Plans (2) Brandon Shaw from: ' Mark Butler [mark.bci @verizon.net] Sent: Wednesday, March 05, 2008 5:24 PM To: Brandon Shaw Cc: marcia salmieri Subject: Barrows Road Estates - Combustion Air Vent Attachments: 2nd Floor Framing.pdf; Firewall.pdf; Partial Found.pdf; Ground Floor.pdf Brandon: I have looked at the 3 additional plan review issues on the Barrows Road Estates project (permit numbers MST2007 -00225 to MST2007- 00232). The issues are addressed below with 8 -1/2 x 11 sketches attached.of the changes. 1. Combustion Air in Mechanical R gym: The 70,000 BTU furnace plus the 40,000 BTU water heater will require 27.5 sq in of vent area. Ar through -wall vent will provide 28.3 sq in. The vent callout on sheets A -4, A -5 and A -6 needs to be changed to a 6" duct as shown on the attached ground floor plan sketch. 2. Fire -rated listing @ separation wall: The detail 14/S6 has been modified to call out UL -U359 which is a standard 1 -hour exterior wall detail. The ground floor shear wall has been shortened to not extend into the 5' length of wall at the offset to preserve the rated wall assembly. See the attached firewall detail and the 2nd floor framing plan. Sheet S -4 will need to be revised. The ground floor shear wall "2" is now 31' -4" long with a uniform shear load of 340.2 plf, less than the allowable 350 plf for shear wall type "B ". 3. Slab insulation beneath entry slab: The slab insulation has been extended 24" beneath the stairs as shown on the attached partial foundation plan. This will need to be revised on Sheets S -3, S -4 & S -5. Please do not hesitate to call if you have any questions. Let me know if you need more formal documentation regarding these changes. Mark Butler Butler Consulting, Inc. (503) 658 -0200 MSi 0 ov7 CeW //373 S te✓ ,fal(vvtar ie_v' 5 oz) 7 - CR9 .g-e,0 // 3(P 51-v �- -- 415r �a /( 365 re-v Ai � 7- )0 IT / 3 5 3 it P — 4,57- - oz�aa 1i S /if A7157- 0 1.0z)7- - a 2 i i 3 3 S . �°-� .M sTa�7 - X023/ /1-3 � ' 51--c7-0 7- 3 Z /3 / 7 /(7,L_ee ��✓ tSAU v . u.i D - r ire Kesistance Kaungs - A1N n/ UL Lb. rage 1 of • • 0 ONLINE CERTIFICATIONS DIRECTORY —� BXUV.U359 Fire Resistance Ratings - ANSI /UL 263 Page Bottom Design /System /Construction /Assembly Usage Disclaimer • Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Listed or Classified products, equipment, system, devices, and materials. • Authorities Having Jurisdiction should be consulted before construction. • Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field. • When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction. • Only products which bear UL's Mark are considered as Classified, Listed, or Recognized. Fire Resistance Ratings - ANSI /UL 263 See General Information for Fire Resistance Ratings - ANSI /UL 263 Design No. U359 February 27, 2006 Bearing Wall Rating — 1 Hr Finished Rating — 29 Min Load Restricted for Canadian Applications — See Guide BXUV7 9 • • P.=1 N ! . 1. Wood Studs — Nom 2 by 4 in., spaced max 16 in. OC. 2. Batts and Blankets* (Optional, Not shown) — Placed to completely or partially fill the stud cavities, any glass fiber or mineral wool insulation bearing the UL Classification Marking as to Surface Burning Characteristics and /or Fire Resistance. See Batts and Blankets (BKNV or BZJZ) Categories for names of Classified companies. 3. Gypsum Board* — Applied either horizontally or vertically. Vertical joints centered over studs. When used in widths other 48 in., wallboard is to be installed horizontally. Nom 5/8 in. thick board attached to studs and plates with 6d cement coated nails (1 -7/8 in. long) spaced 7 in. OC or with 1 -7/8 in. long Type S screws spaced 7 in. OC or 1 -1/4 in. long Type W coarse thread gypsum panel steel screws spaced a max 8 in. OC, with last srcrew 1 in. from edge of board. UNITED STATES GYPSUM CO — Type FRX -G http : / /database.ul.com/cgi- bin/XYV /template /LISEXT /1 FRAME /showpage.html ?name =BX... 3/6/2008 BXU V.U359 - Fire Resistance Ratings - ANSI /UL 263 Page 2 of 2 4. Joints and Nailheads — (Not shown) — Wallboard joints covered with paper tape and joint compound. Nailheads covered with joint compound. *Bearing the UL Classification Mark Last Undated on 2006 -02 -27 Questions? Notice of Disclaimer Page Top Copyright Cd 2008 Underwriters Laboratories Inc.® The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow -Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow -Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and /or Listings (files) must be presented in their entirety and in a non - misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright 2008 Underwriters Laboratories Inc. ®" An independent organization working for a safer world with integrity, precision and knowledge. http:/ /database. ul.com/cgi- bin/XYV /template /LISEXT/ 1 FRAME /showpage.html ?name =BX... 3/6/2008 p I 1 -i 3' -0" x 3' -0" x 12" FTG • I I /w/(3)#4EAWAY 3'-6" " x 3' -6" x 12" FTG -_ I EXTEND SLAB I .I, , ; , y , , w/ 4 #4 EA WAY INSULATION 24 ' ,1������ � � � �/1 12 " WIDE x8 "DEEP () L J I BEYOND BOTTOM STAIR H /CONT&6"STEMW INT. FTG w/ (2) #4 ' / " / „Z ALL A BLOCKOUT I WA : : :. / / /// 4 SLAB -ON -GRADE � iiiiii / I SLOPE TO GARAGE I �iiii DOOR I ,:'[.://://::: , R -15 SLAB I I ' �' 7-r INS ULATION ' B -- -� p 11 I Imo, Aft - - I 1-27_1 1/2" 8'-3" I-8-1/1' S -6 ROUGH OPENING 12" WIDE x 8" DEEP I 1 24" WIDE x 20" DEEP FTG I I INT. FTG w/ (2) #4 LJ � ® 8 w /(3) #5 TOP &BOT & #3 [' CONT & 6" STEM WALL 15" WIDE x 8" DEEP S STIRRUPS @ 12" 0/C INT. FTG w/ (2) #4 16" 0 x 12" DEEP FTG CONT & 8" STEM WALL TYP FOUNDATION PLAN B Plan check - slab insulation MEB 3/05/08 REV Description BY Date Butler BARROWS ROAD ESTATES LOTS 1 -8 Consulting, Inc. TIGARD, OREGON 16110 SE Goosehollow Drive PARTIAL TYP. FOUNDATION PLAN Damascus, Oregon 97089 (503) 658 -0200 Job No. 225 - 0907 -01 Date 2/12/08 Sheet (503) 658 -0204 Client Milestone Homes By MEB SK3 ® WRAPPED WRAPPED P.T. ® .. P.T. 4x6 POST 4x6 PT POST I . 18' -0" f g I ' -0 1/2" 3' -3 1/2" 7' -8" `" 0 MIN SCREENED VENT THRU WALL FOR I B ` COMBUSTION AIR MAX 12" BELOW CEILING -W M E C H ROOM 8 UNHEATED SPACE 3' -8" x 6' -5" 8' -0" CLG 5KD 80% MIN. EFF. FURNACE w/ (8' CLG') n PLOTLG WATER r - BONUS B • \ � , / i 22 x 30 I �x� CRAWL SP. 0 r_ ___�ACCESS • PLUMBING ELEC 7' -10" , 10' -2" STACK TV/PH I I I I I FLOOR UNT GROUND TYP B Plan check - slab insulation MEB 3/05/08 REV Description BY Date Butler BARROWS ROAD ESTATES LOTS 1 -8 Consulting, Inc. TIGARD, OREGON 16110 SE Goosehollow Drive PARTIAL TYP. FOUNDATION PLAN Damascus, Oregon 97089 (503) 658-0200 Job No. 225 - 0907 -01 Date 2/12/08 Sheet (503) 658 -0204 Client Milestone Homes By MEB SK4 . D D A • JECK / _ \ ON LOT ; _ _.. -� Al, r I A I I I I I I TYPHEADER I o A•JACEN7 UNIT ® - ,P - - --- I - I I I I i j � 1, 4x4 POSTI I I g l 1 I I_ 'I I I I ....., 0 Ii L. _ T ill \ice © it _ _ P I I I FROM 4x4 ABOVE POST 1 % x117 A . 1 11X" TJI -110 an 19.2" 0/C I TYP FLOOR JOIST I :111. I 4x6 POT I 1 4x 117 "LSL I / I _ 3Yx11 X "PSG t 1 4 I6 POS T k S-6 ak I I I � I I � I © — I I 1 1 J J I 1 l I I I S -6 I I X1 I - I I I 1 x I I I I\ I XI 4x6 POST FROM I _ I ABOVE w/ CMST14 I I I I STRAP EA SIDE I 3 y 11X" LItL'1� 1 6l x 12" GLULAM i'li m II 1 : , 4Pc I T w/ HGLB -7 BEAM SEAT 7 CC )46 •L CAP —1I— LI 1 T I' 1 4x8 CF #2 _ 1 _ 14x8 DF #2 1 _ 1 I I�I I 8" THICK FULL -HT CONCR. WALL w/ (3) #5 EA END 2ND FLOOR FRAMING PLAN - LEFT END UNIT B Shear wall length MEB 3/05/08 REV Description BY Date B utler BARROWS ROAD ESTATES LOTS 1 -8 Consulting, Inc. TIGARD, OREGON 16110 SE Goosehollow Drive 2ND FLOOR FRAMING PLAN Damascus, Oregon 97089 (503) 658-0200 Job No. 225 - 0907 -01 Date 3/05/08 Sheet (503) 658 -0204 Client Milestone Homes By MEB SK5