e 97d
15,0096 ?
90• ,. 10.00%
096 70% 20% 3096 1096 Stl% 6096 70% ROR 90■ 100%
5OD%
7b ]! NO M 600 4e6
96 of Rated 0utput Potwar RLIITUWIRN4 M
l /
2 AURORA UNO
TECHNICAL DATA 1 VALUES PVI-3.0-OUTD-US 1 PVI-3.6-OUTD-US PVI-3.8-OUTD-US PVI-4.2-OUTD-US
Nominal Output Power W 3000 3600 3300 3800 4200
Maximum Output Power W 3000 3300' 3300' 3600 4000' 4000' 3300 4200' 4200' 4200 4600' 4600'
Rated Grid AC Voltage V 208 240 277 208 240 277 208 240 277 208 240 277
Input Side(DC)
Number of Independent MPPT Channels 2 2 2 2
Maximum Usable Power for Each Channel W 2000 3000 3000 3000
Absolute Maximum Voltage(Vmax) V 600
Start-Up Voltage(Vstart) V 200 (adj.120-350)
Full Power MPPT Voltage Range V 160-530 120-530 140-530 140-530
Operating MPPT Voltage Range V 0.7xVstart-580(>-90V)
Maximum Current(Idcmax)for both MPPT in Parallel A 20 32 32 32
Maximum Usable Current per Channel A 10 16 16 16
Maximum Short Circuit Current Limit per Channel A 12.5 20.0 20.0 20.0
Number of Wire Landing Terminals Per Channel 2 pairs
Array Wiring Termination Terminal block,Pressure Clamp,AWG10-AWG4
Output Side(AC)
Grid Connection Type 10/2W Split- 10/2W 10/2W Split 10/2W 10/2W Split- 10/2W 10/2W Split- 10/2W
_._._.,_ 0/3W 0/3W 0/3W 0/3W
AdjustableVoltage Range(Vmin-Vmax) V 183-228 211-264 244-304 183-228 211-264 244-304 183-228 211-264 244-304 183-228 211-264 244-304
Grid Frequency Hz 60
Adjustable Grid Frequency Range Hz 57-60.5
Maximum Current(lacmax) Awu 14.5 143 12.0 17.2 16.0 16.0 16.0 16.0 16.0 20.0 20.0 20.0
Power Factor >0.995
Total Harmonic Distortion At Rated Power 96 <2
Grid Wiring Termination Type Terminal block,Pressure Clamp AWG10-AWG4
'
Protection Devices '
Input +t.i ' -
Reverse Polarity Protection Yes
Over-Voltage Protection Type Varistor,2 for each channel
PV Array Ground Fault Detection Pre start-up Riso and dynamic GFDI(Requires Floating Arrays)
Output
Anti-Islanding Protection - Meets UL 174t/IEE1547 requirements
- External AC OCPD Rating . A 20 20 15 25 20 20 20 20 [ 20 25 25 25
Over-Voltage Protection Type Varistor,2IL,-L/L.-G) �'„
Efficiency "
Maximum Efficiency 96 96.9 97 97 97
CEC Efficiency i 96 + 96
Operating Performance ', '7111111111111111111.111.11111111.111.111 "111111=111.111111.1111111.111M
Night Time Consumption Wass <0.6
Stand By Consumption Was, <8
Communication
User-Interface 16 characters x 2 lines LCD display
Remote Monitoring(1 xRS485 incl.) AURORA-UNIVERSAL(opt.)
Wired Local Monitoring(1xRS485 incl.) PVI-USB-RS485_232(opt.),PVI-DESKTOP(opt.)
Wireless Local Monitoring PVI-DESKTOP(opt.)with PVI-RADIOMODULE(opt.)
Environmental 1111111r
Ambient Air Operating Temperature Range __ °F(°C) -13 to+1401-25 to+60)with derating above 122(50)
Ambient Air Storage Temperature Range ___ °F(°C) -40 to 176(-40 to+80)
Relative Humidity 96 RH 0-100 condensing
Acoustic Noise Emission Level a db(A)41m <50
Maximum Operating Altitude without Derating I ft(m) 6560(2000)
Mechanical Specifications
Enclosure rating 1 NEMA 4X
r
Cooling Natural Convection
Dimensions(H x W x DI in(mm) 33.8 x 12.8 x-8.7(859 x 325 x 222)
Weight lb Ikg) <47.3(21.3)
Shipping Weight lb(kg) <60(27.0)
Mounting System Wall bracket
Trade size KOs:(tea x 1/2")and
Conduit Connections' (tea x 1-1/4;3 places side,front,rear)
Side:(2)plugged 3/4"openings,(2)Concentric EKOs 3/4°1"
Back:(4)Concentric EKOs 3/4;1"
DC Switch Rating-(Per Contact) AN 25/600
Safety 1111111111111 ARP . ,,, a. .k
Isolation Level Transformerless(Floating Array)
Safety and EMC Standard UL 1741,IEE1547,IEE1547.1,CSA-C22.2 N.107.1-01,UL1998 UL1699B,FCC Part 15 Class B
Safety Approval 1 ,CSA,,,
Warranty
Standard Warranty i t years 10
Extended Warranty I years 15&20
Available Models
,, . __ _ nail �_
Standard-Without DC Switch and Wiring Box PVI-3.0-OUTD-US PVI-3.6-OUTD-US PVI-3.8-OUTD-US PVI-4.2-OUTD-US
Standard-With DC Switch and Wiring Box PVI-3.0-OUTD-S-US PVI-3.6-OUTD-S-US PVI-3.8-OUTD-S-US PVI-4.2-OUTD-S-US
With DC Switch,Wiring box and Arc Fault Detector PVI-3.0-OUTD-S-US-A PVI-3.6-OUTD-S-US-A PVI-3.8-OIITD-5-US-A PVI-4.2-OUTD-S-US-A
and Interrupter
'All data is subject to change without notice
'Capability enabled at nominal AC vohage and with sufficient DC power available
'When equipped with optional DC switch and Wring Box AURORA UNO 3
•
•
ti
u
O
C
7
0
L
3
C
Ql
E
a
E.
• ,,,' ,q. �'.,. �. .* `.A
E..�4 e ti � �ti k e'` cam � " ',.,`\
e� t •„,: s my y _A°g X m d
C
N
C
0
D.
a
grjtag.21&11
ti-r
Z
O
it
M
IMIll
www. • ower-one.co
Power-One Renewable Energy Worldwide Sales Offices
Country Name/Region Telephone Email
Australia Asia Pacific +61 2 9735 3111 sales australia @power-one.com
China(Shenzhen) Asia Pacific +86 755 2988 5888 sales.china @power-one.com
China(Shanghai) Asia Pacific +86 21 5505 6907 sales.china @power-one.com
India Asia Pacific +65 6896 3363 sales.india @power-one.com
Japan Asia Pacific 0+36-546588960-23731643/+81 3 4580 2714 sales.japan @power one.com
Singapore
Asia Pacific sales.singapore @power onecom
Belgium/The Netherlands/Luxembourg
Europe +32 2 206 0338 sales.belgium @power-one.com
France
Europe +33(0)141 796 140 sales.france@power one.com
Germany Europe +49 7641 955 2020 sales.germany @power one.com
Greece Europe 0080000287672 sales.greece @power one.com
Italy Europe 0080000287672 sales Italy @power one.com
Spain Europe +34 91 879 88 54 sales spam @power-one.cam
United Kingdom Europe +44 1903 823 323 sales.uk @power-onecom
Dubai Middle East +971 50 100 4142 sales.dubai @power-one.com
Israel Middle East +972 0 3 544 8884 sales.israel @power-ane.com
Canada North America +1877261-1374 sales.canada @power-one.com
USA East North America +t 877 261 1374 sales.usaeast @power-one.com
USA Central North America +i 8887777772266
77 261-1374 sales.usacentral @power one.com
USA West North America +t 877 261-1374 sales.usawest @power-one.corn
CSA ,
Certificate of Compliance �.. ..-
Certificate: 2096477 Master Contract: 173688
Project: 2682842 Date Issued; November 28, 2013..,.•:: :
Issued to Power-One,Inc
3201 E Harbour Dr
Phoenix,AZ 85034
USA
Attention:Mr Robert White
The products listed below are eligible to bear the CSA.
Mark shown with adjacent indicators 'C' and 'US'for
Canada and US or with adjacent indicator 'US'for
US only or without either indicator for Canada only.
Roi-ff emp toth Issued by: Rob Hempstock,AScT.
C CD
US
PRODUCTS
-CLASS 5311 09 .-POWER SUPPLIES-Distributed Generation Power Systems Equipment •
CLASS.531189 ' POWER SUPPLIES-Distributed Generation-Power Systems Equipment
-.Certified to U.S. Standards
Utility‘Interactive'Inverter,Models PVI-4.2-OUTD-US PVI-3.8-OUTD-US,.PVI-3:6-OUTD-US,PVI-3.0i
OUTD-US,PVI-4.2-OUTD-S-US,PVI-3.8-OUTD-S-US,PVI-3;.6-OUTD-S-US,PVI-3 0-OUTD-S-US,
PVI-4.2 OUTD-S-US-A,PVI-3.8=OUTD-S'-US-A,PVI-3.6-OUTD-S-US-A,PVI 3.0-OUTD-S US-A,PVI-4.2-
OUTD-US-W,PVI-3.8-OUTDUS-W,PVI-3.6-OUTD-US-W and PVI-3.0-OUTD-US-W provided with two
DC input channels,permanently connected
Notes:
I. All above models in this series may include expansion board with wireless antennae option and will be
identified with model designation including"-Z"suffix.
2. For details related to ratings,reference should be made to the CSA Certification Record,Appendix l or the
Descriptive Report.
DQD 507 Rev 2012-05-22 Pte.
•
',rr . . Group
Certificate 2096477-. .
••' _.. . . • .... 1tilfaster:Cointract::• 1173
_:.. Pxoi;ect . .-:-=:: •2682$42-:`., : • .:.: ::. : •.`'.•
::'.• .. ... .: : . .<,:.• . 28,:201
. D.st
. . to Iss
ue�; - : - : •:Noventiber 3 .:_. • : ;
. PPLICABLE REQU NTS
IR�EME' •
CSA.C22 2 No 1071 01 General Use•Power Suppli0
IVI*StiliNiii, 1741uSecond Editronl:-JtiVerters,•Cohvertcrs;:Controllers and.1tstereonneetran System Equipment°.
.
for Use With ITtstributed Ene Resources (anti. . 28-,:21)191,-....,, '
UL_1:699I4.• • Ch fine ofJnvestigation for•Photovoltaic(PV)DC Arc-Fautt Circuit Protection(Issue Number 2;
•
January 14,2013)= - .
CSA TIL M-07 -•Interim Certification Requirements for Photovoltaic(PV) DC Arc-Fault Protection(Issue
Number I,March 11,2013)
*Note: Conformity to UL 1741-Second Edition(January 28, 2010)includes compliance with applicable
requirements ofIE.EE 1547 and IEEE 1547.1
•
•
•
•
•
•
•
•
•
•
•
•
•
•
)QD 507 Rev.2012-05-22
Page:2