May 20, 2010 2525 E Burnside Street
Portland, Oregon 97214
503.226.3617 phone
503.226.3715 fax
RE: TENANT IMPROVEMENT AND ADDITION seallp.com
Project Information
Building Permit: BUP2010-00044 (Bldg A)
BUP2010-00094 (Bldg B) Construction Type: 5-B
Address: 11895 SW Greenburg Rd. Occupancy Type: B
Area: 8424 Sq. Ft. Stories: 2
Name: Luke-Dorf Sprinklers: No
Our responses to your April 12th comments (included) are listed in bold below with the
revised drawings shown underlined.
1) Please provide completed lighting and insulation State of Oregon Energy
Forms.
These completed forms are attached.
2) Please show required locations for all areas of rescue assistance as per
OSSC 1107 and all construction details.
Per our meeting with Mark Van Domelen on May 5th, we are providing
one area of rescue assistance (constructed in room B013 per 1107.2.1.5)
adjacent to the north exit in the basement of Building B (see sheet A2.1
revisions for location and details). Wall assembly W-6A has been added
for the smoke barrier around the room.
3) Please indicate locations for signage showing single accessible exit on
ground floors as per OSSC 1107.5.
Sheet A2.2 has been revised with signage indicating paths to the
accessible exits provided.
4) Please show locations and construction details for all fire rated corridors as
per OSSC Table 1017.1.
Per our meeting with Mark Van Domelen on May 5th, I have revised our
occupant loads on sheet A0.1 to reflect less than 49 occupants in all
spaces of both buildings, meeting exception 4 of 1017.1 for unrated
corridors.
5) Please provide completed Statement of Special Inspections as per OSSC
1704.1 .1 .
Per our meeting with Mark Van Domelen on May 5th, sheet S1.2 should
satisfy this requirement.
6) Please provide listing for fire rated wall less than 5ft from property line and for
wall that is 5 to 10ft from property line on north side. Please show type of
glass to be used in less than 5ft wall.
Wall assembly W-8 (GA File No. WP-8105) has been added to sheet A0.2
and referenced on sheet A2.2. The 3/4-HR rated windows are called out
already on sheet A9.0 and A9.1. The two proposed windows are each
10.5 SF for a total of 21 SF in a 184 SF wall, less than the 15% maximum
area for protected windows 3-5 feet from a property line (T704.8).
7) Please show compliance with OSSC 3403.2.3.1 and 3403.2.3.2 for existing
structures.
This project is in compliance with OSSC 3403.2.3.1 and 3403.2.3.2 for
existing structures. The new additions to buildings A and B have lateral
force resisting wood shearwalls in all four directions supporting the
new lateral forces created by the additions. The new additions have
their own floor and roof diaphragms, which deliver the lateral forces to
their new supporting elements. These new diaphragms are sufficiently
stiff to have a negligible effect on the existing structures. The additions
conform with the requirements for new structures in the 2007 OSSC and
the additions do not increase the seismic forces in or decrease the
seismic resistance of any structural elements of the existing structure
by more than 10 percent. The walls of the existing structures that are
adjacent to the new additions will have new plywood sheathing and
nailing as specified on detail 3 on sheet S5.1 and plan keynote 9 on
sheet S2.8.
8) A separate building permit is required for each building.
This has been done. Both permit numbers are listed at the top of this
response.
9) Separation of exits is to be 50% of diagonal distance measured from midpoint
of exit door(s) on ground floor of building B.
This is not required as our main entry is the only required exit (the
common path of egress from all spaces is less than 75 feet).
10)Office in basement in building A needs to be shown on floor plan.
This space has been renamed on sheet A2.1.
,cg-u-f°ao/o-°9 5"
Z31 — q .
Form 3a Project Name: Luke-Dorf Campus - Building B Page:
BUILDING ENVELOPE - GENERAL
Check all boxes that 1. Exceptions (Section 1312)
- apply. El No Envelope Components. The building plans do not call for new or altered building envelope
components, e.g., walls, floors or roof/ceilings.
❑ A Non-conditioned Building.The proposed structure has no spaces heated or cooled by
an HVAC system.
Exceptions El Exception. All new or altered building envelope components do not comply with the
Discussion of qualifying requirements, Section 1312, but qualify for Exception: 0-1 0-2 ❑-3 ❑-4 ❑-5
exceptions in instructions Portions of the building that qualify:
section.
Plans/Specs
Show compliance by The plans/specs show compliance in the following locations:
including a drawing sheet,
detail number,
specification section 2.Air Leakage (Section 1312.1.1)
and/or subparagraph. El Complies. Plans require penetrations in building envelope are sealed and windows and
doors are caulked, gasketed or weatherstripped.
The plans/specs show compliance in the following locations:
Sheets A9.0 &A9.1
3. Suspended Ceiling (Section 1312.1.2.1)
L Complies. Building plans do not show suspended ceilings used to separate conditioned
space from unconditioned space. No exceptions permitted.
4. Recessed Light Fixtures (Section 1312.1.2.2)
❑ Complies. The building plans do not show recessed light fixtures installed in ceilings
separating conditioned spaces from unconditioned spaces.
El Exception. The building plans require that fixtures installed in direct contact with insulation
be insulation coverage (IC) rated. The plans/specs show compliance in the following locations:
Electrical Specification Section 16500.2.1.B
5. Moisture Control (Section 1312.1.4)
C Complies. A one-perm vapor retarder is installed on the warm side (in winter) of all exterior
floors, walls and ceilings, and a ground cover installed in the crawl space of both new and
existing buildings where insulation is installed.
The plans/specs show compliance in the following locations:
Sheet A0.2
El Exception. All new or altered building envelope components do not comply with the vapor
retarder requirements of the code, but qualify for an exception. Note applicable exception.
Section 1312.1.4, Exception: ❑-1 ❑-2
Portions of the building that comply:
Climate 6. Climate Zones
Zones 111 Zone 1 -A building site is in Climate Zone 1 if its elevation is less than 3000 feet above
sea level and it is in one of the following counties: Benton, Columbia, Clackamas, Clatsop,
Coos, Curry, Douglas, Jackson, Josephine, Lane, Lincoln, Linn, Marion, Multnomah, Polk,
' Tillamook, Yamhill, or Washington.
of 0 ❑ Zone 2 -Building sites not in Zone 1, or where construction site elevation is 3000 feet or
higher in Zone 1, are in Zone 2.
'859'
3-1
Compliance with OSSC.effective 04/01/07
Form 3b Project Name: Luke-Dorf Campus- Building B Page:
PRESCRIPTIVE PATH Part 1 of 4
CLIMATE
ZONE 1
Exterior Wall
Window Area Area Glazing Maximum Glazing
(total rough frame ft2) (gross ft2) % Fraction Complies
Glazing Conditioned 578 + 3,037 X 100= 19.0% Yes
Percent Space
Calc- Semi-
ulation Conditioned + X 100= Yes
See instruction Space
section for a Conditioned
discussion Mechanical + X 100= Yes
e
glazing ing percent
calculation. Penthouse
Windows Window Max Minimum Window Shading Minimum
From Work-sheet (from Worksheet 3d) U-Factors Assembly (from Worksheet 3d) Coefficient2 Assembly
3d,place the Storefront 0.500 ❑ Storefront window 0.430 ❑
highest Overall ..t„d,,,",
Window U-factor U-Value Complies Yes SC Complies Yes
and highest
Center-of-Glass Required
SC.Or check Minimum Required Minimum
minimum Assembly(Fixed N/A Assembly N/A
assembly and
identify window. winrinwe\
Required Mini-
mum Assembly
(Operable N/A
. Windows and
Curtainwall)
The plans/specs show window compliance in the following locations:
Sheet A9.0&A9.1
Notes 1 From Worksheet 3d,place the highest Overall Window U-factor or check(Minimum Assembly). See"Window Requirements"in table on the following
oaae for specific MA requirements. Excel version will automatically insert minimum assembly reauirements or greatest U-value from Worksheet 3d.
2 From Worksheet 3d,place the highest"center-of-glass"shading coefficient(SC)for glass or check MA(Minimum Assembly). See"Window Require-
ments"in following table for specific MA requirements. Excel version will automatically insert minimum assembly requirements or greatest SC from
Worksheet 3d.Shading Coefficient(SC)can be calculated from Solar Heat Gain Coefficient using the equation:SC=SHGC+0.87. Manufacturers
data may also be used to document SC.
Walls R-Value
Wall/Insulation Type Insulation Only U-Factor3
See instructions Frame(wood or metal framing)
for a discussion 19 or
of wall require-
ments. Or
A or
A or
Jor
J or
w
Below-Grade R-Value
Walls Insulation Only U-Factor3
Below-Grade Walls (Min.R-7.5) (Max.0.11)
See instructions f:1".,
- fora discussion of Continuous rigid board insulation 7.5 or �'
requirements. o. rr.-t,l' --)4,
Notes 3 Submit Worksheet 3a for each calculated assembly U-factor ti`s
3-2
Compliance with OSSC,effective 04/01/07
Form 3b Project Name: Luke-Dorf Campus- Building B Page:
PRESCRIPTIVE PATH Part 2 of 4
Code Requirements - Zone 1
Discussion of these requirements in the instruction section.
ZONE 1
Wall Requirements Window Requirements
Max.
Max.Glazing R-Value Shading
Fraction` Wall I Insulation Type Insulation Only U-Factor Max.U-Factor Coefficient
Up to 15% CMU'Masonry5,w/integral loose fill°insulation N/A or 0.300 0.540 0.57
Masonry or concrete5,w/cont.exterior insulation 1.4 or 0.300
CMU Masonry5,w/integral rigid°fill insulation N/A or 0.210
Masonry or concrete5,w/interior insulation 11 or 0.130
Up to 30% Masonry or concrete5,w/cont.exterior insulation 2.8 or 0.210 0.5407 0.57
Frame9(wood or metal framing) 13 or 0.130
Other(provide short description) 13 or 0.130
CMU Masonry5,w/integral rigid°fill insulation N/A or 0.210
Masonry or concrete5,w/interior insulation 11 or 0.130
Up to 40% Masonry or concrete5,w/cont.exterior insulation 2.8 or 0.210 0.37070 0.3510
Frame9(wood or metal framing) 13 or 0.130
Other(provide short description) 13 or 0.130
Code Requirements - Zone 2
Discussion of these requirements in the instruction section.
ZONE 2
-
Wall Requirements Window Requirements
Wall I Insulation Type Max.
Max.Glazing R-Value U-Factor Max.U-Factor Shading
Fraction` Insulation Only Coefficient
Up to 15% CMU'Masonry5,w/integral loose fill°insulation N/A or 0.300 0.50011 0.5711
Masonry or concrete5,w/cont.exterior insulation 1.8 or 0.270
CMU Masonry5,w/integral rigid°fill insulation N/A or 0.160
Masonry or concrete5,w/interior insulation 13 or 0.090
- U p to 25%e Masonry 0.500 or concrete 5,w/cont.exterior insulation 4.3 or 0.160 11 0.5711
Frame9(wood or metal framing) 19 or 0.090
Other(provide short description) 19 or 0.090
CMU Masonry5,w/integral rigid°fill insulation N/A or 0.160
Masonry or concrete5,w/interior insulation 13 or 0.090
Up to 33% Masonry or concretes,w/cont.exterior insulation 4.3 or 0.160 0.37012 0.4312
Frame9(wood or metal framing) 19 or 0.090
Other(provide short description) 19 or 0.090
Notes `The Simplified Trade-off Approach must be used if glazing fraction exceeds allowable percentages.
5 Minimum weight of masonry and concrete walls=45 Ib/ft2 of wall face area
6 All cores to be filled.At least 50%of cores must be filled with vermiculite or equivalent fill insulation.
7 Prescriptive MA(Minimum Assembly)-For Fixed Windows:double-glazed window with a 0.5 inch air space,low-e coating and aluminum frame.
MA shading coefficient description is a tinted outboard pane of glass.For Operable Windows or Curtainwall:double-glazed window with a 0.5
inch air space,low-e coating and thermally broken frame.MA shading coefficient description is a tinted outboard pane of glass.
6 All cores except bond beams must contain rigid insulation inserts approved for use in reinforced masonry walls
9 Batt insulation installed in metal or wood frame walls shall be insulated to the full depth of the cavity,up to 6 inches in depth.
10 Prescriptive MA(Minimum Assembly)-For Fixed Windows:double-glazed window with a 0.5 inch argon filled space,low-e coating(e<=0.05)
and thermal break frame.For Operable Windows or Curtainwall:only use Max U-Factor.MA shading coefficient description is a 0.25-inch thick
glass with low-e coating(e<=0.05)with a tinted outboard pane.
11 Prescriptive MA(Minimum Assembly)-For Fixed Windows:double-glazed window with a 0.5 inch air space,low-e coating and aluminum frame.
For Operable Windows or Curtainwall:double-glazed window with a 0.5 inch air space,low-e coating(e<=0.1)and thermally broken frame.
MA maximum shading coefficient description is a tinted outboard pane of glass.
- Air 1 >. 12 Prescriptive MA(Minimum Assembly)-For Fixed Windows,a double-glazed window with a 0.5 inch argon filled space,low-e coating(e<=0.05)
:. 1.1;t.I. and thermal break frame.For Operable Windows or Curtainwall,only use Max U-Factor.MA shading coefficient description is a 0.25-inch thick
alass with low-e coatina fe<=0.05).
3-3
Compliance with OSSC,effective 04/01/07
Form 3b Project Name: Luke-Dorf Campus- Building B Page:
PRESCRIPTIVE PATH Part 3 of 4
R-Value
Roofs/ Insulation Only U-Factor12
Ceilings Roof I Ceiling" (Min.R-19) (Max.0.050)
See instructions Continuous spray-applied insulation 19 or
fora dicussion of
roofs/ceilings.
Notes 71 Write-in a short description for assembly with the lowest insulation R-value or the highest assembly U-factor.
12 Submit Worksheet 3b for each calculated roof/ceiling assembly U-factor.
Skylight Area Roof Area Skylight Maximum Skylight
(total rough frame ft2) (gross ft2) %.13 Fraction Complies
Skylights Conditioned
Includes glazed Space 22 + 1,520 X 100= 1.4% Yes
smoke vents.
Semi-
See instructions Conditioned + X 100= N/A
for a dicussion of
skylights. Space
Conditioned
Mechanical + X 100= N/A
Penthouse
Skylight Area Roof/Ceiling Area Skylight
(total rough (gross ft2) Percent'ft2)
Skylights Skylights Max Minimum Skylights Shading Minimum
From Worksheet (from Worksheet 3d) U-Factor74 Assembly (from Worksheet 3d) Coefficient15 Assembly
3d,place highest
Overall Vertical #N/A - ❑ #N/A - N/A
Window U-factor
and highest U-Value Complies Yes SC Complies Yes
Center-of-Glass
SC. Required Required Minimum
Minimum N/A Assembly N/A (must use SC)
Assembly
The plans/specs show window compliance in the following locations:
Sheet A9.0
Code Compliance Thermal Performance Shading Coefficient
Option Overall Vertical U-Factor Center of Glass SC
Require- Performance U-1.230 for overall assembly in overhead plane SC-0.47 center-of-glass
meets Min.Assembly Double glazed,0.5-inch airspace N/A
(MA)
Notes 13 Skylight percentage area is based on total skylight and smoke vent rough frame area divided by total conditioned roof area. Percentage must not
exceed 6 percent of total roof/ceiling area in conditioned building space. The Simplified Trade-off Approach must be used if glazing fraction
exceeds allowable percentages.
14 From Worksheet 3d,place the highest Overall Vertical U-factor or write-in MA(Minimum Assembly). See"Skylight Requirements"in table above
for specific MA requirements.
15 From Worksheet 3e,place the highest"center-of-glass"shading coefficient(SC)for glass. See"Skylight Requirements"in table above for
specific MA requirements. Shading Coefficient(SC)can be calculated from the Solar Heat Gain Coefficient using the equation:SC=SHGC+
0.87. Manufacturers data may also be used to document SC.
3-4
Compliance with OSSC,effective 04/01/07
Form 3b Project Name: Luke-Dorf Campus- Building B Page:
PRESCRIPTIVE PATH Part 4 of 4
Floors R-Value
See instructions Floors over Unconditioned Spaces16 Insulation Only U-Factor
for a dicussion of -
floors. or
Heated Concrete Slab Edge R-Value
Insulation Only
Heated Slab-on-Grade(Section 1312.1.2.4)
❑ Complies. Building plans show insulation extending downward from the top of the slab a minimum
distance of 24 inches or downward and under the slab for a combined minimum distance of 24
inches or to the bottom of the thickened edge of the of slabs used as a foundation.
The plans/specs show compliance in the following locations:
Notes 16 Write-in a short description for assembly with the lowest insulation R-value or the highest assembly U-factor.
17 Submit Worksheet 3c for each calculated floor assembly U-factor.
18 Write-in a short description for Heated Slab,which has heat,integrated into slab such as hydronic heat. If more than one floor
type,enter the lowest insulation R-value or the highest component U-factor of any floor.
Code Compliance Options
Require- Min.R-Value Max.U-
Q Component Insulation Only Factor
Floor over Unconditioned Spaces I 11 I or I 0.070
Climate Climate
Component Zone 1 Zone 2
Heated Concrete Slab Edge, Min.R-Value I 7.5 I « 10.0
Doors R-Value U-Factor
See instructions Doors19 Insulation Only Center-of-Panel
for a dicussion of opaque,with leaf width greater than 4' (Min.R-5) (Max.0.20)
doors.
or
Notes 19
Write-in a short description for Doors. If more than one door type,enter the lowest insulation R-value or the highest center-of-
panel U-factor of any door. The following doors are exempt from door and window U-factor and shading coefficient requirement
•
3-5
Compliance with OSSC,effective 04/01/07
1 I. a r ■
a
',torksheet 3,1 Project Name: Luke-Dorf Campus-Building B Pane:
Window Schedule
Window Properties-List All Window Types in Project
ial (b) (e) (d) (e) (0 I (g) (h) (0 5) (k)
Manufact- Moe Center of Overall Center of
Docwnenlilion stars Modell Window Frame TRW Glass Window Glass
Name Salsa No __Ty.pe/Claes Tye, OIee jh l rat Other(6 bane-sir specs..ewk low E) ,U-factor U-factor SC
National Fenesbaton Ftisiting Camel Jed-Wen Fixed j WoodNIryt �� Clear tiN" x Double Gladnlg 112"airspace ea0.4 on suface 2 n.a. 0.28 0.28
Wood picture window Diced-Sal
National Fenestration Rating Cow Jeld-Wen Operable Wood/Vinyl Clear t/b" Double Gleans 1/2"airspace 0=0.4 on surface 2 n.a. 0.32 0.23
Wood awning window +
_ Awning ` j
Wood casement window
National Fenestration Rating Council + Jed-Wen Operable WoodNinyl ,t Clear tA' �` Dottie GYdrp 1R'Nrspsce s'•OA on surface 2 ' r a 0.32 0.22
Casemera J
Exterior sliding door
National Fenestration Rang Council tiding Patio Operable WoudNi yl Clear - U6' w Double Glazing 12'airspace a=0.4 on surface 2_ :-i n.a. 0.29 0.24
National Fenestration Rating Council _e*neer EnCore Fixed I Aluminum with Thermal Break .__.._ Clear 1A" Doubts Gazing 12'skapen es0A on surfaca 2 me- • 0.50 0.43
Storetrca window J
1
1
it
--
y.
1
___ „.
`
J
J
I J j I -
.1
. I
7
7 I 3
I 3
C J I J. 1 - .,...,,,,.:.,,,,,:.:
Column Instructions
(a) Enter the name of the window product.It is recommended that you choose a name that corresponds with that used on project plans and specifications.
(b)Provide documentation source.
Write-in'NFRC"if window is rated through NFRC 100-97 Procedure for Determining Fenestration Product Thermal Performance.Enter all columns except(i).
Write-in"ASHRAE Default W/Mfg COG'if Center-of-Glass U-factor and Shading Coefficient is available from glass manufacturer.Enter all columns.
Columns(i)and(k)from manufacturers data sheet.
Write-in"ASHRAE Default'if only descriptive parameters of window are known.Enter all columns.Columns(i).(j),and(k)from ASHRAE default table.
(c) If Document Source is either"NFRC"or"ASHRAE Default W/Mfg COG,"enter the manufacturers model number.
(d)Choices are Fixed,Operable,or Curtain Wall.
(e)Choices are wood,vinyl,reinforced vinyl,aluminum dad,insulated fiberglass,aluminum,aluminium w/thermal break(see definitions for thermal break requirements.)
(f) Enter glass tint. Write"clear if there is no tint.
(g)Enter glass thickness
(h) Include window properties such as argon fill,low-e coating,insulating spacers.etc.
(I) COG U-factor from manufacture's data or ASHRAE 2001 Fundamentals Handbook,Chapter 30,Table 4.For NFRC rated products leave blank.
Q) Overall U-factor from NFRC rating orASHRAE 2001 Fundamentals Handbook,Chapter 30.Table 4.For skylights value must be for horizontal position. +f ,.,`,c
(k)COG Shading Coefficient from manufacture's data or ASHRAE 2001 Fundamentals Handbook,Chapter 30,Table 4.For NFRC rated products SHGC is provided.
To nvert SHGC to SC.SC=SHGC/0.87. 3'h=
m '
I i
3.11
Canplimce with OSSC.effective 04/01/07
t s s 5 0
Worksheet 3e Project Name Luke-Dorf Campus-Building B Page:L
Skylight Schedule
Skylight Properties-Ust All Skylight Types in Project
(a) (b) (c) (d) (e) (1) (9) (h) (I) g) (k)
•
Manufact- Glass Center at Overall Centered
•
Documentation urea Model) word Frame Thick- Glass Skylight Glees
Name Source No. _ TtsdClaea Tws _ TIOt nese Other(9 canes.alt soave.anion.low El U-factor U-factor SC
National Ferestrasion Rating Council —delux FCM w/ Manufactured(94/Curb)j Aluminum with Memel Break Clear 1/8' 'l Double Glazing 1/Y argon n.a. OAO 0.39
Skylight :ComforlPlus J
f -i�
< � JIAI
I J 4
—
I J { Y I -�
- ;
i
I 4 j
J a
a
J
J 3 . ;.i
J 3
J I
-
j
•
_ I
Column Instructions
(a) Enter the name of the window product.k is recommended that you choose a name that corresponds with that used on project plans and specifications.
(b)Provide documentation source.
Write-m"NFRC if window is rated through NFRC 100-97 Procedure for Determining Fenestration Product Thermal Performance.Enter all columns except(i).
Wrue-in'ASHRAE Default W/Mfg COG'ti Center-of-Glass U-factor and Shading Coefficient is available from glass manufacturer.Enter all columns.
Columns(i)and(k)from manufacturer's data sheet.
Write-in"ASHRAE Default"it only descriptive parameters of wndow are known.Enter all columns.Columns(i).(j),and(k)from ASHRAE default table.
(c) k Document Source is either"NFRC-or'ASHRAE Defautt W/Mfg COG'enter the manufacturer's model number.
(0)Choices are Manufactured or Site Built.
(e)Choices are wood.vinyl.reinforced vinyl.aluminum clad.nsulated fiberglass,aluminum,aluminum wMermal break(see defintions for thermal break requkements.)
(f) Enter glass tint.Write"clear a there 5 no tint.
(9)Enter glass thickness
(h)Include skylight properties such as argon fill,tow-e coating.insulating spacers,etc.
(i) COG U-factor from manufactures data or ASHRAE 2001 Fundamentals Handbook,Chapter 30,Table 4.For NFRC rated products leave blank.
r-.
(I) Overall U-factor from NFRC rang orASHRAE 2001 Fundamentals Handbook,Chapter 30,Table 4.For skylights value must be for horizontal position. -,
(k)COG Shading Coefficient from manufactures data or ASHRAE 2001 Fundamentals Handbook,Chapter 30,Table 4.For NFRC rated products SHGC is provided. v`y.,.,
To convert SHGC to SC.SC=SHGC/0.87. `%h f.
3.11
cerr,Mhw sell oesc,dlesve o4etvl7
15.a/9020/6— ivy /a —o 9y
Form 5a Project Name: Luke Dorf Campus-Building B Page:
LIGHTING - GENERAL
1. Interior Exceptions (Section 1313.1)
❑ No Interior Lighting.The building plans and specifications do not call for new or altered interior lighting.
Skip to item 5,Exterior building Lighting-General,below.
Exceptions ❑ Exceptions. 1.The building or part of the building qualifies for an exception from code lighting
Discussion of qualifying requirements.Applicable code exception is number:
exceptions in instructions
section. 2.Lighting equipment that qualifies for an exception-in addition to general lighting and is separately
controlled.Applicable code exception is number:
Areas of the building and equipment that qualify for any exceptions:
Plans/Specs
Show compliance by including a
drawing sheet,detail number,
and/or specification section and
subparagraph.
2. Local Shut-off controls (Section 1313.3.1.1)
O Complies.At least one local shut-off lighting control for every 2,000 square feet of
lighted floor area and for all spaces enclosed by walls or ceiling height partitions.
This control is detailed in the building plans on drawing number Sheets A3.1,A3.2,A3.3
❑ Exception. The building or part of the building qualifies for an exception.
Applicable code exception is Section 1313.3.1.1,Exception:
Portions of the building that qualify:
3. Automatic Shutoff Controls (Section 1313.3.1.2)
❑ Not Applicable.Office floor area is not over 2,000 square feet of contiguous office floor area or
permitted space is not over 5,000 square feet. No offices less than 300 square feet,meeting
or conference rooms,or school classrooms.
O Complies.All interior lighting systems are equipped with a separate automatic control to shut off lighting
during unoccupied periods.Offices less than 300 square feet,meeting and conference rooms,and school
classrooms are equipped with occupancy sensors that comply with Section 1313.3.1.2.1.
Compliance details in plans/specs: Sheets A3.1,A3.2,A3.3
❑ Exception. The building or part of the building qualifies for an exception.
Applicable code exception is Section 1313.3.1,2,Exception:
Portions of the building that qualify:
4. Daylighting Controls (1313.3.1.3)
C No classrooms or atriums with skylights or window to wall ratio greater than 50%.
❑ Complies.All classrooms and atriums with window to wall ratio greater than 50%and/or skylights are
equipped with automatic daylight sensing controls,as required by Section 1313.3.1.3.1 and Section
1313.3.1.3.2. The daylight sensors specified comply with Section 1313.3.1.3.3.
Compliance details in plans/specs:
Exterior Build-ing 5. Exterior Lighting (Section 1313.5)
Lighting ❑ Complies.The plans do not call for use of incandescent or mercury vapor lamps for use on building exterior.
is lighting directed to illuminate ❑ Exception. the building plans indicate luminaires with incandescent or mercury vapor lamps,but are
the exterior of the building and specified for use in or around swimming pools,water features,or other locations subject to requirements
adjacent walkways and loading
areas with or without canopies. of Article 680 of the 2002 National Electrical Code.
Clock Switches
shall be astronomic(seasonal 6. Exterior and Canopy Lighting Controls (Section 1313.3.2)
correcting for each day of the type with separate
programs f 0 Complies.The building plans and specifications include photoelectric and/or clock switches on all exterior
week and shall store energy to lighting systems which are designed and programmed to extinguish lights when daylight is present,as
maintain timekeeping during required by Section 1313.3.2.
power outages.
7. Connected Lighting Power (Section 1313.4)
YES Complies. The lighting power does not exceed the power allowance established
in either the Tenant Space Method(Form 5b)or the Space-by-Space Method(Form 5c).
• Tenant Space Method(Form 5b) Space-by-Space Method(Form 5c)
iltoa
ice•'!
b-1
v2.4.1-Compliance with 2007 OSSC
Form 5b Project Name: Luke Dorf Campus-Building B Page:
INTERIOR LIGHTING POWER - Tenant Space Method
Lighting Budget (a) (b) (c) (d)
Occupancy/ Tenant or Building Type Floor Area Max Power Lighting Power
Use Types (Table-13G) (sq ft) Density(W/ft) Budget(W)
See instructions for desc- `— --_-- -- ---
ription of occupancy types joffice "1 5,930 1.0 5,930
Lighting Power 1. Total Interior Lighting Power Budget(Watts)for Building. 5,930
Budget
Track Lighting 2. Total length of track lighting(ft)
Power
3. Line 2 multiplied by 50 Watts/ft
4. Total amperage of circuit breaker(s)serving track lighting(amps)
5. Voltage of circuit breaker serving track lighting(volts)
6. Maximum wattage of track lighting(multiply line 4 by line 5)
7. VA rating of the inline current limiter or the low voltage transformers
8. Track Lighting Power(the lesser value of line 3,6 or 7)
9. Total Interior Lighting Power from Worksheet 5b-1 (Sum of Column(m)) + 3,829
Building's Interior 10. Total Adjusted Interior Lighting Power (line 8+line 9) = 3,829
Lighting Power
11. Does Interior Lighting Design Meet Budget? Line 10 must be no greater than line 1. YES
Exterior Canopy
12. Do Exterior Canopies Meet Budget (Worksheets 5c)? YES
Parking Garage
Lighting Power 13. Does Parking Garage Meet Budget (Worksheets 5c)? N/A
ry
r,.
4,9
5-2
V2.4.1-Compliance with 2007 OSSC
.v C� Project Neme.I Luke Dorf CemPle-Bulldog B I PoDoI
LIGHTING FIXTURE SCHEDULE(see Table 5c in instructions for default luminaire power).
•
10 01 PI 10 W 10
4
. 1M 4r ra Lunlnvl•
NO ImoMbo Lrrc aAre Parr From
ire 1■Wm. N• Lab•aoNo Ns, er•rl evYl Table Sc
51 CeAlrtl9www*NOe1 ECT42w I 2 QOroVra2W4 2 arE.1e S2 YES
52 Imp M �
Compel S1T10■ 1CNOSmwOIs-S EC1-2M 1 CFM lEwnX2UgZ I al/ONC 21 YES
(
wt 1 Lae CarwOePI.. .rS .1$SO4MI 12T21wQe112LECRrw - 1 FT22W/2011 1 MOM. 27 YES
ul ure•rt >MLOm1 I S IOW N•WWri n NO
• wt F•rS•OrtIJ• LENNIE 1-rar etecr-eM I MI I YeL 01111[[110 A YES
w9 I Cowed OY•OautOrNl 10 NS-RECT22TY-SFw 5 wasommia 1 >MrYmig r YES
R 1 FkwnFeU LaIESn {1+1SettCY 11 FITS / OM 100 30 YES
FLtwsMIYeaL .TO 112STSe'ECES 77 1 MS I al•L lompooilla 90 YES
Pl rC/mwthemgarsOet W9IMme341361CT2 iV4711 I Crageme M3 1 ATYa00mlo r YES
TS1 11.s woo 1.e LOW, — — SD YES
. 57 IcawSRF ugOweTMa cme1 I-crsN1 MHICLECt--CIF 1 CFlM2w51O1Nl1 errFtr M YES
1
1
I
Jf
I- f ,
1 1 1
,..
r .
1
1
•
I A-
.
I A- A
- - --- ------ -
f i i
---- - ----
i 11
A
A
•
M
•
w•+•Cat...own 10D1 amC
Worksheet 5b-1 Project Name: Luke Dorf Campus-Building B Page:
INTERIOR LIGHTING POWER
Space-by-Space Method Only
Skip to column(f)if using the Tenant Space Method
(a) (b) (c) (d) (e) Lum ID (9) (h) f) G) (k)
from Quantity of
Room ID (do Space Type Space Lighting Power Worksheet Luminaires(or Luminaire Lighting Room
not leave any Area (Table 13-H) Type Budget 5a Cdumn lineal ft.for track Power Exempt Power Total Ltg.
blanks) (ft2) (enter space type only once per room) LPD (b)x(d) (a) lighting) (Watts) Fixtures (g)x(h) Power
' Each room 8001 — — C1 1 52 ❑ 52 115
must be 8001 — -- C2 l 3 21 ❑ 63 —
identified. 8002 — — F1 2 30 ❑ 60 60
Describe luminaires
for each individual B003 — — C1 � 1 52 ❑ 52 94
room in plans.
B003 — — C2 2 21 ❑ 42 —
B004 — — Cl ji 1 52 ❑ 52 94
B004 — — C2 2 21 ❑ 42 —
B005 — — C2 • 5 21 ❑ 105 159
For track lighting B005 — — W1 2.1 2 27 ❑ 54 —
enler lineal lest in
B006 — — C2 1 21 ❑ 21 48
column column(g).
B006 — — W3 • 1 27 ❑ 27 —
Column(k),enter B007 — — C2 4 21 ❑ 84 138
sum of column(j)for 6007 — — W1 2 27 ❑ 54 —
each room only once Fl 1 30 ❑ 30 30
at first entry for the B010 — —
room.See example
in instructions. B011 — — C2 1 1 21 ❑ 21 48
B011 — — W3 J 1 27 ❑ 27 —
B012 — — C1 LI 3 52 ❑ 156 158
B013 — — C1 3 52 ❑ 156 156
B014 — — C2 • 3 21 ❑ 63 144
6014 — — W1 3 27 ❑ 81 —
B015 — — C1 3 52 ❑ 156 264
B015 — — U1 ii 2 30 ❑ 60 —
B015 — — C2 1 21 ❑ 21 —
8015 — — P1 ▪ 1 27 ❑ 27 —
B017 — — F1 • 1 30 ❑ 30 30
8018 — -- F1 1 30 ❑ 30 30
•
B101 — — C1 LI 8 52 ❑ 416 830
B101 — — C2 J 12 21 ❑ 252 --
B101 — — W3 LI 1 27 ❑ 27 —
' 8101 — — P1 ▪ 5 27 ❑ 135 --
6109 -- — C1 11 52 ❑ 572 1,034
B109 -- — C2 10 21 ❑ 210 --
B109 -- — W1 J 4 27 ❑ 108 —
B109 — — W3 J 2 27 ❑ 54 --
B109 — — F2 LI 2 30 ❑ 60 —
B109 — — U1 J 1 30 ❑ 30 —
B201 — — C1 LI 3 52 ❑ 158 297
B201 — — C2 4 21 ❑ 84 —
B201 — — W3 1 27 ❑ 27 —
B201 — — F2 1 30 ❑ 30 —
6207 — — C2 2 21 ❑ 42 102
B207 — — F2 J 2 30_ ❑ 60 -
- Worksheet 5b-1 Total Budget • Wksht 5b-1 Total Lighting Power(excluding exempt/track fixtures) 3,829
Other Pages Total Number of Additional Worksheet 5b I 0 J
List the additional
worksheets nece-
ssary to catalog all -
luminaires in building (I) (m) (n)
Lighting Power Budget: Proposed Buiding Lighting
Space-by-Space only(Total of Power (Total of column(k), Area Sqft.(not required
Worksheet Number column(e)) excluding exempt/track) for Tenant Method)
5b-1 - 3,829 -
.
5b-2
5b-3
Sum of additional 5b worksheets
' ff' P
y' i Total Budget(of all worksheets) - 3,829 -
k. eF
5-5
V2.4.1-Compliance with 2007 OSSC
Worksheet 5c Project Name: Luke Dorf Campus-Building B Page:
EXTERIOR CANOPY AND PARKING GARAGE LIGHTING POWER
Exterior Canopy Lighting
(a) (b) (c) (d) (e) Lum ID (g) (h) (i) G) (k)
from Qty of
Room 10 (do Space Lighting Power Wore Luminaires(or Luminaire Lighting Room
not leave any Area Type Budget 5e Column lineal ft.for track Power Exempt Power Total Ltg.
blanks) 012) Canopy LPD (b)x(d) (a) bghti(1g) (Watts) Fixtures (g)x(h) Power
Each room B115 204 Canopies Under 15 feel in height 1.5 306 S7 3 46 ❑ 138 138
must be _ _ - ❑ - -
identified. _ _ - ❑ - —
Describe luminaires
for each individual — — - ❑ - —
room in plans. - —
— — - ❑ - —
For track lighting — — - ❑ - —
enter lineal feet in
column column(g) -— — ❑ - —
— — - ❑ - —
Column(k),enter — — - ❑ - -
sum of column(j)for
each room only once — _ - ❑ - —
at first entry for the — _ - ❑ - —
room.See example
in instructions. — — ❑ - —
— — - ❑ - —
204 Total Exterior Canopy Budget 306 Total Exterior Canopy Lighting Power(excluding exempt fixtures) 196
Parking Garage Lighting
m
(a) (b) (C) (d) (e) Lum ID (9) (h) (i) (j) (k)
from Quantity of
Room ID (do Space Lighting Power Worksheet Luminaires(or Luminaire Lighting Room
not leave any Area Parking Garage Type Budget 5s column lineal ft.for track Power Exempt Power Total Ltg.
blanks) (112) LPD (b)x(d) (a) lighting) (Watts) Fixtures (g)x(h) Power
•
— — - ❑ - -
- ❑ - -
- — - ❑ - -
- — - ❑ - —
— — - ❑ - -
- - ❑ - -
- _ - ❑ - —
— — - ❑ - -
- — - ❑ - —
— — - ❑ - —
— — - ❑ - —
— — - ❑ - —
— — - ❑ - -
- - o - —
- Total Parking Garage Budget - Total Parking Garage Lighting Power(excluding exempt fixtures) -
Does Canopy Lighting Power Comply? YES
Does Parking Garage Lighting Power Comply? "VA
(•, .W...'
.,._r,u
5-6
•
V2.4.1-Compliance with 2007 OSSC