Plans STARK 4001 Main Street, Suite 305
FOUNDATIONS Vancouver WA, 98663
P: 360.566.7343
STRUCTURAL CALCULATIONS
PREPARED FOR RECEIVED
RAMJACK WEST
FOR AUG 21 2014
FOUNDATION REPAIR CITY OF TIGARD
7005 SW VENTURA DRIVE BUILDING DIVISION
TIGARD, OR
PROJECT NUMBER: 14.034.RAM
DATE: AUGUST 18, 2014
Approved plans PROJECT MANAGER: DANIEL STARK
shall be on job site.
SPECIAL INSPECTION REQUIRED
State of Oregon Structural Specialty Code PROFFSn
vAG I NEER u 7
O Concrete and Reinforcing Steel 74s PE --.
Bolts installed In Concrete (çiicY") r :Oar
❑ Special Moment-Resisting Concrete Frame 4
❑ Reinforcing Steel &Prestressing Steel Tendons 0Ifw '
O Structural Welding DOD.: 08/30/18
a High-Strength Solting t}
❑ Structural Masonry
OFFICE COPY
❑ Reinforced Gypsum Concrete
❑ Insulating Cracrete Fill CITY OP TIGARD
REVIEWED FOR CODE COMPLIANCE
❑ Spray Applied Fire-Resistive Materials ; ,
Approveas A/wove ot)i,_,
r flings, Drilled Piers and Caissons
❑ Shotcrete Permit : b/ - d "3
Addreeet
❑ Special Grading, Excavation and Filling
" 8utte i� .
❑ Smoke-Control Systems ate.c Dates_ , L /
sommum.7 ei„
❑ Other Inspections `���
BTARK 4001 Main Street, Suite 305
FOUNDATIONS Vancouver WA, 98663
P: 360.566.7343
TABLE OF CONTENTS
Project Background 2
Geologic Setting 3
Summary 3
Floor Level Survey 4
Design Calculations 5
Foundation Repair Plan and Detail 7
ICC ESR 1854 (applicable pages only) 9
STARK 4001 Main Street, Suite 305
FOUNDATIONS Vancouver WA, 98663
P: 360.566.7343
August 18, 2014 SFI Project No.: 14.034.RAM
Mr. Ken Marquardt
RamJack West
850 Bethell Drive
Eugene, Oregon 97402
Re: 7005 SW Ventura Drive, Tigard, OR: Project Summary& Soils Investigation
PROJECT BACKGROUND
We understand that the property has an existing retaining wall about 8-9 feet tall. The retaining
wall retains the garage slab and soils underneath as well as serves as a bearing wall for the
exterior wall and roof above. We understand that the retaining wall in question has a couple of
small vertical cracks and approximately 1/4"— 1/2" of lateral displacement at the top of the wall.
Three 2-7/8 inch diameter helical tie-backs have been proposed to prevent any future
displacement.
yt ! 1Z½7'
• V e It/
.d....:::,:i'. - ',..-• : ''', - ,., \ \ 4, / ii t
)r r it
aka 1 \ ...
;;-••:•.'-'''' ' " \ 1 \ ' ' .
1
�� t 1 i t t I • 1
t
-4---_-_,\' .,‘ ,- ,k4„,\,..*,... .
s
�.1� r t
Image 1:
View of Garage Retaining Wall
Page 2 of 11
STARK 4001 Main Street, Suite 305
FOUNDATIONS Vancouver WA, 98663
P: 360.566.7343
GEOLOGIC SETTING
The existing residential home site is located in Tigard, Oregon, west of 1-5 along the Washington
Square Estates Open Space. The geologic structure in the area is comprised of sandy clay
loames. There is no noticeable slope instability at the site that would indicate that the site is
sliding and according to DOGAMI, the site is not located within a landslide hazard zone.
It is our opinion that the lateral displacement occurred over time, possibly due to poor drainage.
We believe that suitable support can be achieved by installing helical tie-backs to prevent any
future potential movement.
SUMMARY
Based on the geologic setting, we expect the tie-backs to achieve adequate capacity at
approximately 35 to 40 feet from the back of the retaining wall, installed at a 20 to 30 degree
angle. We recommend that helical piers with a 2-7/8"shaft with an 8"and 10"helix plate
configuration. The tie-backs should be installed to a minimum length of 20-ft and a minimum
installation torque of 5,240 ft-lbs. This will achieve an ultimate load of 52,400 lbs.
PROOF TESTING
Proof testing of the helical piers should be performed and shall consist of loading at least one of
the helical piers tested to 150 percent of the design load. The 150 percent of design load
increment should be held for five (5) minutes and the displacement monitored. If the total
displacement is less than 1/8", the helical pier may be considered acceptable. However, if the
recorded strain exceeds 1/8"inches,the helical pier should either be deepened and retested or
abandoned and a new helical pier shall be installed and tested.
Please give our office a call if you have any questions or need further assistance.
Regards,
Daniel Stark, P.E. ��J PRO,cs�/
,
Stark Foundations, Inc. N, ttAGINEEjP
741 APE
vor
`9 vGZ a 1.0
EXP.: 06/30/16
/
8/15/2014 |numxphp(675x 900)
10.21 AM mi•
17:1 il-A15
0 -
.8
"r
. ----g--o-~~i~'~~e ~°~°=^�=~w�°�"~=�^�"i"� ��n�a�twm ��
�-- °- . ^ ��
. � 0r
�
.
. .
, ` :
• 40ft
. _ ' _ . -- _ . - ----- ' -_---'-~ -'.`_
--------.^'
m '---' -(
'-
, - -_
. ' . ' -
--- . - .
' - ..... .� - ' .. ' r - - -- /
`
-'----_--_
� -� �
' ' ■
i
i '
• / � ' ~ �m�
! »��� �
|
—
. i
. '-.-- .. .
� .
2 Car � |
��• Attched � � I
CV ''- ---' _=_ ° ' ,° .•
-'__--- ---_- __'—___'-__---
•
.
|
�
� • ~_—.__'--_---_-. -
mnfi
.
..�.'-----. - •-.' ..—. - � . . - -'-' • --' - — - .
Date: 18-Aug-14
STARK W Ramlack West- Retaining Wall Bracing Designed by: NDS
FOUNDATIONS ^ 7005 SW Ventura Drive
wNewberg,OR
Job No.: 14.034.RAM
Deal.n Criteria
Code(s):
International Building Code(IBC)2009
ASCE 7-05
Design Loads:
Dead: Soil:
Roof= 15 psf Lateral Bearing Pressure = 60 psf/ft
2nd Floor= 0 psf
Garage Slab = 50 psf
Walls= 10 psf
Foundation Wall = 100 psf
Live:
Roof(snow) = 25 psf or
2nd Floor= 0 psf
Garage Slab= 40 psf
Wind: not applicable
Exposure = B Importance Factor, I = 1.0 Category I
Wind Speed,V= 95 mph K„= 1.0
GCp,= 0.56 Kd = 0.85
GCpi = -0.18 K,= 0.90
Height,h,= 15 ft
Design Wind Pressure: Design Load Combo= D+ L+wW
where: pw= q,(GCpf-GCp) w= 1.3
q,= 0.00256 K,K,t Kd V2 I
Therefore:
q,= 17.7 psf
pw= 13.1 psf
Factored Wind Pressure, p'. = 17.0 psf
Page 5 of 11
• Date: 18-Aug-14
STARK G W RamJack West- Retaining Wall Bracing Designed by: Nos
FOUNDATIONS C 7005 SW Ventura Drive
w Newberg,OR
CL
Job No.: 14.034.RAM
Helical Pier Design-Well Tie-back
?...... . tk; -= 600 17t-- ' 9 - 4-0' Tvf
f, - o.5 C4o • `1 - Zq-' ,
Lk.)Z = (40,-s .+ .- ,...V- .. 4 = 3(.,c9 'Pt_.
1 F = 34 d - 1 ' 32401/
z.
- i
�A c - jet' e 4- thki ;
4' �Co�C' = v.. 66044- (lke2 t.�_ cameo
T
.f� = 2Z�CP g6/ eosv = 2(e i (c,�),UGc ,�
Tx_x . d uE I gr = Quist- /
QUIT ^ L fQ v 2, 4Gc
("1- '--=- Q r / �k ot,et r Li , 0 Z 4 B'S'c
1 `
;
STARK
FOUNDATION`
4001 MAIN STREET,SUITE 305
VANCOUVER WA 98663
P 360 566 7343
E starkdcstarkldo corn
LEGEND
10K< INDICATES HELICAL
T1E-BACK & UNFACTORED
DESIGN LOAD (KIPS)
0
N
INDICATES CRACK
IN WALL (TYP)
22.2K<
•
22.2K< - \
ry
22.2K<
0
N
O
N
E) SLAB ON
GRADE
OPARTIAL FOUNDATION REPAIR PLAN
Page 7 of 11
e :Se____
STARK
FOUNDATIONS
4001 MAIN STREET,SUITE 305
VANCOUVER WA 98663
P 360.566 7343
E starkd @starkidn corn
1 1/2'0 X 18' ASTM A36
THRD'D ROD W/ WEDGE WASHER
3/8'0 X 0.19' WALL
(Fy= 65 KSI, Fu = 80 KSI)
W/ (2) 3/4'0 SAE J429
GRADE 8 THRU BOLTS
N
ta-
ALLOWABLE TENSION
n
(E) coNC WALL 27.9K (20'ANGLE)
27.6K (30'ANGLE)
20' TIP EMBED MIN
/ .X8.5 X S-0'
10'0 HOLE W/ (2) 3/4'0 THR'D RODS W/
GROUT WI NON-SHRINK 1r SIMPSON SET EPDXY (EMBED 6')
GROUT A-g-(N) HELICAL TIE-BACK ASSEMBLY a
W/8' AND 10' HELIX PLATE 1
(RAMJACK PN: 4550.78) +
N If
E) CONC STAIR r'
if ru c.Aikt
ilWi:
NOTE: RECOGNIZED BY ICC-ES
IN ESR-1854
1. SPECIAL INSPECTION OF HEUCAL ANCHOR INSTALLATION & EPDXY BOLTS
IS REQUIRED.
2. PROOF TEST (1) HEUCAL TIE-BACK UP TO 150%OF THE DESIGN LOAD.
THE 150% LOAD SHALL BE HELD FOR (5) MINUTES AND THE DISPLACEMENT
MONITORED. IF THE TOTAL DISPLACEMENT IS LESS THAN 1/8', THE HELICAL
TIE-BACK MAY BE CONSIDERED SUCCESSFUL
DESIGN AXIAL LOAD = 22.2 KIPS WORKING / 52.4 KIPS ULTIMATE
O2
TYPICAL WALL TIE-BACK DETAIL
.. . ,m
Page 8 of 11
Z ICC EVALUATION
SERVICE Most Widely Accepted and Trusted
ICC-ES Evaluation Report ESR-1854*
Reissued December 1, 2012
This report is subject to renewal February 1, 2015.
www.icc-es.org ( (800)423-6587 I (562)699-0543 A Subsidiary of the International Code Council®
DIVISION: 31 00 00—EARTHWORK 27/8- or 31/2-inch-outside-diameter (73 or 89 mm) steel pipe
Section: 31 63 00—Bored Plies having a nominal shaft thickness of 0.217 or 0.254 inch,
respectively. Helical-shaped discs, welded to the pipe,
REPORT HOLDER: advance the helical piles into the soil when the pile is
rotated. The helical discs (plates) are 8, 10, 12 or
GREGORY ENTERPRISES, INC. 14 inches (203, 254, 305 or 356 mm) in diameter, and are
13655 COUNTY ROAD 1570 cut from 318-inch- or 1/2-inch-thick (9.5 or 12.7 mm) steel
ADA, OKLAHOMA 74820 plate. The helical plates are pressed, using a hydraulic
(580)332-9980 press and die, to achieve a 3-inch (76 mm) pitch, and are
www.ramjack.com then shop-welded to the helical lead shaft. Figure 1
steve@ramlack.com illustrates a typical helical pile. The extensions have shafts
similar to the lead sections, except without the helical
ADDITIONAL LISTEE: plates. The helical pile lead sections and extensions are
connected together by using an internal threaded pin and
RAM JACK MANUFACTURING, LLC box system that consists of a box shop-welded into the
13655 COUNTY ROAD 1570 trailing end of the helical lead or extension sections. Each
ADA, OKLAHOMA 74820 extension consists of a threaded pin and box on opposing
ends. Figure 2 illustrates the helical pin and box
EVALUATION SUBJECT: connections. The lead shafts and extensions are coated
with a polyethylene copolymer coating complying with the
RAM JACKS HELICAL FOUNDATION & DRIVEN ICC-ES Acceptance Criteria for Corrosion Protection of
FOUNDATION SYSTEMS Steel Foundation Systems Using Polymer (EAA) Coatings
(AC228), and having a minimum coating thickness of
1.0 EVALUATION SCOPE 18 mils (0.46 mm) as described in the approved quality
Compliance with the following codes: documentation.
2012, 2009 and 2006 International Building Code(IBC) 3.2.2 Hydraulically Driven Pile System—Pilings,
Properties evaluated: Connectors, Starter, and Guide Sleeve: The pilings
consist of 27/8-inch-outside-diameter (73 mm) pipe having a
Structural and geotechnical nominal shaft thickness of 0.217 inch, in either 3-, 5- or 7-
2.0 USES foot-long (914, 1524, or 2134 mm) sections. Connectors
used to connect the pilings together are 12-inch-long
Ram Jacke Foundation Systems include a helical pile
system and a hydraulically driven steel piling system. The (305 mm), 2%-inch-outside-diameter(60.3 mm)pipe having
helical pile system is used to transfer compressive,tension, a nominal shaft thickness of 0.19 inch, shop crimped and
and lateral loads from a new or existing structure to soil inserted in one end of the piling section so that
bearing strata suitable for the applied loads. The approximately 6 inches of the connector extends out of one
hydraulically driven steel piling system is used to transfer end of the piling section. During installation, the subsequent
compressive loads from existing foundations to load-bearing piling section slides over the connector of the previous piling
soil strata that are adequate to support the downward-
section. Figure 3 illustrates a typical piling used in
applied compression loads. Brackets are used to transfer conjunction with a bracket. The starter consists of a 2'/8-
the loads from the building foundation to the helical pile inch-diameter (73 mm) steel pipe Shaving a nominal shaft
system or the hydraulically driven steel piling system. thickness of 0.217 inch, and a 2 /8-inch-outside-diameter
(60.3 mm) pipe having a nominal shaft thickness of 0.19-
3.0 DESCRIPTION inch, which is shop crimped and inserted in one end of the
3.1 General: piling section so that approximately 6 inches of the
The Ram Jack® Foundation Systems consist of either connector extends out of one end of the piling section. A
helical piles or hydraulically driven steel pilings connected to 2/8-inch diameter-by- /8-inch-thick (3.2 mm by 60.3 mm)
ASTM A36 steel soil plug is shop-welded inside the
bearing foundation of a structure. 27/8-inch (73 mm) starter section against the 23/8-inch
60.3 mm) connector. The starter section is jobsite-installed
3.2 System Components: into the end of the initial piling and leads the piling in order
3.2.1 Helical Pile System—Lead Shafts with Helical o expand the soil away from the piling with a
Plates and Extensions: The lead shafts consist of either 1/2-inch-outside-diameter (89 mm) steel ring having a
'•evl ed eb ary 2014
ICC-FS Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed T•D,
as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as
to any finding or other matter in this report,or as to any product covered by the report.
Copyright C 2014 Pagel of 14
CJR-i oo4 I Most Widely Accepted and Trusted Page 8 of 14
loaded helical piles is less than three times the 5.13 Settlement of the helical pile is outside the scope of
diameter of the largest helix plate at the depth of this evaluation report and must be determined by a
bearing. An analysis prepared by a registered design registered design professional as required in 2012 and
professional must also be submitted where the center- 2009 IBC Section 1810.2.3 and 2006 IBC 1808.2.12.
to-center spacing of laterally loaded helical piles is less 5.14 The interaction between the hydraulically driven pile
than eight times the least horizontal dimension of the
pile shaft at the ground surface. Spacing between system and the soil is outside the scope of this report.
helical plates must not be less than 3D, where D is the 5.15 The Ram Jacks Foundation Systems are manufactured
diameter of the largest helical plate measured from the at the Ram Jack Manufacturing, LLC, facility located in
edge of the helical plate to the edge of the helical plate Ada, Oklahoma, under a quality control program with
of the adjacent helical pile; or 4D,where the spacing is inspections by ICC-ES.
measured from the center-to-center of the adjacent 6.0 EVIDENCE SUBMITTED
helical pile plates.
Data in accordance with the ICC-ES Acceptance Criteria for
5.12 Connection of the side load bracket or the repair Helical Foundation Systems and Devices (AC358), dated
bracket as it relates to seismic forces and the June 2013.
provisions found in 2012 and 2009 IBC Sections 7 0 IDENTIFICATION
1810.3.11.1 and 1810.3.6.1 and 2006 IBC Section
1808.2.23.1, and for all buildings under 2012 and 2009 The Ram Jacks Helical Foundation & Driven Foundation
IBC Section 1810.3.6 (second paragraph) and 2006 System components are identified by a tag or label bearing
IBC Section 1808.2.7, are outside the scope of this the Ram Jack logo, the name and address of Gregory
evaluation report. Compliance must be addressed by Enterprises, Inc., the catalog number, the product
the registered design professional for each site, and description, and the evaluation report number(ESR-1854).
the work of the design professional is subject to
approval by the code official.
TABLE 1—FOUNDATION STRENGTH RATINGS OF BRACKETS'
PRODUCT DESCRIPTION PILING DIAMETER ALLOWABLE CAPACITY
NUMBER (inches) (kips)
Compression Tension Lateral
4021.1 Side load bracket 2'/8 33.651'5 N/A N/A
4021.55 Side load bracket 31/2 55.12'•5 N/A N/A
4038.1 Side load bracket 2'/e 19.701'5 N/A N/A
4039.1 Side load bracket 27/8 32.071'5 N/A N/A
4075.1 New construction 2'/8 See Table 3A See Table 3B 1.4945
4079.1 New construction 27/8 See Table 3A See Table 3B 1.492.5
4076 New construction 3Yz See Table 3A See Table 3B 2.7945
41•3. Slab bracket 27/8 See Table 5 N/A N/A
27.9 @ 20°angle(tension only)`5
4550.2875.1 Tieback assembly 27/a s
27.6 @ 30°angle(tension only)
or : n = .• mm, 1 kip(1000 Ibf)=4.48 kN.
'Load capacity is based on full scale load tests per AC358 with an installed 5'-0 unbraced pile length having a maximum of one coupling per
2012 and 2009 IBC Section 1810.2.1 and 2006 IBC 1808.2.9.2.A 4-foot-long guide sleeve must be installed at the top of the shaft as required
in Figures 3,5 and 7.Side load bracket must be concentrically loaded. Side load bracket plate must be fully engaged with bottom of concrete
foundation. Only localized limit states such as mechanical strength of steel components and concrete bearing have been evaluated.
'Lateral load capacity is based on lateral load tests performed in firm day soil per Section 4.1.1 of this report For any other soil condition,the
lateral capacity of the pile must be determined by a registered design professional. The bracket must be installed with minimum embedment
of 3 inches when measured from the bottom of the concrete foundation to the bottom of the bracket plate. Minimum width of footing must be
12 inches.
'The capacities listed in Table 1 assume the structure is sideway braced per 2012 and 2009 IBC Section 1810.2.2 and 2006 IBC Section
1808.2.5.
`Tieback assemblies must be installed in accordance with Section 4.2.5 of this report. Only localized limit states such as mechanical strength
of steel components and concrete bearing have been evaluated. The tieback assembly must be installed to support a minimum 6-inch thick
concrete wall. Two through bolts are required for connection between bracket sleeve and helical shaft. Bolts must be'/4-inch diameter
complying with ASTM A325 and installed snug-tight with threads excluded.
5The tabulated values are based on installation with normal-weight concrete having a minimum compressive strength of 2500 psi(17.23 MPa).
N/A=not applicable.
ESR-1854 I Most Widely Accepted and Trusted Page 11 of 14
TABLE 5-ALLOWABLE COMPRESSIVE LOAD CAPACITY RATING OF RAM JACK'S#4093 SLAB BRACKET SUPPORTING
MINIMALLY REINFORCED NORMAL WEIGHT CONCRETE SLAB''
(Max.load rating=11.7 kips)
Minimum Area
Concrete of steel
28-day reinforcement In
Compressive Concrete Concrete Slab', Maximum Pile Spacing Pile Load(kip)
Strength,fc Floor Slab A.,mM Live
Depth(t) Load
(psi) (in) (In') (psi) 1 &2 Span 3 Span 1 &2 Span 3 Span
40 4'-10" 5'-5" 2.12 k 2.65 k
44 0.06 50 4'-6" 5'-1" 2.08 k 2.60 k
100 3'-7" 4'-0" 1.99 k 2.49 k
40 5'-8" 6'-4" 3.36 k 4.20 k
54 0.075 50 5'-5" 6'-0" 3.31 k 4.14 k
100 4'-4" 4'-11" 3.15 k 3.94 k
2,500
40 6-6" 7-3" 4.90 k 6.13 k
6 0.09 50 6'-2" 6-11" 4.83 k 6.03 k
100 5'-1" 5'-8" 4.59 k 5.74 k
40 8'-8" 9'-1" 10.61 k 11.70 k
83 0.12 50 8'-3" 8'-9" 10.30 k 11.70 k
100 6-9" T-T 9.34 k 11.67 k
40 5'-1" 5'-8" 2.33 k 2.91 k
44 0.066 50 4'-9" 5'-4" 2.29 k 2.86 k
100 3'-9" 4'-3" 2.19 k 2.73 k
40 6-0" 6'-8" 3.69 k 4.62 k
54 0.082 50 5'-8" 6'-4" 3.64 k 4.54 k
100 4'-T 5'-2- 3.46 k 4.33 k
3,000 40 6-10" T-T 5.39 k 6.73 k
6 0.098 50 6-6" T-3" 5.30 k 6.63 k
100 6-4" 6'-0" 5.05 k 6.31 k
40 9'-1" 9'-2" 11.66 k 11.70 k
83 0.131 50 6-8" 8'-9" 11.31 k 11.70 k
100 7'-1" 7'-7" 10.26 k 11.70 k
For SI: 1 inch=25.4 mm;1 kip(1000 Ibf)=4.48 kN;1 psi=6.89 kPa; 1 psf=47.88 Pa.
'The maximum pile spacing shown are for floor slabs constructed of normal weight concrete(150 pcf)with minimum reinforcement(fy=60 ksi)
'The ACI 318 Section 10.5.1.
The maximum floor slab spans shown assumes the minimum floor slab reinforcement is placed in the center of the slab (t/2). Longer spans
can be achieved if the slab reinforcement is proven to be larger and/or placed below the central line of the floor slab. Structural calculations
must be submitted for approval by a registered design professional for spans greater than those shown for a reinforced floor slab.
'The maximum load rating of the 4093 slab bracket controls the pile spacing.
`The spans and pile loads shown for the 4-inch and 5-inch thick floor slab assumes the floor slab are being placed on a vapor barrier. Per
Section 7.7.1 of ACI 318,the minimum concrete cover required is 11/2 inches.This table should not be used for the 4-inch and 5-inch thick floor
slabs placed directly on soil, where the minimum concrete cover is 3 inches, which places the reinforcement above the neutral axis. Table 7
should be used for the 4 inch and 5 inch thick concrete slab cast directly on soil.
TABLE 6-ALLOWABLE TENSION AND COMPRESSION LOADS FOR HELICAL PLATES(KIPS)
yri rTIr11!*1177r+.TFglIPIIIIPwTT'l'rITITM7'rI1' 711"47_751ww
(Inches) 2'/e 3'A
8 63.29 79.84
10 55.51 66.29
12 39.40 65.74
14 42.07 _ 60.42
For SI: 1 inch=25.4 mm; 1 kip= 1000 lbf=4.45 kN.
'Allowable load values are for helical plates made from 3/e-inch thick steel, except for
the 14-inch diameter plate,which is made from%-inch thick steel.