DATA SUBMITTAL
FOR
FIRE PROTECTION SYSTEM
May 13, 2009
09-4302
FIRE PROTECTION CONTRACTORS
Coram Alternate Site Services
May 13,2009
Page 2 of 2
TABLE OF CONTENTS
Pipe & Fittings
Pipe
CIS Fittings
Hangers
Tolco Pipe Ring Fig. #200
Sammy Super Screws Fig. #gst20
Sammy Sidewinder Screws Fig. #SWG20
Sprinkler Heads
Reliable Model Fl '/s" 155 Degree Chrome Pendent
Reliable Model Fl '/z" 165 Degree Brass Upright
FIRE PROTECTION CONTRACTORS
as a= MINNa111■ 1111111111 a a- MINIM MA air
r
----Pipe and Supply Corp.
Pipe Specification A135
Specification A135 NPS 1/4--30", Schedules 10, 40 and XL THD, Lightwall
Scope Covers two grades of electric resistance welded steel pipe. Grade A is adapted for flanging and bending and is suitable for
welding. Purpose for which pipe is intended should be stated on order.
Kinds of Steel Permitted Open-hearth Basic-oxygen
For Pipe Material Electric-furnace
Permissible Variations The minimum wall thickness at any point shall not be more than 12.5%under the nominal wall thickness specified.
in Wall Thickness Threadable,lightwall(XL)must meet manufacturers minimums.
Chemical C max% Mn max% P max% S max
Requirements Seamless or ERW
Grade A 0.25 0.95 0.05 0.06
Grade B 0.30 1.20 0.05 0.06
Tensile Grade A Grade B
Requirements Tensile Strength,min.,psi 48,000 60,000
Yield Strength,min.,psi 30,000 35,000
NDE& Hydrostatic inspection test pressures for plain end and threaded are specified. Hydrostatic pressure shall be maintained
Hydrostatic for not less than 5 seconds for all sizes of electric resistance weld pipe. Non-destructive electric test should be in accordance
Testing with practices E213,method E227 or practice E213.
Permissible Variations Plus or Minus 10%schedule 10
in Weights per Foot Plus 10%minus 3 1/2%schedule 40
Permissible Variations Plus or minus 1%
in Outside Diameter
Mechanical Tests Tensile Test--Transverse returned on pipe NPS 8 and larger.
Specified Flattening test--Three steps required with weld located 0°or 90°from the line of direction of force required.
Number of Flattening and tensile on one length of pipe from each lot of 400 lengths or less of a style.
Tests Required
Lengths Pipe shall be furnished in 38'with a minimum of 20 ft. Pipe furnished to schedule 10 shall be in a specified length between
16 and 22 ft.
Required Markings Rolled,Stamped or Stenciled(Mfgrs.Option)
on Each Length Name or brand of manufacturer.
(On Tags attached to Kind of pipe,that is,electric-resistance welded A,electric welded B,same schedule wall thickness,schedule 10 or 40,NL
each Bundle in case ASTM A135
of Bundled Pipe) Length of pipe.
General End finish may be plain end beveled or plain end square cut.
Information
Standards and Specifications
Z ANVIL
Ill
iart•a•rnaa•c. INC.
Dimensions Material Galvanizing Thread Pressure FederaUOther
M.I.Fittings Rating
Class 150/PN 20 ASME 816.3• ASTM A 197 ASTM A-153 ASME Bt 2Q.t+ ASME 815.3• ASME 816.3"
) Class 300/PN 50 ASME 816.3* ASTM A-197 ASTM A-153 ASME 81 201+ ASME 816.30
M.I.Unions
Class 150/PN 20 ASME 816.39• ASTM A-197 ASTM A•153 ASME Bt 20.1+ ASME 816.39• ASME 816.39-
Class 250 ASME 816.39• ASTM A-197 ASTM A-153 ASME 81 20.1+ ASME 816.39•
Class 300/PN 50 ASME 816.39• ASTM A-197 ASTM A-153 ASME 8120.13 ASME 816,39•
Cast Iron Threaded Fittings
1 -
# Class 125 ASME 816.4• ASTM A-126(A) ASTM A-153 ASME 81.20.1+ ASME 816.4• ASME B16.4111
Class 250 ASME 816.4• ASTM A-126(A) ASTM A-153 ASME 81.2014 ASME 816.4• ASME 816.48
C.1.Plugs and Bushings
ASME 816.14• ASTM A-126(A) ASTM A-153 ASME 81.201+ ASME 816.14' 1 WW-P-471
C.1.Drainage Threaded Fittings
ASME 816.12• ASTM A-126(A) ASTM A-153 ASME 81.20.1+ ASME 816.12•
C.1.Flanges and Flanged Fittings
Class 125(1--12-) ASME 818.t• IASTM A-126(A)or(8) ASTM A-153 ASME 81.201+ ASME 816.1 ASME 816.1•
Class 125(14'-up) ASME 816.1• ASTM A-126(8) ASTM A-153 ASME 81.20.1+ I ASME 816.1 ASME 8161•
Class 250(11%121 ASME 816.1• ASTM A-126(A)or(8) ASTM A-153 ASME 81.20.1+ ASME 816.1 ASME 616.1•
Class 250(14"-up) ASME 816.1• ASTM A-126(8) ASTM A-153 ASME 81.20,1+ (I ASME 816.1 ASME 8161•
Forged Steel Threaded Fittings
. ASTM A105.
Class 2000.3000.
6000 ASME 816.i t• ASTM A382„ ASME81.20.1+ ASME 816.11•
ASTM A350
Pipe Nipples
Steel Pipe ASTM A733 ASTM A53 ASME 81.20.1+ WWN 351
-Welded Type F or Type E
Steel Pipe -
-Seamless ASTM A733 ASTM A106 Gr.8 ASME 81 20.14 WWN 351
(High Temp) .
Brass ASTM 843 ASME 8120.1+ WWN 351
-
'The standard
*an American National standard(ANSI)
+ASME 81.20.1 was ANSI 82.1
•Formerly WW-P-501
"Formerly WW-P-521
.''Formerly WW-U-531
PF- 149 I
.
Tosco www.toico.com
.', NIBCO• Revision 5/24/2001
Fig. 200 - "Trimline" Adjustable Band Hanger
C OOS usTED
Size Range— 1/2"thru 8"pipe 4>
Material—Carbon Steel, Mil. Galvanized to G90
specifications
Function— For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger . `` ,---'',/'.. `.
adjustment after installation.
Features— �'.— l
• (1/2"thru 2") Flared edges ease installation for Il ;f
all pipe types and protect CPVC plastic pipe from if..,. % \1 /"
abrasion. Captured design keeps adjusting nut i .:J%k
from separating with hanger. Hanger is easily e 1 t.. B 1 /f
installed around pipe. r
• (21/"thru 8" Spring tension on nut holds it A (1::: A
securely in hanger before installation. Adjusting
nut is easily removed. ''� r'
Approvals—Underwriters' Laboratories listed (1/2" /r
thru 8") in the USA(UL) and Canada (cUL)for steel
and CPVC plastic pipe and Factory Mutual Engineering /r
Approved (3/4"thru 8"). Conforms to Federal ,-- 1/2 THRU 2 INCH PIPE 2 1/2 THRU 8 INCH PIPE
Specifications WW--H-171 E,Type 10 and Manufacturers
Standardization Society SP-69,Type 10. ___........
Maximum Temperature—650°F �%:
Finish —Mil. Galvanized. For Stainless Steel materi- z
als, order TOLCOT"" Fig.200WON. •-• • ,1 — "\
Order By— Figure number and pipe size f( '�" 1
\\ / 1
ill/ \. /1 ti r/
K‘ . y \;:„, i ,
1
Dimensions •Weights
Pipe Rod Size Max.Rec. Approx.
Size Inch Metric A B Load Lbs. Length
1/2 3/8 8mm or 10mm 31/2 25,6 400 11
3/4 3/8 8mm or 10mm 31/2 2112 400 11
1 3/8 8mm or 10mm 3% 2% 400 12
1 IA 3/8 8mm or 10mm 3% 21/2 400 13
11/2 3/8 8mm or 10mm 31/2 21/2 400 14
2 3/8 8mm or 10mm 41/2 3 400 15
21 3/8 10mm 5% 41/2 600 27
3 3/8 10mm 51 4 600 29
31 3/8 10mm 7334 51/4 600 34
4 3/8 10mm 7% 5 1000 35
5 1/2 12mm 91 6' 1250 66
- 6 1/2 12mm 101/2 63/4 1250 73
8 1/2 12mm 131/2 83/4 1250 136
® OFFICE/MANUFACTURING FACILITY•1375 SAMPSON PSON AVE •CORONA.GA 92879•PH: 951 717 5599•FAX 951.737.0330
CUSTOMER SERVICE•800.786.5266
www tolco.com
* csr '`�= :-i
IN i
SAMMYS 'A
WOOD • 1/4"Rod• Vertical Mount 1/ox quantity 100 except as nosed with this marking(t)
Use#14 Nut Driver(Item#100) • Box quantity 30
Item 4 ModN Rod Size Shk Dia Shk Lgth
20 GST.750 1/4-20 1/4 314
,___ i...... ....... •u them 01501
21 GST 100 1/4-20 1/4 1
22 GST 200 1/4-20 1/4 2
23 GST 300 1/4-20 1/4 3
24• GST 600 1/4-20 1/4 6 See page 13 far Stainless Steel
WOOD•3/8"Rod•Ve ,: Note:Screws less than 2"in
length will be plated yellow.
Use#14 Nut Driver(Item#100) ", " - Greater than 2"are clear
1 FM Test UL Test UL1FM zinc per ASTM8633111
Item 4 Model Rod Size Shk Da Shk Lgth Load,lb. Load.lb. Pipe Size ActuaI Pullout
10 GST.75 38-16 1:4 3,'4 5641-6 Fly
11 GST 10 ' 3/8-16 1/4 1 1 1 /210.-7/16 068 i
I_ 6708-3r4-Fly
12 GST20 3/8-16 1/4 2 I 9401 850# } 3/4-21/2 i 17601-Fit• 814iftemritlat
g1 27 • GST 25-380 3/8-16 3/8 212 1500# 4 2113#-Fir
4m ut- 13 GST 30 3/8-16 1/4 3 1475* 15004 3/4-4 2060*-F
403• GST 40 3/8-16 1/4 4 21804-Fir
it • GST 60 3/8-16 1/4 e I 2230#-Fir
WOOD • 1/2"Ro. • e "Ica 7 ouii T.
Use#14$W Nut Driver(Item#101)
Item 4 Model Rod Size Shk Dia Shk Lgth Actual Pullout
8 • GST 2 1/2-13 1,4 2 17604-Fir rtarwthem rich
06• GST 2.5-384 112-13 348 2 112 211340 Nett:Me'NSW mat be used
-Fir for wog.wrjl la"e p
15• GST 3 1/2-13 1/4 3 22754-Fir
16• GST 4 1/2-13 1/4 4 21804-Fir
Installations Not less than
17• GST 6 1/2-13 1 r'd 6 2 -Fir n saaons 7-nommat width
II 1/2't
.See Page 5 for installation instructions.
{
fit- Installation /{ E
perNF1':■ 13 ;
z .
6 t.
jj Y
TGi Joist/Truss -'
Consuft truss manufacturer tut
I:2:� ri, recommended installation point
Wood Flooring (See"Special Notes'
on"/writ r'l
L7-1 Sammy w I ;.
.-.Wood Joist Lowe,taco of l •� --. Sammy
beam or foist si
'`�Y Minimum 2'imbrdmsnt ittto base al
" - _ material for NFPA tJ compliance
' _ ._.._.... -. For vertical use. ellari
Install in center
f •• Sammy of lower face.
Doubts Sheetrock Ceding
if you don'I scat it,calf us at II I
1.888.77 3.COO I
4 wood-Sammys I Note:Must be installed with appropriate nut driver to comply with warrants.
5111;
.C,,9 i
lielliali.kiiiiM „...I
tw . Wood
See e 13 for Stainless Steel SIDE IVINDERS
WOOD•1/4"Rod•Horizontal Mount Box quantity /00 eserpt as noted with this marking OP)
Us14SW Nut Driver(Item#101)
• Buz quantity 50
t:�#
Item It Model Rod Size Shk Oia Shk Lgth Actual Shear/Pullout
___.._._._. MUSK'{ItemsI013
300 SWG 200 1 4-20 1.4 2 17254-Fr
WOOD 3/8"Rod•Horizontal Mount Screws less than 2"in length
will be plated Yellow.Greater than
Use xt4SW Nut Driver(item#101) 2"are clear zinc per
UL Test UL Pipe Actual ASTM86331I1
Item # Model Rod Size Shk Dia Shk Lgth Load.lb. Size Shear/Pullout
18 SWG 10 3%8-16 1.`4 1 014%11 r hem IVtftn
I19 SWG 20 38-16 1,4 2 12504 3 17254 - Fir
26 • SWG 25-380 18-16 3.8 2 1;`2 15004 4 22494 -Fir
25• SWG 30 3.8-16 1.4 3
M fastening through gusset plates.use the S WD 20(see page St
Installations
TGI Joist/Truss
"t - -- .-.:;„` g Consult truss manufacturer for
recommended installation point.
Sid n s-. (Sue'Special Notes"
Floor Joist .-. on..i i r 71
I.1 1 •"s Sldewinoar s
a
$ t r
1110111111 I I ✓;
WOOD INSTALLATION INSTRUCTIONS
GST&SWG—See diagram figures 1-4,11-14 on page ' "
18 and 19.
Not less than 2-nominal width(1 1)2')
(Self drilling&self-tapping into wood) up to 3 1/2'pupa:not less than 3'
nominal width 4-&5- pipe
Step 1: Insert the appropriate nut driver into a 3/8"or 1/2"
portable drill: (a) Use#14 for GST for 3/8"and 1/4"rod;(b) Installation
use#14SW for SWG,and for GST for 1/2"rod. per NIT A 13 I I i/
( if
Step 2: Insert the screw into the nut driver. Now you are
ready to install the screw. l'
Step 3: Position drill and begin installation: (a)for installing
GST drill should be in a vertical position;(b)for installing
SWG drill should be in a horizontal position at a right angle Sale,
to the structural member.
Minimum 2 1;2"from nottom for
s
branch lines.Minimum 3 from
Step 4. When the nut driver spins freely on the cap of the notion,for main rn.,•z E*cr' °.°
This requirement shalt not apply to 2
screw installation is complete. or thicker nailing sh pe resting
on lop of steel beams. ■
Step 5:Screw is now ready to receive 1/4', 3/8", 1/2'or
metric all thread rod or bolt stock.
- Eye protection should be worn at all times when install- I
ing this product.
.Note:Must be installed with appropriate nut driver to comply with warranty. Wood- Stdeuiinders 5
Bulletin 117Rev Q
ReIiabIi ® Model Fl
Model Fl Recessed
Standard Response 5
S • rinklers
cp
The Designer® Model Fl Sprinkler
Standard Upright - 2 ,,;.
Standard Pendent
, a,
Extended Coverage Pendent
Conventional "' 4
Vertical Sidewallm
Horizontal Sidewall Upright Pendent
-HSW 1 Deflector
Horizontal Sidewall Extended Coverage
-EC-6 Deflector i,
The Designer®II Model Fl Recessed Sprinkler
Recessed Pendent
Recessed Extended Coverage Pendent
Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional
Approval Organizations
1. Underwriters Laboratories Inc.
2. Underwriters' Laboratories of Canada .� ~ 1111110'.. . ;
3. Factory Mutual Research Corp. t 1 e/
4. Loss Prevention Council
5. NYC BS&A No. 587-75-SA Horizontal Sidewall Recessed Pendent
6. Pleniere Assemblee
7. Verband der Schadenversicherer
8. NYC MEA 258-93-E ` `-.
UL Listing Category
Sprinklers, Automatic &Open (VNIV)
Product Description Extended Coverage Recessed Extended
The Fl Glass Bulb Sprinkler combines the durability of a Horizontal Sidewall Coverage Horizontal
standard sprinkler with the attractive low profile of a decora- Sidewall
tive sprinkler. Whether installed on exposed piping or in an
office ceiling, it is functional and attractive. The Horizontal 411
and Vertical Sidewall Sprinklers provide an equally attractive , _.
appearance when ceiling piping cannot be used.
4-fir
Beautifully versatile is the description for the Reliable , 4
Model Fl Recessed Designer glass bulb sprinkler. Re-
cessing The Designer®enhances its already low profile dec-
orative appearance, and facilitates a rapid and perfect Extended Coverage Recessed Extended
installation. Pendent Coverage Pendent
Model Fl Recessed Designer's escutcheon is highly ad- At normal temperatures,the glass bulb contains the fluid in
justable.The two piece construction makes field installation a both the liquid phase and in the vapor phase. The vapor
very easy and rapid task.This also allows ceiling panels to phase can be seen as a small bubble.As heat is applied,the
later be removed without shutting down the fire protection liquid expands forcing the bubble smaller and smaller as the
system, thus facilitating maintenance of above ceiling ser- liquid pressure increases. Continued heating forces the liq-
vices. uid to push out against the bulb,causing the glass to shatter,
The Designer® Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute
glass bulb. The glass bulb consists of an accurately con- the discharging water.
trolled amount of special fluid hermetically sealed inside of a The Fl Sprinkler temperature rating is identified by the
precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where
specially constructed to provide fast thermal response. applicable.
The Reliable Automatic Sprinkler Co.,Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Model Fl Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
''' \ ..,', -t, ;
mss` fit �
> . SAS
t- 44 ill
Upright Pendent Conventional Upright(2)
Installation Data:
Nominal Sprinkler
Nominal Thread Sprinkler Approval Identification
Orifice Size K Factor Height Organization Numbers(SIN)
US Metric , Upright Pendent
Standard-Upright(SSU)and Pendent(SSP)Deflectors Marked to Indicate Position
1/2"(15mm) 1,"NPT(R1/2) 5.6 80 2.2"(56mm) 1,2,3,4,5,6,7 R1725 R1715
'%"(20mm) 34"NPT(R3/4)(1) 8.0 115 2.3"(58mm) 1,2,3,4,7,8 R1722 R1712
1/2"(15mm)(4) 'h"NPT(R1/2) 5.6 80 2.2"(56mm) 7 R1795 R1705
'%"(20mm)(4) 34"NPT(R314) 8.0 115 2.3"(58mm) 7 R1792 R1702
'+e"(11mm) 'h"NPT(R'h)(2) 4.2 60 2.54"(65mm) 1,2,8 R1723 R1713
%"(10mm) '/'z"NPT(R1/2)(2)(3) 2.8 40 , 2.54"(65mm) 1,2,8 R1721 R1711
10mm XLH R%e 4.2 60 56.1mm 4,6,7 R1724 R1714
Conventional-Install in Upright or Pendent Position
10mm XLH R% 4.2 60 56.1 mm R1774
15mm 1/2"NPT(R1/2) . 5.6 80 56.1mm 4,6,7 R1775
20mm 34" NPT(R34) 8.0 115 58.1mm 4,7 R1772
(1)LPC Approval up 286°F(141°C)
(2)Small Orifice identified by a pintle extending beyond the deflector.
(3)FM Approval for SSU only,up to 200°F(93°C).
1 (4)VdS Approval for Intermediate Response 155°F(68°C)only.
2.
Model Fl Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
L 2 r/s'IV(t Dil -
(57.a IJ
I WIG'DM.
/4 +"1
r si1
N•, J 1'X 1/1'MAKER
� ,; ..-
RAY=AR �[23.Iinrn X u.7mmJ
Nom s
AVAST SPRINKLER
, 1 WWII DOSS i1) 1 n
' -Ili
�.�' 1111 .L - f
�, .•�nrAn " � Jre.J
�Ari_ _rt idyl%//// + !
Fl Recessed ��' Ve }
[52"..J r•(25.+ .J
1
IIIFGOIA gut;al
(2)When installed directly into a tee,the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval
Orifice Size Height Organizations us Identification
Numbembe
US Metric Numbers(SIN)
X"(15mm) y,"NPT(RY,) 5.6 80 2.2"(56mm) 1,2,3111,4,5,7 R1715
IX„"(20mm) , y,"NPT(RXJ 8.0 115 2.3"(58mm) 1,2,3111,4,8 R1712
X"(15mm)141 y,"NPT(RY,) 5.6 80 2.2"(56mm) 7 R1705
_1X„'(20mm)(4) X;”NPT(RX,) 8.0 115 2.3"(58mm) 7 R1702
' X."(11mm)(2) , y,"NPT(R1/2) 4.2 60 2.54"(65mm) 1,2,8 R1713
X"(10mm)(2) , y,"NPT(R' ) 2.8 40 2.54"(65mm) , 1,2,8 R1711
10mm RX 4.2 60 56.1mm 4(31,7 R1714
(1)FM Approval
• Light Hazard-No Limitations.
• Ordinary Hazard-Groups 1 &2,Wet Systems only.
(2)Identified by a pintle extending beyond the deflector.
(3)LPC Approval is XLH,OHI and OHII Occupancies only,
57°C through 93°C ratings.
(4)VdS Approval for Intermediate Response 155°F(68°C)only.
3.
Model Fl Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
o-
Vertical Sidewall
U.S. Patent No. 6,374,9201
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval
Orifice Size Height Organizations u
US Metric Numbmbers s identification(SIN)
y"(15mm) y"NPT(RY2) 5.6 80 2.2"(56.1mm) 1,2,3,4111,6,8 R1785
(1)LPC Approval is pendent only,57°C through 93°C ratings.
Sprinkler Deflector to
Type Ceiling Distance
(Min.-Max.)
Upright 4"(102mm)-12"(305mm)
Pendent 4"(102mm)-12"(305mm)
Model Fl Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench --»
•c •
Horizontal Sidewall
Installation Data:
Nominal Approval Organizations PP g Sprinkler
Nominal Thread K Factor Sprinkler Identification
Orifice Size Length Light Ordinary Numbers(SIN)
US Metric Hazard Hazard
'/z"(15mm) '/z"NPT(R'/) 5.6 BO 2.63"(67mm) 1,2,3,5 1,2,5 R1735
Note. UL and ULC Listing permits use with F1 escutcheons,light hazard only.
4.
Model Fl Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model D Sprinkler Wrench � ,
Approval Type: Extended Coverage-Light Hazard Occupancy 4
4
,
Installation Data: �>
Nominal Temperature Sprinlder
Nominal Thread K Factor Sprinkler Approval Rating identification
Orifice Size US Metric Height Organizations °F °C Numbers(SIN)
1%,,"(20mm) ;;"NPT(R3/4) 8.0 115 2.2"(56mm) 1,2,8 135; 155 57;68 R1742 Extended Coverage
y"(15mm) y,"NPT(R'/) 5.6 80 2.2"(56mm) 1,2,8 135; 155 57;68 R1745 Pendent
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
K=8.0(115) K=5.6(80)
gpm Umin psi bar psi , bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9
33 125.0 17.0 1,2 34.7 2,4 18x18 5.5x5.5
40 151.4 25.0 1,7 51.0 3,5 20x20 6.0 x 6.0
Model Fl Recessed Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model RC1 Sprinkler Wrench Ile MOLE
Approval Type: Extended Coverage - Light Hazard Occupancy (573in"J
(I f3/1BJ'ON
47.2mm
--I---`_
r L� -t, I•x 5/4'REDUCER
L. TJ 12. x IA/mmJ
OR
TIRRy COLLAR I I 1'x I/2'REDUCER
UN72 IICRT 1�(2&4mm A 12.7 J
AWNS.BOSS -\\ I I
GANSr BOSS
,,,,,,3 ' = - i
� 3/4 M (0 03 ra '�'"'
[19.Imm] ��"ii� [2dMrn,
_ e ii"
--_� ) +
Extended Coverage A __ ' "^^�
Recessed
I I7,OO2A 2 27/17.OK ■
(72.2..J
"'When installed directly into a tee,the escutcheon
dimension's adjustment will be reduced.
Installation Data:
Nominal Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations
°F oC Numbers(SIN)
'Y,"(20mm) 9'"NPT(R3h) 8.0 115 2.2"(56mm) 1,2,8 135; 155 57;68 R1742
y,"(15mm) y7"NPT(R'h) 5.6 BO 2.2"(56mm) 1,2,8 135; 155 57;68 R1745
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
. K=8.0(115) . K=5.6(80)
qpm _ Umin , psi . bar . psi bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20x20 6.0 x 6.0
5.
Model Fl Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC-6
Glass Bulb: 3mm 155°F(68°C) Standard, Unless 5mm 135°F (57°C) is Specified
Installation Wrench: Model D Sprinkler Wrench
. Approval Type: Extended Coverage— Light Hazard Occupancy
Extended Coverage Horizontal Sidewall
Installation Data:
Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations ,F oC Numbers(SIN)
'%'(20mm) %'NPT(RN) 8.0 115.3 2.75"(70mm) 1,2,8 135(5mm bulb) 57 R1762
155(3mm bulb) 68
COVERAGE AREA
Max. Area Deflector to
Flow Rate Pressure Width x Length Ceiling Dimensions
(Min. -Max.)
gpm L/min psi bar ft. x ft. m x m
36 136.3 20.3 1,4 16 x 22 4.9 x 6.7 4"(102mm)-6"(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4"(102mm)-6"(152mm)
6.
Model Fl Recessed Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC-6
Glass Bulb: 3mm 155°F (68°C) Only
Installation Wrench: Model GFR1 Sprinkler Wrench
Approval Type: Extended Coverage—Light Hazard Occupancy
13/76- t/R•0.2m71J
(u.e l (ro,.m.ro f82.4rmmJ
M ' TURN COLLAR'
Mi UNTIL nait AcUN sr
' r
J�
Recessed Extended Coverage t
Horizontal Sidewall REC,,,,,E,,,OED ^;'
ONLL HOLE
(57.2mm) (u
J/4 ALLUSTuevr
(19.171v0
"'When installed directly into a tee,the escutcheon dimension's
adjustment will be reduced.
Installation Data:
T
Nominal Thread K Factor Sprinkler Approval Temperature Sprinkler Rating 1 Identification
• Orifice Size Height Organizations
US Metric °F °C Numbers (SIN);
"%2"(20mm) Y."NPT(R3/4) 8.0 115.3 2.75"(70mm) 1,2,8 155 68 R1762
COVERAGE AREA
Max. Area Deflector to Ceiling
Flow Rate Pressure Width x Length Dimensions
(Min.- Max.)
gpm Umin psi bar ft.x ft. m x m
36 136.3 20.3 1,4 16 x 22 4.9 x 6.7 4"(102mm)-6"(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4"(102mm)-6"(152mm)
7.
' Model Fl & Fl Recessed Sprinklers Maintenance
Application The Models Fl and Fl Recessed Sprinklers should
Model Fl and Fl Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main-
fire protection systems: Wet, Dry, Deluge or Preaction. tained in accordance with NFPA 25. Do not clean sprin-
Care must exercised that the orifice size, temperature rat- clea with soap mo water, pmmor ammonia whor ich any other
een
ing, deflector style and sprinkler type are in accordance cleaning fluid. Remove any sprinkler which has been
• with the latest published standards of the National Fire Pro- painted(other than factory applied)or damaged in any
wa
tection Association or the approving Authority Having y. A stock of spare sprinklers should be maintained
Jurisdiction. to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be
Installation maintained in the original cartons and packaging until
Model Fl sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers
tended for installation as specified in NFPA 13.They must that would cause improper operation or non-operation.
also be installed with the Model D Sprinkler Wrench specifi-
cally designed by Reliable for use with these sprinklers.
The Model Fl Recessed Sprinklers are to be installed Temperature Ratings
with a maximum recess of 3/4 inch (19mm). The Model F1 sprinkler Maximum Ambient
Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb
be used with the Model F1 Pendent and EC Sprinklers.The °F °c °F °C Color
of any other recessed escutcheon will void all approv- Ordinary l 135 57 100 , 38 Orange
als and negate all warranties.When installing Model Fl Re- Ordinary 155 68 100 1 38 Red
cessed Pendent,EC Pendent,and EC HSW Sprinklers,use Intermediate 175 79 150 66 Yellow
the Model GFR1 Sprinkler Wrench. Any other type of Intermediate 200 93 150 66 Green
wrench may damage these sprinklers. High (1) 286 18 225 107 Blue
y g p Extra High 360 182 300 149 Mauve
Glass bulb sprinklers have orange covers to protect the
bulb during the installation process. REMOVE THIS PRO- "'Not Available For Fl Recessed
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No.6,374,920
STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model F1 Vertical Sidewall Sprinklers.
ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers Finishes t1)
are in place.
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
Ordering Information White Polyester Coated"' White Painted
Specify: Special Application Finishes
1. Sprinkler Model Sprinkler Escutcheon
• 2. Sprinkler Type Bright Brass`'`°' Bright Brass
3. Orifice Size Black Plated Black Plated
Black Paint Black Paint
4. Deflector Type Off White mu') Off White
* Satin 5. Temperature Rating: Lead P late
de 4 Satin Chrome
Specify ty Bulb Size when ordering Wax Coated`3""`6'
Wax Over Lead'9"t5)
Model Fl EC HSW Sprinkler.
6. Sprinkler Finish "'Other colors and finishes are available on special order.
Consult factory for details.
7. Escutcheon Finish(where applicable) '4 200°F(93°C)maximum.
"'UL and ULC Listed,and NYC Approved Only.
"'155°F to 200°F(68°C to 93°C)ratings only.
`5'286°F(141°C)Sprinklers may be coated for ambient conditions
not exceeding 150°F(66°C).
`8)LPC approved for 10mm and 15mm sprinklers only.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries
Manufactured by
i The Reliable Automatic Sprinkler Co.,Inc.
Recycled
Heliab' (800) 431-1588
(800) 848-6051 1 Sales Offices ReP°data.
Fax Revision lines indicate updated or new data.
(914) 668-3470 Corporate Offices
www reliablesprinkler.com Internet Address EG printed in USA. 12/03 P/N 9999970011