Report ., . 7 iii Building Division Oregon State Mechanical Specialty Code Provision 507.16 TIGARD COMMERCIAL KITCHEN HOOD PERFORMANCE VERIFICATION Mechanical Permit No.: ZOrV _CO ZD Z Jurisdiction: ileC Site Address: 7069 560 ilice.l7 E1.11D 1 YS- Type of Hood: ® Type I Hood ❑ Type II Hood Classification of Cooking Appliances: ❑ Extra Heavy Duty p Heavy Duty ❑ Medium Duty ❑ Light Duty CFM of exhaust fan intake 10 minute test: Start of test: 3$z5 - End of test: 36-x.4-/Z5- Dimension of duct opening into hood: l9X (? re Duct Velocity: /826 FPM Length of Hood: 8 yZy Amount of total makeup air provided for all hoods: 31(1?'Z- CFM Signature: �� Date: 5" 3- .0/4/ Print name of person performing test: (f -4/ (47 c2 Print name of Contractor: (a) Sys 6eS cic,74)4 3 CCB #: /827/g This form satisfies the requirements of Oregon State Mechanical Specialty Code provision 507.16. All information given on this sheet shall be provided by the installing contractor or air balancing agency if applicable. Information given shall be obtained by the field testing and site verification of installation information. This form shall be completed and submitted to the inspector prior to fmal inspection approval. 1'\Building\Forms\COM-KitchenHoodPerfVerifdoc 07/01/08 Hood, Mechanical and Ventilation Caesar's Construction, LLC. DATE; 6 / 3 / 2014 CCB# 182918 Po Box 1231, Clackamas, OR 97015 Phone 503-734-4490 Fax 877-849-6232 hmvcontractors®gmail.corn COMERCIAL KITCHEN HOOD PERFORMANCE VERIFICATION CITY OF Tigard Mechanical permit Number: Mec2014-00202 Street Address: 9009 sw hall blvd 145 Type I Hood Type II Hood: X_ Canopy Hood Non Canopy Hood CFM of exhaust fan intake 10 min test: Start of test: 3825 End of test: 34425 Dimension of duct opening into hood: 19" x 19" Velocity of exhaust in duct: 1826 Horizontal surface area of hood: 8424 Amount of makeup air provided: 3442 cfm, ,5ov /o/c z_ - 3 zolc/ Printed name /of person performing test Signature/Date eSG(r S. Ens kt-,7[0 s /8 G 7 4 Contractor Name CCb This form satisfies the requirements of Oregon State Mechanical Specialty Code Provision 507.17 all information given on this sheet shall be provided by the installing Contractor or air balancing agency if applicable. Information given shall be obtained by The field testing and site verification of installation information. This form shall be completed and submitted to the inspector prior to final inspection aprobal. Thank you for your business! Exhaust Baffle Filter CFM Worksheet for Shortridge VelGrid Job Number=OLLS` rev.4 Job Name= 13DF46(26. Hood Number 1 Information Model=4818SND2-PSP-F Length= 12Ilotes: Filter#1 Filter#2 Filter#3 Filter#4 Filter#5 _ Filter#6 _ Filter#7 — Filter#8 _ Filter#9 Filter#10 Filter#11 Total CFM Filter Size 16"x 20" 16"x 20" 5 16"x 20" 16"x 20" 7` 16"x 20" - 16"x 20" 16"x 20" 16"x 20" 16"x 20" TNo Filter I No Filter 1 Velocity 182 193 205 218 230 208 206 200 184 CFM 378 401 426 453 477 432 428 415 382 0 0 3791 Hood Number 2 Information Model= Length= Notes: Filter#1 Filter#2 Filter#3 Filter#4 Filter#5 Filter#6 Filter#7 _Filter#8 _ Filter#9 Filter#10 Filter#11 Total CFM Filter Size No Filter No Filter No Filter 1 1 No Filter No Filter No Filter No Filter No Filter No Filter No Filter No Filter Velocity CFM 0 0 0 0 0 0 0 0 0 0 0 0 Hood Number 3 Information Model- Length= Notes: Filter#1 Filter#2 Filter#3 Filter#4 Filter#5 Filter#6 _ Filter#7 _ Filter#8 _ Filter#9 _ Filter#10 Filter#11 Total CFM Filter Size No Filter No Filter No Filter No Filter No Filter No Filter No Filter No Filter No Filter No Filter No Filter Velocity _ CFM 0 0 0 0 0 0 0 _ 0 0 0 0 0 Hood Number 4 Information Model= Length= Notes: Filter#1 Filter#2 Filter#3 Filter#4 _ Filter#5 Filter#6 Filter#7 Filter#8 Filter#9 Filter#10 Filter#11 Total CFM Filter Size ,No Filter No Filter No Filter No Filter No Filter No Filter r No Filter TNo Filter .No Filter r,No Filter No Filter Velocity CFM 0 0 0 0 0 0 0 _ 0 0 0 _ 0 0 Total Exhaustt CFM's= 3791 CFM a