Beman/Summers Building
7175 SW Beveland St ' ° y tb o Q
Tigard OR.97223 �, 4 , F �t.� ', i�
x <.
r
•
Remove and replace an existing split system
cooling unit like for like. 1
n
Existing Ruud unit is 250 pounds €
Y
II ti
i 1
•
New RTU is a Ruud UANL-060CAZ
Weight is 250 pounds € _
4
13 SEER. y
M
I ,', �?
Earthquake strap to existing roof curb 9
.4 , ' .: ; s''''''''
Existing mixing box economizer cooling. xry x
01 V
r o
crl
, i t '
".....,-,=:,...
. u a ` X ie 4`� ,i
3: �� u ,'
Yt�
� ." .y« 3 s �'' ''lrr, ss s :..4.
(3-'e 6 '' ' ,..: , ii ,,e:i: : ,,,,
IL ' ;
CI OF ARD '�
Ile
a
a�
A
lititoi pproved N�. [ 0 t r t x ,
Conditionally Approved - - ] -sir' ,." Ai-
r;. }. 'G q�%N7 �:aayy�as++,».... sus:? ''.,
See Letter to ]
Attached ' '• ,i 0R c '3" s cs r �"�r`4,f ; ` iy , {' �":P''d
Permit Number: U�- :` -.rr ( ' w 4, R . R� K'
Address: ��w 1'i�: I� "" `°`• ,,..
By �ii.•h Date: LIm
t
1'Yl 1D 503) 786-9522
HEATING &COOLING / ie, .✓ 4 :,,"„:-t-0-46°;'
www.pyramidheating.com ` " °
4142611- .
withstanding the test of time - r -
Approved plans REFRIGERANT PIPING
shall be on job site. SHALL NOT BE INSTALLED IN A _ 0 1 50 FT
MEANS OF EGRESS,AND SHALL '
OFFICE COPY COMPLY WITH OMSC 1107.2.2
FOR PENETRATIONS
FORM NO.A22-184 REV.6
Supersedes Form No.A22-184 Rev.5
CONDENSING UNITS
UAPL- Ip rif;Y
14 SEER Models
Efficiencies up to 16.00 SEER RIJIID
Nominal Sizes 11/2 to 5 Tons
[5.28 kW]to[17.6 kW]
Seven Models 111111■11111111111.11,
Cooling Capacities
18,200 t0 59,500 BTU/HR
AcHwR
[5.33 kW]to[17.44 kWJ
--> UANL- f0A Series
13 SEER Models
Nominal Sizes 11/2 to 5 Tons
[5.28 kW]to[17.6 kW] The Ruud Achiever® Series High Efficiency UAPL- and
Seven Models UANL- Condensing Units were designed with perfor-
Cooling Capacities mance in mind. These units offer comfort, energy conser-
18,300 to 62,000 BTU/HR vation and dependability for single, multi-family and light
[5.36 kWJ to[18.17 kW] commercial applications.
These units also contain the most advanced alternate
refrigerant which contains no chlorofluorocarbons(CFCs),
or hydrochlorofluorocarbons (HCFCs), or other com-
pounds that may leak from air-conditioning systems and
potentially harm the protective ozone layer of the Earth's
atmosphere.
The Ruud Achiever®Series UAPL-and UANL-Condensing
,.,r ' Units are the result of an ongoing development program for
' at improved efficiencies. These units are flexible enough to
achieve up to 16.00 SEER in specific match-ups,continuing
fri �,,..----� „ 4 a tradition of high efficiency.
•Attractive, louvered wrap around jacket protects the coil
from yard hazards and weather extremes. Top grille is
steel reinforced for extra strength. Cabinet is powder
painted for all-weather protection.
•Air is discharged upward away from bushes and shrubs.
The discharge
oge pattern of the top grille provides minimum
air
•Combination Grille/Motor Mount secures the motor to
the underside of the discharge grille.The grille protects
the motor windings and bearings from rain and snow.
•All controls are accessible by removing one service
panel. Removable top grille provides access to the con-
denser fan motor and condenser coil.
•Single speed 8-pole fan motor designed for low speed,
quiet,energy-saving operation.
•All models meet or exceed a 1000-hour salt spray test
per ASTM B117 Standard Practice for Operating Salt
Spray Testing Apparatus.
ENEFIGUIDE
l r.M.M MM„IM1Y(YEFAI I ` 1rENIUE R QuI.+IUID16E EE n1 �r
404 ar iii‘1111
_r.taVa,
= C US
• 11.1—UM IMO mow♦f1! 111—Uw MMIM1Ip♦f1A .a1?'.k^3M',bai.•
11'Y YC
SO 9001:2000 zo PARTNER STAR LISTED
14 SEER MODELS&
13 SEER MODELS
(IN CERTAIN MATCHED SYSTEMS)
•
Electrical and Physical Data: UAPL-
ELECTRICAL PHYSICAL
Model Phase Fan Min.Circuit Fuse or HACR Outdoor Coil Refrig. Weight
No. Compr. Comer. Circuit Breaker Per Circuit
UAPL- Hertz RLA LRA Motor Ampacity Face Area No. CFM[Lis] Net Shipping
Volts FLA Amps Min.Amps Max.Amps Sq.Ft.(m'] Rows Oz.[01 Lbs.[kgl Lbs.[kg]
018JAZ 1-60-208/230 9/9 48 0 8 13/13 15/15 20/20 11.00[1.02] 1 1900 [897] 79[2240] 140 [63.5] 155 [70.3]
_024JAZ 1-60-208/230 13.5/13.5 58.3 0.8 18/18 25/25 30/30 11.00(1.02] 1 2300[1085] 105[2977] 140 [63.5] 187 [84.8[
030JAZ 1-60-208/230 12.8/12.8 64 1.2 18/18 25/25 30/30 20.00[1.86] 1 3200[1510] 135[3827] 200 [90.7] 213 [96.6]
036JAZ 1-60-208/230 16.7/16.7 79 1.2 23/23 30/30 35/35 23.01 [2.14] 1 3200[1510] 141 [3997] 230[104.3] 228[103.4]
042JAZ 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 23.01 [2.14] 1 3200[1510] 152[4309] 230[104.3] 252[114.3]
048JAZ 1-60-208/230 21.8/21.8_ 117 1.2 29/29 35/35 50/50 23.01 [2.14] 1 3300[1557] 152[4309] 230[104.3] 253[114.8]
060JAZ 1-60-208/230 26.4/26.4 134 1.2 35/35 45/45 60/60 44.00[4.09] 2 3100[1463] 286[8108] 280 [127] 305[138.3]
Electrical and Physical Data: UANL-
ELECTRICAL PHYSICAL
Model Fuse or HACR Outdoor Coil Weight
No. Phase Fan Min.Circuit
Hertz Compr. Compr. Motor Ampacity Circuit Breaker Face Area No. R 410A Net Shipping
UANL- RLA LRA CFM(L/s] Oz.[g] pp g
Volts FLA Amps Min.Amps Max.Amps Sq.Ft.[me] Rows Lbs.[kg] Lbs.[kg]
018JAL 1-60-208/230 9/9 48 0.6 12/12 15/15 20/20 9.07 [0.84] 1 1775 [838] 70[1984] 130 [59.0] 140 [63.5]
024JAZ 1-60-208/230 12.8/12.8 58.3 0.6 17/17 20/20 25/25 11.00[1.02] 1 1920 [906] 72[2041] 140 [63.5] 150 [68.0]
030JAZ 1-60-208/230 14.1/14.1 73 0.8 19/19 25/25 30/30 12.94[1.20] 1 2470[1166] 94[2665] 160 [72.6] 170 [77.1]
036CAZ 3-60-208/230 13.2/13.2 88 0.8 18/18 25/25 30/30 17.26[1.60] 1 2570[1213] 113[3204] 205 [93.0] 215 [97.5]
036DAZ 3-60-460 6 44 0.4 8 15 15 17.26[1.60] 1 2570[1213] 113[3204] 205 [93.0] 215 [97.5]
036JAZ 1-60-208/230 17.9/17.9 112 0.8 24/24 30/30 40/40 17.26[1.60] 1 2570[1213] 113[3204] 205 [93.0] 215 [97.5]
042CAZ 3-60-208/230 13.5/13.5 88 1.2 19/19 25/25 30/30 17.26[1.60] 1 3290[1553] 130[3686] 205 [93.0] 215 [97.5]
042DAZ 3-60-460 6 44 0.6 9 15 15 17.26[1.60] 1 3290[1553] 130[3686] 205 (93.0] 215 [97.5]
042JAZ 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 17.26(1.60] 1 3290[1553] 130[3686] 205 [93.0] 215 [97.5]
048CAZ 3-60-208/230 13.7/13.7 83.1 1.2 19/19 25/25 30/30 23.01 [2.14] 1 3500[1652] 145[4111] 230[104.3] 240[108.9]
048DAZ 3-60-460 6.2 41 0.6 9 15 15 23.01 [2.14] 1 3500[1652] 145[4111] 230[104.3] 240[108.9]
048JAZ 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 23.01 [2.14] 1 3500[1652] 145[4111] 230[104.3] 240[108.9]
048YAZ 3-60-575 4.8 33 0.5 7 15 15 23.01 [2.14] 1 3500[1652] 145[4111] 230[104.3] 240[108.9]
..�. 060CAZ 3-60-208/230 15.6/15.6 110 1.2 21/21 25/25 35/35 23.01 [2.14] 1 3500[1652] 180[5103] 250[113.4] 260[117.9]
/ 060DAZ 3-60-460 7.8 52 0.6 11 15 15 23.01 [2.14] 1 3500[1652] 180[5103] 250[113.4] 260[117.9]
060JAZ 1-60-208/230 26.3/26.3 134 1.2 35/35 45/45 60/60 23.01 [2.14] 1 3500[1652] 180[5103] 250[113.4] 260[117.9]
060YAZ 3-60-575 5.8 38.9 0.5 8 15 15 23.01 [2.14] 1 3500[1652] 180[5103] 250(113.4] 260[117.9]
[ ]Designates Metric Conversions
18 Ruud Air Conditioning Division
.., ,
r.,,, COMcheck Software Version 3.8.1
Mechanical Compliance Certificate
2009 IECC RECEIVED
Section 1 : Project Information JUN - 6 2013
Project Type: New Construction CITY OFTIGARD
Project Title : Beman Summers BUILDING DIVISION'
Construction Site: Owner/Agent: Designer/Contractor:
7175 SW Beveland St
Tigard,OR 97223
Section 2: General Information
Building Location(for weather data): Tigard,Oregon
Climate Zone: 4c
Section 3: Mechanical Systems List
Quantity System Type&Description
1 HVAC System 1 (Single Zone):
Cooling: 1 each-Split System,Capacity=60 kBtu/h,Efficiency= 13.00 SEER,Air-Cooled Condenser,Air
Economizer
- Section 4: Requirements Checklist
Requirements Specific To: HVAC System 1 :
1. Equipment minimum efficiency: Split System: 13.0 SEER
E-2. Cooling system provides a means to relieve excess outdoor air during economizer operation.
0'3. Integrated air economizer required
Generic Requirements: Must be met by all systems to which the requirement is applicable:
! 1. Plant equipment and system capacity no greater than needed to meet loads
• Exception:Standby equipment automatically off when primary system is operating
Li Exception:Multiple units controlled to sequence operation as a function of load
e-2. Minimum one temperature control device per system
A/AD 3. Minimum one humidity control device per installed humidification/dehumidification system
[0-4. Load calculations per ASHRAE/ACCA Standard 183
-5. Automatic Controls:Setback to 55°F(heat)and 85°F(cool);7-day clock,2-hour occupant override, 10-hour backup
j Exception:Continuously operating zones
U Exception:2 kW demand or less,submit calculations
6. Outside-air source for ventilation;system capable of reducing OSA to required minimum
7. R-5 supply and return air duct insulation in unconditioned spaces
R-8 supply and return air duct insulation outside the building
R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
p Exception: Ducts located within equipment
j Exception:Ducts with interior and exterior temperature difference not exceeding 15°F.
• a-8. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
21.9. Ducts sealed-longitudinal seams on rigid ducts;transverse seams on all ducts;UL 181A or 181B tapes and mastics
10.Hot water pipe insulation: 1.5 in.for pipes<=1.5 in.and 2 in. for pipes>1.5 in.
N/ Chilled water/refrigerant/brine pipe insulation: 1.5 in.for pipes<=1.5 in.and 1.5 in.for pipes>1.5 in.
Steam pipe insulation: 1.5 in.for pipes<=1.5 in.and 3 in.for pipes >1.5 in.
Project Title: Beman Summers Report date: 06/05/13
Data filename: Untitled.cck Page 1 of 2
rD Exception:Piping within HVAC equipment.
L] Exception.Fluid temperatures between 55 and 105°F.
• Exception:Fluid not heated or cooled with renewable energy.
Li Exception:Piping within room fan-coil(with AHRI440 rating)and unit ventilators(with AHRI840 rating).
L] Exception:Runouts<4 ft in length.
Lik11.Operation and maintenance manual provided to building owner
"ifj 12.Balancing devices provided in accordance with IMC(2006)603.17
0,4p 13.Demand control ventilation(DCV)present for high design occupancy areas(>40 person/1000 ft2 in spaces>500 ft2)and served by
systems with any one of 1)an air-side economizer,2)automatic modulating control of the outdoor air damper,or 3)a design outdoor
airflow greater than 3000 cfm.
•
Li Exception:Systems with heat recovery.
[3 Exception:Multiple-zone systems without DDC of individual zones communicating with a central control panel.
U Exception:Systems with a design outdoor airflow less than 1200 cfm.
L] Exception:Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm.
14.Motorized,automatic shutoff dampers required on exhaust and outdoor air supply openings
Li Exception:Gravity dampers acceptable in buildings<3 stories
Li Exception:Gravity dampers acceptable in systems with outside or exhaust air flow rates less than 300 cfm where dampers are
interlocked with fan
N 15.Automatic controls for freeze protection systems present
Fit 16.Exhaust air heat recovery included for systems 5,000 cfm or greater with more than 70%outside air fraction or specifically exempted
[] Exception: Hazardous exhaust systems,commercial kitchen and clothes dryer exhaust systems that the International Mechanical
Code prohibits the use of energy recovery systems.
L] Exception:Systems serving spaces that are heated and not cooled to less than 60°F.
[] Exception:Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy.
L] Exception:Heating systems in climates with less than 3600 HDD.
L i Exception:Cooling systems in climates with a 1 percent cooling design wet-bulb temperature less than 64°F.
[] Exception:Systems requiring dehumidification that employ energy recovery in series with the cooling coil.
L] Exception:Laboratory fume hood exhaust systems that have either a variable air volume system capable of reducing exhaust and
• makeup air volume to 50 percent or less of design values or,a separate make up air supply meeting the following makeup air
requirements:a)at least 75 percent of exhaust flow rate,b)heated to no more than 2°F below room setpoint temperature,c)cooled
to no lower than 3°F above room setpoint temperature,d)no humidification added,e)no simultaneous heating and cooling.
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications
and other calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 2009 IECC
requirements in COMcheck Version 3.8.1 and to comply with the man requirements in the Req rements Checklist.
Name-Title Signature Date
Project Title: Beman Summers Report date: 06/05/13
Data filename: Untitled.cck Page 2 of 2