Specifications
1 METRO Safety & Fire, Inc. 14324 SE Stark St. Portland, Oregon 97233 503-231-2999 Description of Scope of work for: Providence Health Systems — Scholls — 12442 SW Scholls Ferry Rd. - Tigard, Oregon — Fire Alarm Panel Emergency Replacement. As part of an emergency fire panel replacement, we changed the existing Edwards 5723B conventional fire panel with a FCI 7100 Addressable fire alarm panel. We were able to utilize the existing devices by using a AMM- 4SF zone module for the 3 zones and continue to use the existing Silent Knight 5495 notification appliance panel. When an alarm, or trouble condition is detected at the new fire alarm panel it will be retransmitted to the Central Station via a digital communicator. The system is monitored by a UL listed fire monitoring station. CI �j O Approved7T]�d 'GARD [ ►"�`' Conditionally Approved [ ] See Letter to:Follow [ ] Attac ed .. "y�Ci �i Permit N b-r:i ��- - �•" `�, (��� Addre 'mot: By: COO Date: III r ,07A-2.skik Approved plans shall be on job site. OFFICE COPY FCI 7100-1 D FIRE ALARM CONTROL PANEL BATTERY CALCULATION Alberta Rider Elementary QUANTITY STANDBY ALARM TOTAL TOTAL DEVICE DESCRIPTION/MODEL OF DEVICES (A) (A) STANDBY (A) ALARM (A) ANALOG ADDRESSABLE CONTROL PANEL WITH (1) SLC 1 0.0850 0.1050 0.0850 0.1050 REMOTE SERIAL ANNUNCIATOR, LCD DISPLAY (FCI # LCD-7100) 1 0.0500 0.0750 0.0500 0.0750 ANALOG PHOTOELECTRIC SMOKE SENSOR 1 0.0003 0.0070 0.0003 0.0070 ANALOG THERMAL SENSOR, 135 DEG. F FT & ROR 0 0.0002 0.0070 0.0000 0.0000 ANALOG DUCT DETECTOR WITH RELAY 0 0.0002 0.0030 0.0000 0.0000 ANALOG PULL STATIONS (FCI MS-7A) 0 0.0003 0.0003 0.0000 0.0000 BEAM DETECTOR 0 0.0200 0.0800 0.0000 0.0000 ADDRESSABLE MONITOR MODULE, CLASS B (FCI #AMM-2) 2 0.0004 0.0070 0.0007 0.0140 ADDRESSABLE OUTPUT RELAY CONTROL MODULE (FCI #AOM-2R) 3 0.0003 0.0034 0.0010 0.0102 FACP NAC "1" System Sensor Horn Strobe 95cd 0 0.0000 0.1960 0.0000 0.0000 System Sensor Horn Strobe 75cd 0 0.0000 0.1760 0.0000 0.0000 System Sensor Horn Strobe 30cd 0 0.0000 0.1070 0.0000 0.0000 System Sensor Horn Strobe 15cd 0 0.0000 0.0760 0.0000 0.0000 System Sensor Mini Horn 0 0.0000 0.0170 0.0000 0.0000 NAC Expansion Panel 1 0.0750 0.1750 0.0750 0.1750 FACP NAC "2" System Sensor Horn Strobe 95cd 0 0.0000 0.1960 0.0000 0.0000 System Sensor Horn Strobe 30cd 0 0.0000 0.1070 0.0000 0.0000 System Sensor Horn Strobe 15cd 0 0.0000 0.0760 0.0000 0.0000 System Sensor Mini Horn 0 0.0000 0.0170 0.0000 0.0000 NAC Expansion Panel 0 0.0750 0.2500 0.0000 0.0000 CURRENT TOTAL (A) 0.2120 0.3862 STANDBY HOURS REQUIRED 24 ALARM SOUNDING MINUTES 5 TOTAL SYSTEM STANDBY(A) 0.212 TOTAL SYSTEM ALARM (A) 0.386 TOTAL SYSTEM STANDBY(NH) 5.09 TOTAL SYSTEM ALARM (NH) 0.03 MINIMUM NH BATTERY REQUIRED 5.121 BATTERIES PROVIDED AT 12VDC (AH) (2) 7AH 4/1/2013 Page 1 of 4 El( Gamell 1100 Series FIEFIRE CONTROL ' INSTRUMENTS A by Honeywell Compact Analog Addressable Description Fire Alarm Control Panel The Gamewell-FCI 7100 Series fire alarm control panel is a multi processor-based, analog addressable system. The control panel is a compact, yet expandable, platform. Intended for commercial, industrial and institutional instal- lations,the 7100 Series is ideal for life safety and property protection fire alarm applications. , The basic 7100 Series control panel provides one (1) or two(2),analog addressable Signaling Line Circuits(SLCs). Each SLC supports up to ninety-nine(99)analog address- able sensors, as well as up to ninety-eight (98) address- able monitor modules and/or control points. With 197 addresses available on the 7100-1 and 394 addresses available on the 7100-2. The 7100 uses an advanced pro- 7100 Series tocol that ensures an almost instant response to events Features while at the same time suppressing nuisance alarms. • IBC Seismic Certified • Listed per ANSI/UL 864 9th Edition The system may be programmed with either the • 120 or 240 VAC(optional)input line voltage Windows®-based Field Configuration Program(FCP-7100) • Front panel programming with day/night sensitivity or configured through a comprehensive set of intuitive, adjustments secure password protected front-panel programming • 80-character alpha-numeric display options.This important feature allows the system to quickly • One or two Style 4(Class"B")signaling line circuits. adapt to any future requirements due to changes in occu- Style 6(Class"A")with optional CAOM Module pancies, building remodels,or other contingencies. • Two Style Y(Class"B")regulated notification appliance The sophisticated circuitry and powerful analog software circuits rated for 1.5 amp each.Style Z(Class"A")with enables the 7100 Series fire alarm control panel to read the optional CAOM Module • specific sensitivity level of each sensor and compensate for FM/UL Listed for Pre-action/Deluge with optional changes due to age, dust accumulation or other environ- MCOM Module • mental factors. The 7100 incorporates the Gamewell-FCI Periodic trouble reminder • Listed Integrated Sensitivity Testing (LIST) which meets Individual sensor drift compensation • NFPA 72 sensitivity testing and maintenance requirements. Dual stage maintenance alerts("dirty"and"very dirty") • The LIST testing allows substantial savings in both mainte Multilevel sensor sensitivity adjustments(front panel nance and service while eliminating nuisance alarms. programmable) continued on the next page The Model 7100-1D and 2D features an integral Digital Alarm Communicator Transmitter (DACT)with all popular An ISO 9001-2000 Company transmission formats and a 16-digit telephone number SIGNALING field. It is 8-digit Carrier Information Code(CIC)compliant U� O ® MEA and also prevents"dialer-runaway"in the event of intermit- LISTED ..ROVED Approved S1869 3003649307-08-E 7185-rraa:wa(rronly RI*.•∎,mt::°.- tent system faults.The 7100-1D and 2D are UL Listed for 30748E Vol II mo-17w:1a17(tpnrouf aoe.0u4c +p carwof VNA.4asw-ou Microsoft®Word®is a registered trademark of Microsoft®Corporation. 7306911ft 241(u:Owtoo► 1 GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. 02011 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0466 Rev.J page 1 of 3 Description (Continued) LDM-7100 Remote Station, Proprietary, and Central Station fire alarm The LED Driver Module(LDM-7100)is designed to mount systems. It allows ample space for wiring and room for bat- in a UL Listed remote annunciator and provides outputs for teries up to 12 A/H capacity. remote panel switches and thirty-three(33), remote LEDs. Three(3), LDM-7100 modules may be installed in a single Features (Continued) annunciator for a total of ninety-nine(99),LEDs per annun- • Alarm verification per individual sensor ciator. This combination may be repeated up to five times • Positive alarm sequence for sensors or monitor for a total of fifteen(15),LDM-7100 panels installed at up to modules five (5), different locations. Maximum distances of up to 4,000 feet (1,219 m) can be achieved using one pair of • Four levels of system access using six(6),digit pass twisted, non-shielded wire for serial communication and words with up to five(5),user passwords per Level using another pair of straight-lay wire for operating voltage. • Duplicate and extra address indications (For additional information, refer to the LDM-7100 data • March time(60 or 120 BPM)/temporal pattern/coded sheet, Part Number:9020-0519). fours/California Code/user-defined zone coding • Cross zoning • System configuration programming and 280 event log CAOM stored in non-volatile memory The Class"A"Optional Module(CAOM)allows Style Y and • Fan restart with sequential restart delay Z(Class"B" and "A")operation for both Notification Appli- • Upload/download of panel configuration between panel ance Circuits and allows Style 4 and 6(Class "B" and "A") and FCP-7100 program(password protected feature) for both Signaling Line Circuits. It also provides disconnect • Up to sixty-four(64), 7100 panels in the E3 Broadband switches for each signaling line circuit and a common dis network with an optional INI-7100 Module connect switch for both notification appliance circuits. Optional Accessories MCOM The Municipal Connection Option Module (MCOM) pro- LCD-7100 vides three(3)choices of outputs. It can be configured as a The LCD-7100 remote serial display offers an 80-character Municipal Circuit (City Box) output. It may also be set to alphanumeric readout for the remote display of all system serve as a Reverse Polarity output with a nominal voltage events. It duplicates all the information on the 7100 Series output of 24 VDC at 0.012 amp maximum alarm and super- panel display and provides key switch protected functions visory current.The MCOM's third option provides a releas- such as System Reset, Alarm Acknowledge, Trouble ing solenoid output rated at: Acknowledge,Signal Silence,and Drill Test. • 24 VDC nominal voltage. LEDs on the LCD-7100 indicate Alarm, Supervisory, Sys- • 0.005 amp supervisory current. tem Trouble, Power Fault, Systems Silenced, NAC#1, and • 0.710 amp maximum alarm current. NAC#2 Silenced conditions. • 2 ohms maximum line resistance. The LCD-7100 can be surface or semi-flush mounted on a standard four-gang electrical box. It can be installed up to PTRM 4,000 feet(1,219 m)from the main control panel.The 7100 The Printer Transient Module (PTRM) provides RS 232 Isolator/Transient protection for the 7100's RS-232 port Series fire alarm control panel supports up to five (5), (BSM connector J2). It is used in conjunction with a serial remote LCD 7100 annunciators using one pair of twisted, printer applied to the RS-232 port for permanent record non-shielded 18 AWG min. wire or serial communication and uses another pair of 16 AWG min. for operating volt- keeping. age. (For additional information, refer to the LCD-7100 data 1N1-7100 sheet, Part Number:9020-0486). The Intelligent Network Interface Module allows the 7100 Series fire alarm control panel to become the platform of a RAN-7100 peer-to-peer, token ring, self-regenerative network corn- The RAN-7100 maintains the same character display as prised of up to sixty-four(64), 7100 panels. the 7100 Series.The RAN-7100 is mounted in a RAN2-BB backbox for surface or flush mounting retrofits. (For additional information, refer to the Gamewell Retrofit Kits Data Sheet, P/N:9020-60678). GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 9020-0466 Rev.J page 2 of 3 www.gamewell-fci.com Specifications Ordering Information (Continued) Optional Modules Primary Input Power 120 VAC, 50/60 Hz @ 2.0 amps. Part Number Description or240 VAC,50/60 Hz @ 1.0 amp LCD-7100 Remote Serial Annunciator, LCD Output Power 3.335 amps.@ 24 VDC(total) Display(80-character) Non-resettable Power:1.0 amp max. Dimensions: 4.25"H x 8.25"W x 1.90" Resettable Power: 1.0 amp max. (43 H x 37W x 7.7 D cm) 1.0 amp max.from both circuits RAN-7100 Remote Series Annunciator, LCD Two(2)Notification Display(80-character) Appliance Circuits: 1.5 amp each @ 24 VDC Dimensions: 10"W x 5 1/4"H x 2 7/16"D Current: Supervisory Alarm (25 1/4 W x 131/3 H x 6 9/10 D cm) 7100-1 (One SLC) 0.065 amp 0.085 amp LDM-7100 Remote LED Driver Module 7100-1D 0.075 amp 0.095 amp Dimensions: 6"W x 4.50"(15.2 x 11.4 cm) (One SLC w/DACT) CAOM Class A Option Combination Module 7100-2(Two SLC) 0.065 amp 0.085 amp with disconnect switches for both 7100-2D 0.085 amp 0.105 amp signaling line circuits and notification (Two SLC w/DACT) appliance circuits LCD-7100 0.050 amp 0.075 amp LDM-7100 0.035 amp 0.200 amp MCOM Municipal Connection Option Module (All LEDs lit) for local energy city box reverse INI-7100-UTP,-FO 0.040 amp 0.040 amp polarity signaling,or releasing solenoid PTRM Printer Transient Module Operating Temperature: 32° 120°F(0° 49°C) INI-7100-FO Intelligent Network Interface Module, % Fiber-Optic Relative Humidity: 93 /o(non-condensing) INI-7100-UTP Intelligent Network Interface Module, Battery Charger 31 A/H(Cabinet accommodates Unshielded,Twisted Pair Capacity: 12 A/H size batteries) Replacement Parts Alarm&Trouble T-7100 Transformer, 120 VAC input Relay Contacts: Form"C",2 amps.@ 24 VDC (replacement) (resistive) T-7100-240 Transformer,240 VAC input Ordering Information (replacement) BSM-7100-1 Replacement board for 7100-1 Systems BSM-7100-1D Replacement board for 7100-1D Part Number Description 7100-1-PNL 7100 Addressable FACP, 1 SLC Seismic Battery Bracket Kits mounted in 7100-CAB enclosure, red 7100-1D-PNL 7100 Addressable FACP w/DACT, Part Number Description 1 SLC mounted in 7100 CAB 90516 7100-Slim 7 A/H Seismic Battery Bracket kit enclosure,red E3 B-Slim 7 A/H Seismic Battery Bracket Kit Basic Kits 90517 7100-SLim 12 A/H Seismic Battery 1100-1311 Basic System Kit, 2 SLC E -St Kit E3 3 B B-Slim 12 A/H Seismic Battery (BSM, Keypad Display,Transformer) Bracket Kit 1100-1312 Basic System Kit w/DACT,2 SLC 90518 NetSOLO 7100 7 A/H Seismic 1100-1313 Basic System Kit,2 SLC,240 VAC Battery Bracket Kit 1100-1314 Basic System Kit w/DACT,2 SLC, For additional information on the Seismic Battery Brackets, 240 VAC refer to the following documents: Cabinets • Seismic Battery Bracket Installation Guide, P/N: 53839 7100-CAB 7100-Slim(Narrow Enclosure,red) • E3 Series Cabinets Data Sheet, P/N:9020-0649 14.09"W x 20.1"H x 4.55"D (35.8Wx54.61 H x 11.550cm)Enclosure 1100-0480 Enclosure, E3 Series Broadband, black Enclosure, 1100-0481 E3 Series Broadband, red Dimensions: 19 3/8"H x 19 3/8"W x 4"D (49 H x 49 W x 10 D cm) GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 www.gamewell-fci.com 9020-0466 Rev.J page 3 of 3 J Gamewell Velociti® Series • ° FIC� INSTRUUMENTS ASD-PL2F, ASD-PTL2F by Honeywell and ASD-PL2FH Description Analog, Addressable Photoelectronic Smoke Sensor The Gamewell-FCI Velociti° Series, analog address- able plug-in smoke sensors with integral communica- aj .- ` tion provide features that surpass conventional sensors. Sensitivity can be programmed in the con- trol panel software, and is continuously monitored and reported to the panel. Point ID capability allows each sensor's address to be set, providing exact locations for selective maintenance when the cham- ber contamination reaches an unacceptable level. ASD-PL2F/ASD-PTL2F ASD-PL2FR The ASD-PL2F photoelectric sensor's unique optical sensing chamber is engineered to sense smoke pro- Features duced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-tern- • Sleek, low-profile design perature thermal sensing on the ASD-PTL2F model. • Visual rotary, decimal switch addressing(01-159) • Built-in functional test switch activated by an external The Velociti° Series use a communication protocol magnet that substantially increases the speed of communica- • Bicolor LEDs flash green whenever the sensor is tion between the sensors and certain Gamewell-FCI addressed, and light steady red on alarm* analog addressable fire alarm controls. These • devices operate in a grouped fashion. If one of the Optional relay, isolator, or sounder bases • devices in the group has a status change, the panel's Low standby current microprocessor stops the group poll and concen- • Analog addressable communication trates on the single device. The net effect is a • Stable communication technique with noise immunity response speed up to five times greater than earlier • Optional remote, single-gang LED Indicator(RA100Z) designs. • Compatible with Gamewell-FCI analog addressable panels Ordering Information Note: Only the red LED is operative in panels that do not operate in Velociti°mode. Model Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing ASD-PL2FR Analog, addressable photoelectronic smoke sensor used with the DNR duct base when An ISO 9001-2000 Company the remote test is required. SIGNALING Velociti®is a registered trademark of Honeywell International Inc. ® M EA = UL®is a registered trademark of Underwriters Laboratories Inc. LISTED APPROVED Approved NMI S1913 3023594 219-02-E Vol.VI 7272.1703:0121 GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1653 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only.are not intended for installation purposes.and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. 02011 by Honeywell International Inc. All rights reserved. www.gamewel1-fci.com 9020-0617 Rev. I page 1 of 2) Installation Specifications ASD-PL2F plug-in sensors use a separate base to ASD-PL2F, ASD-PTL2F, ASD-PL2FR: simplify installation, service, and maintenance. A Dimensions: 2.1"(5.1 cm)height special tool allows maintenance personnel to plug-in Diameter: 4.1"(10.4 cm)installed in the B501 base and remove sensors without using a ladder. 6.1"(15.5 cm)installed in the B210LP base Shipping Weight:5.2 oz.(147 g) Mount the base on a box which is at least 1.5"(3.8 cm) Operating ASD-PL2F: ° ° deep. Suitable mounting base boxes include: Temperature: 32°F to 120 F(0 C to 49°C) ASD-PTL2F: • 4.0"(10.2 cm)square box 32°F to 100° F(0°C to 38°C) • 3.5"(8.9 cm)or 4.0"(10.2 cm)octagonal box UL®-Listed 0-4000 ft./min. (1,219.2 m/min.), • Single-gang box(except relay or isolator bases) Velocity Range: suitable for installation in ducts. • With B200S or B200SR base, mounted on a 4.0" Relative 10-93%(non-condensing) (10.2 cm)octagonal or square box Humidity: • With B224RB or B224BI base,mounted on a 3.5" Thermal Ratings: Fixed-temperature setpoint 135° F(57°C) (8.9 cm)octagonal box,or a 4.0"(10.2 cm)octagonal or square box Electrical Specifications NOTE: Because of the inherent supervision provided Voltage Range: 15-32 volts DC peak by the SLC, end-of-line resistors are not required. Standby Current: (max.avg.): .0003 A @ 24 VDC Wiring "T-taps" or branches are permitted for Style 4 (one communication every 5 (Class"B")wiring. seconds with LED blink enabled) Maximum Alarm- Current: .0065 A @ 24 VDC(LED)lit). Sensor Spacing Gamewell-FCI recommends that the spacing sensors Bases and Options be used in compliance with NFPA 72. B501 Plug-in sensor base without flange Dimensions: 4.1"(10.4 cm)diameter B210LP Flanged mounting base Dimensions: 6.1"(15.5 cm)diameter B210LPBP Flanged mounting base bulk pack Dimensions: 6.1"(15.5 cm)diameter B224RB Plug-in sensor base with auxiliary Relay Base relay,SPDT, rated 2 amps @ 30 VDC (resistive) Screw terminals: Up to 14 AWG(2.0 mm2) 2 coil latching relay 1 Form C contact UL/CSA Rating: 0.9 A© 125 VAC,inductive 0.9 A @ 110 VDC,inductive 3 A @ 30 VDC,resistive Dimensions: 6.1"(15.5 cm)diameter Maximum:25 devices between isolator bases. B200S Intelligent sensor sounder base Dimensions: 6.875"(17.5 cm)diameter B200SR Standard sounder base, UL 8649th • Edition compliant, ULC Listed Dimensions: 6.875"(17.5 cm)diameter RA100Z Remote LED Annunciator BCK-200 Black detector covers(box of 10) DNR Duct smoke housing GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1653 USA•Tel:(203)484-7161 •Fax:(203)484-7118 9020-0617 Rev. I page 2 of 2 www.gamewell-fci.com Gamewell Velociti® Series rc' FIRE CONTROL INSTRUMENTS AMM-2F by Honeywell Description Addressable Monitor Module The Gamewell-FCI Velociti® Series, addressable monitor module AMM-2F is a single Style B, Class B initiating device circuit(IDC)with a 47KW end-of-line resistor. This module provides an address for any -- device or group of devices connected to this circuit on the signaling line circuit (SLC) of the Gamewell- ((I 71 - FCI addressable series fire alarm control panel. Any ■ initiating device with normally open (N.O.) dry con "'• tacts may be made addressable when connected to the AMM-2F module. AMM-2F The Velociti® Series use a communication protocol that substantially increases the speed of communi- Features cation between the sensors and certain Gamewell- FCI analog addressable fire alarm controls. These Compact size allows easy installation • devices operate in a grouped fashion. If one of the Class B, Style B, initiating circuit devices in the group has a status change, the • 40 Ohm line resistance for each initiating device circuit panel's microprocessor stops the group poll and • Connects to any normally open dry contact device concentrates on the single device. The net effect is response speed up to five times greater than earlier Specifications designs. Supervisory Current: .000375 amps The AMM-2F module can be programmed to provide Alarm Current: .00060 amps a wide variety of input functions to the Gamewell-FCI Operating Temperature: 32° to 120° F (0° to 49° C) addressable series fire alarm control panels. It can Relative Humidity: 10 to 93% be identified as a manual station, heat detector, pie- (non-condensing) num detector, waterflow switch, tamper switch, N.O. End-of-Line Resistance:47K ohms contact, smoke detector, projected beam smoke Dimensions: 1.3"L x 2.5"W x 0.5"D detector, sub loop, remote zone, etc. It can also (3.3 x 6.4 x 1.3 cm) serve as a remote system silence, system reset, system acknowledge or drill switch. It is even possi Ordering Information ble to customize its device type to meet specific job requirements. The initiating device circuit of the AMM-2F can sup- Part Number Description AMM 2F Addressable B, Class module, single port a maximum line resistance of up to 40 ohms circuit, Style B, Class B allowing the use of linear heat detection devices. The compact size facilitates the installation of the module An ISO 9001-2000 Company inside manual stations, or mounting boxes of various SIGNALING types of alarm initiating devices. 'M! Velociti°is a registered trademark of Honeywell International Inc. ® M EA f ! UL®is a registered trademark of Underwriters Laboratories Inc LISTED APPROVED Approved S1949 3023594 227-03-E VOL IV 7300.1703:102 GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only.are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. `02011 Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0626 Rev.D1 page 1 of 1 9020-0630 E.fm-9020-0630.pdf http://www.gamewell-fci.com/datasheets/9020-0630.pdf Gamewell velocm® Series FCIFIRE CONTROL INSTRUMENTS by Honeywell well AMM-4SF Description Addressable Monitor Module The Gamewell-FCI Velociti'' Series, addressable monitor e s14 module AMM-4SF features a single Style D. Class A initiat- ing device circuit. It may also be configured as a Style B, Class B initiating circuit with end-of-line resistor. This mod- ule provides an address for a group of conventional 2-wire smoke detectors. Any alarm initiating devices with normally open (N.O.) dry c lb ontacts, such as heat detectors, linear heat detection devices, projected beam smoke detectors, 4-wire smoke 4.1.-1.4EF detectors, water flow switches. tamper switches, manual stations, etc. may also be installed in this circuit. Features The Velociti') Series use a communication protocol that • Accommodates up to twenty (20), conventional 2-wire substantially increases the speed of communication smoke detectors. (See the Gamewell-FCI Compatibility between the sensors and certain Gamewell-FCI analog Addendum P/N 9000-0427 for supported detectors) addressable fire alarm controls.These devices operate in a • Class A. Style D. or Class B. Style B initiating circuit grouped fashion. If one of the devices in the group has a • 25 ohm line resistance for each initiating device circuit status change, the panel's microprocessor stops the group • poll and concentrates on the single device. The net effect is Visual rotary, decimal switch addressing (01-159) response speed up to five times greater than earlier • Accommodates any N/O dry contact device designs • Compact size allows easy installation • Bicolor LEDs flash green whenever the module is The AMM-4SF module is designed for installation in the signaling line circuit of any Gamewell-FCI analog address- addressed, and light steady red on alarm* able control panel. The signaling line circuits of Gamewell_ •Note Only the red LED is operative in panels that do not operate in Velociti mode FCI analog addressable panels are designed to accommo- date up to 159 monitor modules per circuit. Specifications The initiating device circuit of the AMM-4SF can support a maximum line resistance of up to 25 ohms allowing the use Supervisory current: 00027 amps. (LED flashing) of linear heat detection devices. This allows the module to Alarm current: .0051 amps. (LED lit) Operating temperature: 32°to 120° F (0'to 49°C) stay in alarm with one smoke detector activated.The AMM- Relative humidity: 10 to 93% (non-condensing) 4SF is designed to mount in a 4"square box 2 1/8"deep. Dimensions: 4 1/2" L x 4"W x 1 1/4" D Ordering Information (11.4 x 10.2 x 3.2 cm) End-of-line resistor: 3.9 K ohms Model Description AMM-4SF Addressable monitor module,single circuit, SIGNALING Style D. Class A \Macro®and t:3 Se testare r ul ® ..' ey5teled tradratffrla d Fivaytn4tl Ir1errra icnel Inc LISTED arriarvEn S1949 3023594 227-03EMc1.IV 7X0-17010122 I Ian( GAMEWELL-FCI 12 Clintonville Road, Northford.CT 06472-1653 USA•Tel (203)484-7161 •Fax (203)484-7118 4xectlIcitions ae to utundlum arty.ae nU otutted kt k>StallAkxn purpcsts,and are a>axt to chop vaUnul nonce Pb respusitiflty is assurbd try aft i 4-Fa k U'sv u3e C2013 Hmeywa filernalicnal Inc. All rights reserved www.gamewell-fci.com 9020-0630 Rev.E page 1 of 1 1 of 2 4/1/2013 11:27 AM FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module 1 m . In an emergency, you need maximum power. The 5495 Distributed Power Module by Silent Knight is the most powerful and cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensor®,Gentex®, AMSECO®, Wheelock and Faraday—what you need to drive power-hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. And,ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost-effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1-800-446-6444. Model 5495 • Independent trouble relay Distributed Power Module • AC loss delay option shuts off power The 5495 is a 6 amp notification power to non-essential high-current expander that provides its own AC accessories like magnetic door power connection, battery charging holders circuit, and backup battery for use with • Built-in synchronization for fire and security controls such as the appliances from System Silent Knight Model 5208 Fire Control Sensor®,Gentex®,AMSECO®, /Communicator.The 5495 is the cost- Wheelock and Faraday effective solution for powering r • notification appliances required by the Stand alone operation Americans with Disabilities Act(ADA). • Lightweight design adds to ease of The 5495 has built-in ANSI cadence installation and reduces shipping pattern,which can upgrade older costs control panels that lack cadence • Operates with most polarized, UL capability. Listed notification devices Features • UL 864& 1481 listed •" "' • UL Listed for 6 amps of notification • CSFM approved power Model 5495 • • Power supply's advanced switch ANSI Cadence pattern output Distributed Power Module mode design reduces damaging capability built-in heat and manages power up to 50% Connection to Local Fire Control more efficiently than other systems The 5495 may be connected to a local 4.7kQ end-of-line resistors provided. • Dip switches allow for easy fire control which utilizes Class A or Since the 5495 draws very little power reconfiguration Class B type notification circuits from the control, it is possible to • 24 VDC filtered output voltage operating between 9 and 32 VDC.The connect one 5495 to each notification control panel's notification circuit is circuit on the control panel and still • • Four power-limited notification provide full supervision of the outputs; 2 Class A or 4 Class B, or 1 connected to one of the inputs on the Class A and 2 Class B 5495.The control panel's notification notification circuits all the way back to circuit end-of-line resistor is also the control panel. • • Additional continuous auxiliary connected across two terminals on the output 5495,which provides supervision • 3 amps per output circuit between the 5495 and the fire control SILENT • 2 inputs; 2 Class B or 2 Class A panel. Polarized audible and/or visual 4 KNIGHT • Ground fault detector/indicator notification devices are then connected to the 5495 signal circuits using the by Honeywell FIRE SYSTEM ACCESSORY Model 5495 2 Distributed Power Module Supervision Current: Input The 5495 supervises a variety of Standby 75 mA voltage range: 9 - 32 VDC functions including: Alarm 175 mA Battery charging • Low AC power Auxiliary capacity: 33.0 AH • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault Notification 0° to 49° C • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A(Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output (1 Class A& 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights the 5495 creates a trouble Amps per AC power on : Green condition on the host control signal output circuit: 3.0 (6.0 amps total)to which it is connected. the p ( p ) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC addition, the 5495 provides a Form @ 3.0 amps each, Aux trouble: Yellow C trouble relay output as an 4.7 kS2 EOL Output alternative to using the notification resistor required troubles (1-4): Yellow • circuit trouble. on each Class B Approvals: Electrical Specification circuit UL: 864 & 1481 • AC input: 120 VAC at 2 amps No. of inputs 2 NFPA: 72 Input CSFM Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Input -Signal 3 P Module 5495 g (Optional) Signal 4 120 VAC Aux.Power 1 Trouble Output Local Fire Control (Alternative to notification • circuit trouble.) • 1:1:1 SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350395 Rev B, 12/05 subject to change without notice. For more information,contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100, Maple Grove,Mn 55369-4927. Copyright©2005 Silent Knight Phone:(800)328-0103, Fax:(763)493-6475. RECEIVED METRO Safety & Fire, Inc. APR 01 2013 14324 SE Stark St. Portland, Oregon 97233 CITY OFTIGARD 503-231-2999 BUILDING DIVISION Description of Scope of work for: Providence Health Systems — Scholls — 12442 SW Scholls Ferry Rd. - Tigard, Oregon — Fire Alarm Panel Emergency Replacement. As part of an emergency fire panel replacement, we changed the existing Edwards 5723B conventional fire panel with a FCI 7100 Addressable fire alarm panel. We were able to utilize the existing devices by using a AMM- 4SF zone module for the 3 zones and continue to use the existing Silent Knight 5495 notification appliance panel. When an alarm, or trouble condition is detected at the new fire alarm panel it will be retransmitted to the Central Station via a digital communicator. The system is monitored by a UL listed fire monitoring station. FCI 7100-1 D FIRE ALARM CONTROL PANEL BATTERY CALCULATION Alberta Rider Elementary QUANTITY STANDBY ALARM TOTAL TOTAL DEVICE DESCRIPTION/MODEL OF DEVICES (A) (A) STANDBY (A) ALARM (A) ANALOG ADDRESSABLE CONTROL PANEL WITH (1) SLC 1 0.0850 0.1050 0.0850 0.1050 REMOTE SERIAL ANNUNCIATOR, LCD DISPLAY (FCI # LCD-7100) 1 0.0500 0.0750 0.0500 0.0750 ANALOG PHOTOELECTRIC SMOKE SENSOR 1 0.0003 0.0070 0.0003 0.0070 ANALOG THERMAL SENSOR, 135 DEG. F FT & ROR 0 0.0002 0.0070 0.0000 0.0000 ANALOG DUCT DETECTOR WITH RELAY 0 0.0002 0.0030 0.0000 0.0000 ANALOG PULL STATIONS (FCI MS-7A) 0 0.0003 0.0003 0.0000 0.0000 BEAM DETECTOR 0 0.0200 0.0800 0.0000 0.0000 ADDRESSABLE MONITOR MODULE, CLASS B (FCI #AMM-2) 2 0.0004 0.0070 0.0007 0.0140 ADDRESSABLE OUTPUT RELAY CONTROL MODULE (FCI #AOM-2R) 3 0.0003 0.0034 0.0010 0.0102 FACP NAC "1" System Sensor Horn Strobe 95cd 0 0.0000 0.1960 0.0000 0.0000 System Sensor Horn Strobe 75cd 0 0.0000 0.1760 0.0000 0.0000 System Sensor Horn Strobe 30cd 0 0.0000 0.1070 0.0000 0.0000 System Sensor Horn Strobe 15cd 0 0.0000 0.0760 0.0000 0.0000 System Sensor Mini Horn 0 0.0000 0.0170 0.0000 0.0000 NAC Expansion Panel 1 0.0750 0.1750 0.0750 0.1750 FACP NAC "2" System Sensor Horn Strobe 95cd 0 0.0000 0.1960 0.0000 0.0000 System Sensor Horn Strobe 30cd 0 0.0000 0.1070 0.0000 0.0000 System Sensor Horn Strobe 15cd 0 0.0000 0.0760 0.0000 0.0000 System Sensor Mini Horn 0 _ 0.0000 0.0170 0.0000 0.0000 NAC Expansion Panel 0 0.0750 0.2500 0.0000 0.0000 CURRENT TOTAL (A) 0.2120 0.3862 STANDBY HOURS REQUIRED 24 ALARM SOUNDING MINUTES 5 TOTAL SYSTEM STANDBY (A) 0.212 TOTAL SYSTEM ALARM (A) 0.386 TOTAL SYSTEM STANDBY (A/H) 5.09 TOTAL SYSTEM ALARM (A/H) 0.03 MINIMUM NH BATTERY REQUIRED 5.121 BATTERIES PROVIDED AT 12VDC (AH) (2) 7AH 4/1/2013 Page 1 of 4 F. Gamewell 7100 Series FIRE NNRTS OL ISTCORUMETN by Honeywell Compact Analog Addressable Description Fire Alarm Control Panel The Gamewell-FCI 7100 Series fire alarm control panel is a multi processor-based, analog addressable system. The control panel is a compact, yet expandable, platform. Intended for commercial, industrial and institutional instal- lations, the 7100 Series is ideal for life safety and property ,. protection fire alarm applications. ". The basic 7100 Series control panel provides one (1) or two(2),analog addressable Signaling Line Circuits(SLCs). Each SLC supports up to ninety-nine(99)analog address- able sensors, as well as up to ninety-eight (98) address- able monitor modules and/or control points. With 197 addresses available on the 7100-1 and 394 addresses available on the 7100-2. The 7100 uses an advanced pro- 7100 Series tocol that ensures an almost instant response to events Features while at the same time suppressing nuisance alarms. • IBC Seismic Certified • Listed per ANSI/UL 864 9th Edition The system may be programmed with either the • 120 or 240 VAC(optional)input line voltage Windows®-based Field Configuration Program(FCP-7100) • Front panel programming with day/night sensitivity or configured through a comprehensive set of intuitive, adjustments secure password protected front-panel programming • 80-character alpha-numeric display options.This important feature allows the system to quickly • One or two Style 4(Class"B")signaling line circuits. adapt to any future requirements due to changes in occu- Style 6(Class"A")with optional CAOM Module pancies,building remodels,or other contingencies. • Two Style Y(Class"B")regulated notification appliance The sophisticated circuitry and powerful analog software circuits rated for 1.5 amp each.Style Z(Class"A")with enables the 7100 Series fire alarm control panel to read the optional CAOM Module • specific sensitivity level of each sensor and compensate for FM/UL Listed for Pre-action/Deluge with optional changes due to age, dust accumulation or other environ- MCOM Module • mental factors. The 7100 incorporates the Gamewell-FCI Periodic trouble reminder • Listed Integrated Sensitivity Testing (LIST) which meets Individual sensor drift compensation • NFPA 72 sensitivity testing and maintenance requirements. Dual stage maintenance alerts("dirty"and"very dirty") • The LIST testing allows substantial savings in both mainte Multilevel sensor sensitivity adjustments(front panel nance and service while eliminating nuisance alarms. programmable) continued on the next page The Model 7100-1D and 2D features an integral Digital Alarm Communicator Transmitter (DACT) with all popular An ISO 9001-2000 Company transmission formats and a 16-digit telephone number SiGNAUNG field. It is 8-digit Carrier Information Code(CIC) compliant 0 ® MEA and also prevents"dialer-runaway"in the event of intermit- LISTED •.P•oEo APPm`d 51869 30035493074•E 7106-17 03:106(16.110 Rh*,w tent system faults.The 7100-1D and 2D are UL Listed for 307-09-E V01.OM7047W:,,7(Hyi RIN VMA 400i401C 7JOD�001:211 acw100) Microsoft®Word®is a registered trademark of Microsoft®Corporation. 7200018 741(LCD147100) GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. W2011 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0466 Rev.J page 1 of 3 Description (Continued) LDM-7100 Remote Station, Proprietary, and Central Station fire alarm The LED Driver Module (LDM-7100) is designed to mount systems. It allows ample space for wiring and room for bat- in a UL Listed remote annunciator and provides outputs for teries up to 12 A/H capacity. remote panel switches and thirty-three(33), remote LEDs. Three(3), LDM-7100 modules may be installed in a single Features (Continued) annunciator for a total of ninety-nine(99),LEDs per annun- • Alarm verification per individual sensor ciator. This combination may be repeated up to five times • Positive alarm sequence for sensors or monitor for a total of fifteen(15), LDM-7100 panels installed at up to modules five (5), different locations. Maximum distances of up to 4,000 feet (1,219 m) can be achieved using one pair of • Four levels of system access using six(6),digit pass twisted, non-shielded wire for serial communication and words with up to five(5), user passwords per Level using another pair of straight-lay wire for operating voltage. • Duplicate and extra address indications (For additional information, refer to the LDM-7100 data • March time(60 or 120 BPM)/temporal pattern/coded sheet, Part Number:9020-0519). fours/California Code/user-defined zone coding • Cross zoning • System configuration programming and 280 event log CAOM stored in non-volatile memory The Class"A"Optional Module(CAOM)allows Style Y and • Fan restart with sequential restart delay Z(Class "B" and "A")operation for both Notification Appli- • Upload/download of panel configuration between panel ance Circuits and allows Style 4 and 6(Class"B" and "A") and FCP-7100 program(password protected feature) for both Signaling Line Circuits. It also provides disconnect • Up to sixty-four(64), 7100 panels in the E3 Broadband switches for each signaling line circuit and a common dis- network with an optional INI-7100 Module connect switch for both notification appliance circuits. Optional Accessories MCOM The Municipal Connection Option Module (MCOM) pro- LCD-7100 vides three(3)choices of outputs. It can be configured as a The LCD-7100 remote serial display offers an 80-character Municipal Circuit (City Box) output. It may also be set to alphanumeric readout for the remote display of all system serve as a Reverse Polarity output with a nominal voltage events. It duplicates all the information on the 7100 Series output of 24 VDC at 0.012 amp maximum alarm and super- panel display and provides key switch protected functions visory current. The MCOM's third option provides a releas- such as System Reset, Alarm Acknowledge, Trouble ing solenoid output rated at: Acknowledge, Signal Silence,and Drill Test. • 24 VDC nominal voltage. LEDs on the LCD-7100 indicate Alarm, Supervisory, Sys- • 0.005 amp supervisory current. tern Trouble, Power Fault, Systems Silenced, NAC#1, and • 0.710 amp maximum alarm current. NAC#2 Silenced conditions. • 2 ohms maximum line resistance. The LCD-7100 can be surface or semi-flush mounted on a standard four-gang electrical box. It can be installed up to PTRM 4,000 feet(1,219 m)from the main control panel.The 7100 The Printer Transient Module (PTRM) provides RS-232 Series fire alarm control panel supports up to five (5), Isolator/Transient protection for the 7100's RS-232 port remote LCD-7100 annunciators using one pair of twisted, (BSM connector J2). It is used in conjunction with a serial non-shielded 18 AWG min. wire or serial communication printer applied to the RS 232 port for permanent record and uses another pair of 16 AWG min. for operating volt- keeping. age. (For additional information, refer to the LCD-7100 data INI-7100 sheet, Part Number:9020-0486). The Intelligent Network Interface Module allows the 7100 Series fire alarm control panel to become the platform of a RAN-7100 peer-to-peer, token ring, self-regenerative network corn- The RAN-7100 maintains the same character display as prised of up to sixty-four(64),7100 panels. the 7100 Series.The RAN-7100 is mounted in a RAN2-BB backbox for surface or flush mounting retrofits. (For additional information, refer to the Gamewell Retrofit Kits Data Sheet, P/N:9020-60678). GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 9020-0466 Rev.J page 2 of 3 www.gamewell-fci.com Specifications Ordering Information (Continued) Optional Modules Primary Input Power 120 VAC,50/60 Hz @ 2.0 amps. Part Number Description or 240 VAC,50/60 Hz @ 1.0 amp LCD-7100 Remote Serial Annunciator, LCD Output Power 3.335 amps.@ 24 VDC(total) Display(80-character) Non-resettable Power:1.0 amp max. Dimensions: 4.25" H x 8.25"W x 1.90" Resettable Power: 1.0 amp max. (43 H x 37 W x 7.7 D cm) 1.0 amp max.from both circuits RAN-7100 Remote Series Annunciator, LCD Two(2)Notification Display(80-character) Appliance Circuits: 1.5 amp each @ 24 VDC Dimensions: 10"W x 5 1/4"H x 2 7/16"D Current: Supervisory Alarm (25 1/4 W x 131/3 H x 6 9/10 D cm) 7100-1 (One SLC) 0.065 amp 0.085 amp LDM-7100 Remote LED Driver Module 7100-1D 0.075 amp 0.095 amp Dimensions: 6"W x 4.50"(15.2 x 11.4 cm) (One SLC w/DACT) CAOM Class A Option Combination Module 7100-2(Two SLC) 0.065 amp 0.085 amp with disconnect switches for both 7100-2D 0.085 amp 0.105 amp signaling line circuits and notification (Two SLC w/DACT) LCD-7100 0.050 amp 0.075 amp appliance circuits LDM-7100 0.035 amp 0.200 amp MCOM Municipal Connection Option Module (All LEDs lit) for local energy city box reverse INI-7100-UTP,-FO 0.040 amp 0.040 amp polarity signaling,or releasing solenoid Operating PTRM Printer Transient Module Temperature: 32° 120°F(0° 49°C) INI-7100-FO Intelligent Network Interface Module, % Fiber-Optic Relative Humidity: 93 /a(non-condensing) INI-7100-UTP Intelligent Network Interface Module, Battery Charger 31 A/H(Cabinet accommodates Unshielded,Twisted Pair Capacity: 12 A/H size batteries) Replacement Parts Alarm&Trouble T-7100 Transformer, 120 VAC input Relay Contacts: Form"C",2 amps. @ 24 VDC (replacement) (resistive) T-7100-240 Transformer,240 VAC input Ordering Information (replacement) BSM-7100-1 Replacement board for 7100-1 Systems BSM-7100-1 D Replacement board for 7100-1 D Part Number Description 7100-1-PNL 7100 Addressable FACP, 1 SLC Seismic Battery Bracket Kits mounted in 7100-CAB enclosure, red Part Number Description 7100-1 D-PNL 7100 Addressable FACP w/DACT, 90516 7100-Slim 7 A/H Seismic Battery Bracket kit 1 SLC mounted in 7100-CAB enclosure,red E3 B-Slim 7 A/H Seismic Battery Bracket Kit Basic Kits 90517 7100-SLim 12 A/H Seismic Battery 1100-1311 Basic System Kit,2 SLC Bracket Kit E3 3 B-Slim Slim 12 A/H Seismic Battery (BSM,Keypad Display,Transformer) Bracket Kit 1100-1312 Basic System Kit w/DACT,2 SLC 90518 NetSOLO 7100 7 A/H Seismic 1100-1313 Basic System Kit,2 SLC,240 VAC Battery Bracket Kit 1100-1314 Basic System Kit w/DACT,2 SLC, For additional information on the Seismic Battery Brackets, 240 VAC refer to the following documents: Cabinets • Seismic Battery Bracket Installation Guide, P/N: 53839 7100-CAB 7100-Slim(Narrow Enclosure,red) • E3 Series Cabinets Data Sheet, P/N: 9020-0649 14.09"W x 20.1"H x 4.55"D (35.8 W x 54.61 H x 11.55 D cm)Enclosure 1100-0480 Enclosure, E3 Series Broadband, black Enclosure, 1100-0481 E3 Series Broadband,red Dimensions: 19 3/8"H x 19 3/8"W x 4"D (49 H x 49 Wx 10 D cm) GAMEWELL-FCI )i 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 www.gamewell-fci.com 9020-0466 Rev.J page 3 of 3 Gamewefl Velociti.® Series Fe' INSSTRUUMEM ASD-PL2F, ASD-PTL2F by Honeywell and ASD-PI2FR Description Analog, Addressable Photoelectronic Smoke Sensor The Gamewell-FCI Velociti® Series, analog address- able plug-in smoke sensors with integral communica tion provide features that surpass conventional sensors. Sensitivity can be programmed in the con- trol panel software, and is continuously monitored and reported to the panel. Point ID capability allows each sensor's address to be set, providing exact locations for selective maintenance when the cham- ber contamination reaches an unacceptable level. ASD-PL2F/ASD-PTL2F ASD-PL2FR The ASD-PL2F photoelectric sensor's unique optical sensing chamber is engineered to sense smoke pro- Features duced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-tern- • Sleek, low-profile design perature thermal sensing on the ASD-PTL2F model. • Visual rotary, decimal switch addressing(01-159) • Built-in functional test switch activated by an external The Velociti® Series use a communication protocol magnet that substantially increases the speed of communica- • Bicolor LEDs flash green whenever the sensor is tion between the sensors and certain Gamewell-FCI addressed, and light steady red on alarm* analog addressable fire alarm controls. These • devices operate in a grouped fashion. If one of the Optional relay, isolator,or sounder bases • devices in the group has a status change, the panel's Low standby current microprocessor stops the group poll and concen- • Analog addressable communication trates on the single device. The net effect is a • Stable communication technique with noise immunity response speed up to five times greater than earlier • Optional remote, single-gang LED Indicator(RA100Z) designs. • Compatible with Gamewell-FCI analog addressable panels Ordering Information Note: 'Only the red LED is operative in panels that do not operate in Velociti®mode. Model Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing ASD-PL2FR Analog, addressable photoelectronic smoke sensor used with the DNR duct base when An ISO 9001-2000 Company the remote test is required. SIGNALING Velociti®is a registered trademark of Honeywell International Inc. M EA (t UL ®• a registered trademark of Underwriters Laboratories Inc. LIISOTED 3023594 219-02 E Vol.VI 7272 10121 GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1653 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use ©2011 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0617 Rev. I page 1 of 2 • Installation Specifications ASD-PL2F plug-in sensors use a separate base to ASD-PL2F, ASD-PTL2F, ASD-PL2FR: simplify installation, service, and maintenance. A Dimensions: 2.1"(5.1 cm)height special tool allows maintenance personnel to plug-in Diameter: 4.1"(10.4 cm)installed in the B501 base and remove sensors without using a ladder. 6.1"(15.5 cm)installed in the B210LP base Shipping Weight:5.2 oz.(147 g) Mount the base on a box which is at least 1.5"(3.8 cm) Operating ASD-PL2F:120° 49°deep. Suitable mounting base boxes include: Temperature: 32°F to 120 F(0°C to 49 C) ASD-PTL2F: • 4.0"(10.2 cm)square box 32°F to 100° F(0°C to 38°C) • 3.5"(8.9 cm)or 4.0"(10.2 cm)octagonal box ULC)-Listed 0-4000 ft./min.(1,219.2 m/min.), • Single-gang box(except relay or isolator bases) Velocity Range: suitable for installation in ducts. • With B200S or B200SR base, mounted on a 4.0" Relative 10-93%(non-condensing) (10.2 cm)octagonal or square box Humidity: • With B224RB or B224BI base,mounted on a 3.5" Thermal Ratings: Fixed-temperature setpoint 135°F(57°C) (8.9 cm)octagonal box,or a 4.0"(10.2 cm)octagonal or square box Electrical Specifications NOTE: Because of the inherent supervision provided Voltage Range: 15-32 volts DC peak by the SLC, end-of-line resistors are not required. Standby Current: (max.avg.): .0003 A @ 24 VDC Wiring "T-taps" or branches are permitted for Style 4 (one communication every 5 (Class"B")wiring. seconds with LED blink enabled) Maximum Alarm- Current: .0065 A @ 24 VDC(LED)lit). Sensor Spacing Gamewell-FCI recommends that the spacing sensors Bases and Options be used in compliance with NFPA 72. B501 Plug-in sensor base without flange Dimensions: 4.1"(10.4 cm)diameter B210LP Flanged mounting base Dimensions: 6.1"(15.5 cm)diameter B210LPBP Flanged mounting base bulk pack Dimensions: 6.1"(15.5 cm)diameter B224RB Plug-in sensor base with auxiliary Relay Base relay,SPDT, rated 2 amps @ 30 VDC (resistive) Screw terminals: Up to 14 AWG(2.0 mm2) 2 coil latching relay 1 Form C contact UL/CSA Rating: 0.9 A @ 125 VAC, inductive 0.9 A @ 110 VDC,inductive 3 A @ 30 VDC, resistive Dimensions: 6.1"(15.5 cm)diameter Maximum: 25 devices between isolator bases. B200S Intelligent sensor sounder base Dimensions: 6.875"(17.5 cm)diameter B200SR Standard sounder base, UL 8649th Edition compliant, ULC Listed Dimensions: 6.875"(17.5 cm)diameter RA100Z Remote LED Annunciator BCK-200 Black detector covers(box of 10) DNR Duct smoke housing GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1653 USA•Tel:(203)484-7161 •Fax:(203)484-7118 9020-0617 Rev.I page 2 of 2 www.gamewell-fci.com Gmewell Velociti® Series ROTROL IFINSTRE CUMNB'JTS by Honeywell AMM-2F Description Addressable Monitor Module The Gamewell-FCI Velociti• Series, addressable monitor module AMM-2F is a single Style B, Class B initiating device circuit(IDC)with a 47KW end-of-line resistor. This module provides an address for any --....... device or group of devices connected to this circuit on the signaling line circuit (SLC) of the Gamewell- ! FCI addressable series fire alarm control panel. Any ' initiating device with normally open (N.O.) dry con- tacts may be made addressable when connected to the AMM-2F module. AMM-2F The Velociti• Series use a communication protocol that substantially increases the speed of communi- Features cation between the sensors and certain Gamewell- Compact size allows easy installation •FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the Class B,Style B, initiating circuit devices in the group has a status change, the • 40 Ohm line resistance for each initiating device circuit panel's microprocessor stops the group poll and • Connects to any normally open dry contact device concentrates on the single device. The net effect is response speed up to five times greater than earlier Specifications designs. Supervisory Current: .000375 amps The AMM-2F module can be programmed to provide Alarm Current: .00060 amps a wide variety of input functions to the Gamewell-FCI Operating Temperature: 32° to 120° F (0°to 49° C) addressable series fire alarm control panels. It can Relative Humidity: 10 to 93% be identified as a manual station, heat detector, ple- (non-condensing) num detector, waterflow switch, tamper switch, N.O. End-of-Line Resistance:47K ohms contact, smoke detector, projected beam smoke Dimensions: 1.3"L x 2.5"W x 0.5"D detector, sub loop, remote zone, etc. It can also (3.3 x 6.4 x 1.3 cm) serve as a remote system silence, system reset, system acknowledge or drill switch. It is even possi- Ordering Information !Die to customize its device type to meet specific job requirements. The initiating device circuit of the AMM-2F can sup- Part Number Description AMM 2F Addressable B,Class module,single port a maximum line resistance of up to 40 ohms circuit,Style B,Class B allowing the use of linear heat detection devices. The compact size facilitates the installation of the module An ISO 9001-2000 Company inside manual stations, or mounting boxes of various types of alarm initiating devices. SIGNALING ow" Velociti®is a registered trademark of Honeywell International Inc. ® ® M EA +� ULeis a registered trademark of Underwriters Laboratories Inc. LISTED •t ',PROVED Approved 1I� $1949 3023594 227-03-E VOL IV 7300-1703:102 GAMEWELL-FCI 12 Clintonville Road,Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118 Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use. ©2011 Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0626 Rev.D1 page 1 of 1 9020-0630_E.fm-9020-0630.pdf http://www.gamewell-fci.com/datasheets/9020-0630.pdf 7GameweO Velociti® Series 51.1 ANTROL INSTRE RUCOMENTS Honeywell AMM4SF by Description Addressable Monitor Module The Gamewell-FCI Velociti Series. addressable monitor module AMM-4SF features a single Style D. Class A initiat- ing device circuit. It may also be configured as a Style B, Class B initiating circuit with end-of-line resistor. This mod- 4 ule provides an address for a group of conventional 2-wire smoke detectors. Any alarm initiating devices with normally open (N.0 ) dry oft contacts. such as heat detectors linear heat detection devices, projected beam smoke detectors, 4-wire smoke detectors, water flow switches. tamper switches. manual stations,etc may also be installed in this circuit. Features The Velociti' Series use a communication protocol that • Accommodates up to twenty(20), conventional 2-wire substantially increases the speed of communication smoke detectors. (See the Gamewell-FCI Compatibility between the sensors and certain Gamewell-FCI analog Addendum PIN 9000-0427 for supported detectors) addressable fire alarm controls.These devices operate in a • Class A, Style D, or Class B, Style B initiating circuit grouped fashion. If one of the devices in the group has a •status change. the panel's microprocessor stops the group 25 ohm line resistance for each initiating device circuit • poll and concentrates on the single device.The net effect is Usual rotary, decimal switch addressing (01-159) response speed up to five times greater than earlier • Accommodates any N/O dry contact device designs. • Compact size allows easy installation • Bicolor LEDs flash green whenever the module is The AMM-4SF module is designed for installation in the signaling line circuit of any Gamewell-FCI analog address- addressed. and light steady red on alarm' able control panel. The signaling line circuits of Gamewell- Note Only the red LED is operative in panels that do not operate in VelociU mode FCI analog addressable panels are designed to accommo- date up to 159 monitor modules per circuit. Specifications The initiating device circuit of the AMM-4SF can support a maximum line resistance of up to 25 ohms allowing the use Supervisory current: 00027 amps. (LED flashing) of linear heat detection devices. This allows the module to Alarm current: 0051 amps. (LED lit) Operating temperature: 32'to 120° F (0°to 49° C) stay in alarm with one smoke detector activated.The AMM- Relative humidity: 10 to 93%(non-condensing) 4SF is designed to mount in a 4"square box 2 1/8"deep. Dimensions: 4 1/2" L x 4"W x 1 1/4"D Ordering Information (11.4x10.2x32cm) End-of-line resistor: 3.9 K ohms Model Description AMM-4SF Addressable monitor module, single circuit, SIGNAUNG Style D, Class A U 'MuJtiip atd t3 Srir s'de r©ystt€Ex1 tradwurks of 1-brewkill t (vEA Irtemebonellft LISTED AfpRokow ^aprved S1949 3023594 227.03-EMI IV 7300-170101M GAMEWELL-FCI 12 Clintonville Road,Northford CT 06472-1653 USA•Tel (203)484-7161 •Fax (203)484-7118 SpedIcAlonsaefar Y*rnrdlonaty,ae rd rtcided tU lust Aaiun pupa cs,ad ae atlat to than vAthal ndice.W re pusi7Ylty is assured by Garew1-FCI ter�e 00131ixemeDkte eliatalitc. slips resened www.gamewell-fci.com 9020-0630 Rev. E page 1 of 1 2 1 of 2 4/1/2013 11:27 AM FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module Lit r In an emergency, you need maximum power. The 5495 Distributed Power Module by Silent Knight is the most powerful and cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensore,Gentex®,AMSECO®, Wheelock and Faraday—what you need to drive power-hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. And,ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost-effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1-800-446-6444. Model 5495 • Independent trouble relay Distributed Power Module • AC loss delay option shuts off power The 5495 is a 6 amp notification power to non-essential high-current expander that provides its own AC accessories like magnetic door power connection, battery charging holders circuit, and backup battery for use with • Built-in synchronization for fire and security controls such as the appliances from System Silent Knight Model 5208 Fire Control Sensor®,Gentex®,AMSECO®, /Communicator. The 5495 is the cost- Wheelock and Faraday effective solution for powering (. • notification appliances required by the Stand alone operation Americans with Disabilities Act(ADA). • Lightweight design adds to ease of The 5495 has built-in ANSI cadence installation and reduces shipping pattern,which can upgrade older costs control panels that lack cadence • Operates with most polarized, UL capability. Listed notification devices Features • UL 864& 1481 listed fi+ "'.""' • UL Listed for 6 amps of notification • CSFM approved power Model 5495 • • Power supply's advanced switch ANSI Cadence pattern output Distributed Power Module mode design reduces damaging capability built-in heat and manages power up to 50% Connection to Local Fire Control more efficiently than other systems The 5495 may be connected to a local 4.7kg2 end-of-line resistors provided. • Dip switches allow for easy fire control which utilizes Class A or Since the 5495 draws very little power reconfiguration Class B type notification circuits from the control, it is possible to • 24 VDC filtered output voltage operating between 9 and 32 VDC.The connect one 5495 to each notification control panel's notification circuit is circuit on the control panel and still • Four power-limited notification provide full supervision of the outputs; 2 Class A or 4 Class B, or 1 connected to one of the inputs on the 5495.The control panel's notification notification circuits all the way back to Class A and 2 Class B the control panel. • Additional continuous auxiliary circuit end-of-line resistor is also output connected across two terminals on the 5495,which provides supervision SILENT • 3 amps per output circuit between the 5495 and the fire control • 2 inputs; 2 Class B or 2 Class A panel. Polarized audible and/or visual ` KNIGHT • Ground fault detector/indicator notification devices are then connected to the 5495 signal circuits using the by Honeywell FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module I Supervision Current: Input The 5495 supervises a variety of Standby 75 mA voltage range: 9- 32 VDC functions including: Alarm 175 mA Battery charging • Low AC power Auxiliary capacity: 33.0 AH • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault Notification 0° to 49° C • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A(Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output (1 Class A& 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights the 5495 creates a trouble condition on the host control signal Amps per AC power on : Green circuits to which it is connected. the output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC Aux trouble: Yellow addition, the 5495 provides a Form @ 3.0 amps each, C trouble relay output as an 4.7 kS2 EOL Output alternative to using the notification resistor required troubles (1-4): Yellow circuit trouble. on each Class B Approvals: circuit UL: 864 & 1481 Electrical Specification AC input: 120 VAC at 2 amps No. of inputs 2 NFPA: 72 Input CSFM Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Signal 3 input Module 5495 g (Optional) Signal 4 120 VAC Aux. Power Trouble Output Local Fire Control (Alternative to notification circuit trouble.) c SILENT NI This document is not intended to be used for installation purposes.We try to MADE IN AMERICA KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350395 Rev B, 12/05 subject to change without notice. For more information,contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100,Maple Grove, Mn 55369-4927. Copyright©2005 Silent Knight Phone:(800)328-0103,Fax: (763)493-6475.