Plans Sew
ELECTRIC
SEPTEMBER 19, 1996
MIKE RUDD
COMMUNITY DEVELOPMENT
13125 S.W. HALL BLVD.
TIGARD, OR 97223
DEAR MIKE:
PRECISION INTERCONNECT/FLIGHT DYNAMICS' EXISTING 1600/800 AMP
SERVICE HAS REACHED ITS FULL SPACE CAPACITY. IN ORDER TO BRING
THE EXISTING SERVICE UP TO CODE AND TO GAIN FUTURE CAPACITY, WE
ARE REPLACING THEM WITH NEW SERVICE GEAR, 2500/1000.AMP'SPARE
SPACES AND ONE NEW 800 AMP CIRCUIT BREAKER TO FEED A NEW 800
AMP SDP LOCATED IN THE MANUFACTURING AREA TO PROVIDE SERVICE
FOR FUTURE EQUIPMENT. THERE IS NO ADDITIONAL SERVICE LOAD TO
CALCULATE AT THIS TIME AND P.G.E. HAS PROVIDED US WITH FAULT
CURRENT INFORMATION BASED ON THEIR NEWLY INSTALLED
TRANSFORMER AND OUR PROPOSED NEW SERVICE. PLEASE CALL IF YOU
NEED MORE INFORMATION. THANK YOU
SINCERELY,
STONER FL.ECTRIC, INC.
47,-eq 2. 1�GREG L. OOLFE
VICE-PRESIDENT
2701 S . 14th Portland, Oregon 97202 (503)233-3631 1-800-548-2701
1000A 2771480V 30 4W \,.___,/ 2500A 2771480V 30 4W
r —1 T I^ 1
d d d d d I
. SPACE \ 200A \ 400A SPACE SPACE \ 400A \ 400A 800A 200A
CT CT
SECTION SECTION
I l
L I r1�_ L J
TO EXISTING PANELS TO EXISTING PANELS (2)-3'C. TO EXISTING
_ w/(4)-500 MCM PANEL
TO SOP
#4 Cu TO GROUND ROD #4 Cu TO GROUND ROD for future
extruders
C
1/0 Cu GROUND 1/0 Cu GROUND n t(
TO WATER TO WATER
0 ' --------C----- CI) \ t
FROM TRANSFORMER (by PGE) -_J L—— FROM TRANSFORMER (by PGE)
FAULT CURRENT CALCULATIONS CITY OF TIGARD
PER BRIAN MOORE, PGE 590-1351 p.1 proved .••• """""" [ �
Conditi0natl�,r Approved..........
CUSTOMER: FLIGHT DYNAMICS CUSTOMER: PRECISION INTERCONNECT For onl the work described in:
ADDRESS: 16600 SW 72nd BLDG. #10 ADDRESS: 166L0 SW 72nd PERMIT NO--P�--t ............•.[ ]:
PORTLAND, OR 97224 PORTLAND, OR 97224 See totter to Follow...•.• ..
Attach....... . ... .. ..... .....
TRANSFORMER KVA: 2500 KVA TRANSFORMER KVA: 2500 KVA - � �`
IMPEDANCE: 5.125% IMPEDANCE: 5.125% lob Addrr�ss Date: G
SECONDARY L—L VOLTAGE: 480V SECONDARY L—L VOLTAGE: 480V
WIRE LENGTH: 25 feet WIRE LENGTH: 25 feet
WIRE SIZE: 350 MCM AL WIRE SIZE: 350 MCM AL
NUMBER OF RUNS: 4 RUNS NUMBER OF RUNS: 4 RUNS SERVICE UPGRADES
WIRE IMPEDANCE R: 0.049 OHMS/1000' WIRE IMPEDANCE R: 0.049 OHMS/1000'
WIRE IMPEDANCE X: 0.037 OHMS/1000' WIRE IMPEDANCE X: 0.037 OHMS/1000'
FAULT CURRENT: 44,181 AMPS FAULT CURRENT: 44,967 AMPS PRECISION TNT. - FLIGHT DYNAMICS
SW 72nd AVENUE PORTLAND, OREGON 97224
STONER ELECTRIC
2701 SE 14TH AVENUE PORTLAND, OREGON 97202 C503)233-3631
scA1.E' NONE DRAWN BY' DW CHEMED GV DRAVING NUMBER.
PROJECT NO, 29483c REVISED DATE' 9/20/96 , 1
__` %//f�/////////// BILL OF MATERIAL
CKT# - QTY. DESCRIPTION CATALOG # LOAD LUGS AIC
r 1-3 3 100 AMP BREAKER HED63B100 1 (1) #14-2/0 42K
20" r 4 1 100 AMP SPACE ONLY HED6
5 1 200 AMP SPACE ONLY FXD6
"'- 6 1 1400 AMP SPACE ONLY ;JXD6
1 circuit #
100/3 1 1
10013 2
NOTES:
90" 100/3 3
100 CONSTRUCTION SWITCHBOARD IS BUILT AND LABELED PER UL 891 IN EFFECT AT THE TIME OF
space 1 4 STANDARD MANUFACTURE.
200
space 5 INCOMING SERVICE AMPERES: 800
400 VOLTS: 4801277
space 6 SYSTEM: 3 PHASE 4 WIRE
INTERRUPTING THE SHORT CIRCUIT INTERRUPTING CAPACITY IS EQUAL TO THE LOWEST SHORT CIRCUIT
RATING RATING OF THE DEVICES INSTALLED,OR THE LIMITATIONS OF THE BUSSING STRUCTURE,
---- --- - -- -
- WHICH EVER IS LESS. AT THE TIME OF MANUFACTURE,THE LOWEST RATED INSTALLED
DEVICE IS 30,000 AIC BUSSING STRUCTURE RATED AT 50000 AMPS
38" ENCLOSURE ENCLOSURE IS NEMA TYPE 1 FOR INDOOR APPLICATION. CUBICAL,FRAMES AND COVERS
CONSTRUCTED FROM CODE GAUGE STEEL-
LIMITED ENTRY, 10" HEIGHT BETWEEN FLOOR
AND BOTTOM OF BREAKER OR SWITCH ENCLOSURE FINISH ANSI 61 LIGHT GRAY PAINT.
4 3" METAL STRUCTURAL EDGE TERMINATIONS ACCESSIBLE FROM THE FRONT.
BUSSING ALUMINUM,SIZED ON A BASIS OF 65 DEGREE C MAXIMUM TEMPERATURE RISE.
800A M.L.O.
'
SERVICE UTILITY
100/3 100/3 CT COMPARTMENT PER EUSERC
U.G.P.S. PER EUSERC
100/3 100 amp space only
,JOB NAME: PRECISION INTERCONNECT
200 amp space only TITLE: 800 AMP SUB DISTRIBUTION BOARD
CUSTOMER: STONER ELECTRIC
400 amp space only P.O.# & DATE OF DRAWING 06/15/96
DWG. #
MFG. LOC. PORTLAND, OR _ ___
GND GND GND GND
SIEMENIS ENERGY AND AUTOMATION, INC.
■
■
'-w . •
BILL OF MATERIAL
CKT # : QTY. DESCRIPTION ; CATALOG # LOAD LUGS l AIC
r��������� xez./ /`�/ ff/i ��`f������� 2 !200/3 BREAKER IHFD63B200 6-350 65 K .
38" j 3 1400/3 BREAKER 'HJD63B400 6-350 65 K
1 800/3 BREAKER LMXD638800 (2) 1-500 MCN 50 K
/� / // // � 1� tjl� 3 400 AMP SPACE ONLY HJD63
_ _
—
1 --_ - L
1 400/3
IT I CT SPACE ONLY --- -
r COMPARTMENT COMPARTMENT 400/3 (J)
400/3 3 j SPACE ONLY ' ‘rir
In 90" 200/3 400/3 /Opt ( ., NOTES:
I i\e/ kap r
1 , I ( ) 400/3 , ;•
a
400/3 1000 AMP 2500 AMP I I `1 \k, CONSTRUCTION SWITCHBOARD IS BUILT AND LABELED PER UL 891 IN EFFECT AT THE TIME OF
,hL �y STANDARD MANUFACTURE.
SPACE 480/277 480/277 `.:
ONLY 800/3 ti Ct
_ "i INCOMING SERVICE AMPERES: 2500 AND 1000 SERVICES
VOLTS: 480/277
UNDERGROUND UNDERGROUND 200/3
PULL PULL SYSTEM: 3 PHASE 4 WIRE
SECTION H SECTION INTERRUPTING THE SHORT CIRCUIT INTERRUPTING CAPACITY IS EQUAL TO THE LOWEST SHORT CIRCUIT
RATING RATING OF THE DEVICES INSTALLED, OR THE LIMITATIONS OF THE BUSSING STRUCTURE,
WHICH EVER IS LESS. AT THE TIME OF MANUFACTURE.THE LOWEST RATED INSTALLED
I DEVICE IS 50,000 AIC BUSSING STRUCTURE RATED AT 100.000 AMPS
38" 46" 46" 38"
ENCLOSURE ENCLOSURE IS NEMA TYPE 1 FOR INDOOR APPLICATION. CUBICAL.FRAMES AND COVERS
LIMITED ENTRY, 10" HEIGHT BETWEEN FLOOR CONSTRUCTED FROM CODE GAUGE STEEL.
AND BOTTOM OF BREAKER OR SWITCH
ENCLOSURE FINISH ANSI 61 LIGHT GRAY PAINT.
3" METAL STRUCTURAL EDGE TERMINATIONS ACCESSIBLE FROM THE FRONT.
1000 AMP 480/277 2500 AMP 480/277 BUSSING ALUMINUM,SIZED ON A BASIS OF 65 DEGREE C MAXIMUM TEMPERATURE RISE
3 PH 4 WIRE 3 PH 4 WIRE
SERVICE UTILITY
400 SPO 400 SPO CT COMPARTMENT PER EUSERC
400/3 U.G.P.S. PER EUSERC
4 400/3 400/3 - -
200/3 400 SPO JOB NAME: PRECISION INTERCONNECT-PLANT #1 _
4 800/3 TITLE:
UTILITY --- —
CUSTOMER: STONER ELECTRIC _
INCOMING P.O.# 07/01/96
200/3 DWG. # - rev #1 07/03/96
MFG. LOC.
GND GND GND GND
SIEMENSENERGY AND AUTOMATION. INC.