Specifications •
Form 4a Project Name: 5At •Page: i
SYSTEMS - GENERAL Part 1 of 6
Applicability Plans /Specs
Discussion of qualifying Show compliance by including a drawing sheet, detail number;
exceptions on page 4 -25 specification section and subparagraph.
1. Applicablity (Section 1317)
is form required?
Form Required. Complete form if a new HVAC system is being installed, or components of an
existing HVAC system are being replaced (I.e., equipment, controls, ductwork, and insulation.)
❑ Exception. The building or part of the building qualifies for an exception from HVAC code
requirements. Applicable code exception is Section 1317.1. Portions of the building that
qualify:
Area: Exception ❑ -1 Li -2 ❑ -3
Area: Exception Li -1 ❑ -2 ❑ -3
Area: Exception ❑ -1 ❑ -2 1:I -3
LI Form Not Required. This project does not contain work required to comply with code.
1 2ample or Complex Systems (Section 1317.9 or 1317.10)
L Simple System. Building contains only Simple HVAC System(s). Complete this form (4a) and
equipment efficiency worksheets as required. Form 4b is not required.
❑ Complex System. Project includes a Complex System. Complete this form (4a), form 4b and
equipment efficiency worksheets as required.
3. Equipment Performance (Section 1317.5)
❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment,
bustion heating equipment, or heat - operated cooling equipment.
Complies. All new HVAC equipment have efficiencies not less than those required by code.
The following equip ent efficiency worksheets are attached:
❑ -4a 0 -4b -4c 0 -4d ❑ -4e ID -4f ❑ -4g ❑ -4h ❑ -4i ❑ -4j
4. Duct Insulation and Sealing (Sections 1317.7 as 1317.8)
❑ Ducts. The building plans and specifications do not call for new HVAC ducts or plenums.
C omplies. The plans and specifications call for all air - handling ducts and plenums to be insulated
and sealed as required by Sections 1317.7 &1317.8.
5. )M tribution Transformers (Section 1316.1)
cu Distribution Transformers. The plans /specs do not call for new distribution transformers.
❑ Complies. All new distribution transformers comply with efficiency, testing, and labeling
requirements of Section 1316.1.1.
❑ Exception. The project qualifies for an exception per Section 1316.1.1, Exceptiion:
❑ -1 ❑ -2 ❑ -3 ❑-4 ❑ -5 ❑ -6 ❑ -7 ❑ -8 ❑ -9 ❑ -10 ❑ -11 ❑ -12 ❑ -13 ❑ -14
Attach relevant documentation for appropriate exception. The plans /specs show compliance in the
following locations: •
11 7
4-1
April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: k Page: Z
SYSTEMS - GENERAL Part 2 of 6
6. HV C Controls (Section 1317.4)
.1 System Thermostat /Zone Controls (Section 1317.4.1)
Complies. All new HVAC systems include at least one temperature control device responding to
temperatures within the zones.
❑ Exception. HVAC system qualifies for an exception from zone control requirements.
The applicable code exception is Section 1317.4.2, Exception ❑ -1 ❑ -2
Portions of the building that qualify:
The plans /specs show compliance in the following locations:
6.2 Off - hour Controls - Auto Setback or Shutdown (Section 1317.4.3)
❑ Complies. Systems must have at least one of the following features:
❑ Control Setback Complies. Each system is equipped with automatic control capable of
r using energy through control setback during periods of non -use or alternate use of spaces
Equipment Shutdown Complies. Each system is equipped with controls capable of reducing
energy use through automatic shutdown during periods of non -use or alternate use of spaces.
❑ AC systems with equipment shutdown are equipped with at least one of the following:
im
Programmable controls (1317.4.3.1 (1))
. ❑ Occupant sensor (1317.4.3.1 (2))
❑ Interlocked to a security system (1317.4.3.1 (3))
LI Manually activated timers with 2 -hour operation max (1317.4.3.1 (4))
Li Exception. The building qualifies for an exception to the requirement for automatic setback or _
shutdown controls. The applicable code exception is Section 1317.4.3 Exception ❑ -1 ❑ -2
The plans /specs show compliance in the following locations:
_ Control Capabilities (Sec. 1317.4.2.1)
Complies. Zone thermostats are capable of being set to the temperatures described in Sec.
1317.4.2.1. Where used to control both heating and cooling, zone controls shall be capable of
providing a temperature range or deadband of at least 5 degrees F within which the supply of
heating and cooling energy to the zone is shut off or reduced to a minimum.
❑ Exception. The building qualifies for an exception to the deadband requirements.
The applicable code exception is Section 1317.4.2.t Exception ❑ -1 ❑ -2
Portions of the building that qualify:
The plans /specs show compliance in the following locations:
I
6.4 Optimum Start Controls (Section 1317.4.3.2)
❑ Complies. Separate HVAC systems have controls capable of varying s - •• JIM- : system to
meet temperature set point at time of occupancy.
Exception. HVAC systems have a design supply air capacity of exceeding 10,000 cfm.
The plans /specs show compliance in the following locations:
IM
• 6.5 eat Pump Controls (Section 1317.4.4)
❑ Heat Pump. The plans /specs do not call for a new heat pump
Complies. All new heat pumps equipped with supplementary heaters are controlled to minimize
the use of supplemental heat as defined in Section 1317.4.4.
. The plans /specs show compliance in the following locations:
4 -2 April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: S _(MG∎ Page:
SYSTEMS - GENERAL Part 3 of 6
7. Economizer Cooling (Section 1317.3)
❑ No Cooling. The building plans do not call for a new fan system with mechanical cooling.
❑ Complies. Each new fan system has an air economizer capable of modulating outside -air and
r n -air dampers to provide up to 100 percent of the esign supply air as outside air.
E xception At least one new fan system qualifies r an exception. The applicable code exception
is Section 1317.3, Exception ❑ -1 ❑ -2 -3 ❑ -4 ❑ -5 ❑ -6
If Exception 3 is selected complete the following:
(a) Total cooling capacity of exempt units (Btu /hr) -911?-00
otal installed building cooling capacity (Btu /hr) 39 `),pp
Complies. Sum of exempt units rated at less than 54,000 Btu /hr is <240,000 or a/b
< 0.10 (10% of total building cooling capacity).
Unit Identifier of exempt units:
The plans /specs show compliance in the following locations:
I
8. conomizer Pressure Relief & Integration (Section 1317.3.1 and 1317.3.2)
No Economizers Required. Project does not contain a new fan system requiring economizers.
❑ Overpressurization Complies. The drawings specifically identify a pressure relief mechanism for
each fan system that will relieve the extra air introduced by the economizer.
❑ Integration Complies. Economizer is capable of providing partial cooling even when additional
mechanical cooling is required to meet the remainder of the cooling load.
❑ Exception. The applicable exception is Section 1317.3.2, Exception LI -1 ❑ -2
The plans /specs show compliance in the following locations:
11 / 14t Gas Bypass (Section 1317.5)
No Hot Gas Bypass
❑ Complies. See allowable amount of hot gas bypass as a percentage of total cooling capacity in
table below.
Unit ID Rated Cooling Capacity Hot Gas Bypass Capacity
Allowable Hot Gas Bypass
'M Rated Cooling Capacity Max Hot Gas Bypass
- :•( <240,000 Btu/ hr 50%
>240,000 Btu /hr 25%
❑ Exception. Unitary packaged system with cooling capacity no greater than 90,000 Btu /h
4 -3 April 2005
• Compliance with OSSC, effective 01/01/05
Form 4a Project Name: 1 -A'C6-(.,t/r3 Page: L
SYSTEMS - GENERAL Part 4 of 6
10. Shutoff Dampers (1317.4.3.3)
❑ t Required. Shutoff dampers are not required on this project.
C omplies. Each outdoor air supply & exhaust system shall be equipped with motorized dampers
❑ Exception. The building qualifies for an exception to the motorized damper requirement. The
applic -able code exception is Section 1317.4.3.3 Exception ❑ -1 ❑ -2 ❑ -3 ❑ -4 ❑ -5
The plans /specs show compliance in the following locations: /s
1. Shutoff Damper Controls (Section 1317.4.3.3.1)
C omplies. Outdoor air supply and exhaust systems shall be provided dampers that automatically
shut when systems or spaces served are not in use or during building warm -up, cooldown, or
setback.
❑ Complies. Stair and shaft vents are capable of being automatically closed during normal building
operation and interlocked to open as required by fire and smoke detection systems.
The plans /specs show compliance in the following locations:
1I 1
.2. Motorized Damper Leakage (1317.4.3.3.2)
C omplies. Motorized outdoor air supply and exhaust air dampers have a maximum leakage rate
of 4 cfm /ft2 at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998.
❑ Exception. Packaged HVAC equipment may have maximum leakage rate of 20 cfm /ft at 1.0 in
w.g. when tested in accordance with AMCA Standard 500 -1998.
•
The plans /specs show compliance in the following locations:
I
1 'p Insulation (Section 1314)
No New Piping. The building plans and specifications do not call for new piping serving a
heating or cooling system or part of a circulating service water heating system.
l> Complies. All new piping serving a heating or cooling system or part of a circulating service
i ts; water heating system complies with the requirements of the Code, Section 1314.1.
Ni' Exception. New piping qualifies for exception: Section 1314.1, Exception ❑ -1 ❑ -2
1 Occupancy Ventilation
Complies. Mechanical ventilation systems provide the required amount of ventilation specified
in Chapter 4 of the Oregon Mechanical Specialty Code.
•
❑ Complies. Natural ventilation systems provide required amount of ventilation as certified by a
reg- istered architect or engineer as specified by Section 1203.4.1, Exception. Attach worksheet
The plans /specs show compliance in
the following locations: m t
The plans /specs show compliance .
on the following pages:
4 -4
April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: S e-t Page: 5
SYSTEMS - GENERAL U Part 5 of 6
13. High Occupancy Ventilation (Section. 1317.2.2)
❑ Complies. HVAC systems with ventilation air capacities of 1,500 CFM or greater that serve
areas having an average occupant load of 20 square feet per person or less from Table
1004.1.2 have a means to automatically reduce outside air intake.
Identify applicable systems:
Plans /specs indicate where equipment (i.e. carbon dioxide sensor) and sequence is specified:
AM I
❑ Exception. HVAC systems are equipped with an energy recovery device with at least 50%
_ effectiveness.
11KNo High Occupancy Systems. Project does not contain an HVAC system as described above.
c i c i t ygxhaust Air Heat Recovery (Section 1318.3)
Not Regulated. HVAC system does not have: 1) design supply air cap. of >10,000 cfm, and 2)
min. outside air supply >70 %, and 3) at least 1 exhaust fan rated at 75% of min outside air
❑ Complies. Heat recovery system increases outside air temperature by 20 °F (Climte Zone 1) or
30 °F (Zone 2) and has provision to provide bypass during air economizer mode.
❑ Exception. An HVAC system qualifies for an exception to this requirement. Applicable
exception from Section 1318.3 Exception ❑ -1 ❑ -2 ❑ -3 ❑ -4 ❑ -5 ❑ -6 ❑ -7
The plans /specs show compliance in the following I •
locations:
Marge Volume Fan Systems (Section 1318.4.2.4)
' Not Regulated. The building plans or specifications do not call for fan systems over 15,000
CFM that serve a single zone and function for the purpose of temperature control.
❑ Complies. Fan systems are equipped with variable frequency drive or two speed motor to
reduce airflow as required by Section 1318.4.2.3.
The plans /specs show compliance in the following c
locations:
y ! variable Speed Drives (Section 1317.10.3.1)
Not Regulated. The building plans or specifications do not call for fan and pump motors 10
horsepower and greater that serve variable -flow air or liquid systems.
❑ Complies. All fan and pump motors 10 hp and greater which serve variable -flow air or liquid
systems are controlled by a variable -speed drive.
❑ Exception. The building qualifies for an exception to the variable -speed drive requirement.
Portions of the building that qualify: -
Applicable code exception is Section 1317.10.3.1, Exception
The plans /specs show compliance in the following
locations: r V
Service Water Heating (Sec. 1315)
N o New Water Heating. The building plans and specifications do not call for new water
heaters, hot water storage tanks or service hot water distribution systems.
❑ Complies. All new water heaters, hot water storage tanks or service hot water distribution
systems comply with the requirements of the Section 1315.
❑ Exception. The applicable code exception is Section: Exception:
Portions of the building that qualify:
N 't 1
The plans /specs show compliance in the following locations:
4 -5 April 2005
Compliance with OSSC, effective 01/01/05
•
Form 4a Project Name: `� Wl Gv P) Page:
SYSTEMS - GENERAL Part 6 of 6
1 wimmiag Pools, Spas and Hot Tubs (Section 1315.5)
No New Pools. The building plans and specifications do not call for new, swimming pools, spas or
hot tubs.
❑ On /Off Controls Complies. Spa and hot tub heaters are equipped with a readily accessible
ON /OFF switch as required by Section 1315.5.1.
❑ Ventilation Controls Complies. Pool ventilation system is controlled based on humidity.
❑ Cover Complies. All heated pools, hot tubs and spas are equipped with a cover.
❑ Heat Recovery Complies. Pools, Spas, and hot tubs, over 200 ft utilize recovered heat as
•
required by Section 1315.5.3.
❑ Exception. Heat recovery is not necessary as pool is heated by renewable energy or waste
heat recovery sources capable of providing at least 70 percent of the heating energy
required over an operating season.
Fume Hoods (Section 1317.2.1.)
No Fume Hoods. The building plans do not call for fume hood systems that have a total exhaust
rate greater than 15,000 cfm.
❑ Complies. Fume hood systems have at least one of the following features:
❑ Variable air volume hood exhaust and room supply systems capable of reducing exhaust
and makeup air volume to 50% or less of design values.
❑ Direct makeup (auxiliary) air supply equal to at least 75% of the exhaust rate, heated no
warmer than 2° F below room set point, cooled no cooler than 3° F above room set point,
no humidification added, and no simultaneous heating and cooling used for
dehumidification control.
❑ Heat recovery systems to precondition makeup air from fume hood exhaust in accordance
with 1318.3 - Exhaust Air Energy Recovery, without using any exception.
The plans /specs show compliance in the following locations:
2Q'Parking Garage Ventilation (Section 1317.2.3)
No Enclosed Garages. The building plans and specifications do not call for enclosed Group S -2
parking garages with a ventilation exhaust rate greater than 30,000 CFM.
❑ Complies. The plans and specifications call for carbon monoxide sensing devices as required by
Section 1317.2.3.
❑ Exception. Open parking garages.
2],,l itchen Hoods (Section 1317.11)
Not Regulated. The plans /specs do not call for any new kitchen hoods with exhaust capacity
greater than 5,000 cfm each.
❑ Complies. All new kitchen hoods with a total exhaust capacity greater than 5,000 cfm have at
least 50 percent of the required makeup air; (a) unheated or heated to no more than 60 °F; and (b)
uncooled or evaporatively cooled.
s. "rr
The plans /specs show compliance in the following locations:
‘t\iN
r utside Heating Systems (Section 1317.12)
Outside Heating Systems. The plans /specs do not call for new permanently installed heating
systems outside the building.
❑ Complies. All new permanently installed outside heating systems are radiant gas fired systems
controlled by an occupancy sensor or timer switch as required by Section 1317.12.
4 -6 April 2005
Compliance with OSSC, effective 01/01/05
•
Worksheet 4c Project Name: S `r\os -- .6.4-6 Page:
UNITARY HEAT PUMP - AIR COOLED
Equipment (a) (b) (c) (d) (e) (f)
Proposed Rating Proposed Heating Rating
Discussion of equip-
ment ratings and Cooling Compliance
• equipment definitions Capacity COP COP Schedule
on page 4 -19. Equip. ID Model Designation (Btu /h) SEER EER HSPF (47 °F) (17 °F) (A -E)
6N6•41 - t 6 VeK to '3 `I, c /04c 1.< 3 'D 3
. Required Indicate source of information
Document- ❑ ARI Unitary Directory, Section AC, page:
ation
❑ A I Applied Products directory, Section ULE, Page:
Product data (Attach data furnished by the equipment supplier, I.e., "cut sheets ")
Code Cooling Capacity Minimum Cooling
(btu /hr) Rating Minimum Heating Rating
Required Compliance But not Seasonal or COP COP
Efficiencies Schedule Equipment Type Over over EER Part Load HSPF (@ 47 °F) (@ 17 °F)
0 65,000 - 9.7 SEER 6.6 - -
Single Package Without a 65,000 135,000 10.1 n/a - 3.2 2.2
This schedule of A Heating Section or With
equipment efficien- Electric Resistance Heat 135,000 240,000 9.3 n/a - 3.1 2.0
cies was reformat- 240,000 - 9.0 9.2 IPLV - 3.1 2.0
tad from the code, 0 65,000 - 10 SEER 6.8
Table 13-M. Split System Without a
B Heating Section or With 65,000 135,000 10.1 n/a - 3.2 2.2
Electric Resistance Heat 135,000 240,000 9.3 n/a - 3.1 2.0
240,000 - 9.0 9.2 IPLV - 3.1 2.0
Single Package With a 0 65,000 - 9.7 SEER 6.6 -
C Heating Section Other Than 65,000 135,000 9.9 n/a - 3.2 2.2
O Electric Resistance 135,000 240,000 9.1 n/a - 3.1 2.0
240,000 - 8.8 9.0 IPLV - 3.1 2.0
Split System With a Heating 0 65,000 - 10 SEER 6.8 - -
D Section Other Than Electric 65,000 135,000 9.9 n/a 3.2 2.2
Resistance 135,000 240,000 9.1 n/a - 3.1 2.0
_ 240,000 - 8.8 9.0 IPLV - 3.1 2.0
4 -13
Compliance with OSSC, effective 01/01/05
•
•
COMBINATION RATINGS Continued
ARI STANDARD RATINGS"
Cooling Heating
Seasonal Efficiency SEER High -Temp Low -Temp
Bryant
Factory- Gas Fur -
UNIT Supplied nace or
SIZE- INDOOR Enhance- Standard Accessory Accessory
SERIES UNIT TC ment Rating TXV" TDR$ EER TC COP TC COP HSPF
FC4CNF036 28,400 TDR &TXV 10.00 - - 8.85 29,200 3.08 17,500 2.18 7.2
FF1 DNA030 28,200 TDR 10.00 - - 9.20 29,000 3.10 17,400 2.18 7.2
FG3AAA036 28,200 NONE - 10.00 10.00 9.10 29,000 3.08 17,200 2.20 7.2
FK4CNF0O1 28,200 TDR &TXV 10.50 - - 9.95 28,000 3.18 16,500 2.30 7.3
FK4CNFOO2 28,400 TDR &TXV 11.00 - - 10.00 28,200 3.26 16,600 2.32 7.5
FK4CNF003 28,800 TDR &TXV 11.00 - - 10.30 28,000 3.30 16,400 2.36 7.5
FK4DNFOO1 28,200 TDR &TXV 10.50 - - 9.95 28,000 3.18 16,500 2.30 7.3
FK4DNF002 28,400 TDR &TXV 11.00 - - 10.00 28,200 3.26 16,600 2.32 7.5
FK4DNF003 28,800 TDR &TXV 11.00 - - 10.30 28,000 3.30 16,400 2.36 7.5
COILS + 315(A,J)AV036070 VARIABLE - SPEED FURNACE
030-E, F CC5A/CD5AA036 28,600 TDR 11.00 - - 10.10 27,400 3.20 16,000 2.30 7.2
CE3AA036 28,000 TDR 10.80 .- - 9.95 27,400 3.14 16,000 2.28 7.2
CK3BA036 28,600 TDR 11.00 - - 10.10 27,400 3.24 16,300 2.32 7.2
CK5A/CK5BA036 28,600 TDR 11.00 - - 10.10 27,400 3.24 16,300 2.32 7.2
CK5A/CK5BT036 28,600 TDR 11.00 - - 10.10 27,400 3.24 16,300 2.32 7.2
COILS + 315(A,J)AV0 VAR IABLE - SPEED FURNACE
CC5A/CD5AA036 28,600 TDR 11.00 - - 10.25 27,400 3.22 15,900 2.32 7.2
CC5A/CD5AW036 28,600 TDR 11.00 - - 10.25 27,400 3.22 15,900 2.32 7.2
CE3AA036 28,600 TDR 11.00 - - 10.15 27,400 3.16 15,800 2.32 7.2
CK3BA036 28,600 TDR 11.00 - - 10.25 27,400 3.26 16,200 2.34 7.2
CK5A/CK5BA036 28,600 TDR 11.00 - - 10.25 27,400 3.26 16,200 2.34 7.2
CK5A/CK5BW036 28,600 TDR 11.00 - - 10.25 27,400 3.26 16,200 2.34 7.2
'F(A,B)4BN(F,C)036 34,200 TDR 10.00 - - 9.30 35,000 3.10 21,200 2.24 7.2
CC5A/CD5AA036 34,200 NONE - 10.00 10.00 9.60 35,000 3.16 23,400 2.26 7.2
CC5A/CD5AA042 34,800 NONE - 10.20 10.20 9.60 35,000 3.16 21,000 2.26 7.2
CC5A/CD5AW036 34,200 NONE - 70.00 10.00 9.60 35,000 3.16 21,000 2.26 7.2
CC5A/CD5AW042 34,400 NONE - 10.20 10.20 9.35 35,000 3.12 20,800 2.26 7.2
CE3AA036 34,200 NONE - 10.10 10.10 9.55 34,800 3.12 20,800 2.24 7.2
CE3AA042 34,600 NONE - 10.20 10.20 9.55 35,000 3.18 21,000 2.28 7.2
CF5AA036 34,200 NONE - 10.00 10.00 9.55 34,800 3.14 20,800 2.26 7.2
CK3BA036 34,200 NONE - 10.00 10.00 9.60 35,000 3.18 21,000 2.28 7.2
CK3BA042 34,800 NONE - 10.20 10.20 9.60 35,000 3.18 21,000 2.28 7.2
CK5A/CK5BA036 34,200 NONE - 10.00 10.00 9.60 35,000 3.18 21,000 2.28 7.2
CK5A/CK5BA042 34,800 NONE - 10.20 10.20 9.60 35,000 3.18 21,000 2.28 7.2
CK5A/CK5BT036 34,200 NONE - 10.00 10.00 9.60 35,000 3.18 21,000 2.28 7.2
CK5A/CK5BT042 34,800 NONE - 10.20 10.20 9.60 35,000 3.18 21,000 2.28 7.2
CK5A/CK5BW036 34,200 NONE - 10.00 10.00 9.60 35,000 3.18 21,000 2.28 7.2
F(A,B)4AN(F,B,C)042 34,800 TDR 10.20 - - 9.55 35,200 3.16 21,200 2.26 7.4
F(A,B)4AN(F,C)036 34,200 TDR 10.00 - - 9.30 35,000 3.10 21,200 2.24 7.2
F(A,B)4BN(F,B,C)042 34,800 TDR 10.20 - 9.55 35,200 3.16 21,200 2.26 7.4
FC4BN(F,B)042 34,800 TDR &TXV 10.20 - - 9.55 35,200 3.16 21,200 2.26 7.4
cdrilicor FC4BNF08 34,200 TDR &TXV 1000 - - 9.30 35,000 3.10 21,200 2.24 7.2
j
FC4CN(F,B)042 34,800 TDR &TXV 10.20 9.55 35,200 3.16 21,200 2.26 7.4
FC4CNFO36 34,200 TDR &TXV 10.00 9.30 35,000 3.10 21,200 2.24 7.2
FG3AAAO36 34,000 NONE 10.00 10.00 9.55 34,000 3.10 20,800 2.24 7.0
FK4CNFOO1 33,800 TDR &TXV 11.00 - - 10.05 34,000 3.20 20,200 2.32 7.5
FK4CNFOO2 33,800 TDR &TXV 11.00 - - 10.05 34,000 3.28 20,400 3.34 7.5
FK4CNF003 34,200 TDR &TXV 11.50 - - 10.50 34,000 3.30 20,000 2.38 7.5
FK4DNFOO1 3 33,800 TDR&TXV 11.00 - - 10.05 34,000 3.20 20,200 2.32 7.5
036 D� F
E, FK4DNFOO2 33 F� TX
34, 00 TDR&TXV 11.50 - - 10.50 34,000 3.30 20,000 2.38 7.5�
t '
COILS + 315(A,J)AV036070 VARIABLE - SPEED FURNACE
CE3AA042 34,600 TDR 11.00 - - 10.00 34,000 3.24 20,200 2.36 7.4
CK5NCK5BEO42 34,800 TDR 11.00 - 10.00 34,200 3.28 20,200 2.36 7.4
,r COILS + 315(A,J)AVO48090 VARIABLE - SPEED FURNACE
CC5A/CD5AA042 34,600 TDR 11.00 - - 10.15 33,800 3.24 19,800 2.36 7.4
CE3AA042 34,800 TDR 11.20 - - 10.15 34,000 3.26 20,000 2.38 7.4
CK3BA042 34,600 TDR 11.20 - - 10.10 34,000 3.28 20,000 2.38 7.4
CK5A/CK5BA042 34,600 TDR 11.20 - - 10.10 34,000 3.28 20,000 2.38 7.4
CK5NCK5BE042 34,800 TDR 11.20 - - 10.15 34,000 3.32 20,200 2.40 7.4
CK5NCK5BT042 34,600 TDR 11.20 - - 10.10 34,000 _ 3.28 20,000 2.38 7.4
COILS + 315(A,J)AV066110 VARIABLE - SPEED FURNACE
CC5A/CD5AA042 34,600 TDR 11.20 - - 10.25 33,600 3.26 19,700 2.38 7.4
CC5NCD5AW042 34,200 TDR 11.20 - - 10.20 33,600 3.22 19,600 2.36 7.4
CE3AA042 34,800 TDR 11.20 - - 10.20 34,000 3.28 20,000 2.38 7.4
CK3BA042 34,800 TDR 11.20 - - 10.20 34,000 3.30 20,000 2.40 7.4
CK5A/CK5BA042 34,800 TDR 11.20 - 10.25 34,000 3.30 20,000 2.40 7.4
CK5NCK5BT042 34,600 TDR 11.20 - - 10.20 34,000 3.30 20,000 2.40 7.4
COILS + 315(A,J)AV066135 VARIABLE - SPEED FURNACE
CC5A/CD5AA042 34,600 TDR 11.20 - - 10.20 33,800 3.24 19,800 2.36 7.4
CC5NCD5AW042 34,200 TDR 11.20 - - 10.15 33,600 3.22 19,700 2.36 7.4
CE3AA042 34,800 TDR 11.20 - - 10.15 34,000 3.28 20,000 2.38 7.4
CK3BA042 34,600 TDR 11.20 - - 10.15 34,000 3.28 20,000 2.40 7.4
CK5A/CK5BA042 34,600 TDR 11.20 - - 10.15 34,000 3.28 20,000 2.40 7.4
CK5NCK5BT042 34,600 TDR 11.20 - - 10.15 34,000 3.28 20,000 2.40 7.4
See notes on page 16.
-13-
•
•
. .dG- '} ;1' •
SPECIFICATIONS
MODEL FK4D -
SIZE 001 002 003 005 006* '
SHIPPING WEIGHT (Lb) 117 130 1 49 167 • - 202
REFRIGERANT R -22 _
Refr. Metering Device TXV
TXV SIZE 3 Ton I 3 Ton I 5 Ton I 5 Ton I 5 Ton
COIL
Type Slope I A I Slope I A I A
Rows - Fins/In. 3 - 14
Face Area (sq -ft) 2.97 I 3.46 I 3.46 I 5.93 I 7.42 .
• - FAN ,
Air Discharge Upfl. v, Downflow, HorizAtal •
525 / 470 525 / 470 700 / 630 875 / 785 1050 / 945
CFM (Nominal Clg/Htg) 700 / 630 700 / 630 875 / 785 1050 / 945 1225 / 1100
875 / 785 875 / 785 1050 / 945 1225 / 1100 1400 / 1260
1050 / 945 1050 / 945 1225 / 1100 1400 / 1260 1750 / 1575
MOTOR HP (ECM) 1/2 1/2 1/2 1/2 3/4
FILTER 21 -1/2 x 16 -3/8 21 -1/2 x 16 -3/8 • 21 -1/2 x 19 -7/8 21 -1/2 x 19-7/8 21 -1/2 x 23 -5/16
• Modular Units
t Fan coil units with TXV must have a start capacitor and relay for single -phase out r (non -scro units.
-3-
• •
00-CbCC CM
SPEC.�L`, S Continued
UNIT SIZE- SERIES 661CO36 -D /E 661CO36 -F /G
Operating Weight (Lb) 176/185 176/185
ELECTRICAL
Unit Volts—Hertz--Phase 208 - 230-60 -1 208/230-60-3 460 -60-3
Operating Voltage Range° - .- . • 197 -253 414 -506
Compressor— Rated Load Amps 18.0/17.2 11.3/11.4 5.7/6.2
Locked Rotor Amps 105.0/86.0 78.0/90.0 40.0/45.0
Condenser Fan Motor —Full Load Amps 1 • 0.8
Min Unit Ampacity for Wire Sizing 23.9/22.9 15.5/15.7 7.9/8.6
Min Wire Size (60 °C Copper) (AWG)t 12 14 14
Min Wire Size (75 °C Copper) (AWG)•
•
12 14 14
Maximum Length (60 °C) (Ft)* 50/55 57/50 227/202
Maximum Length (75 °C) (Ft)$ 50/52 54/50 216/192
Max Branch Circuit Fuse Size °° 35 20 15
COMPRESSOR AND REFRIGERANT
Compressor —Type Scroll/Reciprocating) Reciprocating/Scroll
Refrigerant Charge (Lb) 0) 15 ft 6.38 6.38
OUTDOOR COIL & FAN
Coil Face Area (Sq Ft) 14.8
Fins per In.— Rows--Circuits 20-1-3
Fan Motor HP and RPM 1/4 and 1100 1/4 and 1100
Rated Airflow (CFM) 3000
OPTIONAL EQUIPMENT
Time -Delay Relay KAATD0101TDR
Outdoor Thermostat KHAOT0301 FST
Secondary Outdoor Thermostat KHAOT0201 SEC
Cycle Protector KSACY0101AAA
• Crankcase Heater KAACH1201AAA/Standard Standard
Compressor Start Assist — Capacitor /Relay Type KSAHS1501AAA/KSAHS1101AAA N/A
Compressor Start Assist —PTC Type KSACS0201 PTC N/A
Sound Hood KSASH1901CYUKSASH2001BRL KSASH2001BRUKSASH1901CYL
Bi -Flow TXV Kits (Hard Shutoff)tt KSATX0601HSO
Bi -Flow TXV Kits (RPB) KHATX0501 RPB
High - Pressure Switch KHAHI0101 HPS
Bi -Flow Filter Drier (Liquid Line) P504 -8083S (RCD)
Evaporator Freeze Thermostat KAAFT0101AAA
Isolation Relay KHAIR0101AAA
Liquid -Line Solenoid Valve (LSV)tt KHALSO401LLS
Low - Ambient Pressure Switch KSALA0201 R22
MotorMasterG --Low- Ambient Controller °° KSALA0401AAA . KSALA0501AAA
Ball Bearing Fan Motor HC40GE232 (RCD) HC40GE462 (RCD)
Thermidistat°M Control — Programmable
Thermostat with Humidity Control TSTATBBPRH01 -B
Thermostat —Auto Changeover,
Non - Programmable, °F/°C, Dual Fuel ttt
Must be used with Outdoor Sensor
(TSTATXXSEN01 -B) TSTATBBPDF01 -B
Thermostat —Auto Changeover,
7 -Day Programmable, °F / °C,
2 -Stage Heat, 1 -Stage Cool TSTATBBPHP01 -B
Thermostat —Auto Changeover,
Non - Programmable, °F/°C,
2 -Stage Heat, 1 -Stage Cool TSTATBBNHP01 -B
Builder's Thermostat — Manual Changeover,
Non - Programmable, °F,
2 -Stage Heat, 1 -Stage Cool TSTATBBBHP01
Outdoor Air Temperature Sensor TSTATXXSEN01 -B
Backplate for Non - Programmable Thermostat • TSTATXXNBP01
Backplate for Programmable Thermostat TSTATXXPBP01
Backplate for Builder's Thermostat TSTATXXBBP01
Thermostat Conversion Kit (4 to 5 wire) -10 Pack TSTATXXCNV10
See notes on page 9.
-5-
c tl V■1\ - t *ft.-5 .
ELECTRIC HEATER ELECTRICAL DATA _
BRANCH CIRCUIT
HEATER KW INTERNAL HEATER AMPS MIN AMPACITY MIN WIRE SIZE (AWG) MIN GND WIRE SIZE MAX FUSE/CKT BKR AMPS MAX WIRE LENGTH
PART N0. PHASE CIRCUIT 208!230V 208230V'• 208/2301/ft 208/230V 208230V 208230V (FT)44
PROTECTION Dual Circuit Dual Circuit Dual Circuit Dual Circuit Dual Circuit Dual Circuit
Single Single Single Single Single Single
240v 208v Circuit L1,L2 L3,L4 Circuit L1,L2 L3,L4 Circuit L1,L2 L3,L4 Circuit L1,L2 L3,L4 Circuit L1,L2 L3,L4 Circuit 11,12 13,14
KFCEH0401NO3 . 3 2.3 1 None 10.9/12.0 — — 15.9/17.3 — — 12/12 — — 12/12 — — 2020 — — 67/68 — —
KFCEH0501N05 5 3.8 1 None 18.1/20.0 — — 26.0/28.4 — — 10/10 — — 10/10 — — 30/30 — — 66/66 — —
5 5 3.8 1 None 18.1/20.0 — — 31.2/33.5 — — 8/8 — — 10/10 — — 35/35 — — 85/88
KFCEH2401CO5 5 3.8 1 CktBkr 18.1/20.0 — — 26.0/28.4 — — 10/10 — — 10/10 — — 30/30 — — 66/66 — —
KFCEH2401CO5 5 as 1 Ckt Bkr 18.1/20.0 — — 31.2/33.5 — — 8/8 — — 10/10 — — 35/35 — — 85/88 — —
KFCEH0801N08 8 6.0 1 None 28.9/32.0 — — 44.7/48.5 — — 8/8 — — 10/10 — — 45/50 — — 59/60 — —
KFCEH25o1C08 8 6.0 1 Ckt Bkr 28.9/32.0 — — 44.7/48.5 — — 8/8 — — 10/10 — — 45/50 — — 59/60 — —
9 6.8 1 None 32.8/36.0 — — 49.5/53.5 — — 8/6 — — 10/10 — — 50/60 — — 54/87 — —
KFCEH2901N09 — *
9 6.8 3 None 18.820.8 — — 32.0/34.5 — — 8/8 — — 10 /10 — — 35/35 — — 83/85 — —
KFCEH0901N10 10 7.5 1 None 36.2/40.0 — — 53.8/58.5 — — 6/6 — — 10/10 — — 60/60 — — 78/80 — —
KFCEH2601C10 10 7.5 1 CktBkr 36.2/40.0 — — 53.8/58.5 — — 6/6 — — 10/10 — — 60/60 — — 78/80 — —
KFCEH3001F15 "' 15 11.3 1 Fuse 54.2/59.9 38.2/40.0 18.1/20.0 78.3/83.4 53.8/58.5 22.7/25.0 4/4 6/6 10/10 8/8 10/10 10/10 80/90 60/60 25/25 88/89 78/80 75/76
KFCEH3101C15 15 11.3 1 CktBkr — 36.2/40.0 18.120.0 — 53.8/58.5 22.7/25.0 — 6/8 10/10 — 10/10 10/10 — 60/60 25/25 — 78/80 75/76
KFCEH1601315 15 11.3 3 None 31.3/34.6 — — 47.7/51.8 — — 8/6 — — 10/10 — — 50/60 — — 56/90 — —
KFCEH2001318 18 13.5 3 None 37.6/41.5 — — 55.5/60.4 — — 6/6 — — 10/8 — — 60/70 — — 76/77 — —
KFCEH3201F20•" 20 15.0 1 Fuse 72.3/79.9 36.2/40.0 36.2 /40.0 98.9/108.4 53.8/58.5 45.3/50.0 3/2 6/6 8/8 8/6 10/10 10/10 100/110 60/60 50/50 85 /109 7880 59/59
KFCEH3301C20'•' 20 15.0 1 CM Bkr — 36.2/40.0 36.2/40.0 — 53.8/58.5 45.3/50.0 — 6/6 8/8 — 10/10 10/10 — 60/60 50/50 — 78/80 59/59
KFCEH3401F241"' 24 18.0 3 Fuse 50.1 /55.4 — — 71.2/77.8 — — 4/4 — — 8/8 — — 80/80 — — 94/95 — —
Cr 24 18.0 1
30 22.5 3 Fuse
Fuse 86.7/95.5 — — 116.9/127.9 — — 1/1 — — 6/6 — — 125/150 — - 115/116 — —
62.6/69.2 86.8/95.0 3/3 88 90/100 97/98
KFCEH3501F30t"' .
30 22.5 1 Fu9e 109.0/120.0 — _ — . 144.8/158.5 — — _ WOO — _ — 6/6 , — — 150/175 - — 117/150 — . -
FIELD MULTIPOINT WIRING OF 24 -AND 30 -KW SINGLE PHASE
KW HEATER AMPS MIN AMPACITY MIN WIRE SIZE (AWG) MAX FUSE/CKT BKR AMPS MAX WIRE LENGTH
208230V 208/230V" 208230Vft MIN GND 208230V 208 (FT)$$
HEATER PART NO. PHASE WIRE SIZE _
240V 208V 11,12 L3,L4 15,18 11,1.2 13.14 1 11,1.2 13,14 15,18 208230V 11,12 L3,L4 15,18 L1,L2 13,1.4 15,1.8
KFCEH3401F24t "• 24 18.0 1 28.9/32.0 28.9/32.0 28.9/32.0 44. 7/48.5 36.2/40.0 36.2 /40.0 8/8 8/8 8/8 10/10 45/50 40/40 40/40 59/60 73/73 73/73
KFCEH3501F30Y" 30 22.5 1 36.2/40.0 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 45.3/50.0 6/6 _ 8/8 8/8 10/10 60/60 50/50 50/50 78/80 59/59 59/59
t Field convertible to 1 phase, single or multiple supply circuit.
t Field convertible to 3 phase.
Includes blower motor amps of largest fan coil used with heater.
tt Copper wire must be used. If other than uncoated (non - plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) Is used, consult applicable tables of the National Electric Code
. (ANSI/NFPA 70).
tt Length shown Is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 %.
"' Heaters are Intelligent Heat capable when used with the FK, FV fan coils and corporate 2 -speed programmable thermostat (TSTATBBP2S01 -B), ThermidistatTu Control (TSTATBBPRH01 -B), or Zoning Control.
NOTES: 1. For fan coil sizes 018 -036.
2. For fan coil sizes 042 -060 and all FK4D, FV4B sizes.
3. Single circuit application of F15 and F20 heaters requires single -point wiring kit accessory.