Specifications I �,I 1 August 7, 2006 CI TOG k 'P ®RE Wyatt Fire Protection, Inc. Eugene Lathan 9095 SW Burnham Tigard, OR 97223 . RE: FIRE SPRINKLER SYSTEM REPLACEMENT /MODIFICATION - REVIEW Project Information Building Permit BUP2006 -00 34 Construction Type: H -B Tenant Name: Eddie Bauer Occupancy Type: M Address: 9522 SW Washington Sq Occupant Load: 178 Area: 6,338 sq ft Stories: 1 Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition, Oregon Fire Code 2004 edition, and NFPA 13. The submitted plans are approved subject to the following. TESTING- Section 16.2.1 1. Hydrostatic testing of the system shall occur at sprinkler final. The contractor's material and test certificate required by NFPA 13, 16.1 shall be completed and signed by both the installer and building owner. 2. Unless permitted by 16.2.1.2 through 16.2.1.6, all piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain that pressure without loss for 2 hours. Loss shall be determined by a drop in gauge pressure or visual leakage. The test pressure shall be read from a gauge located at the low elevation point of the system or portion being tested. WATER FLOW ALARMS: - Section 6.9.1 3. Water flow alarm apparatus shall be listed for the service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the smallest orifice size installed on the system will result in an audible alarm on the premises within 5 minutes after such flow begins and until such flow stops. SPRINKLER SYSTEM MONITORING :: OSSC 901.6. - NFPA 13 sec 8.16 4. All valves controlling the water supply for automatic sprinkler systems and water -flow switches on all sprinkler systems shall be electrically monitored where the number of sprinklers are more than 20. HANGERS: NFPA 13 sec 9.2 5. The maximum distance between hangers shall not exceed that specified in Table 9 -2.2. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 6. The maximum distance between hangers for listed nonmetallic pipe shall be modified as specified in the individual product listings. SWAY BRACING: - Section 9.3.5 - 9.3.5.8 7. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads and to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. RESTRAINT OF BRANCH LINES: - Section 9.3.6 8. Restraint is considered a lesser degree of resisting loads than bracing and shall be provided by use of one of the following. (1) A listed sway brace assembly (2) A wraparound U -hook satisfying the requirements of 6- 4.5.3, Exception Number 3 (3) No. 12, 440-lb (200 -kg) wire installed at least 45 degrees from the vertical plane and anchored on both sides of the pipe (4)Other approved means 9. Wire used for restraint shall be located within 2 ft (610 mm) of a hanger. The hanger closest to a wire restraint shall be of a type that resists upward movement of a branch line. The end sprinkler on a line shall be restrained against excessive vertical and lateral movement. Where upward or lateral movement would result in an impact against the building structure, equipment, or finish materials, branch lines shall be restrained at intervals not exceeding 30 ft (9 m) PIPING CLEARANCE: - Section 9.3.4 10. Where pipe passes through holes in platforms, foundations, walls, or floors, the holes shall be sized such that the diameter of the holes is 2 in. (50 mm) larger than the pipe for 1 in. (25 mm) nominal to 3 ' /2" (89 mm) nominal and 4 in. (100 mm) larger than the pipe for pipe 4 in. (100 mm) nominal and larger. Clearance from structural members not penetrated or used, collectively or independently, to support the piping shall be at least 2 in. SPARE SPRINKLERS: - Section 6.2.9 11. The stock of spare sprinklers shall include all types and ratings installed and shall be as follows: a. For systems having less than 300 sprinklers, not fewer than six sprinklers Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfull /IF Val Henzel, Senio Tans Examiner • a.' t'CCI Fire & Building Products , ; Q6-0 c/7- t Z pp6 - Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 e � / � d /VG 0 1 �S 4 Series RFII — 5.6 IC- factor "Royal Flush II" Pendent Concealed Sprinklers Quick & Standard Response, Standard Coverage General Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the escription sprinkler while the ceiling is being in stalled or finished. The tip of the Pro The Series RFII Quick Response tective Cap can also be used to mark ° - • = (3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently -I}rR t II" Concealed Pendent Sprinklers are pushing the ceiling product against the , FI decorative sprinklers featuring a flat Protective Cap. When the ceiling in- cover plate designed to conceal the stallation is complete the Protective sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate tecturally sensitive areas such as hotel Assembly installed. lobbies, office buildings, churches, As an option, the Series RFII Standard and restaurants. Response (5 mm bulb) "Royal Flush II" . Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be sembly that conceals the sprinkler op - fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175 erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM. The separable two -piece design of the intended for sensitive areas where it is Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical blies allows installation of the sprin- through the cover plate from the area klers and pressure testing of the fire above the ceiling. Data protection system prior to installation WARNINGS of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII of the finish coating to a fixed ceiling. PP They also permit removal of sus- Sprinklers described herein must be UL and C -UL Listed. FM Approved. pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353 -01 -E. LPCB (Ref. building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for having to first shut down the fire pro- with the applicable standards of the TY3531) Approved. hav system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv- -ig in addition to the standards of any ice conditions indicated in the Design Also, the separable two-piece design f the the Sprinkler provides o for ig n pi other authorities having jurisdiction. Criteria section and maximum pres- inch the th mm) of er for 1/2 Failure to do so may impair the per- sure ratings indicated in the to reduce the accuracy to which the tormance of these devices. Model /Sprinkler Identification Num length of fixed pipe drops to the sprin- The owner is responsible for maintain- bers section. klers must be cut. ing their fire protection system and de- Approvals for Air & Dust Seal e vices in proper operating condition. (part #10908100) The Series RFII Sprinklers are The with a Disposable Protective The installing contractor or sprinkler UL and C -UL Listed for use with the manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re- with any questions. sponse Concealed Sprinkler. IMPORTANT Temperature Ratings Always refer to Technical Data Model/Sprinkler 155F/68C Sprinkler - 135F/57C Plate Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate WARNING" that provides cautions Identification Discharge Coefficient with respect to handling and instal - p K = 5.6 GPM /psi (80,6 LPM/bar /2 ) lation of sprinkler systems and com- V umbers Adjustment ponents. Improper handling and in- 1/2 inch (12,7 mm) stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass vents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint to operate in a fire situation or cause TY3504 (5mm bulb) & TY3505 (3 mm matches and colors other than white it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by are available on request.) Page 1 of 4 JULY, 2004 TFP181 Page 2 of 4 TFP181 Physical Characteristics 1/2• NPT l % SEALING Frame Bronze - f ASSEMBLY Support Cup Chrome Plated Steel Guide Pins Stainless Steel I . f Deflector Bronze FRAME Jj� �fi �_ �_, Compression Screw Brass i � It 1nL 0-0 CAP Bulb Glass I `� Cap Bronze or Copper SUPPORT t Sealing Assembly CUP WITH 1 I' BULB Beryllium Nickel w/Teflon' ROLL FORMED ) Cover Plate Brass THREADS l Retainer Brass Ann COMPRESSION Ejection Spring .... Stainless Steel "Kell SCREW GUIDE i � � Patents PINS (2) I = / % I ` ' IN U.S.A. 4,014,388 - / ' 1 ,� __�_ _ DEFLECTOR erat® ®n _r -- (DROPPED DEFLECTOR 1 J ; POSITION) C- i When exposed to heat from a fire, the , SPRINKLER/SUPPORTCUP Cover Plate, which is normally sol- ASSEMBLY dered to the Retainer at three points, falls away to expose the Sprinkler As- THREAD INTO RETAINER sembly. At this point the Deflector sup- SUPPORT CUP J O WITH THREAD Y P P UNTIL MOUNTING ■ O t) DIMPLES ported by the Guide Pins drops down SURFACE IS to its operational position. FLUSH WITH EJECTION The glass Bulb contains a fluid that CEILING SPRING expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the m r g „ glass Bulb, activating the sprinkler and allowing water to flow. SOLDER COVER TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY Design FIGURE 1 Criteria SERIES RFII CONCEALED SPRINKLER ASSEMBLY The RFII (TY3551 & TY3504), 5 mm Bulb Type, Concealed Pendent Sprin Step 1. The sprinkler must only be klers are UL and C -UL Listed as stand- Installation installed in the pendent position and and response - standard spray sprin- with the centerline of the sprinkler per- - klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface. current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap. Approved as standard response - tions: standard spray sprinklers for use in Step 3. With pipe thread sealant ap- accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting. The RFII (TY3531 & TY3505) the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler Th 3 mm Th lb Type, Concealed Pendent 3 Sprin- liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench YP P held horizontally, a small air bubble Ref. Figure 3). The RFII Sprinkler klers are UL and C -UL Listed as quick should be present. The diameter of the ( g ure )' P Wrench response - standard spray sprinklers air bubble is approximately 1/16 inch Figure 3. applied to the Sprin- as kler as shh oww n in F for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 be Figur NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tem- Step 5. Replace the Protective Cap proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards and spray sprinklers for use in accord- until it bottoms out against the Support ante with the current FM Loss A leak tight 1/2 inch NPT sprinkler joi Cup. The Protective Cap helps prevent Prevention Data Sheets. should be obtained with a torqu of 7 damage to the Deflector and Arms dur- to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- in ceiling installation and /or during The Series RFII Concealed Pendent mum of 21 Ribs. (28,5 Nm) of torque g g e application Sprinklers are only listed and ap- is to be used to install sprinklers. lng. p t may f the eo nish coating o y the ceiling. proved with the Series RFII Concealed Higher levels of torque may distort the tf the by Cover Plates having a metallic or white sprinkler inlet with consequent leak- the used to hole painted finish. gentlly y pushing the ceiling material al u up age or impairment of the sprinkler. against the center point of the Protec- The Series RFII must not be used in Do not attempt to compensate for in- tive Cap. applications where the air pressure sufficient adjustment in the Sprinkler above the ceiling is greater than that Assembly by under- or over - tightening NOTE below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. As long as the Protective Cap remains port Cup could delay sprinkler opera- Readjust th position of the sprinkler in place, the system is considered to tion in a fire situation. fitting to suit. be Out of Service`. ' Registered Trademark of DuPont • TFP1811 Page 3 of 4 FACE OF CLEARANCE HOLE F CLEARANCE SPRINKLER L–, DIAMETER HOLE FITTING DIMENSION C 1 ►! pMEI i g � SPRINKLER SUPPORT CUP \ i — ASSEMBLY 1/2" (12,7 mm ) I■I_ , „` THRE ADED 11,)S1 _ __ _ _ D ADJUSTMENT FACE OF CEILING, 1 / RETAINING RING I FIGURE 4 MOUNTING DISPOSABLE PROTECTIVE CAP SURFACE • A, ��� l I E Step 6. After the ceiling has been com- J pleted with the 2 -1/2 inch (63,5 mm) ��� __ diameter clearance hole and in prepa- ; ; ; ; , ration for installing the Cover Plate As- 1 1 1 sembly, remove and discard the Pro - cti r -- - T -i r-' tective Cap, and verify that the 3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and REFERENCE 3/32° (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and down freely, replace the entire Sprin- COVER PLATE COVER PLATE kler assembly. Do not attempt to mod - PROFILE DEPTH DIAMETER ify or repair a damaged sprinkler. DIMENSION B DIMENSION A Step 7. When installing an Air and Dust Seal, refer to Figure 5, otherwise proceed to Step 8. To attach the Air and A: 3 - 1/4" (82,6 mm) C: 2 - 3/8" to 2 - 5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out - B: 3/16" (4,8 mm) D: 1 -3/4" to 2 - 1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac- cording to Figure 5. Start the edge of FIGURE 2 the Retainer in the grooved slot of the SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around INSTALLATION DIMENSIONS Dust retainer until the entire Air and Dust Seal is engaged. NOTE The Air and Dust Seal is only to be installed on the periphery of the Re 1 ►)�'. - -- -- FR AME 'bait ip, tainer. % \ Step 8. Screw on the Cover Plate /Re- �� tainer Assembly until the Retainer - _ ; Figure 2 (or Air and Dust Seal - Figure j II S ARM SU PPO RT IR r 0; 5) contacts with the ceiling. Do not C ; / i ( continue to screw on the Cover II i Plate /Retainer Assembly such that it MI��I i �� ��� # lifts a ceiling panel out of its normal i i I^ position. If the Cover Plate /Retainer Assembly cannot be engaged with the — — - O Support Cup or the Cover Plate /Re- 7/8" (23 mm) tainer Assembly cannot be engaged SQUARE sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. ALIGN Q ARROWS WITH C - - -1 FRAME ARMS r t efmfffiC ACCEPTS The Series RFII must be maintained O 1/2° SOCKET and serviced in accordance with the DRIVE following instructions: NOTES FIGURE 3 Absence of the Cover Plate Assembly RFII SPRINKLER WRENCH may delay sprinkler operation in a fire situation. Page 4 of 4 TFP181 When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL - between the lip of the Cover Plate and the ceiling, as shown in Figure 2. This i SHOWN air gap is necessary for proper opera- � PLATE �,� % LA tion of the sprinkler. If the ceiling is to ` ) RETAINER MOM • be repainted after the installation of )i — ll ;►1 ASSEMBLY �� : the Sprinkler, care must be exercised \�j --�. to ensure that the new paint does NOT ' seal off any of the air gap. E i ri � p i - ROOM Factory painted Cov Plates MUST _ � 11-_ LIP OF COVER SEAL NOT be repainted. They should be re- placed, if necessary, by factory RETAINER PLATE painted units. FIGURE 5 Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504) the Enclosure. Separation may result. Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI- work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT it controls, permission to shut down the EQUAL TO THE SALES PRICE. affected fire protection system must be THE FOREGOING WARRANTY IS obtained from the proper authorities Limited MADE IN LIEU OF ANY AND ALL, and all personnel who may be affected ® OTHER WARRANTIES EXPRESS OR by this action must be notified. Warranty IMPLIED. INCLUDING WARRANTIES Sprinklers that are found to be leaking Products manufactured by Tyco Fire OF MERCHANTABILITY AND FIT - or exhibiting visible signs of corrosion y y NESS FOR A PARTICULAR PUR- must be replaced. Products are warranted solely to the POSE Automatic sprinklers must never be original Buyer for ten (10) years Autom n utom otherwise against defects in material and work - painted, the coated s plated, leaving ted, coatte factory. r erwise manship when paid for and properly Ordering altered ed p Modi- installed and maintained under normal Pied sprinklers kle that rs must be replaced. have been exposed d. use and service. This warranty will ex- Procedure Sprinklers corrosive products of combustion, but inkler Aire ten (10) years from date of ship - have not operated, should be replaced ment by Tyco Fire Products. No war- When placing an order, indicate the full ranty is given for products or roduct name. Contact your local dis- if they cannot be completely cleaned p y by wiping the sprinkler with a cloth or components manufactured tributor for availability. Hies not affiliated by ownership hip ip with with by brushing it with a soft bristle brush. Tyco Fire Products or for products and Sprinkler Assembly: Care must be exercised to avoid dam- components which have been subject rating) Specify: (S Series ) (specify temperature Pen - age to the sprinklers - before, during, to misuse, improper installation, corro- dent Sprinkler, P/N (specify). and after installation. Sprinklers dam- sion, or which have not been installed, aged by dropping, striking, wrench maintained, modified or repaired in ac- 155F168C 200Fl93c • twist/slippage, or the like, must be re- cordance with applicable Standards of TY3551 51- 790 -1 -155 51- 790 -1 -200 placed. Also, replace any sprinkler that the National Fire Protection Associa- TY35o4 51 -796 -1 -155 51- 796 -1 -200 has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51- 792 -1 -200 liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200 Section). rials found by Tyco Fire Products to be If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate: reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating) reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify). dislodged during service, replace it im- assume for it, any other obligation in mediately. connection with the sale of products or Brass 56 56- 4C1( 5 parts of products. Tyco Fire Products Bright Brass 56- 792 -2- 135 56- 792 -2 -165 The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9-135 56- 792 -9-165 spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome 56.792- &135 56- 792 -6 system and de- incomplete information supplied by White 56- 792 -3- 135 56- 792 -3 -165 -165 their fire protection s y P pP Y White (RAL9010)' 56-792-3-135 56- 792 -3 -165 vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165 ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off White 56- 792 -5- 135 56- 792 -5 -165 standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Bl 56-792-6-135 56-792-6-165 Custom 56 -792 -X -135 56- 792 -X -165 tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR (a) For use with 155F/68C sprinklers. addition to the standards of any other UNDER ANY OTHER LEGAL THE (b) For use with 200F/93C sprinklers. authorities having jurisdiction. The in- ORY, FOR INCIDENTAL, INDIRECT, * Eastem Hemisphere sales only. stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL Wrench: facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Specs Sprinkler R WreWre Sprinkler Wrench, any questions. LIMITED TO LABOR CHARGES, RE- It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56- 000 -1 -075. sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal: tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal, P/N 56- 908 -1 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 • ta Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series =F ® 2.89 4029 5.5 anre 8.1 NC ® :ac�e.®� U .rill , len'.kent ai Recessed Pendant 6,. r tit) gees Quick = © ' ea ;. se, S�'afl'811i Covvra e mospheres. Although corrosion resis- megi rrh tant coated sprinklers have passed the standard corrosion tests of the appli- . eSC1TLe t®On cable approval agencies, the testing is ". `' . - 1* not representative of all possible cor Y The Series T FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it i 8.0 K- factor, Upright and Pendent is recommended that the end user be t ! "` 1 Sprinklers described in this data sheet consulted with respect to the suitability are quick response - standard cover- of these coatings for any given corro- age, decorative 3 mm glass bulb type sive environment. The effects of ambi- e '� ..,, spray sprinklers designed for use in ent temperature, concentration of Tight or ordinary hazard, commercial chemicals, and gas /chemical velocity, ;�, occupancies such as banks, hotels, should be considered, as a minimum, shopping malls, etc. along with the corrosive nature of the chemical to which the sprinklers will be The recessed version of the Series Y T FRB Pendent Sprinkler, where ap- exposed. plicable, is intended for use in areas An intermediate level versions of the with a finished ceiling. It uses either a Series TY FRB Pendent Sprinklers are two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet ,r° Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- �' i �; cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 t r recessed adjustment or up to 3/4 inch ,- � ,- 1 . , % (19,1 mm) of total adjustment from the WARNINGS _ u� flush pendent position, or a two -piece The Series TY -FRB Sprinklers de- ,, „- Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and 4. f : . inch NPT) Recessed Escutcheon with maintained in compliance with this 1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica- ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro - TY3231 - Pendent 5.6K,1/2 "NPT total adjustment from the flush pen- tection Association, in addition to the TY4131 - Upright 8.0K, 3/4 "NPT • dent position. The adjustment provided standards of any other authorities hay- TY4231 - Pendent 8.0K, 3/4 "NPT by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may the accuracy to which the fixed pipe impair the performance of these de- drops to the sprinklers must be cut. vices. Tea 21 a ©call Corrosion resistant coatings, where The owner is responsible for maintain- �ce'� applicable, are utilized to extend the ing their fire protection system and de life of copper alloy sprinklers beyond vices in proper operating condition. Approvals that which would otherwise be ob- The installing contractor or sprinkler pP tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed. with any questions. FM, LPCB, and NYC Approved. (Refer to Table A for complete approval IMPORTANT information including corrosion resis- Always refer to Technical Data tant status.) Sheet TFP700 for the "INSTALLER G' ;& « ell /p r a nkiler WARNING" that provides cautions ffVi go e a a a Maximum Working Pressure with respect to handling and instal- lloie on 175 psi (12,1 bar) lation of sprinkler systems and com- r . Discharge Coefficient ponents. Improper handling and in- ' (It JE n .N ( I S K = 2.8 GPM /psi / (40,3 LPM/bar / stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM/bar / a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2"NPT K = 5.6 GPM /psil (80,6 LPM/bar / nents and cause the sprinkler to fail TY1231 - Pendent 2.8K,1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /bar / to operate in a fire situation or cause TY2131 - Upright 4.2K,1/2 "NPT Temperature Ratings it to operate prematurely. TY2231 - Pendent 4.2K,1/2 "NPT Refer to Table A and B TY3131 - Upright 5.6K, 1/2 "NPT Page 1 of 8 JULY, 2004 TFP171 • Page 2 of 8 TFP171 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED SURFACE 1/2 MAKE -IN ESCUTCHEON SSU NPT DEFLECTOR 11111 l. 5 2 1/4" - } I� 1 "�� 7/1m J 2 -1 mm) � _� (11,1 NA (57,2 } `_ NOMINA 11� L 2 1- 9/16" I ' r�� 2-3/16" e �� qF 3 (39,7 mm ) WRENCH (55,6 mm) II FLATS = �' 1 SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. 1 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED 1/2" SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR 6 1 —._.--- _ 5 , 3 . Es_ 7/16" 2- 3/16" .�� } (11 mm) (55,6 mm) =� 4-1011 — I N OMINAL I ; 4 1 MAKE IN m (38,1 /mm) I `� 1 (55,6 m o ' 2 WRENCH r, 1 --- II il FLATS _ 3 f f 1 • SSP DEFLECTOR * — 2-7/8" (73,0 mm) DIA. 1/2" NPT 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT Y f C Finishes Bulb Glass w Sprinkler: Refer to Table A and B Compression Screw Bronze O perati®n Recessed Escutcheon: White Coated, Deflector . . . . . . . Copper /Bronze v Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which E expands when exposed to heat. When co Physical Characteristics the rated temperature is reached, the co Ph Y fluid expands sufficiently to shatter the if Frame Bronze glass Bulb, allowing the sprinkler to E Button Brass /Copper activate and water to flow. • Sealing Assembly o Beryllium Nickel w/Teflont .- TFPI71 Page 3 of 8 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR 6 1 � AorrEmm r 7/16 " °r 5 2 -3/16° lo '',.� I (1 1,1 mm) I (55,6 mm) l�� vo w NOMINAL !IV ki 4 1 I I(38,1 mm) ��� 2-3/16" ,Q 2 C H (55 mm) -�— - - � _. S _ i M i 1 SSP DEFLECTOR * . - 2 -7/8" (73,0 mm) DIA. 1 1/2" NPT t PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2 "'(12,7 mm) STYLE 30 or 40 PLATE SEATING ** NOMINAL RECESSED SURFACE 3/4 " MAKE -IN ESCUTCHEON SSU NPT DEFLECTOR 6 1 — �_ 1/2" I 5 2- 5/16" f i (12,7 mm) (58,7 mm) ICI ME — NOMINAL 4 1 `.� MAKE -IN li ir 1- 9/16 " 2-1/4" � 4�b 2 (39,7 mm) I I WRENCH (57,2 mm) % 3 ■ II FLATS 111 01 s 01 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. --"– 3/4" NPT ** f PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT Listing is based on the requirements of m e es g NFPA 13, and FM Approval is based ®t1Sf -1 Il g totn on the requirements of FM's Loss Pre - Criter ®a vention Data Sheets ). Only the Style The Series TY-FRB Sprinklers must be 10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow- The Series TY-FRB Pendent and Up- eon, as applicable, is to be used for ing instructions: right Sprinklers are intended for fire recessed pendent installations. protection systems designed in ac- NOTES cordance with the standard installation Do not install any bulb type sprinkler if rules recognized by the applicable the bulb is cracked or there is a loss of Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler • Page 4 of 8 TFP171 SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob- tained with a torque of 10 to 20 ft.lbs. K TYPE TEMP. BULB NATURAL CHROME WHITE"' LIQUID BRASS PLATED POLYESTER (13,4 to 26,8 A maximum to be of ed ft.lbs. (40,7 Nm) ) of of torque is to be used 135 °F /57 °C Orange to install sprinklers with 3/4 NPT con- PENDENT nections. Higher levels of torque may • 155 °F /68 °C Red distort the sprinkler inlet and cause (TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler. and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green Do not attempt to make -up for insuffi- (TY1131) cient adjustment in the escutcheon 2.8 286 °F /141 °C Blue plate by under- or over - tightening the 1/2" sprinkler. Readjust the position of the NPT 135 °F /57 °C Orange sprinkler fitting to suit. RECESSED 155 °F /68 °C Red PENDENT The Series TY - FRB Pendent and Up (TY1231)* 175 °F /79 °C Yellow right Sprinklers must be installed in Figure 5 200'F/93°C Green 1, 2, 5 accordance with the following instruc- tions. 135 °F /57 °C Orange Step 1. Pendent sprinklers are to be RECESSED Red installed in the pendent position, and PENDENT upright sprinklers are to be installed in (TY1231)" 175 °F /79 °C Yellow the upright position. Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap- 135 °F /57 °C Orange plied to the pipe threads, hand tighten PENDENT the sprinkler into the sprinkler fitting. (TY2231) 155 °F /68 °C Red Step 3. Tighten the sprinkler into the and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13). 2131 With reference to Figures 1, 2, 3, and 4.2 (TY2131) 286 °F /141 °C Blue 1 2 4, the W -Type 6 Sprinkler Wrench is to 1/2° be applied to the sprinkler wrench NPT 135 °F /57 °C Orange flats. RECESSED 155 °F /68 °C Red PENDENT (TY22S1r 175 °F /79 °C Yellow The Series TY - FRB Recessed Pen - Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in accordance with the following instruc- 135°F/57°C Orange tions. RECESSED 155 °F /68 °C Red Step A. After installing the Style 10. PENDENT 20, 30, or 40 Mounting Plate, as appli- (TY2231)" 175 °F /79 °C Yellow cable, over the sprinkler threads and Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the pipe threads, hand tighten the sprin- NOTES: kler into the sprinkler fitting. 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W -Type Sprinklers. 7 Recessed Sprinkler Wrench (Ref. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- Figure 14). With reference to Figure 1, klers. 5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W -Type 7 Recessed 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats. ' Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in- Recessed Escutcheon, as applicable. stalled or the finish coat has been ap- ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment plied, slide on the Style 10, 20, 30, or Recessed Escutcheon, as applicable. 40 Closure over the Series TY-FRB — Frame and Deflector only. Listings and approvals apply to color (Special Order). Sprinkler and push the Closure over N /A: Not Available p p the Mounting Plate until its flange TABLE A comes in contact with the ceiling. LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K- FACTOR SPRINKLERS held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint should be present. The diameter of the should be obtained with a torque of 7 air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi - (1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with temperature ratings. 1/2 NPT connections. A leak tight 3/4 TFP171 Page 5 of 8 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE"' LEAD LIQUID BRASS PLATED POLYESTER COATED 135"F/57°C Orange • PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1,2,3,5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3131) 286°F/141°C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY8231)* 175 °Fl79 °C Yellow Figure 9 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A (TY3231)" 175 °F /79 °C Yellow Figure 10 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4231) 1, 2, 5 and 175 °F179 °C Yellow 1, 2, 3, 4, 5, 6, 7 UPRIGHT 200 °F /93 °C Green 8.0 (TY4131) 286°F/141°C Blue 3/4" NPT 135F/57°C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)* 175 °F /79 °C Red Figure 11 200 °F /93 °C Yellow 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4231)" 175 °F /79 °C Yellow Figure 12 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31- 53-428 -4444 /Fax 31 -53- 428 - 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2° NPT) or Style 40 (3/4° NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. o ' Installed with Style 20 (1/2° NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS Page 6 of 8 TFP171 2 -7/8° DIA. 2 -7/8° DIA. 5/8±1/4" (73,0 mm) 3/4' (19,1 mm) (73,0 mm) 1/2±1/8° 1/2° (12,7 mm) • (15,9±6,4 mm) 2 -1/4' DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE . FITTING FITTING 1/8' 1/8° ig - --= - ---1671 J (3,2 mm) �� (3,2 mm) Al 1 .141 1 \ ---, M OU NTING 111 • MOUNTING 1 SURFACE . SURFACE wr• -a-� iir1112. SERIES 1-5/16' (33,3 mm) SERIES 1 -5/16° (33,3 mm) CLOSURE TY -FRB 13/16" (20,6 mm) CLOSURE TY -FRB 1 -1/16" (27,0 mm) FIGURE 5 FIGURE 6 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. 2 -7/8° DIA. _ 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2° (12,7 mm) (15,9±6,4 mm) 2 -1/4" DIA. 1/4' (6,4 mm) (12,7x3,2 mm) 2 -1/4° DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8° FA �1/UII (3,2 mm) ilfltlfll (3,2mm) ITN ArA -- � -J �, SURFACE IP MOUNTING 111 . SURFACE .- - CLOSURE SERIES 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm) TY -FRB 3/4" (19,1 mm) TY -FRB 1° (25,4 mm) FIGURE 7 FIGURE 8 . SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT used to cover a clearance hole, may and after installation. Sprinklers dam - C are an delay the time to sprinkler operation in aged by dropping, striking, wrench a fire situation. twist/slippage, or the like, must be re- • aintenance Sprinklers that are found to be leaking placed. Also, replace any sprinkler that The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion has a cracked bulb or that has lost p liquid from its bulb. (Ref. Installation maintained and serviced in accord- must be replaced. Section). ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec- painted, plated, coated or otherwise ommended to be initially performed for NOTES altered after leaving the factory. Modi- corrosion resistant coated sprinklers, Before closing a fire protection system fied sprinklers must be replaced. main control valve for maintenance Sprinklers that have been exposed to after the installation has been com- work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor- it controls, permission to shut down the have not operated, should be replaced annual resistant ns oo tions s per r, NAPA A 25 affected fire protection system must be if they cannot be completely cleaned a pec obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of and all personnel who maybe affected by brushing it with a soft bristle brush. specting from the floor level, a random by this action must be notified. sampling of close up visual inspec Care must be exercised to avoid dam- tions should be made, so as to better Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi- TFP171 Page7of8 2 -7/8° DIA. 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4° (19,1 mm) (73,0 mm) (15,9±6,4 mm) 1/211/8° 1/2" (12,7 mm) 2 -1/4° DIA. 1/4'(6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4 "(6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) - 1 SPRINKLER PLATE SPRINKLER MOUNTING PLATE • FITTING FITTING 1/8" 1/8" 1 -i (3,2 mm) (3,2 mm) r i /�� i 1 • MOUNTING 11 MOUNTING �, , SURFACE SURFACE A _ -, A CLOSURE SERIES 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm) TY -FRB 3/4° (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8' DIA. 2 -7/8' DIA. 5/8x1/4° (73,0 mm) 3/4' (19,1 mm) 1/2x1/8° (73,0 mm) 1/2° (12,7 mm) (15,9±6,4 mm) 2 -1/4° DIA. 1/4 °(6,4 mm) (12,7±3,2 mm) f - 2 -1/4° DIA. 1/4° (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8° 1/8" 11 (3,2 mm) n (3.21mm) / ASIMIWi Fi' A rd 1 1 4 . / 1 \ - -- ■ '�. ' MOUNTING oI� t MOUNTING SURFACE SURFACE 11 CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm) TY-FRB 13/16° (20,6 mm) TY-FRB 1 -1/16" (27,0 mm) FIGURE 11 FIGURE 12 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT tion and the long term integrity of the corrosion resistant coating, as it may WRENCH be affected by the corrosive conditions RECESS present. i WRENCH RECESS 3)- The owner is responsible for the in- (END °A" USED FOR + spection, testing, and maintenance of 1/2° NPT MODELS) n their fire protection system and de- . I vices in compliance with this docu- S' UUU ment, as well as with the applicable �°. standards of the National Fire Protec- WRENCH RECESS (END °B° USED FOR PUSH WRENCH tion Association (e.g., NFPA 25), in • ( 3/4° NPT MODELS) IN TO ENSURE addition to the standards of any other ENGAGEMENT authorities having jurisdiction. The in- WITH SPRINKLER stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA facturer should be contacted relative to W -TYPE 6 SPRINKLER any questions. WRENCH It is recommended that automatic FIGURE 14 sprinkler systems be inspected, local requirements and /or national W -TYPE? RECESSED tested, and maintained by a qualified codes. SPRINKLER WRENCH Inspection Service in accordance with Page 8 of 8 TFP171 P/N 57 -XXX -X- XXX I 1 TEMPERATURE MODEL/SIN RATING SPRINKLER 330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C 331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155F/68°C 340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)' 200 200 °F /93 °C 370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED 390 8.0K UPRIGHT (3/4 "NPT) TY4131 391 8.0K PENDENT (3/4 "NPT) TY4231 ' Eastem Hemisphere sales only. TABLE C PART NUMBER SELECTION SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon: Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es- DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N Warranty LIMITED TO LABOR CHARGES, RE- (specify). GARDLESS OF WHETHER TYCO Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2° (15 mm) Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10 original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated P/N 56- 701 -9-010 against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4-010 manship when paid for and properly ABILITY EXCEED AN AMOUNT Whits Rat9010• P/N 56-701-3-010 installed and maintained under normal EQUAL TO THE SALES PRICE. Brass Plated P/N 56 -701 -2 -010 use and service. This warranty will ex- THE FOREGOING WARRANTY IS 1/2° (15 mm) pire ten (10) years from date of ship- Style 20 ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND ALL Chrome Plated P/N 56- 705 -9-010 ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56 -705 -4-010 components manufactured by compa- IMPLIED, INCLUDING WARRANTIES White RAL9010• P/N 56- 705 -3-010 Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Brass Plated P/N 56 -705 -2 -010 Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR 3/4° (20 mm) components which have been subject POS Style 30 to misuse, improper installation, corro- Chrome Plated P/N 56- 705 -9 -011 sion, or which have not been installed, White Coated P/N 56 -705 -4 -011 maintained, modified or repaired in white Plated 0' P/N 56 -705 -3 -011 cordance with applicable Standards of ac- Ordering Brass Plated P/N 56-705-2-011 the National Fire Protection Associa- Procedure 3 /4• (20 mm) tion, and /or the standards of any other Style 40 Authorities Having Jurisdiction. Mate- esintackqguri focal distributor for avail- Chrome Plated P/N 56- 700 -9-010 rials found by Tyco Fire Products to be abq indicate the White Coated P/N 56-700-4-010 defective shall be either repaired or ful product White RAL9010• P/N 56- 700 -3-010 replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56 -700 -2 -010 the Price List for option. Tyco Fire Products neither as- complete listing • Eastem Hemisphere sales only. sumes, nor authorizes any person to of Part Numbers. assume for it, any other obligation in Sprinkler Wrench: connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench, parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387. shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench, incomplete information supplied by temperature rating), Series TY-FRB P/N 56-850-4-001. Y Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating), PRODUCTS BE LIABLE, IN CON P/N (specify from Table C). TRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THE - TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 4". )CO Fire & Building . Products - Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series TY -FRB — 5.6 K- factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage • General provided by the Recessed Escutcheon reduces the accuracy to which the ",,. fixed pipe nipples to the sprinklers �. Description must be cut. {,w The Series TV FRB, 5.6 K- Factor, Hori- Corrosion resistant coatings, where " rry P ; applicab are utilized to extend the l' '' am ''"" = `, described in this data sheet are quick life of copper alloy sprinklers beyond I zontal and Vertical Sidewall Sprinklers /' � � s , �� t response - standard coverage, deco that which would otherwise be ob- - ki !� a x , 44 , r 3 mm glass bulb type spray tained when exposed to corrosive at . 1 4 e sprinklers designed for use in light and mospheres. Although corrosion resin- ti + v ,"* rI . ordinary hazard, commercial occupan- tant coated sprinklers have passed the `71 ° '` cies such as banks, hotels, shopping standard corrosion tests of the appli- .Akz 7" malls, etc. They are designed for instal- cable approval agencies, the testing is ? - lation along a wall or the side of a beam not representative of all possible cor- and just beneath a smooth ceiling. rosive atmospheres. Consequently, it Sidewall sprinklers are commonly is recommended that the end user be used instead of pendent or upright c onsulted with respect to the suitability < ,, sprinklers due to aesthetics or building of these coatings for any given corro- 4 ,. construction considerations, where sive environment. The effects of ambi- piping across the ceiling is not desir- ent temperature, concentration of able. chemicals, and gas /chemical velocity, i i should be considered, as a minimum, ? z - . The recessed version of the Series along with the corrosive nature of the " , -.. Y T FRB Horizontal Sidewall Sprinkler chemical to which the sprinklers will be fy, -__- is in for use in areas with a exposed. r .. . finished wall. It uses a two -piece Style ''414 . ' ^3-. 10 Recessed Escutcheon with 1/2 inch WARNINGS (12,7 mm) of recessed adjustment or The Series TY -FRB Sprinklers de - up to 3/4 inch (19,1 mm) of total adjust- scribed herein must be installed and ment from the flush sidewall position, maintained in compliance with this or a two -piece Style 20 Recessed Es- document, as well as with the applica- Technical cutcheon with 1/4 inch (6,4 mm) of ble standards of the National Fire Pro- recessed adjustment or up to 1/2 inch tection Association, in addition to the Data (12,7 mm) of total adjustment from the standards of any other authorities ha v- flush sidewall position. The adjustment ing jurisdiction. Failure to do so may Approvals impair the performance of these de- UL and C -UL Listed. vices. FM, LPCB, and NYC Approved. The owner is responsible for maintain- (Refer to Table A for complete approval ing their fire protection system and de- information including corrosion resis- IMPORTANT vices in proper operating condition. tant status.) The installing contractor or sprinkler Maximum Working Pressure Zii Always refer to Technical Data manufacturer should be contacted 175 psi (12,1 bar) E Sheet TFP700 for the "INSTALLER with any questions. v WARNING" that provides cautions Discharge Coefficient m with respect to handling and instal- - K = 5.6 GPM /psis / (80,6 LPM/bar lation of sprinkler systems and corn- i�del/Spriiiklei" Temperature Ratings m ponents. Improper handling and in- stallation can permanently damage Identification Refer to Table A a sprinkler system or its compo- Finishes cc nents and cause the sprinkler to fail Numbers Sprinkler: Refer to Table A o to operate in a fire situation or cause Recessed Escutcheon: White Coated, a it to operate prematurely. TY3331 - Horizontal Chrome Plated, or Brass Plated o TY3431 - Vertical } Page 1 of 6 JULY, 2004 4FP176 Page 2 of 6 TFPI 76 SPRINKLER FINISH (See Note 11) K TYPE TEMP. BULB NATURAL CHROME WHITE"' LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange HORIZ. 155 °F /68 °C Red SIDEWALL 1, 2, 3, 4, 9, 10 1, 2, 3, 9 1, 2, 3, 9 (TY3331) 175 °F /79 °C Yellow 200 °F /93 °C Green 5.6 286F/141°C Blue 1/2" NPT RECESSED 135 °F /57 °C Orange HORIZ. 155 °F /68 °C Red SIDEWALL 1,2,4,9,10 1,2,9 N/A (TY3331)* 175 °F /79 °C Yellow Figure 3 200 °F /93 °C Green RECESSED 135 °F /57 °C Orange HORIZ. 155 °F /68 °C Red SIDEWALL 1, 2, 3, 4, 9 N/A (TY3331)'* 175 °F /79 °C Yellow Figure 4 200 °F /93 °C Green VERTICAL 135 °F /57 °C Orange SIDEWALL 155 °F /68 °C Red 5.6 (TY3431) 5, 6, 7, 8, 9 5, 6, 7, 9 1/2" Installed 175 °F /79 °C Yellow NPT Pendent 200 °F /93 °C Green or Upright 286 °F /141 °C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance. 2. Listed by Underwriters Laboratories Inc. for use in Canada (C -UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007a/04) at a 4 to 6 inch (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5. Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada (C -UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06 & 007a/04) as Quick Response Sprinklers. 9. Approved by the City of New York under MEA 354 -01 -E. 10. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) at a 4 to 6 inch (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers. Installed with Style 10 (1/2" NPT) 3/4° Total Adjustment Recessed Escutcheon. ** Installed with Style 20 (1/2" NPT) 1/2" Total Adjustment Recessed Escutcheon. "* Frame and deflector only. Listings and approvals apply to color (Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS Physical Characteristics �y Frame Bronze t% peratt1 o Button Brass /Copper Sealing Assembly The glass Bulb contains a fluid which Beryllium Nickel w/Teflont expands when exposed to heat. When Bulb Glass the rated temperature is reached, the Compression Screw Bronze fluid expands sufficiently to shatter the HSW Deflector Bronze glass Bulb, allowing the sprinkler to VSW Deflector Copper activate and water to flow. Patents U.S.A. 5,810,263 TENTS Page 3 of 6 Design DEFLECTOR Criteri - HAT \ 5 PAASIN `s The Series TY-FRB Horizontal and I— Vertical Sidewall Sprinklers are in- / iL � tended for fire protection systems de- signed in accordance with the stand- ard installation rules recognized by the 6 ' 4 2 3 1 applicable Listing or Approval agency (e.g., UL Listing is based on the re- 9/16" WRENCH 1/2" ** quirements of NFPA 13, and FM Ap- (14,3 mm) FLATS NPT proval is based on the requirements of FM's Loss Prevention Data Sheets). ...4 ���� II Only the Style 10 or 20 Recessed Es ` r N 7 / lira; cutcheon, as applicable, is to be used O I _�,�IIIIIIIIIIIIIIII) for recessed horizontal installations. . installation - 1- 13/16° 7/16° (46,0 mm) (11,1 mm) The Series TY -FRB Sprinklers must be CENTERLINE NOMINAL f installed in accordance with the follow- MAKE -IN ing instructions: OF SPRINKLER WATERWAY 1 -1/2, NOTES (36,1 mm) _ .- Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of 2-3/16° - liquid from the bulb. With the sprinkler (55,6 mm) held horizontally, a small air bubble STYLE ESCUTCHEON should be present. The diameter of the 10 or 20 — i - PLATE SEATING air bubble is approximately 1/16 inch RECESSED SURFACE (1,6 mm) for the 135 °F /57 °C to 3/32 ESCUTCHEON , ::::: - - - inch (2,4 mm) for the 286 °F /141 °C 1-Frame temperature ratings. 2 - Button 3 - Sealing �� '1 A leak tight 1/2 inch NPT sprinkler joint Assembly 7/8 DIA. should be obtained with a torque of 7 4-Bulb 2 7 mm) IIrAl.Mirliall ■ to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- 5 - Compression (73,0 mm ' 1 M1 mum of 21 ft. lbs. (28,5 Nm) of torque Screw ( ) q 6 - Deflector may be used to install sprinklers with 1/2 NPT connections. Higher levels of torque may distort the sprinkler and cause leakage or impairment of the - sprinkler. Do not attempt to make -up for insuffi- * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. cient adjustment in the escutcheon **Pipe thread connections per ISO 7/1 can be provided on special request. plate by under- or over- tightening the sprinkler. Readjust the position of the FIGURE 1 sprinkler fitting to suit. 5.6 K- FACTOR QUICK RESPONSE The Series TY -FRB Horizontal and SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS Vertical Sidewall Sprinklers must be installed in accordance with the follow- ing instructions. Step 3. Tighten the sprinkler into the word "TOP" on the Deflector is to face Step 1. H orizontal sidewall sprinklers sprinkler fitting using only the W -Type towards the ceiling. p p 6 Sprinkler Wrench (Ref. Figure 5), are to be installed in the horizontal With reference to Figure 1 or 2, the Step B. After installing the Style 10 or position with their centerline of water - W -Type 6 Sprinkler Wrench is to be 20 Mounting Plate over the sprinkler way perpendicular to the back wall and applied to the wrench flats. threads, hand tighten the sprinkler into parallel to the ceiling. The word "TOP" the sprinkler fitting. on the Deflector is to face towards the The Series TY -FRB Recessed Hori- Step C. Tighten the sprinkler into the ceiling. zontal Sidewall Sprinklers must be sprinkler fitting using only the W -Type installed in accordance with the follow- 7 Recessed Sprinkler Wrench (Ref. Figure Vertical sidewall sprinklers are to be ing instructions. 6). r installed in the pendent or upright po- 9 )• With peference to Figure 1, sition with the arrow on the Deflector Step A. Recessed horizontal sidewall the W -Type 7 Recessed Sprinkler pointing away from the wall. sprinklers are to be installed in the Wrench is to be applied to the sprinkler Step pipe thread sealant horizontal position with their centerline wrench flats. plied 2 2 . With pe thr thr tighten of waterway perpendicular to the back g p the pipe threads, hand g wall and parallel to the ceiling. The Ste p D. After the ceiling has been in- the sprinkler into the sprinkler fitting. stalled or the finish coat has been ap- • Page 4 of 6 TFPI 76 plied, slide on the Style 10 or 20 Clo- sure over the Series TY-FRB Sprinkler ARROW MUST . and push the Closure over the Mount- POINT AWAY ing Plate until its flange comes in con- 7/16° FROM AND BE \ O tact with the ceiling ESCUTCHEON (11,1 mm) PERPENDICULAR / PLATE SEATING ° ** SURFACE NOMINAL TO THE BACK I Care and NP MAKE -IN WALL SURFACE 1 *6 Maintenance 1 __,-,-- 1 - -,�c� 'f,\ / 5 The Series TY BFR Sprinklers must be 2 - 3/16° — 7 2 - 3/16° maintained and serviced in accord- (55,6 mm) 1 A.. (55,6 mm) li 4 ante with the followin instructions: �� NOTES 1 - 1/2° WRENCH i!'�IP� y 2 Before closing a fire protection system (38,1 mm) FLAT 7 3 main control valve for maintenance work on the fire protection system that � � s - 1 it controls, permission to shut down the affected fire protection system must be SHOWN SHOWN CROSS obtained from the proper authorities PENDENT UPRIGHT SECTION and all personnel who may be affected by this action must be notified. 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Absence of an escutcheon, which is 2 - Button Assembly 5 - Compression 7- Ejection Spring used to cover a clearance hole, may Screw delay the time to sprinkler operation in a fire situation. * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. Sprinklers that are found to be leaking **Pipe thread connections per ISO 7/1 can be provided on special request. or exhibiting visible signs of corrosion must be replaced. FIGURE 2 Automatic sprinklers must never be 5.6 K- FACTOR QUICK RESPONSE painted, plated, coated or otherwise SERIES TY-FRB VERTICAL SIDEWALL (TY3431) SPRINKLERS altered after leaving the factory. Modi- fied sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned spection, testing, and maintenance of ment by Tyco Fire Products. No war - by wiping the sprinkler with a cloth or their fire protection system and de- ranty is given for products or compo- by brushing it with a soft bristle brush. vices in compliance with this docu- nents manufactured by companies not ment, as well as with the applicable affiliated by ownership with Tyco Fire • Care must be exercised to avoid dam- standards of the National Fire Protec- Products or for products and compo- age to the sprinklers - before, during, lion Association (e.g., NFPA 25), in nents which have been subject to mis- and after installation. Sprinklers dam- addition to the'standards of any other use, improper installation, corrosion, aged by dropping, striking, wrench authorities having jurisdiction. The in- or which have not been installed, main- . twist/slippage, or the like, must be re- stalling contractor or sprinkler manu- tained, modified or repaired in accord - placed. Also, replace any sprinkler that facturer should be contacted relative to ance with applicable Standards of the has a cracked bulb or that has lost any questions. National Fire Protection Association, liquid from its bulb. (Ref. Installation and /or the standards of any other Section). It is recommended that automatic Authorities Having Jurisdiction. Mate - Frequent visual inspections are rec- sprinkl systems be inspected, rials found by Tyco Fire Products to be q P tested, and maintained by a qualified o replaced, at Tyco Fire Products' s ired or a ommended to be initially performed for Inspection Service in accordance with defective shall be either repaired corrosion resistant coated sprinklers, local requirements and /or national option. Tyco Fire Products neither sole after the installation has been com- codes. P y as- pleted, to verify the integrity of the cor- sumes, nor authorizes any person to rosion resistant coating. Thereafter, assume for it, any other obligation in annual inspections per NFPA 25 Limited connection with the sale of products or should suffice; however, instead of in- parts of products. Tyco Fire Products specting from the floor level, a random Warranty shall not be responsible for sprinkler sampling of close -up visual inspec- system design errors or inaccurate or tions should be made, so as to better Products manufactured by Tyco Fire incomplete information supplied by determine the exact sprinkler condi- Products are warranted solely to the Buyer or Buyer's representatives. tion and the long term integrity of the original Buyer for ten (10) years IN NO EVENT SHALL TYCO FIRE corrosion resistant coating, as it may against defects in material and work- PRODUCTS BE LIABLE, IN CON - be affected by the corrosive conditions manship when paid for and properly TRACT, TORT, STRICT LIABILITY OR present. installed and maintained under normal UNDER ANY OTHER LEGAL THE - use and service. This warranty will ex- ORY, FOR INCIDENTAL, INDIRECT, The owner is responsible for the in- pire ten (10) years from date of ship- SPECIAL OR CONSEQUENTIAL WWI 76 Page 5 of 6 - 5/8 ±1 /4" G . (15,916,4 mm) FACE OF WRENCH R ECESS MOUNTING SPRINKLER (END 'A° US FOR SURFACE ^ U2° NPT MODELS) FITTING 4 FIGURE 5 CLOSURE ial W -TYPE 6 SPRINKLER WRENCH /_ 2 -7/8" DIA. WRENCH SERIES 121211 I p 2 1/4" DIA. (73,0 mm) RECESS TY -FRB '11,IIIII �� : (57,2 mm) -r -_ d‘4,P11 MOUNTING • PLATE (r y 1/8" PUSH WRENCH rr (3,2 mm) IN TO ENSURE ENGAGEMENT 1 -1/4" (31,8 mm) 3/4" (19,1 mm) WITH SPRINKLER WRENCHING AREA 3/4" (19,1 mm) 1/4" (6,4 mm) FIGURE 3 FIGURE 6 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER W -TYPE 7 RECESSED WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT SPRINKLER WRENCH STYLE 10 RECESSED ESCUTCHEON y 1/2±1/8" (12,7 ±3,2 mm) DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, RE- MOUNTING FACE OF GARDLESS OF WHETHER TYCO SPRINKLER FIRE PRODUCTS WAS INFORMED SURFACE FITTING ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT • 4 SHALL TYCO FIRE PRODUCTS' LI- Q ABILITY EXCEED AN AMOUNT CLOSURE J EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS � = 2 - 7/8" DIA. MADE IN LIEU OF ANY AND ALL SERIES I: I (73,0 mm) OTHER WARRANTIES EXPRESS OR �_ nlll 2 DIA. IMPLIED, INCLUDING WARRANTIES TY �= OF MERCHANTABILITY AND FIT- (57,2 mm) NESS FOR A PARTICULAR PUR- .1 POSE. MOUNTING 1 PLATE o y 1/8" (3,2 mm) 1 -1/4" (31,8 mm) 1/2" (12,7 mm) 1" (25,4 mm) 1/4" (6,4 mm) FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON Page 6 of 6 TFP176 P/N 57 - XXX - X - XXX 1 1 SPRINKLER TEMPERATURE MODEUSIN RATING 378 HORIZONTAL SIDEWALL TY3331 1 NATURAL BRASS 135 135 °F /57 °C 375 VERTICAL SIDEWALL TY3431 4 WHITE POLYESTER 155 155 °F /68 °C 3 WHITE RAL9010)' 175 175 °F /79 °C 9 CHROME PLATED 200 200 °F /93 °C 7 LEAD COATED 286 286 °F /141 °C TABLE B • Eastem Hemisphere sales only. PART NUMBER SELECTION SERIES TV-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS rderii g Procedure When placing an order, indicate the full Recessed Escutcheon: product name. Refer to the Price List Specify: Style (specify) Recessed Es- for complete listing of Part Numbers. cutcheon with (specify finish), P/N Contact your local distributor for avail- (specify). ability. 1/2° (15 mm) Style 10 Sprinkler Assemblies with NPT Chrome Plated P/N 56- 701 -9-010 Thread Connections: 1/2' (15 mm) Specify: (Specify Model /SIN), Quick Style 10 White color Response, (specify K- factor), (specify Coated P/N 56- 701 -4 -010 temperature rating), Series TY FRB 112' (15 mm) (specify Horizontal Sidewall or Vertical Style 10 . Sidewall) Sprinkler with (specify type White RAL9010° P/N 56- 701 -3-010 of finish or coating), P/N (specify from 1/2' (15 mm) Table B). Style 10 Brass Plated P/N 56- 701 -2 -010 1/2' (15 mm) Style 20 Chrome Plated P/N 56- 705 -9 -010 1/2' (15 mm) Style 20 White Color Coated P/N 56 -705 -4 -010 1/2' (15 mm) Style 20 White RAL9010* P/N 56- 705 -3 -010 1/2' (15 mm) Style 20 Brass Plated P/N 56 -705 -2 -010 • Eastem Hemisphere sales only. Sprinkler Wrench: Specify: W -Type 6 Sprinkler Wrench, P/N 56- 000 -6 -387. Specify: W -Type 7 Sprinkler Wrench, P/N 56- 850 -4 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446