Loading...
Specifications RECEIVED MAR 0 3 2009 CITY OF TIGARD BUILDING DIVISION BLACKWATER �► FIRE SUPPRESSION, LLC 49630 SE Highway 26; Sandy,Oregon 97055 PHONE (503)826-1084 FAX (503)746-5478 CCB#182606 Key Realty 16037 SW Upper Boones Ferry Tigard, Oregon FIRE PROTECTION EQUIPMENT SUBMITTAL Key Realty 16037 SW Upper Booties Ferry Tigard, Oregon FIRE PROTECTION EQUIPMENT SUBMITTAL INDEX PRODUCT MAKE MODEL/DESCRIPTION 1. SPRINKLERS RELIABLE Model F1FR Quick Response SSP SIN#3615 Chrome w/Chrome Recessed Esc 2. PIPE ALLIED TUBE Black Steel, Dynathread,ASTM A-135 3. PIPE FITTINGS ANVILSTAR Black Steel, Cast Iron, ASME B16.4 4. HANGERS TOLCO Figure 200 Hanger Ring TOLCO Figure 100 All Thread Rod TOLCO Figure 65 C-Type Beam Clamp **The above listed items are the proposed equipment to be used on this project, however we reserve the right to use an'equivalent'product or manufacturer at our discretion. r Bulletin 136 Rev.O W rieliabit Model F1FR aT Model F1 FR Recessed Quick Response Sprinklers o Model F1 FR Sprinkler Types Standard Upright ¢, Standard Pendent ,,, , Conventional , Vertical Sidewall Horizontal Sidewall ,. - HSW 1 Deflector Model F1 FR Recessed Sprinkler Types , Recessed Pendent Upright Pendent Recessed Horizontal Sidewall -HSW 1 Deflector Listings&Approvals ' . = 1. Listed by Underwriters Laboratories, Inc. (UL) 2. Listed by Underwriters'Laboratories of Canada(ULC) y 3. Certified by FM Approvals , 4. Loss Prevention Council (LPC, UK) X 5. NYC BS&A No. 587-75-SA 6. Meets MIL-S--901C and MIL-STD 167-1 7. Verband der Schadenversicherer(VdS, Germany) . . 4: 8. NYC MEA 258-93-E UL Listing Category Vertical Sidewall Conventional Sprinklers, Automatic&Open Quick Response Sprinkler UL Guide Number .., VNIV ` . r � } Patents: US Patent No. 6,374,920 Applies to 4?. >, ,:,,,..,:411410 Model Fl FR Vertical Sidewall Sprinklers. Product Description Horizontal Sidewall Recessed Pendent Reliable Models F1 FR and Fl FR Recessed Sprinklers are HSW Deflector (Model FP Shown) quick response sprinklers which combine the durability of a pands,forcing the bubble smaller and smaller as the liquid standard sprinkler with the attractive low profile of a decorative pressure increases.Continued heating forces the liquid to sprinkler. push out against the bulb, causing the glass to shatter, The Models Fl FR and Fl FR Recessed automatic sprinklers opening the waterway and allowing the deflector to distrib- utilize a 3.0 mm frangible glass bulb.These sprinklers have ute the discharging water. demonstrated response times in laboratory tests which are five to ten times faster than standard response sprinklers.This Application quick response enables the Model Fl FR and F1 FR Recessed Quick response sprinklers are used in fixed fire protec- sprinklers to apply water to a fire much faster than standard tion systems:Wet,Dry,Deluge or Preaction.Care must be sprinklers of the same temperature rating. exercised that the orifice size,temperature rating,deflector The glass bulb consists of an accurately contrdled amount style and sprinkler type are in accordance with the latest of special fluid hermetically sealed inside a precisely manu- published standards of the National Fire Protection Asso- factured glass capsule. This glass bulb is specially con- ciation or the approving Authority Having Jurisdiction. stn.icted to provide fast thermal response. The balance of Quick response sprinklers are intended for installation as . parts are made of brass, copper and beryllium nickel. specified in NFPA 13, FM Global Loss Prevention Data At normal temperatures,the glass bulb contains the fluid Sheet 2-8N or other applicable standards.Quick response in both the liquid and vapor phases.The vapor phase can sprinklers and standard response sprinklers should not be be seen as a small bubble.As heat is applied,the liquid ex- intermixed. The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523 I. - ""Model'F1FR Quick Response Upright, Pendent&Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench [Installation Data: K Factor Sprinkler Identification Sprinkler Approval Number(SIN) ` Sprinkler Type US I Metric Height Organization SSU J SSP Standard-Upright(SSU)and Pendent(SSP)Deflectors Marked to Indicate Position )"(15mm)Standard Orifice with 4"NFT(R)0)Thread 5.6 80 `22'(56mm) 12,3,4,5,6,7 I 8362511) R3615 1%"(20mm)Large Orifice with 3/4"NPT(R3A)Thread 8.0 115 2.3"(58mm) 1,2,3,4,7,8—� R3622111 R3612 TT/,L,"(17mm)Small Orifice wth y"NPT(R))Thread 4.2 60 2.2"(56mm) 1,2,8 R3623111 R3613 " (10mm)Small Orifice w[h X"NPT(R j2)Thread 2.8 40 2.2"(56mm) 1,2,8 R362111) R3611 10mm Orifice)(LH with R,(,"Thread 4.2 60 567m 4,6,7 R3624 R3614 Conventional-Install in Upright or Pendent Position 10mm Orifice)(LH with R';;Thread 4.2 60 56mm 83674 15mm Standard Orifice with/2"NPT(R)z)Thread 5.6 80 56mm 4,6,7 R3675 20mm Large Orifice with 3A"NPT(R3A)Thread 8.0 1 115 58mm 4,7 R3672 t1''Polyester coated upright UL and ULC listed corrosion resistant. 4 .. ,_ , .„.,. T , Nom, S rE+ Upright Pendent Conventional Model F1FR Quick Response Recessed Pendent Sprinkler Installation Wrench: Model GFR1 Sprinkler Wrench Installation Data: Nominal I K Factor , Thad Sprinkler Approval Sprinkler Identification Orifice Size US ' Metric Height Organizations Number(SIN) )'" (15mm) I X''NPT(R1/2) 5.6 80 2.2"(56rrrn) I 1,2,3,4,5,7,8 R3615 %,2"(20mm) I ,"NPT(R3A) 8.0 115 2.3"(Wm) 1,2,3,8 R3612 %,"(11mm) y"N P T(RV2) 4.2 60 2.2"(56mm) 12,8 R3613 3;;" (10mm) "NPT(R1/2) 2.8 40 2.2"(5611.11) 1,2,8 R3611 1Omm R3/ 4.2 60 I 56mm 4,7 R3614 t1)Refer to escutcheon data table for approvals and dimensions. �_?t!A'HOC£M4 2 5/8'DSA. [66.7mmJ-3 (57. HOLE IN CEILING L T3/16..OP I..* , 5/16°014. [55.7mm]— '�'- (■a7.m.J CUP �i 1--_----1 !' . 1 J 1"Y t/?"REDOCF= I I TURN CO L.W ) I I J.- OM7C FONT t\ AGAINST;RRR-MLER WR[NCII DOSS-� I \ 1_\ I I% i {���j' �i��� 1 J., FACE cx F NC To I') CEILING -_-- L J ADACIMENT(" it I f CELL N;;DdLHSON �L�� s } s ��� 11 — __,___, ' 1 00 da I FACE nF Amn:I nil= i= TO FACE OF C£IUNG .'. I DIMENSION I,I /1 , I . ?r7 37'C"A. '^JI/STMENT 1 11 rxrcc=A (I)POTS 70 Fr&F7 ESC(JTCxFON DATA TAW-FOR APPROVALS AND OMCNgONG 'T)REFER TO FP ESCLCTCFEON DATA TABLE FOR APPROVALS AND DIMENT1ONS. 2. ."Model F1 FR Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: ` Nominal Thread 1 K Factor Sprinkler Approval i Sprinkler Identification Orifice Size Height Organizations Number(SIN) US Metric Number(SIN) ' 1/2" 'h"NPT(R1/2) 5.6 80 2.2"(56mm) j 1,2,3,6,8 ' R3685 15mm '/z"NPT(R'/2) � 5.6 80 i 2.2"(56mm) ] 411) i ''LPC Approval is for Pendent position only. Orientation Deflector to Ceiling i Dimension(Min.-Max.) ,! r,,,._, I Upright 4"-12"(102mm-305mm) - 1 Pendent 6"-12"(152mm-305mm) r Vertical Sidewall US Patent No. 6,374,920 Model Fl FR Quick Response Horizontal Sidewall Sprinkler Deflector: HSW 1 Installation Wrench: Model D Sprinkler Wrench Installation Data: ! I Approval Organizations 1 K Factor and Type of Approval Sprinkler Nominal Thread j Sprinkler Identification Orifice Size 1 US Metric Length Light Ordinary Number(SIN) Hazard Hazard i"(15mm) /2"NPT(R'/2) 5.6 80 2.63"(67mm) 1,2,3,5,8 1,2,5,8 R3635 NOTE:UL,ULC and MEA Listing permits use with Fl or F2 recessed escutcheon. 1,360004 1 F,4CE 00 F'Z(N-.; TO � .asGi DVEN..:N I I / —2 1/4"HOLE aA, :iii # •Yfl F. [57.2mm] .�.n,. 1 .EIL NG T�/,.. �. a I" X1/2"REDUCER ---7 �.A: li ,5 _"i DFEL El,T?R �fi� I 4 ; fr--r,� _ Horizontal Sidewall ' '7� 6 `IA` it lti�i_ " 1 it Zt. _111m [722-,) TURN COLLAR UNTIL — i. , . TIGHT AGAINST SPRINKLER I1 it WRENCH BOSS. i ADJU.S.TUENT(1) f (I) REFER TO ESCUTHCEON DATA TABLE FOP APPROVALS AND DIMENOON>. 3. r Installation Quick response sprinklers are intended for installation as tie vacuuming. Remove any sprinkler which has been specified in NFPA 13,FM Global Loss Prevention Data Sheet painted (other than factory applied) or damaged in any 2-8N or other applicable standards. Quick response sprin- way. A stock of spare sprinklers should be maintained to klers and standard response sprinklers should not be inter- allow quick replacement of damaged or operated sprin- mixed. klers. Prior to installation,sprinklers should be maintained The Model FIFA Recessed Quick Response Sprinklers are to in the original cartons and packaging until used to mini- be installed as shown. The Model Fl or F2 Escutcheons illus- mize the potential for damage to sprinklers that would trated are the only recessed escutcheons to be used with the cause improper operation or non-operation. Model Fl FR Sprinklers. The use of any other recessed escutch- Sprinkler Types eon will void all approvals and negate all warranties. When installing Model Fl FIR Sprinklers,use the Model D Sprin Standard Upright kler Wrench. When installing Model Fl FR Recessed Pendent or Standard Pendent Sidewall Sprinklers,use the Model GFR1 Sprinkler Wrench. Any Conventional other type of wrench may damage these sprinklers. Sidewall(Vertical, Horizontal HSW1) Glass bulb sprinklers have orange bulb protectors to minimize Recessed Pendent bulb damage during shipping, handling and installation. RE- Recessed Horizontal Sidewall HSW1 MOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE PRO I ECTION.Re- Finishes "'r" moval of the protectors before this time may leave the bulb vui- !Standard Finishes nerable to damage. RASCO wrenches are designed to install Sprinkler Escutcheon sprinklers when covers are in place. REMOVE PROTECTORS I Bronze Brass BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS Chrome Plated Chrome Plated(3' TO REMOVE THE PROTECTORS. ( )Polyester Coated'') White Painted(31 Temperature Ratings iSpecial Application Finishes 1 S.rinkler Escutcheon Class cation Temperature Max.Ambient Bulb i Bright Brass Bright Brass °C of Temp. Color Black Plated Black Plated Ordinary 57 135 1W (38°C) Orange 'Black Paint Black Paint Ordinary 68 155 100"F(38°C) I Red Off White Off White Intermediate 79 175 11 (66°C) I Yellow ;Satin Chrome Satin Chrome Intermediate 93 200 150°F(66°C) Green High(1) 141 286 225°F(107°C) Blue (1) Other finishes and colors are available on special order. Consult the factory for details. (1)Not available for recessed sprinklers. (2) FM Approvals is limited to bronze and brass,chrome or black Escutcheon Data plated finishes only. I `3' FP Push-on/Thread-off escutcheon. FaoeafFittfng `4i UL and ULC listed corrosion resistance. Model APR pin to Ceing or SIN numbers:R3621,R3622.R3623, R3625. I l 1}2° Note: For 1/,''' orifice pendent FM approved white F1 1,2,4,8 Max Recess (38.1mm) I *;"-1X€" polyester coated and UL approved white polyester Mir Recess %" I (5rrn-24mm) corrosion resistant sprinklers refer to Bulletin 014. (19.1mm) 1X" I Max Recess (38.1mm) I W'-%" Ordering Information I F2 1,23,4,5,7,8 5 Specify: Min Recess 'Y,e° (5mn-17mm) fly (24mm) 1. Sprinkler Model FP I 1,2 Max Recessed ' 1)"(38.1nm) j 2. Sprinkler Type (11mm) I Push-on/ , ° 3. Orifice Size Thread-off 1,2 Min Recessed (24mm) j 1"(25.4mm) i; 4. Deflector Type No Dimensional Figure for FP 5. Temperature Rating 6. Sprinkler Finish Maintenance 7. Escutcheon Type The Models F1FR and F1FR Recessed Sprinklers should be inspected quarterly and the sprinkler system 8. Escutcheon Finish (where applicable) maintained in accordance with NFPA 25. Do not clean Note: When Model F1FR Recessed sprinklers are sprinklers with soap and water, ammonia or any other ordered, the sprinklers and escutcheons are packaged cleaning fluids. Remove dust by using a soft brush or gen- separately. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and aso with the provisions of gcvemmenta codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years,and are installed and serviced by the most highly qualif led and reputa- ble sprinkler contractors located throughout the United States.Canada and foreign countries. + Manufactured by The Reliable Automatic Sprinkler Co.,Inc. ® Receded. Reliabid (800)431-1588 Sales Offices 0 (800)848-6051 Sales Fax Revision lines indicate updated or new data (914)829-2042 Corporate Offices www.re!iablesprnkier.com Internet Address EG.Printed In U.S.A.3/07 PM9999970027 yna-Thread® Full Line Sch-40 Replacement Dyna-Thread' offers the life expectancy of Sch4O with superior hydraulics and greater value. Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages. Comparison to Schedule 40 Comparison to L.W.T. Pipes • Dyna-Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread to 3.6%larger than Sch-40 giving it weight,Dyna-Thread reduces (CRR=1.00)gives Dyna-Thread superior hydraulics.And,when used installation fatigue and is ideal for better life expectancy than lightwall in combination with Dyna-Flow pipe, retro-fit applications. threadable pipe joints. down sizing often occurs. Corrosion Resistance Ratio(CRR) is a • Unlike lightwall threadable pipe, • Dyna-Thread is fully listed and UL(Underwriters Laboratory)term for Dyna-Thread has no thread gauge approved by UL, ULC,and FM for the estimated life expectancy of a pipe warning. fire sprinkler applications. joint.This is based on the calculated wall thickness at the base of the first • Dyna-Thread is approved for • The life expectancy of Dyna-Thread standard hanger spacing(15 ft. and Sch-40 are equal based on the exposed thread,assumed to be the O.C.),can be used as earthquake calculated wall thicknesses per UL. weakest point of the pipe length. Dyna sway bracing, and is safe to use as Thread and Sch-40 have the same drops. • The consistent quality of steel used to calculated wall thicknesses at this point make Dyna-Thread facilitates smooth and are both assigned the same CRR of • Dyna-Thread is safer to weld on. threading and lower maintenance 1.00. costs. • Dyna-Thread is more widely The internal surface of all black Allied accepted than lightwall threadable • The exterior of Dyna-Thread is where Sch-40 is specified. protected by a clean,durable mill Tube&Conduit Fire Sprinkler pipe coating for extended shelf life and products up to 4.5000" in diameter is easy paint application. coated with our new Antibacterial Formula,"ABF'. In scientific laboratory test,ABS proved to have superior Specifications & Approvals - resistance to microbial colonization of 0 ® pipe walls,thereby delaying or possibly Super 40/Dyna-Thread pipe is preventing the onset of manufactured to meet:ASTM A-135, Microbiologically Influenced corrosion Grade A and is in compliance with Listed Approved Listed NFPA-13.All sizes of Super 40/Dyna- (MIC)when the First Sprinkler System is first installed. Thread are rated at 300 psi working pressure.Super 40/Dyna-Thread is UL Specifications and ULC Listed for wet,dry deluge and NPS Nominal 1.0. Wt. Wt.(H20 Filled) Peal Wt/Lift(21') lilttlLift(24') Wilt(25') pre-action sprinkler systems and FM Approved for use in wet systems. Super In;mm In;mm Lbs/Ft;Kg/m Lbs/Ft Kg/m Lift Lbs;Kg Lbs;Kg Lbs,Kg 40/Dyna-Thread can be"hot dip" 1' 1.080 1.330 1.75 70 1955 2234 2327 galvanized to meet FM requirement for 25 27.4 2.0 2.60 70 887 1013 1056 dry systems.Super 40/Dyna-Thread is 1'A 1.408 1.870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 35.8 2.8 3.78 51 908 1038 1081 welded outlets and is suitable for all 11/2 1.639 2.290 3.22 44 2115 2418 2519 roll-grooved,and plain-end fittings. 40 41.6 3.4 4.79 44 959 1097 1143 (See listing information). 2' 2.104 3.050 4.57 30 1921 2196 2287 50 53.4 4.5 6.80 30 871 996 1037 Vico allied 16100 S. Lathrop•Harvey, IL Customer Service: l'J 11350 Norcom Rd. •Philadelphia,hia, PA 19154 (800)882-5543 a vital part of your world TUBE&coNouf 2525 N.27 th Ave. •Phoenix,AZ 85009 Fax 708-339-1806 S3- 3 imm ii- - 9D° Elbow - Straight Astar F:re Products Divisor of Anvil'Internetioned �> lL. Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet . ® Cl :0°4°70 APPROVED i V Far LlslinglAppraval Details ' and Limitations vlsit our Web Site ft 10 Www.anviltielsom or contact an Anvil'/AnvilStar''Sales Representative. FIGURE 351 90° ELBOW STRAIGHT Weight Size A I B black gale. 6—6 NPS/DN In/mm /n/mm fbs./kg lbs. kg HA�I 0.16 0.17 j/16 IsA6 0.25 0.26 BL4 1.46 11/e 0.4 0.41 3 1516 0.6 0.61 .7 e c ze- 1 Iii lik 0.92 0.95 :4 `;3 0.42 17,, 114 l3/A 1.4 1.5 44 0.65 11: 15/6 115/ia 2 2 3 4,3 0.PB 2 19M 21/4 3.1 3.2 4" 51 1.4 '. 2' 113/6 211A6 4.9 5.1 17 <, 3 23/u. 31/4 7.2 7.4 6 79 3.3 4 231/46 3t1/46 12 13 5..5 5 35A6 41/a 21 — 1t6 10 • 6 31/4 51/4 31 33 I30 1,1 B 5306 69/ii 65 67 16/ /9 MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-B16.4 (except plugs 1/4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). = Inspected Fire Protection Equipment and Materials" issued by ithe Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date: undefined Phone: undefined Architect/Engineer: undefined Contractor: undefined Address: undefined Notes 1: undefined - Notes 2: undefined Anvil Cast&Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule. REV.06.09.06001 go to www.anvilslar.com or contact your local AnvilStar representative .mm1 ANNA-Star- 90° Reducing Elbow F re Pnxlurta Divfvlon of Anva"International I w Oki my /IL: Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet FIGURE 352 90° REDUCING ELBOW ()11>g Site A B C D bla kt Site A B C 0 Weight APPROVED NPS/DH NPS/DN In./mm In./mm In./no fn./mm lks./kg NPS/DN NPS/DN Minn In/mm In./mm i Injmm.,Iks./kg . For Listlnp/Approval Details -:3 3, I,,,6 I!'; 0.4 1 l:46 I l'','.6 2 ale 27A6 - 33 and Umltatlons visit our Web Site I� 2 a4nw.anvWnf.camor contact an f 3 5'- '' ',i ,� .7 I �' L/ Anvn'�/AnutlStar"Sales Representative. ' •'t A5 At 1 Ad 11/26 0.34 2 I A& 11/4 23/46 2316 4 1 3/4 1 11/46 13Ad 11/4 j' 0.51 11/4 15% 13/4t 213/16 213/46 6 ',rn 6, 11/16 '5At 1316 1% 0.61 I1tt I'.it 23/16. 215A6 215/16 5.7 I 3 i', C 3/4 13/16 15/16 17/16 11/16 0.76 2 15/6 21/4 115/16 2% 5.7 1,2 11A6 1'46 1 Y1 11k 1.1 21/ 11/6 13At. 3'Ad 31A6 6.4 l34 3/4 1346 11/4 151/4 13,4 1 31/2 3 23At 21/16 33% 33/4 8,9 ....—D--- 1 1 3/1 6 11Va l'i/id 111/%6 1.2 2 23/46 113/46 33/4 33/4 12 B--4-1 24 ,c 1/ 3/4 11/4 13/a 1 Vs 1.5 11/2 23/46 13/4 33,E 33/4 11 L, 16:' 4 i t1 A 3/4 1,r, I As 113/16 113/16 1.6 9 3 13/16 211/16 35A 3'/a 11 C 11/2 '� :'. 4; 4., rr/ li _55 r , l 1 11/4 113/16 113A6 1.4 31/ 21A6 2116 313/46 311/16 12 • - 4; 4 ^S °" 6' cr 11/4 13/46 116 11A 11,§ 1.7 211/4 213/46 31/2 43/4 43/4 20 'k PAt 11/16 I3AI 1% 2.1 5 3 213/46 33/4 t 431/4 43/6 19 F5 1='S ?0 /.'s 9/ 1?! ?ii 3/4 15A6 1�1/ 2 2 2.2 4 213/46 35A6 43/4 4316 16 "' , ;n0 / :'0 H1 '1 2 1 11Ad 11A6 2 2 ' 2.1 3 23/46 313A6 1 413/46 413/46 19 j? 124 11/4 13/Id VAd 21/,6 23/46 2.3 6 4 213/46 31/4 4136 415A6 14 1 15A6 11/2 2'A 21/4 2.6 5 33/e 313/46 5 5 17 1 1 13/4 23/16 23/46 2.4 8 6 43/46 51/4 63/e 63% 51 21 2, 44 62 11/4 13/46 13/4 23/6 23/4 3.4 .. '4 c",r' MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-B16.4 (except plugs 1/4 NPS - 12NPS (8 - 300 DN), are included in the "list of and bushings, ASME B16.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date:undefined I Phone: undefined Architect/Engineer:undefined Contractor:undefined Address:undefined Notes 1: undefined • Notes 2: undefined Anvil Cast&Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule, REV.06.09.06-002 go to www.anvilstar.com or contact your local AnvilStar representative = INY112; • 356 45° Elbow A N ALStarTM Farr.Produlls Divisror of Anvil"19 temational (10 AnivIL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet 0®g FIGURE 356 45° ELBOW APPROVED Weight For Listing/Approval Details Site A B • and Limitations visit our Web Site black galy. www.anvitintt.cam or contact an NPS/DN In.1mm la/rnm !bx/kg Ibs./ky AndriAnvilStar'""Sales Representative. - -0.16 0.17 3hl '`< 13/II 0.23 — ih h 0 3 0.38 (4,41 ?5 22 3/4 1 0.55 0.56 � I* 11,4 0.83 0.88 } 11/4 11,4 1.3 1.4 32 - 11/2 s;,, 17/1s 1.8 1.8 y� 2 1 1-the 2.4 3 S 1'h 1 11`She 4.3 4.3 if� 3 1;11 2":d 6.4 6.1 31h 1314 2$ 8.4 — . ;C 35 4 1344 25$ 11 11 t19. 40 6/ 5 171$ 31AS 17 17 43 i 1 i� 6 As 37/is 26 26 8 21.5$ 41/4 50 52 7rz • .1 NPS/DN(25 ON)size ovoilable in 1 NPS/DN x'12 NPS/DN(25 x 15 ON)reducing size, black or galvanized. MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-B 16.4 (except plugs I/4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B 16.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date: undefined (Phone: undefined Architect/Engineer:undefined Contractor: undefined AddreSS: undefined Notes 1: undefined Notes 2: undefined Anvil Cast&Malleable Iron Fittings For the latest UL/ULG Listed and FM Approved pressure ratings,versus pipe schedule, �M/IIL. REV.06.09.06-003 go to www.anvilstar.com or contact your local AnvilStar representative • ANvi .Starr° .3)=.0 Straight Tee Fire Products Divuuor of Anva Mternetiond /ZNVIL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet . Cz ® tc APPROVED ForLitationsvirovalDetails FIGURE 358 STRAIGHT TEE • and Limitations visit our Web Site www.anvoto.sem or contest an Anvil'1AnvllStar""Sales Representative. Weight Size A B black golv. NPS/ON In./mm In./mm 1bs./kg ibs./kg 1/4 14 0.22 0.23 IV, , 's Sh I 0.35 0.36 6 1141 0 55 0.56 4 =.'6 1`/.6 0.84 0.85 1 6 11h 1.3 1.3 r} 1;: 1 -s 13/4 2 2.1 44 1,:. 1'6 115/16 2.7 2.7 2 1 Vii 21/4 4.2 4.3 4o 5/ 1? A -A j-.--_-- 21 113/i6 211/is 6.7 6.8 A a L- 3 2346 Vs 10 10 31/2 27Ft 37As 13 14 4 2 1l16 33/4 16 17 s 5 35/1t 4'h 27 28 6 31/s Si` 41 41 8 53/16 69/,6 79 81 'i -6 MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-816.4 (except plugs 1/4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Inspected lire Protection Equipment and Materials" issued by the Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date: undefined I Phone: undefined Architect/Engineer:undefined Contractor: undefined Address: undefined Notes 1: undefined Notes 2: undefined Anvil Cast&Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule, �t1�/II_ REV.06.09.06005 go to www.anvilstar.eom or contact your local AnvilStar representative AN Y& Aft -Star- 355 Reducing Tee ,.Products Division of Anvil°Inieraauunal 6r)AniviL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet 1.—D--.-j—E-1 APPROVED For Listing/Approval Details A- 9 and Limitations visit our Web Site -- f Www.anvliintl.com or contact an ', f AnvR'/AnvllStarTM Sales Representative. F FIGURE 359 REDUCING TEE We'ohl ©�® © Weight Size 0 8 C D E f Size D f block gall'. hladk aqIv..,_ NPS D rarE uIE uii M®®In. mm in. mm lbs- ! lbs. r NPS 0 (�i (dam®�®®©[�®fn mm lbs r lbs. ® iid re ® 1,A I;� 0.57 ®®���®® 18 1.1 — a • ' iii, H® 1( 1 5 I'fi 0.57 — ®�E '`id ®® 1,/,' 09 - 2,i � ��� 1/4 d O.bB - 111111111,1111 1 it 1 At 0.91 - NENE 11/2 1.AI 13/8 v5 ® ii® 131_ 13/ 1.1, -• A. ���� 1/4 /1 0.79 — 5 ����� 1 A 0.89 - ®nnimogra l A 1'/4 O.b6 - 1 3 j HHHHHH 1!'d —1 - 1E11/11131111H151 138 e,': - k Yid At A At id •Ad 0.62 - V At At IA IA l/4 IA 1 — 4 74 22 . 01 77 7% 2 ,5 =4 % 11/8 1tAt 15/6 '3/4 '3/Is 1'A 0.15 - 'F 11/1d 11/1d ISlld 111A 1l%1 13/8 1 1 U HHH?9 7 !' G t z c l /1d 11/4 0.16 .1 gam !d ism 1116 1.1 - ® 2a>Fd MIN I/16 1 At 13A 0.99 - 37 3% 33 0.45 �iiii /16 1 Fd 14A6 l9/d 1.5 - ,1 Sa 11, 1'A 1/4 1 I Ad 1 /1d I-A 1.8 - 32 25 ,. - MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-816.4 (except plugs I/4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date:undefined Phone: undefined Architect/Engineer:undefined Contractor:undefined Address:undefined Notes 1: undefined Notes 2: undefined PAGE 1 OF 5 Anvil Cast&Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule, REV.06.09.06-006 go to www.anvilstar.com or contact your local AnvilStar representative � -AWL ' �/j Am/II-Star- 367 Concentric Reducers F.reProducts avis:m of AnwY,nternational ® jvn. Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet II TLC #H8 APPRDVED �_ For Listing/Approval Details ▪ and Limitations visit our Web Site www.anviiimi.cam or contact an Anvil'/AnvilStar' Sales Representative. FIGURE 367 CONCENTRIC REDUCERS Weight Weight Size A B Heck Size A I B Mack NPS/t?N r VON N tn./mm In./mm tbs./kg NPSIDI NPS/DN tn./mm In./mm lbs./kg k 1'r,6 0.4 2 1/4 1rs 2v 1.8 •1/2 i1/6 111,116 0 54 11 %13 23,16 2 1 •374 'At 11/2 0 6 11/2 3A 2 2,1 _ 21t d 'h 9h6 134 084 2 1 29A6 3 11/4 3/4 I 214 l.1 314 l5/16 21/2 4.3 l 15/16 21/2 1.1 3 2 l iAs 2314 4 / 1 15/s 1 21/2 15A6 213A6 4.4 ^ 3/4 th PA l.2 2 13/16 215/it 6.5 111 4/ 59 1 'h i3/4 1.5 4 21h 13A6 3A 7.8 25 44 65 30 11/4 1 21/4 1.5 3 1 iht 31A 7 25 r.T 1h ye 2 2 5 4 1-1/2i 35/e 10 19 /5 • 2 3/4 3/4 2 1-9 4 1'1/s 31A6 14 6 4' 1 3/4 2 1.8 •52 5 1 1/6 39/16 I f . �.. s7 8 6 11/4 37/s 29 Ill hex end MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-816.4 (except plugs 1/4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date: undefined I Phone: undefined Architect/Engineer: undefined Contractor: undefined Address: undefined • Notes 1: undefined • Notes 2: undefined Anvil Cast& Malleable Iron Fittings For the latest UL/ULG Listed and FM Approved pressure ratings,versus pipe schedule, L REV.06.09.06-0011 go to www.anvilslar.com or contact your local AnvilStar representative /�!M/�,-. • • 360 Straight Cross / Star- F re Products DIvrvo+of Anvil'htemarronal (0;11L Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet UL ® D H —. D—•1 APPROVED F,,:,. I k.—E., For Listing/Approval Details T- and Limitations visit our Web Site k-- q'T-- rfcasos wtw.anvl lnfl.com or contact an "•• +Cc, Anvil AnvtiStar""Sales Representative. 17. � TM;' G 5 __J_ r FIGURE 360 STRAIGHT CROSS Size A 13 Weig t black NP5/ON an/mm in/mm lbs/kg 13/16 '76 2.8 3/4 15/16 1'rt 1. '0 33 0.4% i Oh 1'5 1.6 5 t'.;'? l'-'4 13/4 1-S 2.4 a.5 115/16 Pi's 3.2 2 21/4 I'6 5.1 3/ 21/2 211A6 11 8.1 r5 68 3 3146 23/i 12 4 313/i6 2"- 20 5 4'h 35i 6 31 5 51/B 3''•6 48 MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-816.4 (except plugs I/4 NPS - 12NPS (8 - 300 DN), are included in the "list of and bushings, ASME B16.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' laboratories, Inc. NOTE:See the Technical Data section for pressure temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date:undefined Phone: undefined Architect/Engineer:undefined Contractor:undefined Address:undefined Notes 1: undefined . Notes 2: undefined Anvil Cast& Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule, REV.06.09.06.0012 go to www.anvilstar.cam or contact your local AnvilStar representative = ANVIL 3 8 3 Hex Bushing A�w .Stare F re Products olvis,on OF Anna•Ntemaronal 0 ANVIL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet APPROVED . For Listing/Approval Derails s and Limitations visit our Web Site ^ A www.anvillntl.com or contact an Anvil's/AnvllStarTM Sales Representative. FIGURE 383 HEX BUSHING Size We' ht _ Sae black gale. black gala. _. NPS/DN i Hex NPS/ON Ibs-/kg Ibs./kg NPS/DN Hex 1 NPS/ON lbs./kg lbs./kg 0.19 0.3 0 02' 0.02 • 0.05 0.05 • s 0.29 0.29 0.04 0.04 11'{ • h 0.3 0.3 r - 24 0.39 0.39 IA 0.06 0.06 0.01 0.07 I 0.3 0.3 0.05 0 05 /4 0.47 0.49 0.09 0.09 ■ 3ti 0.41 0.5 0.1 Oil • 1,42 0.41 0.47 < 1 is 0.12 0.12 • 3.4 0.47 0.5 -1 ,' 0.1 0.11 1 0.5 0.52 IA 0.21 0.22 11/4 0.33 0.33 t• - 1/4 0.19 0.19 • 1 • `/a 0.18 0.19 r h 0.21 0.22 3/4 0.17 0.17 MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-816.4 (except plugs 1/4 NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME 816.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date:undefined Phone: undefined Architect/Engineer:undefined Contractor:undefined Address:undefined Notes 1: undefined ' Notes 2: undefined PAGE 1 OE 2 Anvil Cast& Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule, REV.06.09.060016 go to www.anvilstar.com or contact your local AnvilStar representative ANVIL 387 Square Head Plugs (Cored) A star'" Flre Prxiurts DIvL,nr of M.ril'Intemali..l = AM/IL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet ® �c APPROVED For Listing/Approval Details and Llmitatlons visit our web Slte www.anvirlortcom or contact an Anvil'/AnvilStar""Sales Representative. FIGURE 387 SQUARE HEAD PLUGS (CORED) Weight Size black gale. NPS/DN lbs/kg lbs/kg 3.13 0.14 1 0.25 0.28 11/4 0.39 0.41 al 1 0.5 0.52 1.23 2 0.81 0.83 3 1.3 1.3 3 1.9 1.9 35 2.5 2.5• 4 4 4 POA • •Not stocked 0 Ye,t/a,3/8 NPS/DN(6,8&10 DN)plugs furnished in steel. I/2 and 3/e NPS/DN(15&20 DN)countersunk plugs furnished in malleable iron. MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-B16.4 (except plugs VI NPS - 12NPS (8 - 300 DN), are included in the "List of and bushings, ASME B16.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings- See AnvilStar Web site for the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date: undefined Phone: undefined Architect/Engineer:undefined Contractor: undefined Address: undefined • Notes 1: undefined Notes 2: undefined Anvil Cast & Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule, ANVIL REV.06.09.06-0019 go to www.anvilstar.com or contact your local AnvilStar representative -..�--... 1, I NV .Star- aS 1 Cap F re Products Doss,or of Anvil"Htemwtinnal ,r.xv L Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet APPROVED Far Listing/Approval Details AMOR and Limitations om visit or contact Web Site aww.anv111nN.tom or contact an n Anvir/AnvilStar"4 Sales Representative. FIGURE 381 CAP Weight Size black gals. NPS/DN lbs./kg lbs/lrg 2'f 2.5 — 3 4.1 — 4 6.4 — 5 11 6 14 15 8 77 28 • MATERIAL SPECIFICATIONS Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes manufactured in accordance with ASME-816.4 (except plugs 1/4 NPS- 12NPS (8 -300 DN), are included in the "List of and bushings, ASME B16.14). Inspected Fire Protection Equipment and Materials" issued by the Underwriters' Laboratories, Inc. NOTE:See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site For the most current Listings and approvals. PROJECT INFORMATION: APPROVAL STAMP: Project: undefined Date: undefined Phone: undefined Architect/Engineer:undefined Contractor: undefined Address: undefined Notes 1: undefined Notes 2: undefined Anvil Cast&Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings,versus pipe schedule, REV.06.09.060021 go to www.anvilstar.cem or contact your local AnvilStar representative .L TDLCO „„„‘„A„.,.......-.„„„‘„A„.,.......-._ _ ;NIBCO• , 2_;C, .,Fig. 200 - "Trimline” Adjustable Band Hanger . cO,S Mal Size Range— 1/2"thru 8" pipe der Material—Carbon Steel, Mil. Galvanized to G90 • specifications Function—For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features— , • (1/2"thru 2") Flared edges ease installation for c all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily installed around pipe. • (2W thru 8"Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. I Approvals—Underwriters'Laboratories listed (1/2" thru 8") in the USA(UL) and Canada (cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering + r Approved (3/4"thru 8"). Conforms to Federal `R '`' ` " '' ' ` '`` K'` Specifications WW-H-171 E,Type 10 and Manufacturers Standardization Society SP-69,Type 10. Maximum Temperature—650°F Finish—Mil. Galvanized. For Stainless Steel materi- als, order TOLCOTM' Fig.200WON. Order By—Figure number and pipe size . Dimensions •Weights Pipe Rod Size Max.Rec. Approx. Size Inch Metric A B Load Lbs. Length 1/2 3/8 8mm or 10mm 31 2% 400 11 3/4 3/8 8mm or 10mm 31/4 21 400 11 1 3/8 8mm or 10mm 3% 2% 400 12 11 3/8 8mm or 10mm 3Y4 214 400 13 11/2 3/8 8mm or 10mm 31/4 274 400 14 2 3/8 8mm or 10mm 41 3 400 15 21/2 3/8 10mm 5% 41A 600 27 3 3/8 10mm 51 4 600 29 31/2 3/8 10mm 73 51/a 600 34 4 3/8 10mm 7% 5 1000 35 • 5 1/2 12mm 91/4 61A 1250 66 6 1/2 12mm 101 63 1250 73 8 1/2 12mm 131/2 83 1250 136 ® OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA.CA 92879•PH 951 737.5599•FAX 951 737 0330 CUSTOMER SERVICE•800 786 5266 www loicacom (ti TOLCO www.tolco.com NIBCO• r<x /_:,, I 1 u2U ∎, Component of State of Fig. 98 - Rod Stiffener CaifomnaOSFIPDApproved C OUSUSTEo Seismic Restraints System Size Range—Secures 3/8"thru 7/8" hanger rod Material—Carbon Steel '=-' • Function—Secures channel to hanger rod for vertical seismic bracing. Approvals—Underwriters Laboratories Listed in the USA(UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved t , by the State of California Office of Statewide Health Planning and e- 1 Development(OSHPD). For additional load, spacing and placement 1 information relating to OSHPD projects,please refer to the TOLCO rl Seismic Restraint Systems Guidelines Finish—Electro Galvanized , , Note—Available in HDG finish or Stainless Steel materials. Order By—Figure number Fig. 99 - All Thread Rod Cut to Length Size Range—Secures 3/8"thru 7/8"rod in Dimensions •Weights 1"increments Rod Max.Rec.Load Lbs. Material—Carbon Steel `"t ' ( Size For Service Temps Maximum Temperature—750°F "( ���//! 650°F 750°F Finish—Plain rfl(( 1/2 1130 010 1 1/8 1830 1610 Note—Available in Electro Galvanized and U({((f(((//��� 5/a 1810 1610 HDG finish or Stainless Steel materials. 3/4 2710 2420 Order By Figure number, rod diameter, rod tif(( 7/8 3770 3360 length and finish • Fig. 100 - All Thread Rod Full Lengths • r Size Range—Secures 3/8"thru 7/8"rod in • 10'lengths Material—Carbon Steel lj Maximum Temperature—750°F `mss }. Finish—Plain ,,, Note—Available in Electro-Galvanized and 6f .-/ ��" HDG finish or Stainless Steel materials. tTrir, , Order By—Figure number, rod diameter r(f ,r and finish �E((� �'f( Dimensions •Weights (f Max Rec.Load Lbs. { Rod For Service Temps Approx. { Size 650°F 750°F Wt./100 . 1/4 240 215 12 3/8 610 540 29 1/2 1130 1010 53 5/8 1810 1610 84 3/4 2710 2420 123 7/8 3770 3360 169 1 4960 4420 222 11/4 8000 7140 360 11/2 11630 10370 510 ® OFFICEIMANUFACTURING FACILITY•1375 SAMPSON AVE •CORONA.CA 92819•PH 051.131,5509•FAX ,951./31.0330 CUSTOMER SERVICE-800.786.5266 wwwfofco.com a) TOLCO www.tolco.coal NIBCO Re vir,ion 9.22 2001 Fig. 65 and Fig. 66 Reversible C-Type Beam Clamps 3/4" and 11/4" Throat Openings Size Range—(Fig.65 and Fig.66) 3/8", 1/2"and 5/8"rod Component of State of 4> • California OSHPD Approved Material—Carbon Steel with hardened cup point set screw and Seismic Restraints System jam nut U� c 0 Function—Recommended for hanging from steel beam where flange thickness does not exceed 3/4"(Fig.65)or 1'/4'(Fig. 66). Features—All steel construction eliminates structural deficiencies associated with casting type beam clamps. May be used on top or bot- tom flange of the beam. (Beveled lip allows hanging from top flange . B where clearance is limited.) May be installed with set screw in up or ='F ; D 1 r 1 i down position. Offset design permits unlimited rod adjustment by .,,,•'' 1 allowing the rod to be threaded completely through the clamp. Open r s 3 mss' E design permits inspection of thread engagement. - C Approvals—Underwriters'Laboratories Listed in the USA(UL) and f ..---T Canada (cUL). Factory Mutual Engineering approved. Conforms to i E f' Federal Specification WW-H-171 E,Type 23 and Manufacturers F i -"- - Standardization Society SP-69,Type 19. Exceeds requirements of the I t r National Fire Protection Association (NFPA), Pamphlet 13, 3/8"rod will support 1/2"thru 4" pipe, 112" rod will support 1/2"thru 8"pipe. �r A Included in our Seismic Restraints Catalog approved by the State of *Irk California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement relating to lir OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Finish—Plain Note—Available in Electro-Galvanized and HDG finish. Order By—Figure number, rod size and finish Fig. 65 Patent#4,570,885 B Fig.65 Q Dimensions •Weights Pr Is"` C Rod Size Max.Rec. Approx. %pl. A B C D E F Load Lbs.* Wt./100 If 3/8 1hI F 3/4 1 7/16 1 610 28 {r 1/2 11/2 3/4 1 9/16 11/4 1130 55 '7--. t d #, 5/8 11/2 3/4 1 9/16 11/4 1130 55 lE i ' * Max.loads for clamp with set screw in up or down position. �..± Fig.66 .. I' I .- A Dimensions •Weights y i Rod Size Max.Rec. Approx. A B C D E F Load Lbs.* Wt./100 3/8 1'/,b 11/, 1 7/16 1 610 28 1/2 11/2 11/4 1 9116 1'14 1130 55 5/8 11/2 11/4 1 9/16 1114 1130 55 Max.loads for clamp with set screw in up or down position. ® OFFICE/MANUFACTURING FACUTY•1375 SAMPSON AVE •CORONA.CA 02819•P11. 951 13/.5599•FAX. 951/3/0330 CUSTOMER SERVICE•800.786.5266 wwwiolcacaa