Report Ansul wet chemical fire system. Model R-102 9 gallon capacity. 3-3 gallon cylinders. Duct: 10"x18" Duct: 10"x18" Flow point capacity: 33 Flow points used: 27 Fusible 3/8"blk pipe Links 2W 2W 2W 2W 450F e a a 6 33'Type I Hood --1-1 1-1-1— I — 1 Single Filter Bank -ED 01 1N 1N ANSUL e 9 9 9 9 9 9 9 9 3N 3N 3N IN IN IN 1N IN IN 25" 25" 25" 30" 30" 30" 30" 30" 30" 35" 35" 35" 40" 40" 40" 40" 40" 40" l'iot Oemote Pull - Ig Remote `v, 10'-20'from hood. 45 b r. t .e. Z,.- c,,;A, 48"-54" $ e' • '"' r* '''"'' "c–:-; It; K Class Exting- i I 22" 22" 24" 24" 'i��,� P f wisher _ : ‘� w/placard. / — 1 I _I 1,1 I -1 al I►=" c 0 4 it 6 Hole Wok Unit orj Automatic gas Fry 18"x18" 14"x15"14"x15" ! y 0 ori shut off valve. Dump Fryer Fryer Fryer n N O Manual resetting type. n 0 4 till 0 Fuel to equipme to shutrdow o ire G system actuaticff b Fire System Drawing Front View System shall sigal bu �ltyr system resent. (� ht, Guardian Fire Protection Job: Mizumi Buffet Notes; Fire system inst 1 acc ordance Ai Ansul 4025 Commercial Way SE 13500 SW Pacific Hwy design, installatio .nd"maintenance manual. 3' Tigard OR Albany OR 97321 System tested in accordance with UL 300. CCB # 100355 exp. 6/14 Date: 01/15 Drawn by: MAF SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-1 7-1-09 REV.8 SYSTEM DESIGN GENERAL INFORMATION The ANSUL R-102 Restaurant Fire Suppression System may be 1.Nozzles must be located 2-8 in.(5-20 cm)into the center of the used on a number of different types of restaurant cooking appli- duct opening, discharging up.See Figure 1. ances and hood and duct configurations.The design information listed in this section deals with the limitations and parameters of this pre-engineered system.Those individuals responsible for the design of the R-102 system must be trained and hold a current ANSUL certificate in an R-102 training program.IJjjIIIIIIIIIIPIPI The R-102 and the PIRANHA systems use compatible agents and components, therefore, they may be used together for cooking appliance, hood, and duct protection. The primary ANSUL AUTOMAN Release can be either an R-102 or a PIRANHA ANSUL AUTOMAN Release and can actuate up to two additional R-102 or PIRANHA Regulated Actuators. In systems utilizing a 101 remote release, any combination of the maximum number of I 2-8 IN regulated actuators can be used s zo cm) • Both systems must actuate simultaneously. • Each system must be designed and installed per its appropri- FIGURE 1 ate manual. 000,]3 • Adjacent appliances requiring protection must be protected 2. In installations where a UL listed damper assembly is with the same type of system, either R-102 or PIRANHA, employed, the duct nozzle can be installed beyond the 8 in. unless the center-to-center spacing between the adjacent (20 cm) maximum, to a point just beyond the damper assem- ' R-102 and PIRANHA nozzles is no less than 36 in.(91.4 cm). bly that will not interfere with the damper. Exceeding the maxi- When appliances are protected with R-102 nozzles, the hood mum of 8 in. (20 cm) in this way will not void the UL listing of and connecting duct above those appliances cannot be pro- the system. tected with PIRANHA nozzles. 3.Previously listed 3 flow number and 5 flow number duct pro- • Mixing systems in a common plenum is not allowed tection detailed in earlier published manual, Part No. 418087- One of the key elements for restaurant fire protection is a correct 06, can also still by utilized. system design.This section is divided into ten sub-sections-Noz- DUCT SIZES UP TO 50 IN. (127 cm) zle Placement Requirements, Tank Quantity Requirements, Actu- PERIMETER/ 16 IN.(41 cm) DIAMETER ation and Expellant Gas Line Requirements, Distribution Piping Requirements, Detection System Requirements, Manual Pull Sta- One 1W nozzle (Part No.419336) =one flow number tion Requirements, Mechanical Gas Valve Requirements, Electri- • 50 in (127 cm) perimeter maximum cal Gas Valve Requirements, Electrical Switch Requirements, and Pressure Switch Requirements. Each of these sections must be • 16 in.(41 cm)diameter maximum completed before attempting any installation. System design sketches should be made of all aspects of design for reference DUCT SIZES UP TO 100 IN. (254 cm) during installation. PERIMETER/32 IN.(81.3 cm) DIAMETER NOZZLE PLACEMENT REQUIREMENTS • One 2W Nozzle (Part No.419337) =two flow numbers This section gives guidelines for nozzle type, positioning, and • 100 in. (254 cm) perimeter maximum quantity for duct,plenum, and individual appliance protection.This • 32 in.(81.3 cm)diameter maximum section must be completed before determining tank quantity and piping requirements. The chart below shows the maximum protection available from each duct nozzle Duct Protection—Single Nozzle Part 3.0 Gallon 1.5 Gallon All duct protection is UL listed without limitation of maximum duct Description No. System System length (unlimited length).This includes all varieties of ductworks 2W Nozzle 419337 Maximum Maximum both horizontal and vertical including ducts that run at angles to 100 in.(254 cm) 100 in.(254 cm) the horizontal and ducts with directional bends. Perimeter Perimeter The R-102 system uses different duct nozzles depending on the 1W Nozzle 419336 Maximum Maximum size of duct being protected. 50 in. (127 cm) 50 in.(127 cm) Perimeter Perimeter SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-5 7-1-09 REV.5 Plenum Protection The R-102 system uses the 1W Nozzle (Part No.419336) or the q 1N Nozzle (Part No 419335) for plenum protection.The 1W noz- zle 20 IN.(s1 cm) tip is stamped with 1W and the 1N nozzle tip is stamped with MAXIMUM 1N, indicating they are one-flow nozzles and must be counted as one flow number each. When protecting a plenum chamber, the entire chamber must be protected regardless of filter length �y w 1 IN.(2.5 cm) MINIMUM VERTICAL PROTECTION—GENERAL �B: =- 1 W NOZZLE — PART NO. 419336 — SINGLE AND"V" BANK ' PROTECTION 20 IN (51 cm) One 1W nozzle will protect 4 linear feet (1.2 m) of plenum.The MAXIMUM maximum distance from the end of the hood to the first and last nozzle must be no more than 2 ft(0.6 m).After the first nozzle,any t additional nozzles must be positioned at a maximum of 4 ft(1.2 m) 1 IN.(2.5 cm) apart down the entire length of the plenum.The plenum width must MINIMUM not exceed 4 ft(1.2 m).(The 1W nozzle can be used on single or I'd`• r V-bank filter arrangements.) See Figure 6. FIGURE 7 000199 2 FT(0.6 m) MAXIMUM ., Option 2:The 1W nozzle must be placed perpendicular, 8-12 in MAX MUM) (20-30 cm)from the face of the filter and angled to the 4 FT(1.2 m) /J�4 FT(1.2 m) center of the filter.The nozzle tip must be within 2 in. 2 FT(0.6 m)MAXIMUM MAXIMUM (5 cm) from the perpendicular center line of the filter. MAXIMUM ' See Figure 8. �v 4*—..-----'-A° ' r 12 IN.(30 cm) MAXIMUM ► / IN.110 cm) w 8IN.(20 cm) ,`/ / Ii' MINIMUM NOZZLE TIP 41V Ai t MUST BE WITHIN ," F THIS AREA FIGURE 6 ::: 000 i9? it When protecting plenums with the 1W nozzle,two options of cov- LI" erage are available: FIGURE 8 000200 Option 1:The 1W nozzle must be on the center line of the single or "V" bank filter and positioned within 1-20 in HORIZONTAL PROTECTION—OPTION 1 (2.5-51 cm) above the top edge of the filter. See 1N NOZZLE—PART NO.419335—SINGLE BANK PROTECTION Figure 7. One 1N nozzle will protect 10 linear feet(3.1 m)of single filter bank plenum. The nozzle(s) must be mounted in the plenum, 2 to 4 in. (5 to 10 cm) from the face of the filter, centered between the filter height dimension, and aimed down the length.The nozzle must be positioned 0-6 in.(0-15 cm)from the end of the hood to the tip of the nozzle.See Figure 9. '1i. 2—4 IN. 10 FT.(3.1 m) N (5—10 cm) MAXIMUM il 1 • 000201 11111 i� FIGURE 9 SECTION IV - SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-9 4-1-06 REV.8 Fryer-Single Nozzle Protection (Continued) Maximum Area Dimensions-Single Nozzle Fryer Protection (Continued) Max.Size Max.Size Overall Type of Nozzle Height Nozzle • Frypot Only With Dripboard Nozzle Above Top of Fryer Location 19.5 in.x 19 in. 19.5 in.x 25 3/8 in. 290 13 in.to 16 in. See Figure 17 (50 cm x 48 cm) (50 cm x 65 cm) (33 to 41 cm) • 19.5 in.x 19 in. 19.5 in.x 25 3/8 in. 3N See Figure See Figure 18 (50 cm x 48 cm) (50 cm x 65 cm) 18 •18 in.x 18 in. 18 in.x 27 3/4 in. 3N 25 in.to 35 in. See Figure 19 •(46 cm x 46 cm) (46 cm x 70.5 cm) (64 cm to 89 cm) -r-, = -T-�, J .,I ' I � 1 'r 1 II ) 1 I II I I I i I =' TOP OF FRYER I� � I I 71:6111°.' FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD pq0 F�O 290 NOZZLE TIP POSITIONED OVER THE MIDPOINT OF THE HAZARD AREA±3 IN. (7.6 cm)FROM THE MIDPOINT ALONG THE LONGEST SIDE OF THE HAZARD AND±1 RIGHT-TO-LEFT 000008 IN.(2.5 cm)FROM THE MIDPOINT ALONG THE SHORTEST SIDE OF THE HAZARD AND 000010 CENTERLINE AIMED AT THE MIDPOINT OF THE COOKING AREA. FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD FIGURE 17 NOTE: 3N NOZZLE TIP MUST BE LOCATED WITHIN THE PERIMETER OF THE SURFACE 002286 AREA WITHIN THE FRONT HALF OF THE FRY POT AND AIMED AT THE CENTER. FIGURE 19 34 IN.(86 cm)MAXIMUM DIAGONAL DISTANCE BETWEEN NOZZLE AND CENTER OF HAZARD AREA -T._ T, >,'1 >G- - 1 � .J 21 in.(53 cm) I �>\':,/,''.::-.--- MINIMUM K .%1 1 ''''-.1-1 `-y-''- I VERTICAL I -. I_ I 1 I NOZZLE �� HEIGHT I .'� 41114i111%. 1110.1° FRYER WITHOUT DRIPBOARD FRYER WITH DRIPBOARD 3N NOZZLE TIP POSITIONED ANYWHERE ALONG OR WITHIN PERIMETER OF COOKING SURFACE AND AIMED TO THE CENTER OF THE COOKING AREA. FIGURE 18 onnv SECTION IV — SYSTEM DESIGN UL EX3470 ULC EX3470 Page 4-27 7-1-09 REV.5 Wok Protection 2 A 1N Nozzle, Part No.419335,will protect a wok 11 in.(28 cm) The R-102 system uses two different nozzles for the protection of minimum diameter up to 24 in. (61 cm) maximum diameter. woks The wok depth must be no less than 3 in. (8 cm) and no greater than 6 in. (15 cm).The nozzle tip is stamped with 1N 1. A 260 nozzle, Part No. 419341, will protect a wok 14 in. indicating that this a one-flow nozzle and must be counted as (36 cm) minimum diameter up to 30 in. (76 cm) maximum one flow number.When using this nozzle, the nozzle must be diameter. The wok depth must be no less than 3.75 in. positioned anywhere along or within the perimeter of the wok, (9.5 cm)and no greater than 8 in. (20 cm). aimed at the center, 30 in.to 40 in. (76 to 102 cm) above the The nozzle tip is stamped with 260 indicating that this is a two- ' hazard surface, as shown in Figure 65. flow nozzle and must be counted as two flow numbers. NOTICE When using this nozzle, the nozzle must be positioned as When using this type of wok protection, only . shown in Figure 64. 5 flow numbers are allowed on a 1 1/2 gal . (5.7 L) system, and only 11 flow numbers are NOZZLE MUST BE POSITIONED WITHIN 1 IN.(2 cm)RADIUS • allowed on a 3 gal (11.4 L)system. OF THE CENTER OF THE WOK,POINTED VERTICALLY DOWN r 1 I . ,1 '1 I 1 / I 1 4o IN. , ! r 1 , \ (102 cm) ` � / i 260 NOZZLE / 1 / 130 IN. I I i ' / ) (76 cm) MINIMUM DEPTH T I 3.0 IN.(7.6 cm) I . . i MAXIMUM DEPTH 6.0 IN (15 cm) 35—45 IN. 11 IN.(28 cm)MINIMUM DIAMETER (89—114 cm) 24 IN.(61 cm)MAXIMUM DIAMETER MINIMUM DEPTH 3.75 IN.(9.6 cm) MAXIMUM DEPTH 8 IN.(20 cm) I ■ FIGURE 65 _ 000261 4 I , 14 IN.(35.6 cm)MINIMUM DIAMETER 30 IN.(76.2 cm)MAXIMUM DIAMETER FIGURE 64 000261 SECTION IV - SYSTEM DESIGN • UL EX3470 ULC EX3470 Page 4-56 REV.4 7-1-09 DISTRIBUTION PIPING REQUIREMENTS(Continued) ► Distribution Piping Requirements-9.0 Gallon System I - Igii Ai This optional configuration consists only of three 3-gallon tanks,all pressurized from a single double-tank nitrogen cartridge with •expellant gas hoses connected as shown in Figure 117.Tanks No. 1 and No.2 must be connected directly to the regulator with sepa- rate expellant gas hoses and Tank No. 3 must be connected to ■ Tank No.2 with a third expellant gas hose as shown in Figure 117. Each tank must be connected to an independent distribution pip- •ing network as shown in Figure 117. Distribution piping require- ments for each network must be as follows. 1 - -- +1 1. The maximum length between the start of the first branch line r 1��-f.'i' - •and the start of the last branch line must not exceed 24 ft • (7.3 m).When the supply line is split, the combined total of s 1 both legs of the supply line (from the start of the first branch I • • line to the start of the last branch line) must not exceed 24 ft it ► (7.3 m). See Figure 113. 2. The total length of all branch lines must not exceed 36 ft • ► (10.9 m).See Figure 113. , 3.0 3.0 3.0 DI GALLON GALLON GALLON 3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. TANK TANK I TANK i', No.3 NO.2 NO.1 • supply line • 4 A maximum of two nozzles are allowed per duct branch line . ,. / 1 5. When using this 9.0 gallon system configuration, no mani- I y g TWO TANK ENCLOSURE 3 GALLON REGULATED DOUBLE TANK NITROGEN folding of distribution piping is allowed. ASSEMBLY PART NO RELEASE ASSEMBLY, CARTRIDGE OR 430324(INCLUDES(2) OR 3 GALLON LT-A-101-30 CARTRIDGE 6. When an ANSUL AUTOMAN Regulated Release is utilized in HOSES AND(2) REGULATED ACTUATOR (REGULATED ACTUATOR this configuration, additional regulator actuators cannot be GROMMETS) ASSEMBLY ONLY) used. NOTE: WHEN THREE(3)3.0 GALLON TANKS ARE CONNECTED TO ONE(1) 7. Only 3 gallon tanks Can be utilized In this Configuration. AUTOMAN REGULATED RELEASE ASSEMBLY,NO ADDITIONAL REGULATED ACTUATOR(S)ASSEMBLIES CAN BE USED. 8. The requirements of the following table must not be exceeded ► FIGURE 117 for each 3 gallon tank. 508126 Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in 3/8 in. 3/8 in. Maximum Length 40 ft 8 ft 4 ft 12 ft (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 ft 4 ft 2 ft 2 ft (1.8 m) (1.2 m) (0.6 m) (0.6 m) Maximum 90° 9 4 4 6 Elbows Maximum Tees 1 2 2 4 Maximum Flow 11* 4 2 4 Numbers 'Exceptions: 1.Twelve(12)flow numbers are allowed in any one tank for duct and plenum protection ONLY. 2.Twelve(12)flow numbers are allowed with any one tank using only two-flow appliance nozzles. 3.Twelve(12)flow numbers are allowed with any one tank using only three-flow appliance nozzles. Special Instructions: ■ 1. When four(4)Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 66 on Page 4-32,the discharge piping must be as shown in Figure 67 on Page 4-32 2. For certain McDonald's applications.11.5 flow numbers are allowed when using a combination of one(1)2W duct nozzle,one(1)1/2N electrostatic precipitator nozzle, one(1)1N plenum nozzle,and four(4)two-flow appliance nozzles.Contact Ansul Applications Engineering Department for additional information.