Plans , , iraI REV DATE DESCRIPTION BY CONTACT GENERAL NOTES UTILITY V A 17SEP08 CO REVIEW KHT A. NATURAL GAS PIPING SHALL BE POLYETHYLENE BELOW GRADE AND NATURAL GAS `B 19 2013 0 o9oCTO8 CO FINAL KHT SCHEDULE 40 BLACK IRON ABOVE GRADE. NW NATURAL r 1 180EC12 REISSUE CO FINAL KHT CALL 503.226.421 1, EXTENSION 2360 OR 2364, FOR SERVICE OFTf AD O STALLATIN B. FOR TRENCHING SEE 4/A2.0. INSTALLATION 310`, C. DESIGN SHOWN BASED ON MTU GENERATOR MODEL 50—GC6NLT1 . IT IS THE CONTRACTOR'S RESPONSIBILITY TO CAREFULLY COORDINATE - NOTIFY ENGINEER IF DIFFERENT MODEL OF GENERATOR IS ALL ASPECTS OF SERVICE WITH THE RESPECTIVE UTILITY COMPANIES. PROVIDED. D. ALL WORK AND MATERIALS SHALL CONFORM TO APPLICABLE LEGEND CODES, REGULATORY AGENCIES, AND STANDARDS, INCLUDING BUT L<wireless NOT NECESSARILY LIMITED TO IBC, IMC, IPC, IFC, NEC, OSHA, G G NATURAL GAS (ABOVE GRADE) W1 NFPA, ETC. INFORM CONSTRUCTION MANAGER OF CONFLICTS PRIOR 5430 NE 122nd AVENUE TO BID. WHERE TWO CODES OR STANDARDS DIFFER, THE MORE G G NATURAL GAS (BELOW GRADE) PORTLAND,OREGON 97230 STRICT OF THE TWO SHALL BE FOLLOWED. 503.408.3400 E. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, GAS CONNECTION SCHEDULE POR TUALATIN BENDS, ELBOWS, TURNS, EXISTING CONDITIONS, ETC. CONTRACTOR IS RESPONSIBLE TO VERIFY ALL DRAWINGS, INSTALLATION - - CONDITIONED AND COORDINATE WITH OTHER TRADES AS REQUIRED. EQUIPMENT TAX LOT #W262492 DESCRIPTION LOCATION LOAD INPUT PROVIDE ADDITIONAL BENDS AND OFFSETS REQUIRED FOR CONNECTION SIZE X75 SW SANDBURG ST. COMPLETE INSTALLATION AT NO ADDITIONAL COST TO PROJECT. PARKING GENERATOR LOT 600 MBH 1 -1/2" TIGARD, OR 97223 F. ALL WORK SHALL BE DONE IN FIRST CLASS, WORKMANLIKE CITY F TIGARD MANNER. ALL EQUIPMENT AND MATERIALS PROVIDED SHALL BE NEW AND CONFORM TO ALL CURRENT CODES AND APPROVAL Approved... a ... ...LJj [_j- PIPE SIZE MBE AGENCIES HAVING JURISDICTION. INSTALL ALL EQUIPMENT AND Conditionally 1 pproved [ ] 1/2„ 279 MATERIALS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS See Letter to:F)Ilow [ ] AND RECOMMENDATIONS. PERFORM ALL LUBRICATION A Cached [ ] 3/4" 583 REQUIREMENTS PRIOR TO STARTING EQUIPMENT. 961$1N.Po.�w.ya Permit t �J1 3-00103 0 as,o7 Address? �V 1" 1,040 6aa.en003)292 97005 G. CUT WALL FOR PROPER EQUIPMENT, DUCT OR PIPE INSTALLATION. ��j���'�] ' Phone (503)1.16000 By. Date: ENGINEERING,INC. far (5°3)776-33'6 FILL HOLES WHICH ARE CUT OVERSIZE SO THAT A TIGHT FIT IS ,,..a,g►r gr.,.d.nb„on.. E. ""693."In9C ' OBTAINED AROUND OBJECTS PASSING THROUGH. PATCH AND SEAL PIPE SIZING BASED ON 2 PSIG DELIVERY, 2009 NFPA 54 TABLE PrgeU No 2291079001 Cor,ac, KRISTIN TROVE FINISHED TO MATCH NEW OR EXISTING FINISHES. 6.2(c) 215' TOTAL DEVELOPED LENGTH. H. ALL ROOF PENETRATIONS SHALL BE SEALED WATERTIGHT. FR(�c�� Approved plans �� I N�- J/p I. CONTROLS AND WIRING SHALL MEET ALL ELECTRICAL shall be on job site. 4) REQUIREMENTS OF APPLICABLE ELECTRICAL SPECIFICATIONS AND • r 4,-41111./•REQUIREMENTS OF OWNER, BUILDING OFFICIALS AND EQUIPMENT FROM TEST PORT , SUPPLIERS OF EQUIPMENT INSTALLED ON PROJECT. METER TO GENERATOR •REGO (FLEX PIPING -4. �� J. ELECTRIC MOTORS SHALL HAVE BUILT—IN THERMAL OVERLOAD GAS COCK '� II 5 LAST 12 INCHES) IA_ >>>2� s �''1- PROTECTION OR BE PROTECTED EXTERNALLY WITH SEPARATE WITHIN COCK OF z Rk D. .10\'\'(- i� r THERMAL OVERLOAD DEVICES, WITH LOW—VOLTAGE RELEASE OR GENERATOR tD GAS PRESSURE REGULATOR EXPIRES 6/30/13 LOCK OUT AS REQUIRED. u VENT IF REQUIRED K. ALL NEW EQUIPMENT, PIPING, CONDUIT, AND DUCTWORK SHALL BE DIRT LEG DRAWING FILE INSTALLED PER IBC SEISMIC REQUIREMENTS. OFFICE COPY WF.\229\1079\ool\DW '\P01 L. MAINTAIN CODE REQUIRED AND MANUFACTURER RECOMMENDED 1 GAS CONNECTION DETAIL PLUMBING SHEET TITLE CLEARANCES AROUND ALL EQUIPMENT. M0 NOT TO SCALE SCHEDULE SHEET NUMBER P01 r ■ REV DATE DESCRIPTION BY A 17SEP08 CO REVIEW KHT 0 090CT08 CD FINAL KHT 1 18DEC12 REISSUE CD FINAL KHT // \ V Wilfinwireless s. \ 5430 NE 122nd AVENUE ` PORTLAND,OREGON 97230 C \ 503.408.3400 POR TUALATIN \ TAX LOT #W262492 P _ 2975 SW SANDBURG ST. TIGARD, OR 97223 00 \ 17515 8 W A^en BWMrn I &Ma 107 R6VV Beavennr'.Oregon 97005 ` Phone (507)2926000 \ ENGINEERING,INC. Fet 4503)725-3725 Trobworing►repvlre 11o1u1er' E-met rwer19Srwwq tarn Pro;ectNo-. 229.1079-001 Contact IQitSTit1 !NONE GENERATOR, SEE 1 \ 7 �� �� PRO, Fs ��c,1Nz4- 2,,, NEW GAS METER • O $ 9 J G I OREGiilf EXISTING II IV -- != �4Rc — — - - - - --- GAS_.METERt_� -/ / -- __/ G / - f- -- -f_ / _G / -/_ _L G_ - J______ I- - I G _ - ---- - - --G/ / - /__-/ /- -- - . �q ti 11. RK D. JON tili 'Z 1" G I EXPIRES 6/30/13 I 1 DRAWING FILE 1 SITE PLAN- PLUMBING a WF:,229\906VO1\DWO\P02 SHEET TITLE Pot SCALE: 1"=20 —0" PLUMBING SITE PLAN SHEET NUMBER P02