From: Forster, Steve [steve.forster @tvfr.com]
l Sent: Tuesday, October 12, 2010 2:37 PM
To: Mark VanDomelen
Cc: Weisgerber, Gregory A.; Darby, Ty M.
Subject: Tigard Home Depot
Mark,
I was briefed by Deputy Fire Marshal Ty Darby regarding the non-operational remote operated smoke and
heat vents currently installed at the Home Depot store located at 14800 SW Sequoia Parkway. After reviewing
our files, we've concluded that the approved removal of the curtain boards on May 20, 1993, was allowed
without any additional AHJ conditions. Our records do not indicate any correlation between the removal of
the curtain boards and the installation of the remote operation capability of the smoke and heat vents.
TVF&R will endorse the removal of the remote operation capability from the existing smoke and heat vents
and believes that a traditional smoke and heat vent installation will meet the minimum requirements of the
Uniform Fire Code adopted by the State of Oregon in 1993.
Please feel free to call me if you have any questions. Thank you
Steve Forster
Fire Marshal/ Division Chief
r Tualatin Valley Fire & Rescue
Ph. 503.356.4729
1 Fax 503.644.2214 C OF TIG RD
steve.forster @tvfr.com
Approved . .. [t
Conditionally ApproNed [ ]
See Letter to:Follow [ ]
A • hed ]
Permit N mber.: .1' •`g LL
A.. -ss: ' ` `c L '!►, M
By II IVAN Date: 1111 A •
Approved plans
shall be on job site.
OFFICE COPY
r
1
Double Glazed Frame Model 870FM
Section 08620
Signature Series Dome Available Frame Finish
J , ` Natural Mill(Aluminum)
Factory Mutual Approved 4 `
Smoke Vent Industrial Skylight with FM Approval # 4430
Insulated Thermal break and
(Optional) Safety Security Guard
Details(Scale:3' =1'-0") CLEAR ARMORS CLEAR PRISMATIC POLYCARBONATE OVER CLEAR ARMORS HIGH WHITE PRISMATICPOLYCARBONA'E LENS
:: I Double Glazed % ;fi HINGE BLOCK iii
TORSION BARS i�`:r ��{ ` SILICON ZEAL J
} RELEASE
LATCH BRACKET TRH ,.
VENT FRAME srt..�
■■ II
��4 .. C! ill f_._1 li,;1 ' /L &E p �• PLATED STEEL
.. ..I it oftu r( Q ' i� HNGE PIN........ _ LJI• •• I', '
CURB SEAL TAPE RIGED INSULATIO 1r -- ! RELEASE p
' �1}f ,il�•:�:'�ARM r' CURB FRAME
"�INSJLATED THERMAL •O11 �o
r �� Y
1 I e
BREAK n J -C) e
CONNE:TING MULLION ROD SAFETY-SECURITY GUARD 7.
-
E.� MATH STAPLES DR CLIPS t F
(OPTIONAL DR)
CUPS
ro CLEAR FRAME)
WEATHER SWEEP r NOTE:Finished curb should be 1"less then Net I.D.clear Frame SKYLIGHT
(OPTIONAL) or 1/2"clearance on all sides between frame and finished flashing. FASTENERS
CURBS y 011 . - ill
ti Ilifilit in:
AND
FLASHING - -- -----
(BY OTHERS)
kiilllimill'im I I 1 I
/tllhllllllllllllltll ■
Standard Sizes
CaK-0Jt Sae Nut 4D,CMer Frame
4080 541,'16'z 99 718'
5060 63 38"x 75 3'8"
5080 63 38'x99 3'8"
Soar Heat Gan Coefficient= 49,U Value=.82,Visible Light Transmission= 62 (Acrylic Glazing Only)
Specifications A. Smoke Vents shall be Sunoptics model 870FM Factory Mutual(curb mounted)as manufactured by Sunoptics Skytghts,6201 27th
Street,Sacramento Ca.95822 916/395-4700.
B. Smoke Vents shall be glazed ready for installation
C. Smoke Vent frames shall be fabricated from 6063 T6 aluminum,finish to be natural mill Frames shall have integral condensation
and weepage gutters which drain interior moisture to the outside.Corners shall be mitered and welded.The acrylic glazing shall be
separated from the skylight frame with a Silicon Seal.
D. Smoke Vents shall operate by a fusible ink with a minimum tempature rating of 386 degrees.The fusible link mechanism with Gas
Shocks shall include an exterior manual release cable for testing.Smoke Vents shall open to a minimum angle of 105 degrees.
E. Skylights shall be Double glazed using CLEAR ARMOR®Clear Prismatic Polycarbonate over CLEAR ARMOR®High White
Prismatic Polycarbonate lens,CC 1 Rated,glazed in a Signature Series Dome configuration
F (Optional)OSHA compliant Safety Security Screen fabricated from a wire mesh galvanized cold rolled steel The safety screen shall
.., be tested to withstand the impact of a 240 pound weight,one foot in diameter,dropped from a height of 3 feet and support a
concentrated load of 600 pounds after the impact.Install using Staples or Clips provided at 12"0 C between cross members.
•� 6201 27th Street 916/395-4700 4.,, •�
•
LY SUNOPTI CS Sacramento,CA 800/289-4700 ® 3 =�
95822 FAX/395-9204
High Performance Prismatic Daylighting www.sunoptics.com Arat4w® �e«aca 2-9
T - 7
Conerd Notes RECEIVED
It SEP , 6 2010
CITY Of TIGARD
UNOPTICS 4080 Ten Pound(10 lb)Rated Smoke Hatch-Typical(43 Total) BUILDING DIVISION
I 1 1
1 - 1 f I I I 1 I I I 11
UNOPTICS 4080 Standard Skylight-Typical(30 Total)
11 I 0 O I I I I I
I I I I I I I I I I I I- I [ I 11
I I I n I I 11 1 1 11 f I 11 I I
No. Revision/limo* Dot.
n.Mane we Me-
Ct
C
DRI COMMERCIAL
cr 17182 Armstrong I 1 1 I I 1 I I I I I 1 I f l 9 Avenue
a
c; Irvine,CA 92614
R.
C
4
4
C
...lose--he..t
C
C HE T
I
148OM00 Southwest Sequoia Parkway
I I I I I I I I I I I I 1 1 I I 11 Tigard,OR 97223
N
C
o. ROOF PLAN
C
C
E l 1 [ I 1 1 11 I I I I I I I I 11 I I
•
.w. ...
HOME DEPOT
iww
9/7/2010
R-1
—
• l/32-= '
1'-0.
C: