Plans City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 April 29, 2009 1111 • • RE: FIRE SPRINKLER SYSTEM Project Information T I GARD Building Permit: FPS2009-00018 thru 24 Construction Type: 5-B Tenant Name: Longstaff Condominiums Occupancy Type: R-1 Address: Bldg's 1,2,4,5,6,7&8 Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13) 2002 edition and the State of Oregon Fire Code (OFC) 2007edition. The underground lines for this sprinkler system are to be inspected, pressure tested and flushed under the supervision of TVWD. The flushing of piping and minimum flow rate shall be in accordance with NFPA13 10.10.2.1. A copy of the acceptance report noting the witness of the flush by TVWD shall be provided at final inspection. GENERAL 1. A key box shall be installed in a location approved by the Fire Chief. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Section 506.1 OFC. Please contact Tualatin Valley Fire & Rescue for key box information at 503-612-7010 2. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers on the property. Sections 6.2.9.1 & 6.2.9.2 NFPA 13. 3. The spare sprinklers shall be kept in a cabinet located where temperatures will not exceed 100 degrees "F" at any time. A special sprinkler wrench shall be provided and kept in the sprinkler cabinet to be used in the removal and installation of sprinklers. Sections 6.2.9.3 & 6.2.9.6 NFPA 13. 4. The clearance between the deflector and the top of storage shall be 18 inches or greater. Section 8.6.6.1 NFPA 13. The distance shall be increased to 36 inches for Large Drop sprinkler heads. Section 8.11.6 NFPA 13 ' • 5. Sprinklers shall be located a minimum of 4 inches from walls and spaced not less than 6 feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13. Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard-or.gov • TTY Relay: 503.684.2772 6. Clearances shall be provided around all piping extending through platforms, foundations, walls and floors. The diameter of the hole shall be 2 inches larger than the penetrating pipe for pipe sizes 1 inch through 3 1/2 inches. The diameter of the hole shall be 4 inches larger than the penetrating pipe for pipe sizes 4 inches and larger 2 inches is required. Sections 9.3.4.1 & 9.3.4.2 NFPA 13. 7. All valves controlling the water supply for automatic sprinkler systems and all water flow monitoring devices shall be electrically monitored when the system serves more than 20 heads. Section 903.4 OFC 8. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. Such sprinkler water-flow devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Section 903.4.2 OFC 9. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. 10.The end sprinkler on a line shall be restrained against excessive vertical and lateral movement. 11. New sprinkler system piping shall be hydrostatically tested at 200 psi and shall maintain that pressure without loss for two hours. Where addition or modification is made to an existing system affecting less than 20 sprinklers this test need not be done.NFPA13 16.2.1.1 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, jv\ Dan Nelson, Senior Plans Examiner (503) 718-2436 dann @tigard-or.gov Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 HYDRAULIC DESIGN INFORMATION SHEET Job Name: Longstaff Condos Location: Tigard, Oregon Drawing Date: 4/17/09 Remote Area Number: 1 Contractor: 3ND FIRE SPRINKLER INC. Telephone: (503) 968-5200 12155 SW GRANT AVE. SUITE D. TIGARD, OREGON 97223 Designer: JEFF DUTTON Calculated By:SprinkCAD RECEIVED www.sprinkcad.com 451 N. Cannon Ave. Lansdale, PA 19446 JUL 0 2 2009 Construction: Occupancy: Reviewing Authorities:CITY OF TIGARD CITY OF TIGARD BUILDING DIVISION SYSTEM DESIGN Code:NFPA 13R, 07 Hazard:RES System Type:WET Area of Sprinkler Oper. 1296 sq ftl Sprinkler or Nozzle Density (gpm/sq ft) 0.052 1 Make: TYCO Area per Sprinkler 324.0 sq ftl Model: LFII Hose Allowance Inside 0 gpm 1 K-Factor: 4. 90 Hose Allowance Outside 0 gpm 1 Temperature Rating: 155 CALCULATION SUMMARY 4 Flowing Outlets gpm Required: 78.1 psi Required: 88.6 @ CITY CONN. WATER SUPPLY Water Flow Test Pump Data Date of Test 4/23/08 Rated Capacity 0 gpm Static Pressure 106.0 psi Rated Pressure 0.0 psi Residual Pres 84 . 0 psi Elevation 0 At a Flow of 2120 gpm Make: Elevation 0" Model: Location: 95th & Longstaff Source of Information: TVWD SYSTEM VOLUME 35 Gallons Notes : PROpe .6C' I N F tt>�♦�'� ' /PA'j OREGON A, 1� `QO • Longstaff Condos Drawing Date: 4/17/09 6/30/09 8:52 HYDRAULIC CALCULATION DETAILS HYDRAULIC FLOW LOSS QTY DESCRIPTION LENGTH C ID gpm psi TOTALS Hydr Ref W Required at Hyd Area 1 78 77.4 psi 1 Pipe 14" PVx15 8' 150 1. 602 78 1. 1 1 24" Grvd Back Flow Valve Ames "COLT CHART LOSS 78 6.1 Elevation Change 8' 6" 3.7 Total Loss for RISER 10.8 psi Hydr Ref R1 Required at BASE OF RISER 78 88.3 psi 1 4" MJ Tee 20' 120 4. 026 78 0. 0 2 4" MJ 45 Ell 8 ' 120 4.026 78 0.0 2 4" MJ 90 Ell 20' 120 4 . 026 78 0.0 1 Pipe 4" DIx18 Cl 350 100' 140 4.238 78 0.1 1 Pipe 8" DIx18 Cl 350 2000' 140 8. 488 78 0.1 Hydr Ref R2 Required at UNDERGROUND 78 88. 6 psi Hydr Ref R2 Required at CITY CONN. 78 88. 6 psi Water Source106. 0 psi static, 84.0 psi residual @ 2120 gpm 78 gpm 106.0 psi SAFETY PRESSURE 17.3 psi Available Pressure of 106.0 psi Exceeds Required Pressure of 88. 6 psi This is a safety margin of 17.3 psi or 16 % of Supply Maximum Water Velocity is 25. 6 fps Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Page 3 FITTING NAME TABLE ABBREV. NAME C Coupling E 90' Standard Elbow F 45' Elbow S Straight Flow Thru Tee T 90' Flow Thru Tee ✓ Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. _ K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNG'S Number of fittings. See table above. TOTAL Total length (PIPE + FTNG'S) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0.433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x 4.52 x (Q/C) ^1.85 / ID^4.87 Pv Velocity pressure (psi) where Pv = 0.001123 x Q^2/ID^4 Pn Normal pressure (psi) , where Pn = Pt - Pv NOTES: - Pressures are balanced to 0.01 psi. Pressures are listed to 0.1 psi. Addition may vary by 0.1 psi due to accumulation of round off. - Calculations conform to NFPA 13. - Velocity Pressures are not considered in these Calculations Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Page 4 NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K-FACTOR FLOW FLOW DENSITY (FT) (GPM/ (PSI^11) ) (PSI) (GPM) (GPM) (GPM/SQ.FT) 1 8.50 12.4 1S 8.00 4.90 12.1 17.0 17.0 0.05 2 8.50 14.8 2S 8.00 4.90 14.2 18.4 17.0 0.06 3 8.50 21.4 3S 8.00 4 . 90 20.4 22.2 17.0 0.07 4 8.50 18.0 4S 8.00 4.90 17.4 20.4 17.0 0.06 7 17.50 49.2 10 8.50 53.1 12 17.50 49.2 13 17.50 49.2 14 17.50 49.2 18 8.50 27 .9 19 8.50 21. 6 20 8.50 22.6 21 8.50 36.3 - 22 8.50 53.1 23 8.50 15.9 Al 8.50 76.7 B1 8.50 72.1 W 8.50 77.4 Max velocity of 25.60 occurs in the pipe from 21 TO 20 Nodes with "S" indicate a node at the top of a sprig or bottom of drop pendent. The node without an "S" is on the branch. • Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Tyco Fire Products Page 5 . HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 1 FROM HYDRAULIC REFERENCE 1 TO W (PRIMARY PATH) 17.01 0.874 1T 0.50 12.1 12.1 K = 4 . 90 1S C=150 3.00 -0.2 0.0 17.01 0.155 3.50 0.5 12. 1 Vel = 9.19 0.874 2E 24 . 98 12 .4 12.4 EqK = 4. 83 1 C=150 10 11.00 0.0 0. 0 17.01 0.155 2S 35.98 5.6 12.4 Vel = 9.19 20.45 0.874 1T 3. 99 18.0 18.0 EqK = 4 .82 4 C=150 3.00 0.0 0.0 37 .46 0. 669 6. 99 4.7 18.0 Vel = 20.23 9.95 0.874 iT 9.26 22.6 22. 6 20 C=150 1S 4.00 0.0 0.0 See PATH 4 47 .41 1.034 13.26 13.7 22.6 Vel = 25.60 1.101 lE 38.84 36.3 36.3 21 C=150 6S 11.00 0.0 0.0 47.41 0.336 49.84 16.7 36.3 Vel = 16.13 30. 65 1.256 lE 24.72 53.1 53.1 22 C=150 3T 17.92 0.0 0. 0 See PATH 2 78.06 0.445 42.64 19.0 53.1 Vel = 20. 41 1.256 lE 4 .32 72.1 72.1 B1 C=150 6.00 0.0 0.0 78.06 0.445 10.32 4.6 72.1 Vel = 20.41 1.256 1.75 76.7 76.7 Al C=150 0.00 0.0 0.0 78 .06 0.445 1.75 0.8 76.7 Vel = 20.41 W 78 .06 77.4 K = 8.87 . UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) • Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Tyco Fire Products Page 6 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn 20.45 0.874 1T 0.50 17.4 17.4 K = 4 .90 4S C=150 3.00 -0.2 0.0 20.45 0.218 3.50 0.8 17.4 Vel = 11.04 4 20.45 18 .0 K = 4 .82 PATH 2 FROM HYDRAULIC REFERENCE 2 TO 22 18.45 0.874 1E 0.50 14.2 14.2 K = 4 .90 2S C=150 4 .00 -0.2 0.0 18.45 0.180 4.50 0.8 14.2 Vel = 9.96 0. 874 6.56 14 .8 14 .8 EqK = 4 .80 2 C=150 0.00 0.0 0.0 18.45 0.180 6.56 1.2 14.8 Vel = 9. 96 0.874 2E 19.34 15 .9 15. 9 - 23 C=150 iT 12.00 0.0 0.0 18 .45 0.180 1S 31.34 5 .7 15.9 Vel = 9.96 12.21 0.874 1T 9.56 21.6 21.6 19 C=150 1S 4.00 0.0 0.0 See PATH 3 AND 4 30. 65 0. 461 13.56 6.3 21.6 Vel = 16.55 1.101 5E 106.80 27.9 27. 9 18 C=150 5T 61.50 0.0 0.0 30. 65 0.150 9S 168.30 25.2 27.9 Vel = 10.43 22 30. 65 53.1 K = 4.21 PATH 3 FROM HYDRAULIC REFERENCE 3 TO 19 22.16 0.874 1E 0.50 20.4 20.4 K = 4.90 3S C=150 4 .00 -0.2 0.0 22.16 0.253 4.50 1.1 20.4 Vel = 11. 97 0.874 0. 92 21.4 21.4 EqK = 4.79 3 C=150 0.00 0.0 0.0 22.16 0.253 0.92 0.2 21.4 Vel = 11. 97 - UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Tyco Fire Products Page 7 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn 19 22.16 21.6 K = 4.77 PATH 4 FROM HYDRAULIC REFERENCE 19 TO 20 9.95 0.874 1T 12.95 21. 6 21.6 19 C=150 2S 5.00 0.0 0.0 See PATH 2 AND 3 9.95 0.058 17.95 1.0 21. 6 Vel = 5.37 20 9. 95 22. 6 K = 2. 09 • UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) Job Water Required Hose Allowance Longstaff Condos Static Pressure: 106.0 psi Pressure: 88.6 psi Inside: 0 gpm Residual Pressure: 84.0 psi System Flow: 78 gpm Outside: 0 gpm Tigard, Oregon Flow: 2120 gpm System+Hose: 78 gpm Remote Area: 1 Date: 4/23/08 Safety Pres: 17.3 psi Loc: 95th & Longstaff Head Elev Pres: 3.5 psi 140 120 100 1 J OM II mi..11. 80 ,-u■---_ illpirm IIII.M S I MN =num 80 40 20 3.5 psi 600 900 1200 1500 1800 2100 2400 2700 3000 • Flow(gpm) • Langstaff Condos Drawing Date: 4/17/09 6/30/09 8:52 HYDRAULIC DESIGN INFORMATION SHEET Job Name: Longstaff Condos Location: Tigard, Oregon Drawing Date: 4/17/09 Remote Area Number: 2 Contractor: JND FIRE SPRINKLER INC. Telephone: (503) 968-5200 12155 SW GRANT AVE. SUITE D. TIGARD, OREGON 97223 Designer: JEFF DUTTON Calculated By:SprinkCAD www.sprinkcad.com 451 N. Cannon Ave. Lansdale, PA 19446 Construction: Occupancy: Reviewing Authorities:CITY OF TIGARD SYSTEM DESIGN Code:NFPA 13R, 07 Hazard:RES System Type:WET Area of Sprinkler Oper. 1296 sq ft ! Sprinkler or Nozzle Density (gpm/sq ft) 0.052 I Make: TYCO Area per Sprinkler 324 . 0 sq ftl Model: LFII Hose Allowance Inside 0 gpm 1 K-Factor: 4 . 90 Hose Allowance Outside 0 gpm 1 Temperature Rating: 155 CALCULATION SUMMARY 4 Flowing Outlets gpm Required: 75.1 psi Required: 95.0 @ CITY CONN. WATER SUPPLY Water Flow Test Pump Data Date of Test 4/23/08 Rated Capacity 0 gpm Static Pressure 106.0 psi Rated Pressure 0. 0 psi Residual Pres 84 . 0 psi Elevation 0 At a Flow of 2120 gpm Make: Elevation 0" Model: Location: 95th & Longstaff Source of Information: TVWD SYSTEM VOLUME 35 Gallons Notes : 0 PROc. o►NF ss JO% u ' OREGON AFa 1q 14° 000 •t`F LOC 'T:.7i:�S: 12 31- Longstaff Condos Drawing Date: 4/17/09 6/30/09 8:52 HYDRAULIC CALCULATION DETAILS HYDRAULIC FLOW LOSS QTY DESCRIPTION LENGTH C ID gpm psi TOTALS Hydr Ref W Required at Hyd Area 2 75 84 .1 psi 1 Pipe 111" PVx15 8 ' 150 1. 602 75 1. 0 1 211" Grvd Back Flow Valve Ames "COLT CHART LOSS 75 6. 0 Elevation Change 8 ' 6" 3.7 Total Loss for RISER 10. 7 psi Hydr Ref R1 Required at BASE OF RISER 75 94. 7 psi 1 4" MJ Tee 20' 120 4 .026 75 0. 0 2 4" MJ 45 Ell 8' 120 4 .026 75 0.0 2 4" MJ 90 Ell 20 ' 120 4 . 026 75 0. 0 1 Pipe 4" DIx18 Cl 350 100' 140 4.238 75 0. 1 1 Pipe 8" DIx18 Cl 350 2000' 140 8 . 488 75 0 . 1 Hydr Ref R2 Required at UNDERGROUND 75 95.0 psi Hydr Ref R2 Required at CITY CONN. 75 95.0 psi Water Source106.0 psi static, 84.0 psi residual @ 2120 gpm 75 gpm 106.0 psi SAFETY PRESSURE 10. 9 psi Available Pressure of 106.0 psi Exceeds Required Pressure of 95.0 psi This is a safety margin of 10.9 psi or 10 % of Supply Maximum Water Velocity is 25. 6 fps Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Page 3 FITTING NAME TABLE ABBREV. NAME C Coupling E 90' Standard Elbow F 45' Elbow S Straight Flow Thru Tee T 90' Flow Thru Tee ✓ Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. _ K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNG'S Number of fittings. See table above. • TOTAL Total length (PIPE + FTNG'S) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0.433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x 4 .52 x (Q/C) ^1.85 / ID^4 . 87 Pv Velocity pressure (psi) where Pv = 0.001123 x Q^2/ID^4 Pn Normal pressure (psi) , where Pn = Pt - Pv NOTES: - Pressures are balanced to 0.01 psi. Pressures are listed to 0. 1 psi. Addition may vary by 0 . 1 psi due to accumulation of round off. - Calculations conform to NFPA 13. - Velocity Pressures are not considered in these Calculations ' Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Page 4 NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K-FACTOR FLOW FLOW DENSITY (FT) (GPM/ (PSI^i) ) (PSI) (GPM) (GPM) (GPM/SQ.FT) 5 17.50 16.2 5S 17 .00 4.90 15.8 19.5 17.0 0.06 6 19.00 12.5 6S 18.50 4.90 12.1 17.0 17. 0 0.05 7 17 .50 18.4 7S 17 .00 4. 90 17.8 20.7 17.0 0.06 8 19.00 14.0 8S 18 .50 4.90 13.4 18 .0 17.0 0.06 10 8 .50 60.2 12 17.50 18.5 13 17 .50 18.1 14 17 .50 36. 9 15 17.50 17. 4 16 19.00 13.3 17 19.00 14.7 18 8.50 63. 9 19 8 .50 63. 9 20 8.50 63. 9 21 8.50 63. 9 22 8 .50 63. 9 Al 8 .50 83.3 B1 8.50 79.0 W 8 .50 84.1 Max velocity of 25.56 occurs in the pipe from 10 TO 14 Nodes with "S" indicate a node at the top of a sprig or bottom of drop pendent. The node without an "S" is on the branch. ' Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Tyco Fire Products Page 5 HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 1 FROM HYDRAULIC REFERENCE 6 TO W (PRIMARY PATH) 17.01 0.874 1E 0.50 12.1 12.1 K = 4. 90 6S C=150 4 .00 -0.2 0.0 17. 01 0.155 4.50 0.7 12.1 Vel = 9.19 0.874 1E 0. 91 12.5 12.5 EqK = 4.80 6 C=150 4.00 0.0 0.0 17.01 0.155 4.91 0.8 12.5 Vel = 9. 19 0. 874 2E 11.50 13.3 13.3 16 C=150 iT 11.00 0. 6 0.0 17 .01 0.155 22.50 3.5 13.3 Vel = 9.19 19.45 1.101 2.96 17.4 17.4 15 C=150 0.00 0.0 0.0 See PATH 3 36. 46 0.207 2.96 0. 6 17.4 Vel = 12.41 -17.87 1.101 2S 5.62 18.1 18.1 13 C=150 2.00 0.0 0.0 See PATH 5 18.59 0.059 7.62 0.5 18.1 Vel = 6.33 17 . 96 1.101 3T 61.63 18 .5 18.5 12 C=150 12S 27.00 0.0 0.0 See PATH 2 36.55 0.208 88.63 18.4 18.5 Vel = 12.44 38 .57 1.101 1E 13.65 36. 9 36.9 14 C=150 1T 11.00 3. 9 0.0 See PATH 4 75 .12 0.787 1S 24.65 19.4 36.9 Vel = 25.56 1.256 1T 2.82 60.2 60.2 10 C=150 6.00 0.0 0.0 75 .12 0.414 8 .82 3.7 60.2 Vel = 19.64 1.256 1E 24.72 63.9 63.9 22 C=150 2T 11. 92 0.0 0.0 75.12 0.414 36.64 15.2 63.9 Vel = 19. 64 1.256 lE 4 .32 79.0 79.0 131 C=150 6.00 0.0 0.0 75.12 0.414 10.32 4.3 79.0 Vel = 19. 64 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Tyco Fire Products Page 6 HYD. Qa DIA. FITTING PIPE Pt Pt REF "Cu TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 1 FROM HYDRAULIC REFERENCE 6 TO W (PRIMARY PATH) 1.256 1.75 83.3 83.3 Al C=150 0.00 0.0 0.0 75.12 0. 414 1.75 0.7 83.3 Vel = 19. 64 W 75 .12 84.1 K = 8.19 PATH 2 FROM HYDRAULIC REFERENCE 8 TO 12 17. 96 0.874 lE 0.50 13.4 13.4 K = 4.90 8S C=150 4 .00 -0.2 0.0 17. 96 0.172 4.50 0.8 13.4 Vel = 9.70 0.874 4 .02 14.0 14.0 EqK = 4 .80 8 C=150 0.00 0.0 0.0 17. 96 0.172 4.02 0.7 14.0 Vel = 9.70 0.874 2E 7.48 14.7 14 .7 17 C=150 1T 11.00 0.6 0.0 17 .96 0.172 18.48 3.2 14.7 Vel = 9.70 12 17. 96 18.5 K = 4.18 x PATH 3 FROM HYDRAULIC REFERENCE 5 TO 15 19.45 0.874 1T 0.50 15.8 15.8 K = 4 .90 5S C=150 3.00 -0.2 0.0 19.45 0.199 3.50 0.7 15.8 Vel = 10.50 0.874 1S 5.04 16.2 16.2 EqK = 4.83 5 C=150 1.00 0.0 0.0 19. 45 0.199 6.04 1.2 16.2 Vel = 10.50 15 19. 45 17. 4 K = 4 . 66 . UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) Longstaff Condos Drawing Date:4/17/09 6/30/09 8:52 Tyco Fire Products Page 7 • HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn PATH 4 FROM HYDRAULIC REFERENCE 7 TO 14 20.70 0.874 1T 0.50 17.8 17.8 K = 4. 90 7S C=150 3.00 -0.2 0.0 20.70 0.223 3.50 0.8 17.8 Vel = 11.18 1.101 2T 57 . 62 18.4 18 .4 EqK = 4.82 7 0=150 13S 23.00 0.0 0.0 38.57 0.229 80.62 18.5 18.4 Vel = 13. 13 14 38.57 36.9 K = 6.35 PATH 5 FROM HYDRAULIC REFERENCE 13 TO 7 17 .87 1.101 1T 0.50 18.1 18.1 13 C=150 1S 6.00 0.0 0.0 See PATH 1 17 .87 0.055 6.50 0.4 18.1 Vel = 6.08 7 17.87 18.4 K = 4.17 20.70 0.874 1T 0.50 17.8 17.8 K = 4. 90 7S C=150 3.00 -0.2 0.0 20.70 0.223 3.50 0.8 17.8 Vel = 11.18 7 20.70 18.4 K = 4.82 . UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) • Job Water Required Hose Allowance Longstaff Condos Static Pressure: 106.0 psi Pressure: 95.0 psi Inside: 0 gpm Residual Pressure: 84.0 psi System Flow: 75 gpm Outside: 0 gpm Tigard, Oregon Flow: 2120 gpm System+Hose: 75 gpm Remote Area: 2 Date: 4/23/08 Safety Pres: 10.9 psi Loc: 95th & Longstaff Head Elev Pres: 8.0 psi 140 120 100 • Sup ly — 80 S 60 - - - 40 - 20 • 8.O psi — 600 900 1200 1500 1800 2100 2400 2700 3000 • Flow (gpm)