MEMORANDUM
TO: Mr. Brett Groves
Riverside Homes
17933 NW Evergreen Parkway,Ste. 370
Beaverton, OR 97006
Bgroves @Riversidehome.com ,`��FD PROFFsdf
GINe
DATE: September 26,2014 1864 S
&Et•
FROM: Stig Widell, PE
1°'
�0Ly10
Associate
P. SNV'�/
RE: Lot 5, Fern Hollow EXPIRES: 81301 K/
Hillsboro, OR
NOTE:
This memo is intended to provide our recommendations for changes to the original
engineering. It is our understanding that the 6/0 slider door at the basement level
is being shifted from back wall to the right side. The new header will support 8.5ft
tributary floor load and a post supporting the window headers in the master bed
and great room. The post above shall be a maximum of 6" from the beam support.
We recommend using a 4x10 D.F. #2 header for this door.
If you have any questions please give me a call.
CC: File-Riverside 092614.doc
X51 ;CI 00 g9
Sherman Engineering Inc.
• 3151 NE Sandy Blvd. Ste. 100, Portland OR 97232
BeamChek v2007 licensed to:Sherman Engineering Inc. Reg#7992-66413
6/0 slider header
Prepared by:SEW Date:9/26/14
Selection 4x 10 DF-L#2 Lu=0.0 Ft
•
Conditions NDS 2005
Min Bearing Area R1=8.0 in2 R2=2.8 in2 (1.5) DL Defl= 0.03 in
Data Beam Span 6.0 ft Reaction 1 LL 3046# Reaction 2 LL 1204#
Beam Wt per ft 7.87# Reaction 1 TL 4974# Reaction 2 TL 1749#
Bm Wt Included 47# Maximum V 4974#
Max Moment 3218'# Max V(Reduced) 3247#
TL Max Defl L/240 TL Actual Defl L/990
LL Max Defl L/360 LL Actual Defl L/>1000
Attributes Section(in3) Shear(in2) TL Defl(in) LL Defl
Actual 49.91 32.38 0.07 0.04
Critical 35.75 27.06 0.30 0.20
Status OK OK OK OK
Ratio 72% 84% 24% 20%
Fb(psi) Fv(psi) E(psi x mil) Fc1(psi)
Values Reference Values 900 180 1.6 625
Adjusted Values 1080 180 1.6 625
Adjustments CF Size Factor 1.200
Cd Duration 1.00 1.00
Cr Repetitive 1.00
Ch Shear Stress N/A
Cm Wet Use 1.00 1.00 1.00 1.00
CI Stability 1.0000 Rb=0.00 Le=0.00 Ft
Loads Uniform LL:340 Uniform TL: 468 =A
•
Point LL Point TL Distance
2210 B=3040 0.5
C=830 0.5
Uniform Load A
Pt loads: B
R1 974
R2= 1749
SPAN=6 FT
Uniform and partial uniform loads are lbs per lineal ft.