Plans i
PLUMBING GENERAL NOTES PLUMBING ABBREVIATIONS DOMESTIC WATER PRESSURE REDUCING VALVE SCHEDULE
1 . PIPING MATERIAL SCHEDULE: ABBV FULL NAME ABBV FULL NAME UNIT MANUFACTURER SERIES SIZE GPM PRESSURE FALL OFF NOTES AAAA
PIPING LOCATION MATERIAL JOINT A COMPRESSED AIR LINE MNR HOT WATER RETURN NO. _ MODEL# INLET OUTLET PRESSURE
COLD WATER ABOVE GROUND COPPER/L LEAD FREE SOLDER AFF ABOVE FINISHED FLOOR HWS HOT WATER SUPPLY PRV-1 WILKINS 500 2" 70 108PSI 60PSI 5PSI
HOT WATER ABOVE GROUND COPPER/L LEAD FREE SOLDER
BFP BACKFLOW PREVENTER INVERT ELEVATION
CB CATCH BASIN MH MANHOLE
C 1 CAST IRON MG MEDIUM PRESSURE GAS MacDonald Miller
WASTE ALL ABS/PVC SCH 40 SOLVENT CEMENT CO CLEAN OUT OFD OVERFLOW DRAI N
CW COLD WATER ORL OVERFLOW RAIN LEADER
ABOVE GROUND ABS/PVC SCH 40 SOLVENT CEMENT CV CHECK VALVE POC POINT OF CONNECTION DRAIN FIXTURE CONNECTION SCHEDULE Company, Inc.
DCBP DOUBLE CHECK BACKFLOW PREVENTER PRV PRESSURE REDUCING VALVE NO. FIXTURE LOCAL CONNECTION
VENT ALL ABS/PVC SCH 40 SOLVENT CEMENT DN DOWN RD ROOF DRAIN WASTE VENT STORM 1240 SE 12th AVE.
ELEV ELEVATION RL RAIN LEADER FD-1 FLOOR DRAIN - ZURN ZN-415B CAST IRON BODY w/ 5" ADJUSTABLE, 2" 1 1/2" Portland, OR 97214
ABOVE GROUND ABS/PVC SCH 40 SOLVENT CEMENT (E) EXISTING SD STORM DRAIN TYPE B NICKEL BRONZE STRAINER.
F FIRE SS SANITARY SEWER
INDIRECT WASTE ALL COPPER/DWV/M LEAD FREE SOLDER FCO FLOOR CLEAN OUT TOG TOP OF GRATE RD-1 ROOF DRAIN - ZURN Z-100-R-C. CAST IRON BODY. CLAMPING COLLAR 4" - -
FD FLOOR DRA 1 N TP TRAP PRIMER W/ POLYDOME & UNDERDECK CLAMP. PIlOftf; (503) 230-8991
NATURAL GAS ABV GROUND SCH 40 STL. THREADED G NATURAL GAS UNO UNLESS NOTED OTHERWISE Fox: (503 230-9238
GLV GLOBE VALVE V VENT
HB HOSE BIBB VTR VENT THRU ROOF
HW HOT WATER w WASTE
2. PIPING INSULATION SCHEDULE: HWC HOT WATER CIRCULATING w/ WITH PLUMBING FIXTURE CONNECTION SCHEDULE
PIPING PIPE INSULATION INSULATION CONDUCTIVITY WOO WALL CLEAN OUT
WH WALL HYDRANT NO. FIXTURE LOCAL CONNECTION
TYPE SIZE TYPE THICKNESS RANGE WASTE VENT HOT COLD
OVERHEAD COLD WATER ALL FIBERGLASS 1/2'" - -
COLD WATER WITHIN WALLS - NOT REQUIRED - -
WC-1 WATER CLOSET - KOHLER K-4330, WALL MOUNTED FLUSH 4" 2" 1"
HOT WATER AND REC I RC 1/2"-2" FIBERGLASS 1 " 0.24 - 0.28 VALVE, BEMIS #1955C-OF SEAT LESS COVER, WHITE, W/
2" - 6" FIBERGLASS 1 1/2" 0.24 - 0.28 Z-6000-WS-1 SERIES 1.6 GAL FLUSH VALVE, ZURN ZR-1200
COIL CONDENSATE PIPING ALL ARMAFLEX 1/2' SERIES WALL CARRIER REQUIRED.
SYMBOL PLUMtIP IOr�.EGEND ABBREVIATION
N CHECK VALVE CV WC-2 HANDICAP WATER CLOSET - KOHLER K-4330, WALL MOUNTED 4" 2" - 1"
FLUSH VALVE, ELONGATED, SIPHON JET, MOUNT W/RIM AT
D4 GATE VALVE GV 17" AFF, BEMIS #1955C-OF SEAT LESS COVER, WHITE, W/
D3:1 BALL VALVE BV Z-6000-WS-1 SERIES 1.6 GAL FLUSH VALVE, ZURN ZR-1200
- ALL PIPING INSULATION: AND COVERINGS SHALL HAVE AN ASTM FLAME SPREAD RATING OF 25 Db PRESSURE REDUCING VALVE PRV SERIES WALL CARRIER REQUIRED. (FLUSH HANDLE TO POINT
OR LESS AND AN ASTM SMOKE DEVELOPED RATING OF 50 OR LESS.
TO WIDE PART OF STALL)
- ELASTOMERIC INSULATIONS WHICH MEET THESE RATINGS MAY BE USED AS A SUBSTITUTE FOR - COLD WATER CW
FIBERGLASS. -- HOT WATER PIPING HW UR-1 URINAL - KOHLER K-5016-T SIPHON JET, W/Z-6003-WS-1 2" 1 1/2" - 3/4"
- PROVIDE A VAPOR BARRIER COVERING ON ALL ROOF DRAIN, RAIN LEADER, AND COLD WATER -- RETURN HOT WATER PIPING RHw SERIES 1.0 GAL FLUSH VALVE, WHITE.
PIPING INSULATION. SANITARY SEWER ABOVE GRADE W L-1 LAVATORY - KOHLER K-2196 COUNTER TOP 4" CENTER 1 1/2" 1 1/2" 1/2" 1/2"
- PROVIDE A COVERING FOR ALL INSULATION EXPOSED TO SIGHT WITHIN THE BUILDING. SANITARY SEWER BELOW GRADE SS LAVATORY, WHITE, W/KOHLER K-15199-P CP SINGLE
- PROVIDE AN INCOMPRESSABLE INSULTATED PAD WITH A MINIMUM THERMAL RESISTANCE OF R-10 VENT PIPING V LEVER FAUCET W/JAMECQ 629 1 1/4" CP GRID DRAIN,
UNDER ALL ELECTRIC WATER HEATERS IN UNCONDITIONED SPACES OR ON CONCRETE FLOOR. 0 VTR VENT THRU ROOF VTR BRASSCRAFT OCR-1920-A CP SUPPLIES, 1 1/4" CP 17 GA
3. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE
0 FLOOR CLEAN OUT FCO P-TRAP.
REQUIRED. THE PLUMBING CONTRACTOR IS TO COORDINATE WITH ALL OTHER TRADES AND IS TO WALL CLEAN OUT WCO L-2 HANDICAPPED LAVATORY - KOHLER K-2196 COUNTER TOP 1 1/2" 1 1/2" 1/2" 1/2"
VERIFY ALL CLEARANCES BEFORE COMMENCING WORK. G GAS PIPING WCO 4" CENTER LAVATORY, WHITE, W/KOHLER K-15199-P CP
SINGLE LEVER FAUCET W/JAMECO 629 1 1/4" CP GRID
NOTE: ALL EXISTING PIPING & EQUIPMENT IS SHOWN IN LIGHT LINE WEIGHT. DRAIN, BRASSCRAFT OCR-1920-A CP SUPPLIES, OFFSET
4. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 1994 1 1/4" CP 17 GA P-TRAP. (PROVIDE TRUBRO HANDI
EDITION OF THE UNIFORM PLUMBING CODE. W/1996 OREGON AMENDMENTS. LAV-GUARD INSULATION KIT #102 W/#105)
5. ALL PIPE SIZES NOTED ON DRAWINGS ARE MINIMUMS.
JS-1 JANITOR SINK - KOHLER K-6710, 28x28 FLOOR SINK, 2" 1 1/2" 1/2" 1/
WHITE, W/ KOHLER K-8940 RIM GUARD, KOHLER K-9142,
6. SLOPE ALL RAIN LEADER, STORM, AND WASTE PIPING AT 2% UNLESS OTHERWISE NOTED ON 2" IPS DRAIN, CHICAGO 897 CP SERVICE FAUCET W/VACUUM
DRAWINGS. OBTAIN APPROVAL FROM CODE AUTHORITY BEFORE INSTALLING PIPING AT LESS THAN BREAKER.
2% (EVEN IF LESSER SLOPE IS INDICATED ON DRAWINGS) .
DF-1 HANDICAP WATER COOLER - ELKAY EBFSA-4, STAINLESS 1 1/2" 1 1/2" - 1/2"
7. HANGERS AND SUPPORTS FOR PIPING SHALL BE IN ACCORDANCE WITH SECTION 314.0 OF THE 1994 STEEL FINISH, W/ BRASSCRAFT CR-1920-A-C QUARTER TURN
UNIFORM PLUMBING CODE. PROVIDE EARTHQUAKE SWAY BRACING AT 40' INTERVALS FOR ALL SUPPLIES, 1 1/4" CP 17 GA P-TRAP, 115 V/1 PHASE,
PIPING WH1CH IS 2 1/2" AND LARGER WHICH HAVE HANGERS THAT EXCEED 12" IN LENGTH AS
4.8 FLA, 8.0 GPH.
DESCR 1 BED BY THE SMACNA SEISMIC BRACING MANUAL. SH-1 HANDICAP SHOWER - FIBER-FAB 36H, WHITE, W/GRAB 2" 1 1/2" 1/2" 1/2"
BARS, FOLD-UP SEAT (SPECIFY RIGHT OR LEFT),
8. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED FIBER-FAB S-SH SHOWER ROD, MOEN 2370 CP POSI-TEMP
WITH LISTED MATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR SHOWER, ONDINE 28654 24" GLIDE BAR, ONDINE 28196
WALL. FLEX HOSE, ONDINE 28088 PUSH BUTTON HAND SPRAY,
ONDINE 28716 INLINE VACUUM BREAKER, ONDINE 28630
SWIVEL CONNECTOR, ONDINE 27420 CP SUPPLY ELBOW,
9. FOR EXACT ROUGH-IN LOCATIONS AND ELEVATIONS OF PLUMBING FIXTURES REFER TO 101BR CP BRASS SHOWER DRAIN.
ARCHITECTURAL DRAWINGS.
HB-1 HOSE BIBB - WOODFORD 24P CP, NON-FREEZEPROOF, - - - 3/4"
10. PROVIDE LOOSE KEY STOPS OR ANGLE VALVES AT ALL FIXTURES W/ VACUUM BREAKER & OPERATING KEY.
11 . PROVIDE TRAP PRIMERS FOR ALL FLOOR DRAINS.
12. PROVIDE DIELECTRIC CONNECTIONS BETWEEN DISSIMILAR METALS. IF THE ELECTRICAL IS 0'2 GROUNDED TO THE P i PE SYSTEM THEN ALL DIELECTRIC CONNECTIONS REQU I RE A JUMPER TO PLUMBING EQUIPMENT SCHEDULE �
MAINTAIN ELECTRICAL GROUNDING.
13. CLEANOUTS SHALL BE INSTALLED SO THEY ARE EASILY ACCESS IBLE.
NO. FIXTURE C5< C5-)\
\\
14. PLUMBING EQUIPMENT, VALVES AND TRAP PRIMERS SHALL BE LOCATED IN EASILY ACCESSIBLE EWH-1 ELECTRIC WATER HEATER - AO SMITH DRE-80, GLASS-LINED 80 GALLON ASME TANK,
LOCATIONS. UNLESS SHOWN ON ARCHITECTURAL DRAWINGS, REQUIRED ACCESS PANELS SHALL BE 18 KW INPUT AT 480 VOLT/3 PHASE. RECOVERY OF 74 GALLONS PER HOUR AT 100'F
FURN I SHED BY THE PLUMB 1 NG CONTRACTOR AND I NSTALLED BY THE GENERAL CONTRACTOR. TEMPERATURE RISE, 40'F ENTERING WATER / 120'F LEAVING WATER, SET THERMOSTAT
AT 140'F, 1 1/4" INLET/OUTLET, 3/4" RELIEF, OPERATING WEIGHT OF 1090 LBS.
15. THE PLUMBER SHALL PROVIDE AND LOCATE ALL REQUIRED FLOOR, WALL, AND FOOTING SLEEVES.
EXT-1 EXPANSION TANK - AMTROL THERM-X-TROL MODEL ST-25V, 10.3 GALLON VOLUME, MAXIMUM
ACCEPTANCE VOLUME OF 10.3 GALLONS, BLADDER TYPE, PRECHARGE OF 65 PSIG.
16. TRENCHING, BACKF I LL I NG, AND COMPACTING FOR UNDERGROUND PIPING SHALL BE THE OPERATING WEIGHT 30 LBS. LOCATION 1ST FLOOR G & 2, WATER HEATER EWH-2. - -
RESPONSIBILITY OF THE PLUMBING CONTRACTOR UNLESS STATED OTHERWISE IN CONTRACT ; ---DOCUMENTS. WCP-1 WATER CIRCULATING PUMP - GRUNFOS UP15-18SU, 2 GPM AT 6 FT HD, 1/25 HORSEPOWER, r
120 VOLT/1 PHASE, STAINLESS STEEL CONSTRUCTION FOR DOMESTIC WATER, WITH TIMER - -
CONTRO L.
CITY IDF TIGARD [ 11:: -
SP-1 SUMP PUMP - PACO PIP 700A, 20 GPM AT 10 FT HD, 1/20 HORSEPOWER, 1Y4" CONNECTION, A(y�roved.�• „,.............. [ - -
120 VOLT/1 PHASE. Conditionally APProVed ,� "jpZSg _
For only the work as de/cribed n: ■Q . P 1S°I -
PERMIT O. rL -
I t: QL.Itn Pei oa
INTERIOR WALL See Letter to:Follow..-•- "' ' [ l• - -
_.... .....4.-...... - -
Att 9-.5 Gt. . ..5 , , G
FACE WHERE Job Address: �I �d
APPLICABLE l - -
CAST IRON PIPE ' /� t]Gte: _-
WITHIN 5'-O" OF / -p t y: ! �'�� - -
1
BLDG. f ; (i� - -
�, / e I _
FINISHED WALL HOT WATER CIRCULATING PUMP�_ -
FLOOR CLEANOUT OR �/I (WCP-1) . r1 -
I CLEANOUT TO GRADE v'` / I -- v
'/ WHERE NOTED. j .-4 ►. , -
f 2
FLUSH VALVE ASSEMBLY = !/ J - -\A WITH TRAP PRIMER OPTION WI I �4" HOT WATER RECIRC LINE J 1 r -
U FIN. GRADE I -�
Ili 1 G DE I FINISHED FLOOR � '
OR PAVING -`" r f " - 1__:::7_-\-HOT -- z - -
. • : . :. ... HOT WATER SUPPLY
i / F... : TO BUILDING •
E7 - -
t14.1 SANITARY Pam 1COVER f SEAL PENETRATION COLD WATER � //>/./`/` ■ =/ fi r. - -0 /r 1 f //
---- Z\ TEE AFTER PIPING IS INSTALLED SUPPLY 1---i- T & P RELIEF VALVE f
sue- �-L -- ■ t ` . l
-$r--- I % 1 • f/ //' -
T -( 1 1/ 1 ` EXPANSION TANK-7 // / -
I {�ii. a �ll .,//_ BLOCK-OUT IN STEM ( )
■ I / 1 ' ', ' f ELECTRIC WATER HEATER - _
.` �, if i /z WM r�// WALL FOR PIPING _` (EWH-1)
-.s--- [:
PROVIDE SEISMIC BRACING
I .. REVISIONS: DATE I 4"MIN SIZE i � " RELIEF
.�__J� `t / I HORIZONTAL _ _ ;
SUMP CONTROL
FLOOR DRAIN VINISHED FLOOR - BELOW GRADE I __ -. SWITCH
�'f �.. _.............. .. DRAIN VALVE .
-- FERNCO, CALDER �
/SERVICE SINK
-217"23---- / / f / / / / -�� OR MISSION / SUMP 4
TIGARD CORPORATE
--- PIPING IN WALL MOLDED RUBBER C-� r/ VERIFY LOCr�TION �•
-- COUPLING Co MATERIAL
/ CENTER - TYPICAL
l) (--� SLOPE PIPING CHANGE
/ SUMP PUMP /
`�'--'�� P-TRAP 0 1, P&i1rr crn Str BUILDING
� r no, r� CORE AND SHELL SET
//,///,744/'/Z/2,?/'
;// /. /' J/2,,/' " e-r �''t�
i TRAP PRIMER DETAIL 2 STORM DRAIN AT WALL FOOTING 3 ELEC. WATER HEATER PIPING DETAIL ELEVATOR PIT-PLAN TG �,/v Stn
P0.01 NO SCALE P0.01 NO SCALE P0.01 NO SCALE a r /-` f
'UMP CONTROL TIGARD, OREGON
SWITCH
0 .
PROVIDE 11/4" NPT FLOOR LEGENDS & SCHEDULE
FITTING ON WALL W/CAP. PLUMBING
REDUCED PORT BALL VALVE �
CHECK VALVE
BYPASS (TWO PIPE SIZES UNION ENGINEER: LAST REVISED:
SMALLER THAN MAIN LINE) N. SCOTT 6-22-99
01°°°1 I - SUMP GRATE
PRESSURE GAUGE (TYP)
_ CHECKED BY: DATE PLOTTED:
n� �.//74,
/f /// / /7/7 -"
R. FREY 6-22-99
0 9 / , AM SUMP
D4 I( I� I I pd J - , ISSUE GATE:
_rjam/. N. SCOTT 6-23-99
BLDG WATER SUPPLY
'r men
TO FIXTURES LIQUID LEVEL DRAWING NUMBER:
GATE VALVE (TYP) SUMP PUMP /////7 / MERCURY FLOAT 289-1000-20
UNION (TYP) (SP-1) LOCATEDMIN
STRAINER MACHINE ROOM
PRESSURE REDUCING
ISSUED FOR
VALVE SET AT 60 PSI ELEVATOR PIT-ELEV. d
PERMIT
LLi
4 PRESSURE REDUCING STATION DETAIL 5 ELEVATOR SUMP PUMP
SHEET NUMBER: z
Li
P0.01 NO SCALE P0.01 NO SCALE
Q.01 a
U