Report acu"i>,rL: quote
4 klN
• �1 'gat"k k
Tuesday, September 30, 2014 Quote#: 2123914 Mizumi Buffet-Tigard
To: From: Ship-To:
Mizumi Buffet David Hong HONG'S RESTAURANT
13500 SW Pacific Hwy. HONG'S RESTAURANT EQUIPT/NISSC
Tigard, OR 97223 EQUIPT/NISSC 7421 NE Beech Street
7421 NE Beech Street Portland, OR 97213
Portland, OR 97213 Phone: (503) 284-7800
Phone: (503)284-7800 hongsinc @yahoo.com
hongsinc @yahoo.com
CaptiveAire Systems proposes to furnish the following equipment. Production of listed items will commence upon
receipt of an approved proposal, a purchase order, an approved submittal, and approved credit.
EQUIPMENT
AECEWED
Hood#1 -Island Hood
6030ND-2WI-PSP-FSS- 14ft 0" Long Exhaust-Only Island Canopy Hood with X1
Front and Two Side Perforated Supply Plenums with Built-in 3" Back Standoff OCT 2 9 2014
and Finished back
CITY OF
430 SS Where Exposed BM-' DIVISION
-FILTER-20"tall x 16"wide Stainless Steel Captrate Solo filter with hook, X j,"U"il,V ING
ETL Listed. Particulate capture efficiency: 93%efficient at 9 microns, 72%
efficient at 5 microns
- L55 Series E26 Canopy Light Fixture-High Temp Assembly, Includes Clear x4
Thermal and Shock Resistant Globe(L55 Fixture), Bulbs By Others
-EXHAUST RISER- Factory installed 10"X 23" x2
-SUPPLY RISER- 14"Square to 12"Round Supply Collar with 12"Round x17
Volume Damper.
• Nailor 1090 Series.
- 1/2 Pint Grease Cup New Style, Flanged Slotted x4
-STRUCTURAL FRONT PANEL x1
-FINISHED BACK- ISL/REV INSTALL 168.00" Long x1
Hood#1 Total Price: $6,300.00
Fire System#1
ANSUL-3.0 Ansul 3 gallon Wall Mounted Fire System(includes pre-piped x1
hood(s)with detection).
Includes piping for hood: 1.
-- INCLUDES: HOOK-UP, PERMIT, TEST,AND PROVIDING (1) x1
Pane 1 of 1
f ,
Tuesday,September 30,2014 Quote#:2123914 David Makoto-Tigard
MECHANICAL GAS VALVE UP TO 2"
-EXCLUDES: HANGING WALL MOUNTED UTILITY CABINET IF
APPLICABLE, LOCKABLE FULL FLOW INDICATING SHUT OFF VALVE
(FOR PIRANHA SYSTEMS), K-CLASS FIRE EXTINGUISHER,
CONNECTING TO BUILDING FIRE ALARM PANEL/SYSTEM; PROVIDING
/CONNECTING FIRE ALARM AUDIO/VISUAL DEVICES,ALL UNION
LABOR&PREVAILING WAGES
-***NOTE***COOKING EQUIPMENT MUST BE VERIFIED PRIOR TO
ORDER RELEASE.ANY CHANGES TO EQUIPMENT TYPE, SIZE, OR
SEQUENCE WILL REQUIRE A NEW QUOTE.ANY CHANGES MADE TO
COOKING EQUIPMENT ONCE ORDER IS RELEASED WILL REQUIRE A
FIELD CHANGE ORDER TO EXECUTE AT AN ADDITIONAL CHARGE
Fire System#1 Total Price: $3,200.00
Fan#1 DU240HFA-Exhaust Fan (EF-1 (Main Hood))
DU240HFA High Speed Direct Drive Centrifugal Upblast Exhaust Fan with x1
speed control, disconnect switch and 24"wheel.
Exhaust Fan handles 4900 CFM @-1.400"wc ESP, Fan runs at 898 RPM.
Exhaust Motor: 5.000 HP, 3 Phase 208 V, 60Hz, 15.0 FLA, ODP, Premium
(E-PIus3) Eff.
-Grease Cup for kitchen-duty centrifugal exhaust fans, x1
Box Dimensions 15-3/4 L X 5-1/16 W X 3-3/4 H (18 GA.) (Includes Down
Spout)
-EF-1 (Main Hood) Curb CRB31.5x20E On Fan# 1 Flat Curb x1
-Hinged Base for Curb. Heavy Duty Hinge attached to curb. Used on Fans x1
with wheels 24 inches or larger.
-Vented Base for Curb x1
Fan Total Price: $1,600.00
Fan#2 A3-D.500-G18-Heater(MAU-1)
A3-D.500-G18 Direct Gas Fired Heated Make Up Air Unit with 18"Blower and x1
12"Burner.
Supply Fan handles 4655 CFM @ 0.750"wc ESP, Fan runs at 713 RPM.
Heater supplies 241315 BTUs. 48°F Temperature Rise. [Fuel: Natural Gas]
Supply Motor: 3.000 HP, 3 Phase 208 V,60Hz,9.5 FLA, ODP (Open Drip
Proof)
Down Discharge-Air Flow Right-> Left
-Sloped Filtered Intake for Size#3 Modular Heater. x1
37.25"Wide X 51.625" Long X 35.188" High.
Includes 2" MV EZ Kleen Metal Mesh Filter.
-RTC Solutions• 40-90°F Discharge Temp Control x1
-Gas Manifold for DF3 GM -BTU 0- 1100001 -7 in.w.c.- 14 in.w.c., No x1
Insurance Requirement(ANSI), BV250-88
-Motorized Back Draft Damper 30"X 30"for Size 3 Standard& Modular x1
Direct Fired Heaters w/Extended Shaft, Standard Galvanized Construction,
3/4"Rear Flange, NFBUP-S Actuator Included
-Cooling Interlock Relay. 24VAC Coil. 120V Contacts. Locks out burner x1
circuit when AC is energized.
-Low Fire Start. Allows the burner circuit to energize when the modulation x1
control is in a low fire position.
-Gas Pressure Gauge, 0-35", 2.5"Diameter, 1/4"Thread Size x1
Tuesday,September 30,2014 Quote#: 2123914 David Makoto-Tigard
-Gas Pressure Gauge, -5 to+15 Inches Wc.,2.5 Diameter, 1/4"Thread Size x1
-Extra Set of V-Belts. Only to be ordered as fan option at time fan is x1
ordered.
- Separate 120VAC Wiring Package for Make-Up Air Units. Option must be x1
selected when mounting VFD in prewire panel or with DCV package.
Provides separate 120VAC input to supply fan. This 120V signal must be run
by electrician from DCV to mua switch.
-MAU-1 Curb CRB35X84X2OINS Insulated On Fan#2 Flat Curb x1
Fan Total Price: $5,750.00
(Add$2,050.00 for Celdek Evap. module which includes freeze protection drain control kit)
Electrical System#1
DCV-1111 Demand Control Ventilation,w/ 1 Exhaust Fan, 1 Supply Fan, x1
Exhaust on in Fire, Lights out in Fire, Fans modulate based on duct
temperature. INVERTER DUTY THREE PHASE MOTOR REQUIRED! Room
temperature sensor shipped loose for field installation.Verify distance between
VFD and Motor; additional cost could apply if distance exceeds 50 feet.
Includes 2 Duct Thermostat kits.
-ESV402NO2TXB571 -Variable Frequency Drive-5 HP Max., 200/240 V, x1
Three Phase, 16.5 A Max., NEMA 1 Enclosure,with 2RJ-45 FOR MODBUS
- ESV222NO2YXB571 -Variable Frequency Drive-3 HP Max., 200/240 V, x1
Single or Three Phase Input, 9.6 A Max., NEMA 1 Enclosure,with 2RJ-45
FOR MODBUS
-20 wide X18 tall X8.62 deep SS HINGED ELECTRICAL BOX NEMA 1 - x1
VENTED. Includes Fan Filter Assembly.
-USED ON NEW SC-EMS CONTROL PANELS
-CASLink Building Monitoring system communications module. Includes x1
monitoring provisions for CORE interlock fire network and hood control
network. Requires internet connection.
-CAT-5E CABLE-100 Foot. x1
-PSP thermostat kit, includes lx duct thermostat, quick seal, and j-box for x1
monitoring of PSP discharge temperature.
- Digital Prewire Lighting Relay Kit. Includes hood lighting relay&terminal x1
blocks. Allows for up to 1400W of lighting each.
-Thermistor CABLE- 18/2 AWG GREEN WHITE, plenum rated. USED for x100
thermistorduct stat. Per Foot Price.
Electrical System#1 Total Price: $3,850.00
IN OREGON, IF PGE OR PACIFIC POWER IS THE ENERGY PROVIDER,
ENERGY TRUST OF OREGON PROVIDES A REBATE OF$750 PER FAN
PER HORSEPOWER WHEN DEMAND CONTROL VENTILATION (DCV) IS
ORDERED AND INSTALLED. FOR THIS PROJECT,THE END USER CAN
RECEIVE A REBATE OF $6,000 BY PURCHASING THE DCV. REBATE
CHECKS ARE ISSUED 4—6 WEEKS AFTER PAPERWORK IS
COMPLETED.
Subtotal: $20,700.00
Shipping: included
Tax: Not Included
Total: USD$20,700.00
HOOD INFORM TION — JabI21,23914
EXHAUST PLENUM HOOD CONFIG.
MAX. TOTAL
HOOD RISER(S) HOOD
NO. TAG MODEL LENGTH COOKING TOTAL SUPPLY CONSTRUCTION END TO ROV
TEMP. EXH. CFM WIDTH LENG. DIA. CFM S.P. CFM END
6030 14' 0.00' 600 De 10' 23' 2450 -0.963' 4655 430 SS ALONE ALONE
1 Island Hood ND-2W-PSP-FSS 9• 4900 10' 23' 2450 -0.963' Where Exposed
JJOOD INFORMATION
FILTER(S) LIGHT(S) UTILITY CABINETS) FIRE HOOD
HOOD EFFICIENCY 0 9 WIRE FIRE SYSTEM ELECTRICAL SWITCHES SYSTEMHANGINC
Na.
TAG TYPE CITY.HEIGHT LENGTH MICRONS OTT. TYPE GUARD LOCATION TYPE SIZE MODEL N QUANTITY PIPING VGHT
1 Island Hood Captrate Solo Filter 10 20' 16' 935 See Filter Spec. 4 L55 Series E26 NO 886
YES
LBS
HOO OPTIONS SPECIFICATION, CAPTRATE.GREASE-STOP.SOLO FILTER
Hoop TAG OPTION
NO. THE CAPTRATE GREASE-STOP SOLO FILTER IS A SINGLE-STAGE FILTER FEATURING
1 Island Hood STRUCTURAL FRONT PANEL A UNIQUE S-BAFFLE DESIGN IN CONJUNCTION WITH A SLOTTED REAR BAFFLE DESIGN,
FINISHED BACK- ISL/REV INSTALL 168.00' Long TO DELIVER EXCEPTIONAL FILTRATION EFFICIENCY,
FILTER 4SS STtrNLESS STEEL CONSTRUCTION, AND SIZED TO FIT INTO STANDARD
PERFORATED SUPPL" PLENUM(S) 2-INCH MEP OOD CHANNEL(S).
HOOD RISERS) UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO
NO TAG POS. LENGTH WIDTH HEIGHT TYPE WIDTH LENG. DIA. CFM S.P. COMPONENTS WHEN ASSEMBLED.
1 Island Hood Front 168' 14' 6' MUA 12' 274 0.095' GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 751 OF GREASE
MUA 12' 274 0.095' PARTICLES FIVE MICRONS IN SIZE, AND 901 GREASE PARTICLES SEVEN MICRONS IN SIZE AND
LARGER, WITH A CORRESPONDING PRESSURE DROP NOT TO EXCEED 1.0 INDIES OF WATER GAUGE.
MUA 12' 274 0.095' ._i —_
MUA 12' 274 0.095' THE CAPTRATE GREASE-STOP SOLD WAS TESTED TO ASTM STANDARD ASTM F2519-05.
MUA 12' 274 0.095' FILTER COLLECTION EFPICIENCYr o,4441.s..�w..44,
MUA 12' 274 0.095'
MUA 12' 274 0.095' .
MUA 12' 274 0.095' .
MUA 12' 274 0.095' t RESETANCG PS.AIRFLOW.rr 4. say.m..
Left 74' 14' 6' MUA 12' 272 0.094'
MUA 12' 272 0.094' .. •' f•
MUA 12' 272 0.094' i •
MUA 12' 272 0.094' B .A
Right 74' 14' 6' MUA 12' 272 0.094' 1 j
MUA 12' 272 0.094' F
MUA 12' 272 0.094' e ' / '/
MUA 12' _272 0.094' • / /•
N FI
PARTICLE DLWET/ Om) AIRYI,OW On)
CAPTRATE FILTERS ARE BUILT IN COMPLIANCE WITH..
NFPA 496
NSF STANDARD 2 Y 0
UL STANDARD N11 E1� CD INT. MECH. CODE <INC)
•
•
•
JOB David Makoto - Tigard
r/TI, �U if °� 'q0 DATETlo9/30/2014ND, OR JOB#23 2123914
- �. _. \�I I I ED -/I6 ? . :'. .y,..
DWG# 1 DRAWN BY
REV SCALE 3/8' = 1'-0'
�:!h.
— 7' 7' --
F3' r 9' - 9'
10 l/4'- 1 /// 1 .•4�
7, 7, —
17 13/1E' 012' I 23' -I t`—23' ---I
— —
0�a•13/16'
t_ 14 .
1;.. U.L. Listed L55 Series E26 Canopy 4
60' Light Fixture - High Temp Assembly
— 7• 0 7•
17 13/1E' 012' 0}•13/16'
_ _ '.-7' i
17 13/1E' 01 • .`le'13/16'liale WWI
'/ % % % // % % % % �/ 10 1/4'
14' =' � //.�.L ' A.L //t�.L /A.L // 1 /A.L , /l.L ' .L ,'iii 3, iii;,‘yr,7. ] 7'J 7'] 7' ] 7' ] 7' ] 7' ] 7• ] 7' ]
I-- 14' 42' 84' 42' — 14' —a
I10 1/4' I 10 7/1C' I 10 7/1C,' I 10 7/16! I 10 7/1G' I 10 7/IC,' I 10 7/16' I D3 T/46' I 10 7/16'
14' 0,00'Nom./14' 0.00'0D
PLAN VIEW — Hood #1 (Island Hood)
14' 0.00" LONG 6030ND-2WI—PSP—FSS
NOTE. Additional hanging angles provided for hoods 12' and longer.
I
I
• JOB David Makoto - Tigard
I�� s LOCATION PORTLAND, OR, 97223
E� i ...
' DATE 9/30/2014 JOB# 2123914
inm tek " DWG# 2 DRAWN BY
• • REV SCALE 3/8' = 1'-0'
1
L55 SERIES E26 CANOPY LIGHT FIXTURE -
HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL
60' AND SHOCK RESISTANT GLOBE (L55 FIXTURE)
EXHAUST RISER
ATTACHING SUPPLY RISER
HANGING ANGLE PLATES WITH VOLUME DAMPER
4' 23.5% OPEN STAINLESS
20' CAPTRATE SOLO /4' STEEL PERFORATED PANEL
�Ill•
FILTER WITH HOOK 1 7411 � 6•
3' INTERNAL STANDOFF 1`I, 30' NOM.
IT IS THE RESPONSIBILITY �OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED-COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
GREASE DRAIN
WITH REMOVABLE CUP 44.0' MAX •
78' AFT REFERENCE
EQUIPMENT
BY OTHERS
11 II
SECTION VIEW - MODEL 6030ND-2WI-PSP-FSS
HOOD - #1 (Island Hood)
• • • •
•
JOB David Makoto - Tigard
��� �N LOCATION PORTLAND, OR, 97223
ONIMIIM MINIM
�C Li • " DATE 9/30/2014 JOB# 2123914
ontertex = DWG# 3 DRAWN BY
• REV. - SCALE 3/8' = 1'-0'
XHAUST FAN IN ORMATION - Job#21239 4
FAN
UNIT TAG FAN UNIT MODEL B CFM ESP. RPM M.P. 0 VOLT FLA WEIGHT (LBS.)SONES
NO.
1 CF-1 (Nah Hood DU240HFA 4900 1.400 898 5.000 3 208 15.0 173 171
MUA FAN INFORMATION - Job#2123914
FAN
UNIT TAG FAN UNIT MODEL * BLOWER HOUSING CFM ESP. RPM H.P. 0 VOLT FLA WEIGHT (LBS.)SONES
NO.
2 MAU-1 A3-D.500-G18 618-PB A3-D.500 4655 0.750 713 3.000 3 208 9.5 982 11.7
,AS IRED�(AKE-U AIR UJIITjSJ
-
FAN ACTS INPUT OUTPUT REQUIRED INPUT GAS
UNIT TAG AIR BTUs BTUs TEMP. RISE PRESSURE GAS TYPE
NO. DENSITY]
2 MAU-1 NO 262299 241315 48 deg F 7 In. w.c. - 14 In. w,c. Natural
FAN OPTIONS -
FAN
UNIT TAG OPTION (Qty. - Descr.)
NO. _
1 EF-1 (Main Hood) 1 - Grease Box
2 MAU-1 1 - Motorized Backdraft Damper for A3-D Housing
1 - AC Interlock Relay - 24VAC Coil
1 - Low Fire Start
1 - Inlet Pressure Gauge, 0-35'
I - Manifold Pressure Gauge, -5 to 15' we
1 - Extra Set of Belts
1 - Separate 120V VlrIng Package (Required and used only for DCV or Prewire with
VFD) - Three Phase Only
FAN ACCESSORIES
FAN EXHAUST SUPPLY
UNIT TAG
NO. GREASE GRAVITY WALL SIDE GRAVITY MOTORIZED WALL
CUP DAMPER MOUNT DISCHARGE DAMPER DAMPER MOUNT
1 EF-1 (Hain Hood) YES
2 MAU-t YES
UP,B ASSEMBLIES
NO. WEIGHT ITEM SIZE
1 * 1 48 LBS Curb 31.500'W x 31.500'L x 20.000'H Vented Hinged
2 * 2 82 LBS Curb 35.000'W a 84.000'L x 20.000'H Insulated
•
•
JOB David Makoto - Tigard
s LOCATION PORTLAND, OR, 97223
E
R E DATE 9/30/2014 JOB# 2123914
.ntsrek `` " DWG# 5 DRAWN BY
• • • REV. - • SCALE 3/8' = 1'-0'
•
•
•
- y►
I I/2'
31 1/2'
FAN #1 DU240HFA - EXHAUST FAN (EF-1 (MAIN HOOD)) VENTED
FEATURES / CURB
-ROOF MOUNTED FMCS \\
43 3/0 -RESTMR —0,(/)ANT MODEL 2D' SS��
-UL7D3 •
-VARIABLE SPEED CONTROL
-INTERN_WRING 40. STEELS
-WEATHERPROOF DISCONNECT CONSTRUCTION
-THERMAL OVERLOAD PROTECTION(SINGLE PHASE)
-HIGH HEAT OPERATION 300•F(149'C) mr
3' FLANGE
IIiYAI RFRA o< eT
37 1/2 EXHAUST FAN MUST PEERAT
E CONTINUOUSLY
P1,
VNLLE EXHAUSTING AIR AT AE «49'C)
3/8 vHIL ALL US PARTS I NAVE D•f(14D / ROOF OPENING
THERMAL EOUILIDRIUM,AND WITHOUT NIT
28 _ / 28 DIMENSIONS
JIIIIL DETERIORATING EFFECTS TO THE FAN WHICH �./
i I�I'_ WOULD CAUSE U(SKE OPERATION.
GREASE DRAIN
2 MEEM
i 23 7/8 I
28 — OPTIONS
GREASE BOX
1.- --\A\3,,A,,i,„/---- J
DUCTWORK BETWEEN
EXHAUST RISER ON HOOD
AND FAN (BY OTHERS)
• JOB David Makoto - Tigard
I _
V LOCATION
PORTLAND, OR, B#
114), +r DATE 9/30/2014 JOBS 2123914
;ntsrtek DWG# 6 DRAWN BY
• • • REV. SCALE 3/8' = 1'-0'
FAN AN A3-D500-GL8-HEATER 01AU-I>
I.DIRECT GAS FRED HEATED MAKE IP AIR UNIT WITH 18'BLOWER AND L2'BURNER.
2 INTAKE HOOD WITH E2 FILTERS
1 DOWN DISCHARGE-AIR FLOW RIGHT->LEFT
4,MOTORIZED BACK DRAFT DAMPER 30'X 30'FOR SIZE 3 STANDARD I MODULAR DIRECT FIRED HEATERS V/EXTENDED SHAFT,
STANDARD GALVANIZED CONSTRUCTION,3/4'REAR FLANGE, MFBUP-S ACTUATOR INCLUDED
S.COOLING INTERL000 RELAY. 24VAC COO.. 120V CONTACTS. LOCKS OUT BURNER CIRCUIT WHEN AC IS ENERGIZED.
6.LOW FIRE START. ALLOWS THE BURNER CIRCUIT TO ENERGIZE WEN THE MODULATION CONTROL IS IN A UN FIRE POSITION
7.GAS PRESSURE GAUGE,0-35',25'DIAMETER,1/4'THREAD SIZE SUPPLY SIDE HEATER INFORMATION
&GAS PRESSURE GAUGE,-S TO 41S DCRES VC.,85'DIAMETER,I/4'THREAD SIZE
A EXTRA SET OF V-BELTS ONLY TO BE ORDERED AS FAN OPTION AT TIME FAN IS ORDERED. WINTER TEMPERATURE=27'F. TEMP.RISE•481-.
10.SEPARATE I2OVAC WIRING PACKAGE FOR MAKE-UP AIR UNITS, OPTION MUST BE SELECTED WHEN MOUNTING VFD IN PREWIRE BTUs CALCULATED OFF STANDARD AIR DENSITY
PANEL OR WITH DCV PACKAGE. PROVIDES SEPARATE 120VA.INPUT TO SUPPLY FAN. THIS 120V SIGNAL MUST BE RUN BY OUTPUT BTUs AT ALTITUDE OF 0.0 ft•241315
ELECTRICIAN FROM DEV TO 141A SWITCH. INPUT BTUs AT ALTITUDE OF 0.0 it.•262299
10 S/16' ■ 19'
CURB OUTER WALL
DISCHARGE OPENING
I
C
E�� I LJ
I
I I
L J
6 1/2'
FLU ts»eT
Pa rill
93 3/4'
41 3/8• 45 1/9' 42 1/8'
G R -- -
LIFTING LW
SERV9 DIRECT FRED MIME I
]MSCORfGt
ABiLOW S1I[TC24
I
39 9/l6'
47 3/8' i•IPT
SLOVSINORXR
AcfESE Mt
24'SERVICE 9 l/2'
CLEMAiE ROLL 1
5 11 s' I-I -11
i (
14 I 3/4' 14 3/4'
LI
20'EQUIPMENT CURB L
ROB'OPENING 2'SMALLER THAN CURB DIMENSION.
JOB David Mo.koto — Tigard
s LOCATION PORTLAND, OR, 97223
O _ DATE 9/30/2014 JOB# 2123914
me ex
DWG# 7 DRAWN BY
REV. SCALE 1/4' = 1'-0'
LECTRICAL PACKAC S - Jobi2123914
NO. TAG PACKAGE * LOCATION SWITCHES OPTION FANS CONTROLLED
LOCATION QUANTITY TYPE 0 M.P. VOLT FLA
1 Llght Exhaust 3 5.000 208 15.0
1 DCV-1111 Wall Mount In SS Box SS Wall Mount Box 1 Fan Smart Controls DCV Supply 3 3.000 208 9.5
JOB David Makoto - Tigard
400 !%' LOCATION PORTLAND, OR, 97223
1. • ' DATE 9/30/2014 JOB# 2123914
�¢ DWG# 8 DRAWN BY
• REV.. • • SCALE 3/8' = 1,-0'
Fire ystem Information — Job#2123914
FIRE • FLOW INSTALLATION '-
SYSTEM Tag TYPE SIZE POINTS
NO. SYSTEM LOCATION ON HOOD
1 Ansul 8102 3.0/1.5 14 Wall Mount LeFt N/A
Fire Su.stem Parts List Key
FIRE
SYSTEM TAG KEY NUMBER - PART DESCRIPTION QTY. BY Q BY
FACTORY
D[S T.
Y.
NO.
1 0 - 0 - METALCAP-CB BLOWOFF CAP - Metal 10 0
1 - 1 - AT - 1.5 TANK(111A) - 1.5 Gallon SS Tank (For use with Autonan Release, Actuator,
1 0 1
or SS Enclosure (UL/ULC))
1 - 1 - AT - 3.0 TANK(*IB) - 3.0 Gallon SS Tank (For use with Autonan Release, Actuator,
1 0 1
or SS Enclosure (UL/ULC))
2 - 2 - AP - AR AUTOMAN RELEASE - Ansul Autonan Mechanical Release (UL)429853 Tank
1 0 separately 0 1
1 3 - 3 - AP - AE ENCLOSURE - Stainless Steel Enclosure Assembly (UL) 429870 0 1
I 5 - 5 - LIQ-3.0 AGENT - Ansulex Low PH Wet Chemical Agent, 3 Gallon (UL) 0 1
1 6 - 6 - LIQ-L5 AGENT - Ansulex Low PH Wet Chemical Agent, 1.5 Gallon (UL) 0 I
1 9 - 9 - 101-30 CARTRIDGE - Carbon Dioxide, 101-30, Cartridge (2-102) 0 I
1 10 - 10 - TLINK LINK - Test Link (1 test link) 0 1
11 - 11 - MICRO-SDA MICROSWITCH - Single Dual Electric Switch, One Standard Switch,
1 One Alarm Duty Switch 437155 0 1
1 12 - 12 - HOSEGROMMET HOSE - Hose/Grommet Package 0 I
13 - 13 - 419337 NOZZLE - 2W Nozzle, Duct (Replaces ANSUL Part* 419348, CAS Part*
1 419337) A0001267 2 0
1 16 - 16 - 419335 NOZZLE - IN Nozzle, Plenum/Appliance (Replaces ANSUL Part* 419346, 7 0
CAS Part* 419335) A0001265
1 19 - 19 - 419338 NOZZLE - 3N Nozzle, Appliance (Replaces ANSUL Part* 419349, CAS 1 0
Part* 419338) A0001268
25 - 25 - 418569 NOZZLE ADAPTOR - Swivel Nozzle Adaptor (Replaces CAS Part * 418569)
1 5 0
A0001274
1 26 - 26 - QSA-3/8 QUIK SEAL - 3/8' (UL) 10 0
1 27 - 27 - QPSA-1/2 PULLEY SEAL - 1/2' Hood Seal (UL) 1 0
1 28 - 28 - S-DET DETECTOR - Series (Scissor Linkage) NEW#435547/435548 (OLD*417369/434480) 4 0
1 29 - 29 - ANS-360FL FUSIBLE LINK - 360deg F, R-102 and PIRANHA 1 0
1 30 - 30 - ANS-500FL FUSIBLE LINK - 500deg F, R-102 and PIRANHA 3 0
1 34 - 34 - RPS-A REMOTE PULL STATION - Red composite (without wire rope) 434618 0 1
1 35 - 35 - PE-LT PULLEY ELBOW - Low Temp. Pulley Elbow, Set Screw Type 0 10
1 36 - 36 - PE-HT PULLEY ELBOW - High Temp Pulley Elbow, Compression Type 1 0
•
• JOB Mizurli Buffet Island Hood
LTI 0 CM ii
LATETION 27/201 ❑R, 9JOB ETh DATE 10/27/2014 JOB# 2123914
nInr:ac:. DWG# 4 DRAWN BY kcurtis
Qn/ Q/-dl F '3/0• - 1'_n•