Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
CRAFTWORK PLUMBING, INC. 7733 SW CIRRUS DRIVE BEAVERTON, OREGON 97008 503-644-8698 CCB# 79666 RESIDENTIAL FIRE SPRINKLER DRAWINGS AND EQUIPMENT SUBMITTAL FOR: SUMMER CREEK TOWNHOMES S.W. MALLOW TERRACE BUILDING 20 LOTS 69/70/71/72/73 TIGARD, OREGON 97223 REVISION 1 LD 06.21.13 TABLE OF CONTENTS: HYDRAULIC CALCULATIONS TYCO LFII SPRINKLERS FIRE PROTECTION SHOP DRAWINGS PREPARED BY: PDQ DESIGN SERVICES 19150 SW OAK STREET ALOHA, OREGON 97007 503-848-5918 T20/2-079299r02a1a - � 3©� M 6 02-(20.36V tit s r ao - C6 c 3 MsT0Ia-o7513o CRAFTWORK PLUMBING,INC. 7737 S.W.CIRRUS DRIVE BEAVERTON,OREGON 97008 (503)644-8698 HYDRAULIC CALCULATIONS FOR SUMMER CREEK TOWNHOMES S.W.MALLOW TERRACE BUILDING 20 LOT 71 TIGARD,OREGON 97223 REVISION 1 06.24.13 --DESIGN DATA-- OCCUPANCY CLASSIFICATION: RESIDENTIAL NFPA 13-D WET SYSTEM DENSITY: N/A AREA OF APPLICATION: 2 heads COVERAGE PER SPRINKLER: 256 sq.ft.(max.) NUMBER OF SPRINKLERS CALCULATED: 2 heads TOTAL SPRINKLER WATER FLOW REQUIRED: 26.3 gpm TOTAL WATER REQUIRED: 26.3 gpm FLOW&PRESSURE(at point of connection): 26.3 gpm @ 76.5 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF DESIGNER: M.S.Aldridge AUTHORITY HAVING JURISDICTION: Local Authority SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 C:\HASSDATA\SUMMERCREEK20B-R1.SDF JOB TITLE: SUMMERCREEK BLDG 20 UNIT eS NFPA 13D 2 HDS K=4. 9 WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) 12 88.0 87. 9 100.0 88.0 26.3 76.5 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 26.3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 101 27.0 K= 4. 90 7.3 13.2 102 27.0 K= 4.90 7.0 13.0 1 28.0 - - - - 9.0 - - - 1A 28.0 - - - - 10.9 - - - 2 28.0 - - - - 9.0 - - - 3 28.0 - - - - 13. 9 - - - 4 28.0 - - - - 18.5 - - - 5 17.5 - - - - 30.3 - - - 5A 17.5 - - - - 34.8 - - - 5B 17.5 - - - - 40. 8 - - - 6 17.5 - - - - 44. 6 - - - 7 8.5 - - - - 55. 1 - - - 8 8.5 - - - - 59.4 - - - 9 1.0 - - - - 63.7 - - - 9A 1.0 - - - - 64.7 - - - 10 -4.0 - - - - 69. 4 - - - 11 -4.0 - - - - 74.4 - - - 12 -4.0 SOURCE 76.5 26.3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 C:\HASSDATA\SUMMERCREEK20B-R1.SDF JOB TITLE: SUMMERCREEK BLDG 20 UNIT 8 NFPA 13D 2 HDS K=4.9 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13.2 0.875 PL 1.00 PF 2.1 101 27.0 4.9 7.3 13.2 7 .1 150 FTG ET PE -0.4 1 28.0 0.0 9.0 0.0 0.097 TL 22.00 PV Pipe: 2 1.8 0.875 PL 13.00 PF 0. 1 1 28.0 0.0 9.0 0.0 0.9 150 FTG E PE 0. 0 2 28.0 0.0 9.0 0.0 0.002 TL 23. 00 PV Pipe: 3 -11.2 0.875 PL 17.00 PF 1. 9 2 28.0 0.0 9.0 0.0 6.0 150 FTG E PE 0. 0 1A 28.0 0.0 10.9 0.0 0.072 TL 27.00 PV Pipe: 4 -13.0 0.875 PL 4.00 PF 2.3 102 27.0 4.9 7.0 13.0 6.9 150 FTG ET PE -0. 4 2 28.0 0.0 9.0 0.0 0.094 TL 25.00 PV Pipe: 5 -15.0 0.875 PL 19.00 PF 4 . 9 1 28.0 0.0 9.0 0.0 8 .0 150 FTG ET PE 0.0 3 28.0 0.0 13.9 0.0 0.122 TL 40.00 PV Pipe: 6 -11.2 0.875 PL 21.00 PF 3.0 1A 28.0 0.0 10.9 0.0 6.0 150 FTG ET PE 0.0 3 28.0 0.0 13.9 0.0 0.072 TL 42.00 PV Pipe: 7 -26.2 0.875 PL 3.50 PF 4. 6 3 28.0 0.0 13.9 0.0 14.0 150 FTG E PE 0.0 4 28.0 0.0 18.5 0.0 0.344 TL 13.50 PV Pipe: 8 -26.2 0.875 PL 11.00 PF 7.2 4 28.0 0.0 18.5 0.0 14 .0 150 FTG E PE 4.5 5 17.5 0.0 30.3 0.0 0.344 TL 21.00 PV Pipe: 9 -26.2 0.875 PL 2.00 PF 4. 5 5 17.5 0.0 30.3 0.0 14 .0 150 FTG T PE 0.0 5A 17.5 0.0 34.8 0.0 0.344 TL 13.00 PV Pipe: 10 -12.7 0.875 PL 36.00 PF 6.0 5A 17.5 0.0 34.8 0.0 6.8 150 FTG 2ET PE 0.0 5B 17.5 0.0 40.8 0.0 0.090 TL 67.00 PV Pipe: 10A -13.5 0.875 PL 29.00 PF 6.0 5A 17.5 0.0 34.8 0.0 7 .2 150 FTG 2ET PE 0.0 5B 17.5 0.0 40.8 0.0 0.101 TL 60.00 PV Pipe: 11 -26.2 0.875 PL 1.00 PF 3.8 5B 17.5 0.0 40.8 0.0 14.0 150 FTG E PE 0.0 6 17.5 0.0 44. 6 0.0 0.344 TL 11.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 C:\HASSDATA\SUMMERCREEK20B-R1.SDF JOB TITLE: SUMMERCREEK BLDG 20 UNIT 6 NFPA 13D 2 HDS K=4.9 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 12 -26.2 0.875 PL 9.00 PF 6.5 6 17.5 0.0 44.6 0.0 14 .0 150 FTG E PE 3. 9 7 8.5 0.0 55.1 0.0 0.344 TL 19.00 PV Pipe: 13 -26.2 1.075 PL 24.00 PF 4 .3 7 8.5 0.0 55.1 0.0 9.3 150 FTG 3E PE 0.0 8 8.5 0.0 59.4 0.0 0.126 TL 34.21 PV Pipe: 14 -26.2 1.070 PL 8.50 PF 1.1 8 8.5 0.0 59.4 0.0 9.4 150 FTG ---- PE 3.2 9 1. 0 0. 0 63.7 0.0 0.129 TL 8.50 PV Pipe: 15 FIXED PRESSURE LOSS DEVICE 9A 1.0 0.0 64.7 0.0 1.0 psi, 26.2 gpm 9 1.0 0.0 63.7 0.0 Pipe: 16 -26.2 1.125 PL 20.00 PF 2.5 9A 1.0 0.0 64.7 0.0 8.5 150 FTG E PE 2.2 10 -4.0 0.0 69.4 0.0 0.101 TL 24.25 PV Pipe: 17 FIXED PRESSURE LOSS DEVICE 11 -4 .0 0.0 74.4 0.0 5.0 psi, 26.2 gpm 10 -4 .0 0.0 69.4 0.0 Pipe: 18 -26.3 1.125 PL 10.00 PF 2.1 11 -4.0 0.0 74.4 0.0 8.5 150 FTG T PE 0.0 12 -4.0 SRCE 76.5 (N/A) 0.101 TL 20. 62 PV NOTES: (1) Calculations were performed by the HASS 7.4 computer program under license no. 38040986 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.005 gpm and a maximum imbalance at any node of 0. 090 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14 .0 ft/sec at pipe 9. (4) PIPE FITTINGS TABLE Pipe Table Name: PEX.PIP SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 C:\HASSDATA\SUMMERCREEK20B-R1.SDF JOB TITLE: SUMMERCREEK BLDG 20 UNIT 6 NFPA 13D 2 HDS K=4.9 PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkViv BfyVly GatVly AlmChk DPV1v NPTee 1.075 2.25 5. 63 2.25 5.63 6.76 1.13 11.27 11.27 5.63 1. 125 2.81 7.03 2.81 7.03 8.44 1.41 14.06 14.06 7.03 PAGE: A MATERIAL: PEX HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T C R B G A D N Ell Tee COUP TEE-RU 0.875 10.00 11.00 1.30 2.30 0.00 0.00 0.00 0.00 0.00 1.070 12.00 13.00 2.00 3.50 0.00 0.00 0.00 0.00 0.00 0 ro WATER SUPPLY ANALYSIS 100.0 Static: 88.00 psi Resid: 87.90 psi Flow: 100.0 gpm H N LEGEND 1 1 0 Available pressure X 87.99 psi @ 26.3 gpm 2 Required pressure n A80.02 \ 76.45 psi @ 26.3 gpm U M % G z E 0 [TJ x P 60.0 _ R c -C E H H S H M t U z o ro � 40.0 _ n I- •• c P N w S x i d H t� 20.0 icn N U] H II x • M .o r1 0 tj 0.0 — co, xro I-■ • ,o cnm -14.7 200 300 400 500 600 700 800 900 1000 FLOW (GPM) GO Contacts v+avv+.tyco-fire.com Contacts Rapid Response Series LFII Residential 4.9 K-factor Concealed Pendent Sprinklers, Flat Plate Wet Pipe and Dry Pipe Systems General The Series[Ell Residential Concealed Pencient Sprinklers(TY3596)has been Description designed with heat sensitivity and wa- ter ter distribution characteristics proven Al glik The TYCO RAPID RESPONSE Se- to help in the control of residential fires ries[Ell Residential 4.9 K-factor Con- and to improve the chance for occu- 1 .r... , . cealed Pendent Sprinklers (TY3596) pants to escape or be evacuated. 7 it are decorative, fast response, fus- The Series LEO Residential Concealed - ible solder sprinklers designed for use Pendent Sprinklers (TY3596) are in residential occupancies such as shipped with a Disposable Protective homes, apartrrents, dormitories, and Cap. The Protective Cap is temporar- hotels. ily removed for installation, and then The cover plate assembly conceals it can be replaced to help protect the the sprinkler operating components sprinkler while the ceiling is being in- above the ceiling.The flat profile of the stalled or finished.The tip of the Pro- cover plate provides the optimum acs- tective Cap can also be used to mark thetically appealing sprinkler design. the center of the ceiling hole into Alas- NOTICE In addition, the concealed design of ter board, ceiling tiles, etc. by gently the Series LEli Residential Concealed pushing the ceiling product against The Series LFIi Residential Con- Pendent Sprinklers(TY3596) provides the Protective Cap. When the ceiling cealed Pendent Sprinklers (TY3596) 1/2 inch(12,7 men)vertical adjustment. installation is complete the Protective described herein must be installed This adjustment provides a measure of Cap is removed and the Cover Plate and maintained in compliance with flexibility when cutting fixed sprinkler Assembly installed. this document and with the applica- drops. ble standards of the National Fire Pro- The Series LFII Residential Concealed Dry Pipe System Application tection Association, in addition to the Sprinklers are intended for use in the The Series LFII Residential Concealed standards of any authorities having ju- Sprinklers scenarios: Pendent Sprinklers offers a laboratory risdiction. Failure to do so may impair following approved option for designing dry pipe the performance of these devices. • wet and dry pipe residential sprin- residential sprinkler systems,whereas, The owner is responsible for maintain- kler systems for one-and two-fam- most residential sprinklers are labora- ing their fire protection system and de- ily dwellings and mobile homes per tory approved for wet systems only. vices in proper operating condition. NFPA 13D Through extensive testing,it has been The installing contractor or sprinkler • wet and dry pipe residential sprin- determined that the number of design manufacturer should be contacted Kier systems for residential occu- sprinklers (hydraulic design are for with any questions. pancies up to and inducing four the Series LFII Residential Concealed stories in height per NFPA 13R Percent Sprinklers(TY3596)need not be increased over the number of de- Sprinkler • wet and dry pipe sprinkler systems sign sprinklers(hydraulic design area) Identification for the residential portions of any as specified for wet pipe sprinkler sys- occupancy per NFPA 13 terns, as is accustomed for density' area sprinkler systems designed per Number NFPA 13. TY3596 Consequently,the Series LFII Residen- tial Concealed Pendent Sprinklers of- IMPORTANT fer the features of non-water filled pipe Always refer to Technical Data in addition to not having to increase Sheet TFP700 for the `INSTALLER the number of design sprinklers (hy- WARNING" that provides cautions draulic design area for systems de- with respect to handling and instal- signed to NFPA 13, 13D,or 13R. Non- lation of sprinkler systems and corn- water filled pipe will permit options for patents. Improver handling and in- areas sensitive to freezing, stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 APRIL 2013 TFP442 TFP442 Page 2 of 6 BODY I SEALING WRENCH (1/2"NPT) ASSEMBLY RECESS 1 It - ' _Z�% SPRINKLER•CAP �1��f 1�',��; �` WRENCHING AREA SADDLE 1 1'�� 1� !; SUPPORT i III Fiiii:iii COMPRESSION W TO ENSURE CUP WITH I 1 i Aulni 1 ( ENGAGEMENT ROLL FORMED l WITH SPRINKLER THREADS I WRENCHING AREA C LEVER FIGURE 2 GUIDE 1 -—_. ��� I W-TYPE 18 PIN •. "..•■•■•.....r;• SPRINKLER WRENCH SOLDER LINK ELEMENT GUIDE PIN HOUSING i DEFLECTOR (OPERATED DEFLECTOR - '---J POSITION) SPRINKLER/SUPPORT CUP ASSEMBLY THREAD INTO j j RETAINER SUPPORT i WITH THREAD CUP UNTIL J DIMPLES MOUNTING SURFACE IS J FLUSH WITH CEILING EJECTION SPRING SOLDER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) 2-1/2'DIA SPRINKLER- (63,5 m) —` 1/2'(12,7 mm) FACE OF SUPPORT CUP 1/2' \ THREADED SPRINKLER ASSEMBLY NPT Il- m ADJUSTMENT FITTING OPERATED may_` ,— SPRINKLER �. • '� 1-7/8't1/4" COVER _ — (47,6 mm PLATE �� w 1/S'GAP t6,4 mm) RETAINER j �w I I (3,2 mm) M-= `41mimi ---4 i i ..1- 7/8'(22.2 mm) I I COVER- SPRINKLER- T MOUNTING RETAINER SUPPORT CUP 3/16' SURFACE \ 1-1/S"(25,6 mm) I∎�■ ASSEMBLY ASSEMBLY (4,8 mm) ■ } 3-3/16'DIA DISPOSABLE DEFLECTOR IN (81,0 mm) ^~ TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR TFP442 Page 3 of 6 Technical Design Criteria Dry Pipe System Water Delivery g When using the Series LFII Residen- Data The TYCO RAPID RESPONSE Series fiat Concealed Pendent Sprinklers LAI Residential Concealed Pendent (TY3596)in dry pipe sprinkler systems, Approvals: Sprinklers (TY3596)are UL and C-UL the time for water delivery mast not ex- UL and C-UL Listed.NYC Approved Listed for installation in accordance ceed 15 seconds for the most remote under MEA 44-03-E-2 with this section. operating sprinkler. NSF Certified to NSF/ANSI 61 The TYCO RAPID RESPONSE Series Note: When conditions exist that are Obstruction to Water Distribution outside the scope of the provided cri- Sprinklers are to be located in accor- LFII Residential Concealed Pendent feria,refer to the Residential Sprinkler dance with the obstruction rules of Sprinklers are only listed with the Se- Design Guide TFP490 for the rnanu- NFPA 13D, 13R,and 13 as applicable ries LFII Concealed Cover Plates hav- facturer's recommendations that may for residential sprinklers as well as with ing a factory applied finish. be acceptable to the authority having the obstruction criteria described with- Maximum Working Pressure: (urisdiction. in the Technical Data Sheet TFP490. 175 psi(12.1 bar) Syr es Operational Sensitivity. The sprin- Discharge Coefficient: Per ttw ULPListing, wet pipe and dry klers are to be installed relative to the K-4.9 GPM/psi'2(70.6 LPM/bar 12) pipe systems may be utilized. Per the ceiling mounting surface as shown in Temperature Rating: C-UL Listing, only wet pipe systems Figure 3. 160"F(71""C)Sprinkler with may be utilized. Sprinkler Spacing. The minimum 139"F(59'C)Cover Plate Refer to Technical Data Sheet TFP485 spacing between sprinklers is 8 feet Vertical Adjustment: about the use of residential sprinklers (2,4 m). The maximum spacing be- 1/2 inch(12,7 min) in residential dry pipe systems. tween sprinklers cannot exceed the Finishes: length of the coverage area(Ref.Table Refer to Ordering Procedure section Ceiling Types A or B) being hydraulically calculated Smooth flat horizontal, or beamed, or (e.g., maximum 12 feet for a 12 ft.x 12 Physical Characteristics: sloped, in accordance with the 2013 ft.coverage area,or 20 feet for a 20 ft. Body Brass Edition of NFPA 13D, 13R, or 13 as x 20 ft.coverage area). Cap Bronze applicable. Saddle Brass The Series LFII must not be used in Sealing Assembly Beryllium Hydraulic Design applications where the air pressure Nickel w/TEFLON (NFPA 13D and 13R) above the ceiling is greater than that Soldered Link Haloes Nickel For systems designed to NFPA 13D below. Down drafts through the Sup- Lever Bronze or NFPA 13R, the minimum required port Cup could delay sprinkler opera- Compression Screw Brass sprinkler flow rates are given in Ta- tion in a fire situation. Deflector Copper or Brass bles A and B as a function of tem- Guide Pin Housing Bronze perature rating and the maximum Guide Pins Stainless Steel allowable coverage areas. The sprin- or Bronze kler flow rate is the nlinirnum re- Support Cup Steel quired discharge from each of the Cover Plate Copper total number of"design sprinklers"as Retainer Brass specified in NFPA 13D or NFPA 13R. Cover Rate Ejection Spring The number of "design sprinklers" Stainless Steel specified in NFPA 13D and 13R for wet pipe systems is to be applied when Operation designing dry pipe systems. When exposed to heat from a fire,the Hydraulic Design Cover Plate, which is normally sd- (NFPA 13) dered to the Support Cup at three For systems designed to NFPA 13,the points, falls away to expose the Sprin- number of design sprinklers is to be kler Assembly. At this point the De- the four rrost hydraulically demanding flector supported by the Arms drops sprinklers.The minimum required dis- down to its operated position.The fus- charge from each of the four sprinklers ible link of the Sprinkler Assembly is is to be the greater of the following: comprised of two link halves that are • flow rates given in Tables A soldered together with a thin layer of g solder. When the rated temperature is and B as a function of temperature reached, the solder melts and the two rating and the maximum allowable link halves separate allowing the sprin- coverage area. kler to activate and flow water. • A minimum discharge of 0.1 gpm/ ft2 over the"design area"comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. The number of "design sprinklers" specified in NFPA 13 for wet pipe sys- tems is to be applied when designing dry pipe systems. TFP442 Page 4 of 6 WET PIPE SYSTEM Maximum Minimum Flow and Residual Pressuretb•ef Maximum Coverage Spacing Ordinary Temp.Rating Minimum Area 160`F(71`C) Ft.x Ft. Ft. Deflector to Installation Spacing (m x m) (m) Flow Pressure Ceiling Type Ft. GPM PSI (m) (L/min) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,46) Ceilings 7/8 to 1-1/8 14 x 14 14 13 7.0 inches (4,3 x 4,3) (4,3) (49,2) (0.48) Beamed 16 x 16 16 13 7.0 Ceilings per 8 13D (4,9 x 4,9) (4.9) (49,2) (0,48) N13R,or 1FPA or 1 3.or Concealed (2.4) Installed in 18 x 18 16 17 12.0 beam (5,5 x 5,5) (5,5) (64,3) (0,83) 7/8 to 1-1/6 inches below 20 x 20 20 20 16.7 bottom of (6,1 x 6,1) (6,1) (75,7) (1,15) beam (a) For coverage area dimensions less than or between those indicated.use the ntininum required flow for the next highest coverage area for which hjdraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler The associated residual pressures are calculated using the nominal K-f actor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 01 ggnftz over the design area of the.flow in accordance with the criteria in this table nest be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flow and Residual Pressurefb,r1 Maximum Coverage Spacing Ordinary Temp.Rating AreaoI Sp 160`F(71`C) Minimum Ft.x Ft. Ft. Deflector to Installation Spacing (m x m) (m) Flow Pressure Ceiling Type Ft. GPM PS1 (m) (L/min) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 14 8.2 inches (4,3 x 4,3) (4,3) (53,0) (0,57) Beamed 16 x 16 16 15 9.4 Ceilings per (4,9 x 4,9) (4,9) (56,6) (0,65) NFPA 13D or Concealed {2.4 i 13R,or 13. Installed in 18 x 18 18 18 13.5 beam (5,5 x 5,5) (5,5) (68,1) (0,93) 7/6 to 1-1/6 inches below 20 x 20 20 21 18.4 bottom of (6,1 x 6,1) (6.1) (79,5) (1,27) beans (a) For coverage area dimensions less than or between those indicate&we the rninimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPf 1)from cads sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section_ (c) For NFPA 13 residential applications,the greater of 0.1 gprnit,over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT(TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TFP442 Page 5 of 6 Installation Step 6.Screw on the Cover Plate As- Care must be exercised to amid dam- sembly until its flange comes in con- age-before,during, and after installa- The TYCO RAPID RESPONSE Series tact with the ceiling. tion.Sprinklers darreiged by dropping, LFII Residential Concealed Pendent Do not continue to screw on the Cover striking, wrench twist/slippage, or the Sprinklers(TY3596) must be installed Plate Assembly such that it lifts a cell- like,must be replaced. in accordance with this section. ing panel out of its normal position. The owner is responsible for the in- General Instructions If the Cover Plate Assembly cannot spection, testing, and maintenance of Damage to the fusible Link Assembly be engaged with the Mounting Cup their fire protection system and devic- during installation can be added by or the Cover Plate Assembly cannot es in compliance with this document, handling the sprinkler by the support be engaged sufficiently to contact the as well as with the applicable stan- cup only(i.e.,do not apply pressure to ceiling, the Sprinkler Fitting mist be cards of the National Fire Protection the fusible Link Assembly). repositioned. Association(e.g.,NFPA 25),in addition to the standards of any other authori- A 1/2 inch NPT sprinkler joint should ties having jurisdiction. The installing be obtained with a minimum to maxi- Care and contractor or sprinkler manufacturer mum torque of 7 to 14 ft.-lbs. (9,5 to should be contacted relative to any 19,0 Nm). Higher levels of torque may Maintenance questions. distort the sprinkler inlet with conse- quent leakage or impairment of the The TYCO RAPID RESPONSE Se- The owner must assure that the sprin- sprinkler. ries LFII Residential Concealed Pen- klers are not used for hanging any ob- dent not attempt to compensate for in- dent Sprinklers (TY3596) must jects and that the sprinklers are only sufficient o not attempt rcpt to cot in the Cover be maintained and serviced in cleaned by means of gently dusting non- Plate/Retainer Assembly in by under-or accordance with this section with a feather duster; otherwise, non- over-tightening the Sprinkler. Readjust Before closing a fire protection system operation in do may re of a lt. or inad the position of the sprinkler fitting to main control valve for maintenance vertent operation may result. suit. work on the fire protection system Automatic sprinkler systems should be Step 1.The sprinkler must only be in- which it controls, permission to shut inspected,tested,and maintained by a Step The in the sprinkler must st nand down the affected fire protection sys- qualified Inspection Service in accor- s a ledenet centerline of the position oi sprinkler per- tern must be obtained from the prop- dance with local requirements and/or with the elc nt the mounting of the s rinkler er authorities and all personnel who national codes. may be affected by this action must be Step 2.Remove the Protective Cap. notified. Step 3. With pipe thread sealant ap- Absence of a Cover Plate may de- plied to the pipe threads,and using the lay the sprinkler operation in a fire W-Type 18 Wrench shown in Figure 2, situation. install and tighten the Sprinkler/Sup- When properly installed, there is a port Cup Assembly into the fitting.The nominal 1/8 inch(3,2 mm)air gap be- W-Type 18 Wrench will accept a 1/2 tween the lip of the Corer Plate and inch ratchet drive. the ceiling,as shown in Figure 3.This Step 4.Replace the Protective Cap by air gap is necessary for proper op- pushing it upwards until it bottoms out oration of the sprinkler by allowing against the Support Cup.The Protec- heat flow from a fire to pass below the Cap helps prevent damage to the and above the Cover Plate to help as- Deflector and Guide Pins during cell- sure appropriate release of the Cover ing installation and/or during applica- Plate in a fire situation. If the ceiling is tion of the finish coating of the cell- to be repainted after the installation of ing. It may also be used to locate the the Sprinkler, care must be exercised center of the clearance hole by gen- to ensure that the new paint does not tly pushing the ceiling material against seal off any of the air gap. the center point of the Cap. Factory painted Cover Plates must Note: As long as the protective Cap not be repainted. They should be re- remains in place,the system is consid- placed,if necessary, by factory paint- ered to be"Out Of Service". ed units. Non-factory applied paint Step 5. After the ceiling has been may adversely delay or prevent sprin- kler with the 2-1/2 inch(63 mm) kler operation in the event of a fire. dianeter clearance hole and in prep- Do not pull the Cover Plate relative to aration for installing the Cover Plate the Enclosure.Separation may result. Assembly, remove and discard the Sprinklers which are found to be leak- Protective Cap,and verify that the De- ing or exhibiting visible signs of corro- flector moves up and down freely. sion must be replaced. If the Sprinkler has been damaged and Automatic sprinklers mist never be the Deflector does not move up and painted, plated, coated, or otherwise down freely, replace the entire Sprin- altered after leaving the factory.Modi- kler assembly.Do not attempt to modi- fled or over heated sprinklers must be fy or repair a damaged sprinkler. replaced. TFP442 Page 6 of 6 Ordering Procedure When placing an order, indicate the full product name. Contact your local distributor for availability. Sprinkler Assembly: Series LFII (TY3596). K=4.9, Resi- dential Concealed Pendent Sprin- kler without Cover Rate Assembly, P/N 51-112-1-160 Cover Plate Assembly: Cover Plate Assently having a(spec- ify)finish for the Series LFII (TY3596). K=4.9,Residential Concealed Pendent Sprinkler.P/N(specify) Ivory(RAL1015) P/N 56-202-0-135 Beige(RAL1001) P/N 56-202-2-135 Pure White(b)(RAL9010) PIN 56-202-3-135 Signal White(a)(RAL9003). PIN 56-202-4-135 Grey White(RAL9002) P/N 56-202-5-135 Brown(RAL8028) P,N 56-202-6-135 Black(RAL9005) P/N 56-202-7-135 Brushed Brass P/N 56-202-8-135 Brushed Chrome P/N 56-202-9-135 Custom Paint PM 56-202-X-135 (a)Previously known as Bright White. (b)East em Hemisphere sales only. Note:All Custom Co.er Prates are painted us- ing Sherwin Williams Interior Latex Paint Contact TYCO Customer Service with any questions re- la ted to custom orders. Sprinkler Wrench: Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 GLOBAL HEADQUARTERS 11400 Penn brook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2012 Tyco Fire Products,LP. All rights reserved. NCO TEFLON is trademark of The DuPont Corporation. MToi — cep ac Pae Page 6 of 6 -� /�1 S I G2 I -4rbi (J Ordering ) g(17 .-c)--0 36 Procedure M When placing an order, indicate oare the full product for blity. your local INS �,gQ distributor for availability. ia -66 Sprinkler Assembly: Series LFII (TY3596), K=4.9, Resi- _Od 3 03 dential Concealed Pendent Sprin- kler wi1h2ut Cover Plate Assembly, P/N /' /) �TL% P/N 51-112-1-160 I ✓/(I J Cover Plate Assembly: Cover Plate Assembly havi (spec- ify)finish for the Series LED 3596), K=• • ' '- Conceal ndent er,P/N s. Ivory(RAL1015) PIN 56 0-135 Beige(RAL1001) •/N 56- -135 Pure White(b)(RAL9010) IN 56-2 135 Signal White(a)(PALOO t" •/N 56-2 135 Grey White(RAL9002).. P/N 56-20 35 Brawn(RAL8028) PIN 56-20 Black(RAL9005).... . P/N 56-202 Brushed Brass -..P/N 56-202- Brushed Chrome.. P/N 56-202- Custom Paint... P/N 56-202-X (a)Previously Is is Bright White. (b)Eastern He. ere sales only. Note:All 1. -.m Cotter Plates are oainted u �. lag Sher ;+!Lams Interior Latex Paint Contac CO .•mer Service with any questions re- t- ustom orders. nkler Wrench: ecify: W-Type 18 Sprinkler Wrench, 56-000-1-265 4111i0000011111101. -- d G AL HEA ARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700 Copyright 020 co Fire ducts,LP. All rights reserved. Y.l.�CO TEFLON is tradema The DuPont Corporation.