Plansi WAC GENERAL NOTES 1. THE HVAC SYSTEM FOR THIS PROJECT IS BASED ON THE FOLLOWING CRITERIA: ROOF "U" VALUE (BTUH/S.F: F) = 0.05 WALL "U" VALUE (BTUH/S.F:F) = 0.10 FLOOR "U" VALUE (BTUH/S.F: F) = N/A - GLASS "U" VALUE (BTUH/S.F: F) = 0.57 GLASS SHADE COEFF. = 0.56 LIGHTING (WATTS/S.F.) = 1.2 MISC. EQUIP. (WATTS/S.F.) = 1..8 PEOPLE DENSITY (S.F./PERSON) = 142 COOLING INDOOR DESIGN TEMP ('F) = 75 COOLING OUTDOOR DESIGN TEMP ('F) = 95 HEATING INDOOR DESIGN TEMP ('F) = 70 HEATING OUTDOOR DESIGN TEMP ('F) = 18 2. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. THE HVAC CONTRACTOR IS TO COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK. 3. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 1997 EDITIONS OF THE UNIFORM MECHANICAL CODE, UNIFORM BUILDING CODE, UNIFORM FIRE CODE AND LOCAL CODES AND ORDINANCES WITH 1998 OREGON AMENDMENTS. 4. DUCT CONSTRUCTION AND HANGING SHALL COMPLY WITH CHAPTER 6 OF THE 1996 GMSC AND WITH CURRENT SMACNA STANDARDS. EARTHQUAKE BRACE ALL DUCTS 28" DIA AND LARGER WHICH ARE SUSPENDED MORE THAN 12" BELOW STRUCTURAL SYSTEM. 5. JOINTS OF MEDIUM AND HIGH VELOCITY DUCT SYSTEMS SHALL BE SEALED WITH GASKETS OR LISTED MASTIC TYPE DUCT SEALANT. 6. DUCTS SHALL BE INSULATED AS INDICATED ON PLANS. - SOUND LINING, WHERE INDICATED, SHALL BE 1" 1.5 LB/CU FT FIBERGLASS DUCT LINING COATED TO PREVENT FIBER EROSION AT VELOCITIES UP TO 4000 FPM. 7. FLEXIBLE DUCTS SHALL CONSIST OF A REINFORCED VAPOR BARRIER, 1 1/2" FIBERGLASS INSULATION, AND NON -PERFORATED INTERIOR LINER WITH WIRE HELIX. DUCT SHALL BE A UL 181 LISTED CLASS 1 AIR DUCT. FLEXIBLE DUCTS SHALL ONLY BE USED WHERE SHOWN AND SHALL NOT EXCEED 12' IN LENGTH UNLESS NOTED OTHERWISE. 8. PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH SECTION 1630 OF THE 1998 OSSC. 9. PROVIDE FIRE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 713.11 OF THE 1998 OSSC. PROVIDE CEILING FIRE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 710.2 OF THE 1998 OSSC. INSTALL FIRE DAMPERS AND CEILING FIRE DAMPERS IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS, THE TERMS OF THEIR LISTING, AND THE REQ'MENTS OF THE CODE. 10. PROVIDE SUPPLY DUCT SMOKE DETECTOR AUTOMATIC SHUT DOWN OF ALL HEATING, COOLING, OR VENTILATION EQUIPMENT DELIVERING IN EXCESS OF 2000 CFM IN ACCORDANCE WITH SECTION 608 OF THE 1996 GMSC. POWER WIRING AND INTERLOCK WIRING WITH THE BUILDING FIRE ALARM SYSTEM IS BY THE ELECTRICAL CONTRACTOR. 11. HVAC EQUIPMENT, VALVES AND DAMPERS SHALL BE LOCATED IN EASILY ACCESSIBLE LOCATIONS. UNLESS SHOWN ON ARCHITECTURAL DRAWINGS, REQUIRED ACCESS PANELS SHALL BE PROVIDED BY THE HVAC CONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. 12. ALL MOTOR STARTERS NOT LISTED AS BEING PROVIDED IN THE HVAC EQUIPMENT SCHEDULES ARE TO BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. 13. ALL DUCT DIMENSIONS SHOWN ON PLANS ARE INSIDE CLEAR DIMENSIONS. DRAWING SHEET INDEX SHEET NUMBER DESCRIPTION MO.01 SCHEDULES - HVAC M1.01 DETAILS - HVAC M2.11 FIRST FLOOR PLAN - HVAC M2.12 FIRST FLOOR PLAN - ZONING PLAN M2.21 SECOND FLOOR PLAN - HVAC M2.22 SECOND FLOOR PLAN - ZONING PLAN DIFFUSER/GRILLE SCHEDULE SYMBOL WAC AR TIONS LEGEND TYPE ABBV FULL NAME ABBV FULL NAME ABBY FULL NAME AC AIR CONDITIONING UNIT ESP EXTERNAL STATIC PRESSURE NOM NOMINAL AFF ABOVE FINISHED FLOOR EXH EXHAUST OA OUTSIDE AIR BDD BACKDRAFT DAMPER EXTR EXTRACTOR OBD OPPOSED BLADE DAMPER BOD BOTTOM OF DUCT FDf FIRE DAMPER OD OUTSIDE DIMENSION BOTT BOTTOM FLA FULL LOAD AMPS RA RETURN AIR BTU BRITISH THERMAL UNITS FOB FLAT ON BOTTOM REG REGISTER (GRILLE WITH DAMPER) BTUH BRITISH THERMAL UNITS PER HOUR FOT FLAT ON TOP REQ'D REQUIRED CAP CAPACITY GALV GALVANIZED RIO ROUGH IN ONLY CFM CUBIC FEET PER MINUTE GC GENERAL CONTRACTOR SA SUPPLY AIR CONN CONNECT GR GRILLE SL SOUND LINING DIFF DIFFUSER GWB GYPSUM WALL BOARD SM SHEET METAL DMPR DAMPER HP HORSE POWER SP STATIC PRESSURE DN DOWN ID INSIDE DIMENSION STL STEEL EC EGGCRATE M -M MACDONALD-MILLER SUSP SUSPENDED EER ENERGY EFFICIENCY RATIO MBH ONE THOUSAND BTUH TOD TOP OF DUCT ELEV ELEVATION MCA MINIMUM CIRCUIT AMPACITY TV TURN VANES 277/1 500 MIN MINIMUM TYP TYPICAL 10 390 MT MOUNT UNO UNLESS NOTED OTHERWISE 330 KITCHEN HGOD 1&3 MUA MAKE-UP AIR VD VOLUME DAMPER 460/3 277/1 19.:; LOW 00 VOLTAGE PHASE & DUCT DIAM �R VPEE-PAR-1111 8 590 180 310 3.5 DRAWING SHEET INDEX SHEET NUMBER DESCRIPTION MO.01 SCHEDULES - HVAC M1.01 DETAILS - HVAC M2.11 FIRST FLOOR PLAN - HVAC M2.12 FIRST FLOOR PLAN - ZONING PLAN M2.21 SECOND FLOOR PLAN - HVAC M2.22 SECOND FLOOR PLAN - ZONING PLAN DIFFUSER/GRILLE SCHEDULE SYMBOL DAMPER LEGEND TYPE SYMBOL DESCRIPTION & MODEL NUMBER SYMBOL DESCRIPTION FLEX CONNECTOR 1 Y2 HOUR VERTICAL COMBINATION FIRE/SMOKE DAMPER FD t Y2 1 Y2 HOUR CURTAIN STYLE VERTICAL FIRE DAMPER < � FSD1&Y2 CESCO FSD(x) OR EQUAL 10640 10640 CESCO 75A -V OR EQUAL t2AJ DUCT ACCESS - BY MECHANICAL CONTRACTOR TITUS MCD BORDER 6 BDD BACKDRAFT DAMPER CESCO BDA OR EQUAL T CFM VOLTS PH STGS FAN HP ACCESS DOOR - 18" x 18" MINIMUM THROUGH BUILDING AS NOTED SURFACE MT RET/EXH AD CONSTRUCTION - BY GENERAL CONTRACTOR 10 1165 350 VDI VOLUME DAMPER TITUS TDCA BORDER 6 AS NOTED SURFACE MT DIFFUSER PROVIDE WITH PATTERN CONTROLLER SHOP FABRICATED, CESCO CDS-OB OR EQUAL 2 1/3 CENTRAL AREA AND RADIAL OPPOSED BLADE DAMPER. o-IZ GENERAL NOTES: AS NOTED LAY -IN RET/EXH COMBINATION FIRE/SMOKE DAMPER FM 1200 FIRE DAMPER REQUIREMENTS: 630 REQUIREMENTS (UNLESS OTHERWISE NOTED): 25 M -M METAL EGGCRATE 12/24 - CLASS II PROVIDE 12/24 ACOUSTICAL BOOT. 2 - BLADES OUT OF AIRSTREAM ON MEDIUM PRESSURE DUCTS - 1657 FUSIBLE LINK LOW - 1657 FUSIBLE LINK - FAIL -CLOSE, 120V ACTUATOR (MA230 OR MA418 STD) VPEE-PAR- 1715 - CLASS II 1250 - ACTUATOR BY MECHANICAL CONTRACTOR, 6.0 18 1035 WIRING BY ELECTRICAL CONTRACTOR. DIRECT 2 1/3 - INTERLOCK TO FIRE ALARM SYSTEM BY EF -B-5 LOW 3 ELECTRICAL CONTRACTOR 10 520 160 DRAWING SHEET INDEX SHEET NUMBER DESCRIPTION MO.01 SCHEDULES - HVAC M1.01 DETAILS - HVAC M2.11 FIRST FLOOR PLAN - HVAC M2.12 FIRST FLOOR PLAN - ZONING PLAN M2.21 SECOND FLOOR PLAN - HVAC M2.22 SECOND FLOOR PLAN - ZONING PLAN DIFFUSER/GRILLE SCHEDULE SYMBOL MANUFACTUER SIZE TYPE NOTES 14/12 SM & MODEL NUMBER SOUNDLINE SHEETMETAL (1" LINING) 14/12 SLSM FLEX CONNECTOR A-SSIZ TITUS MGD BORDER 3 AS NOTED LAY -IN DIFFUSER 120W BUILDING TOTAL 10640 10640 TRANE MODEL NO. INLET SIZE B SIZE RFM TITUS MCD BORDER 6 AS NOTED SURFACE MT DIFFUSER T CFM VOLTS PH STGS FAN HP SIZ TITUS 350RL AS NOTED SURFACE MT RET/EXH PROVIDE WITH OBD CCFM 10 1165 350 610 DD -CSM TITUS TDCA BORDER 6 AS NOTED SURFACE MT DIFFUSER PROVIDE WITH PATTERN CONTROLLER 10700 2 1/3 CENTRAL AREA AND RADIAL OPPOSED BLADE DAMPER. o-IZ TITUS PAR AS NOTED LAY -IN RET/EXH VPEE-PAR-2415 FM 1200 360 630 8.0 25 M -M METAL EGGCRATE 12/24 RETURN/EXH PROVIDE 12/24 ACOUSTICAL BOOT. 2 M -M METAL EGGCRATE 24/24 RETURN/EXH PROVIDE 24/24 ACOUSTICAL BOOT. OUTSIDE AIR PROVISION DUCT LEGEND DESCRIPTION SYMBOL DESCRIPTION SYMBOL BARE SHEETMETAL 14/12 SM FLEX DUCT 120 SOUNDLINE SHEETMETAL (1" LINING) 14/12 SLSM FLEX CONNECTOR BARE ROUND SHEETMETAL 120 1 20 WRAPPED ROUND SHEETMETAL 120W BUILDING TOTAL OUTSIDE AIR PROVISION Project: TIGARD CORPORATE CENTER Room Use Area Code Occupancy Load (sf/person) Ave. Vent. Occupancy Load (# people) Outside Air Required/Person Total Room Outside Air Required Outside Air Provided Building [Office 1 35,774 100 532 1 20 10640 10640 BUILDING TOTAL 10640 10640 NOTES: 1. PARALLEL FAN POWERED TERMINAL UNIT WITH HEAT - PRESSURE INDEPENDENT, SIZE AS LISTED W/DDC CONTROL CARD. DAMPER ACTUATOR, AND INLET VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. DISCONNECT BY ELECTRICAL CONTRACTOR. FACTORY OPTIONS INCLUDE: - FAN CONTROL THROUGH FACTORY WIRED RELAYS - 24V TRANSFORMER, 50VA MIN RATED - FILTER RACK WITH 1" 20% EFFICIENT PLEATED FILTER - FOIL FACED INTERNAL INSULATION 2. COOLING ONLY TERMINAL UNIT - PRESSURE INDEPENDENT, SIZE AS LISTED, W/DDC CONTROL CARD, DAMPER ACTUATOR, AND INLET E VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. CONTROL POWER PROVIDED BY CONTROL CONTRACTOR. a FACTORY OPTIONS INCLUDE: 00 - FOIL FACED INTERNAL INSULATION 66 3. EXISTING UNIT 6 4. DISCONNECT THE SECOND STAGE OF HEAT IN EXISTING PARALLEL FAN POWERED TERMINAL. EXISTING HEATER KW SIZE AND # OF STAGES SHOWN IN PARENTHESIS (#). 5. USE EXISTING VAV-B-226 FROM THE SECOND FLOOR. o w r NOTE TO ELECTRICAL ENGINEER: O - 46OV/3PH TERMINAL UNITS REQUIRE FOUR WIRE POWER FEED TO SUPPLY 277V/1 PH POWER TO FAN. J a UNIT NO. -PACKAGED GAS ELEC VAV BOX SCHEDULE - SUILDiNC B 2 14/ 120 UNIT NO. AREA SERVED TRANE MODEL NOM GAS HEAT TONS IN MBH CFM OUT MBH ESP FAN OA HP CFM EER/ SEER UNIT NO. TRANE MODEL NO. INLET SIZE COOL CFM MIN CFM FAN CFM HEATER KW T CFM VOLTS PH STGS FAN HP VOLTS PH SPD NOTES VAV-6-101 VPEE-PAR-1711 10 1165 350 610 5.0 16 960 460/3 460/3 10700 2 1/3 CENTRAL AREA 277/1 20 LOW 3 VAV-8-102 VPEE-PAR-2415 12 1200 360 630 8.0 25 990 200 460/3 120/1 2 1/3 137 W 277/1 Y LOW 3 VAV-B-103 VPEE-PAR- 1715 10 1250 375 660 6.0 18 1035 3.3 460/3 DIRECT 2 1/3 CONTINUOUS 277/1 EF -B-5 LOW 3 VAV-13-104 VPEE- PAR -1715 10 520 160 270 3.0 21 430 25 460/3 1 2 1/3 GREENHECK CSP -255 277/1 500 LOW 3, 4 6 VAV-B-105 VPEE- PAR -1715 10 390 120 210 3.0 28 330 KITCHEN HGOD 1&3 460/3 ROOFTOP 2 1/3 460/3 277/1 19.:; LOW 3, 4 6 VAV-6-106 VPEE-PAR-1111 8 590 180 310 3.5 22 490 .65 460/3 t 1140 1 1 1/3 1 DIRECT 277/1 1 66 LOW 3, 4 7 VAV-B-107 VPEE-PAR-2415 12 1270 380 670 8.0 23 1050 460/3 set point: 2 1/3 1. The economizer function operates normally. 277/1 LOW 3 VAV-13-108 VPEE-PAR-2415 12 1415 430 750 7.5 19 1180 460/3 (or EMS selectable area) timed overrides. When the push-button is activated, the 2 1/3 following functions occur for a timed (adjustable) period. 277/1 physical position. MED 3 VAV-B-109 VPEE-PAR-2415 12 1160 350 610 7.5 24 960 2. The economizer dampers 'control to the %OA (30% adjustable) or minimum 460/3 2 1/3 277/1 LOW 3 VAV-6-110 VPEE-PAR-2415 12 1320 390 690 9.0 26 1080 460/3 2 1/3 277/1 LOW 3 VAV-B-11 1 VPEE-PAR- 1111 8 750 230 390 5.0 25 620 460/3 2 1 3 277/1 LOW 3 VAV-B-112 VCCE-17 10 870 260 3 VAV-B-113 VCCE-17 10 835 250 3 VAV-B-114 VCCE-24 12 1400 420 3 VAV-B-115 VPEE- PAR- 1107 8 550 160 290 2.0 14 450 277/1 2 1/8 277/1 LOW 3 VAV-6-116 VPEE-PAR-0604 6 370 110 200 1.5 15 310 277/1 2 1/15 277/1 LOW 3 VAV- B-117 VCCE-17 10 970 290 3 VAV-B-118 VCCE-24 12 1280 390 3 VAV-B-119 VPEE-PAR-0604 6 300 90 160 2.0 24 250 277/1 2 1/15 277/1 LOW 3 VAV-B-120 VPEE-PAR-1107 8 700 1 _21 0 370 2.5 13 580 277/1 2 1 1/8 277/1 LOW 3 VAV-B-121 VPEE-PAR-1104 8 360 110 190 2.0 20 300 277/1 2 1/15 277/1 MED 3 VAV-8-122 VPEE-PAR- 1104 8 500 140 260 2.0 15 400 277/1 2 1, 1/15 277/1 MED 3, 5 VAV-B-123 VPEE-PAR-2415 12 1680 510 880 5.5 12 1390 460/3 2 1 3 277/1 MED 1 VAV-B-124 VPEE-PAR-2415 8 1680 510 880 6.5 14 1390 460/3 2 1/3 277/1 MED 1 VAV-B-201 VPEE-PAR-2415 12 1060 320 560 9.0 31 880 460/3 2 1/3 277/1 LOW 3 VAV-6-202 VPEE-PAR-2415 12 1220 370 640 8.0 24 1010 460/3 2 1/3 277/1 LOW 3 VAV-B-203 VPEE-PAR-1715 10 1500 450 790 6.5 16 1240 460/3 2 1/3 277/1 LOW 3 VAV-B-204 VPEE-PAR-3220 14 2560 770 1340 13.0 19 2110 460/3 3 1/2 277/1 MED 3 VAV-B-205 VPEE-PAR-1715 10 1200 360 630 6.5 20 990 460/3 2 --1/3 277 1 LOW 3 VAV-6-206 VPEE-PAR-1715 10 1125 340 590 6.0 20 930 460/3 2: 1/3 277/1 LOW 3 VAV-8-207 VPEE-PAR-1111 8 830 250 440 7.5 33 690 460/3 2 1/3 277/1 LOW 3 VAV-6-208 VPEE-PAR-2415 12 1360 410 710 9.0 25 1120 460/3 2 = 1/3 277/1 LOW 3 VAV-6-209 VPEE-PAR-2415 12 1540 460 810 8.0 19 1270 460/3 1 ' %1/3 277 1 LOW 3 VAV-B-210 VPEE-PAR-2415 12 1380 410 730 8.0 21 1140 460/3 2 1/3 277/1 LOW 3 VAV-B-211 VPEE-PAR-2415 12 1260 380 660 11.0 32 1040 460/3 2 . ' 1/3 277/1 LOW 3 VAV-B-212 VCCE-17 10 890 270 3 VAV-B-213 VCCE-03 5 160 50 3 VAV-6-214 VCCE-03 5 160 50 3 VAV-B-215 VCCE-11 8 730 220 3 VAV-6-216 VCCE-17 10 1000 300 3 VAV-B-217 VCCE-17 10 660 1 200 3 VAV-B-218 VCCE-06 NOT USED VAV-B-219 VCCE-24 12--T 1080 320 3 VAV-B-220 VPEE-PAR-0604 NOT USED VAV-8-221 VPEE-PAR-0604 NOT USED VAV-B-222 VCCE-17 10 1040 1 310 1 1 IF T3 VAV-15-223 VCCE-03 NOT USED VAV-B-224 VCCE-03 5 160 50 1 1 1 1 3 VAV-B-225 VPEE-PAR-1707 10 1060 320 560 1 2.0 1 7 1 880 1 277/1 1 2 1/8 277/1 1 HIGH 3 VAV-B-226 VPEE-PAR-1107 NOT USED VAV-8-227 VPEE-PAR-1104 8 550 170 290 2.0 13 460. 277/1 2 1/15 277/1 MED 3 VAV-8-228 VCCE-24 12 1505 450 2 VAV-B-229 VCCE-24 12 1460 440 2 NOTES: 1. PARALLEL FAN POWERED TERMINAL UNIT WITH HEAT - PRESSURE INDEPENDENT, SIZE AS LISTED W/DDC CONTROL CARD. DAMPER ACTUATOR, AND INLET VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. DISCONNECT BY ELECTRICAL CONTRACTOR. FACTORY OPTIONS INCLUDE: - FAN CONTROL THROUGH FACTORY WIRED RELAYS - 24V TRANSFORMER, 50VA MIN RATED - FILTER RACK WITH 1" 20% EFFICIENT PLEATED FILTER - FOIL FACED INTERNAL INSULATION 2. COOLING ONLY TERMINAL UNIT - PRESSURE INDEPENDENT, SIZE AS LISTED, W/DDC CONTROL CARD, DAMPER ACTUATOR, AND INLET E VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. CONTROL POWER PROVIDED BY CONTROL CONTRACTOR. a FACTORY OPTIONS INCLUDE: 00 - FOIL FACED INTERNAL INSULATION 66 3. EXISTING UNIT 6 4. DISCONNECT THE SECOND STAGE OF HEAT IN EXISTING PARALLEL FAN POWERED TERMINAL. EXISTING HEATER KW SIZE AND # OF STAGES SHOWN IN PARENTHESIS (#). 5. USE EXISTING VAV-B-226 FROM THE SECOND FLOOR. o w r NOTE TO ELECTRICAL ENGINEER: O - 46OV/3PH TERMINAL UNITS REQUIRE FOUR WIRE POWER FEED TO SUPPLY 277V/1 PH POWER TO FAN. J a NOTES: 1. PROVIDE WITH THE FOLLOWING FEATURES: - 2 -STAGE LOW GAS HEAT - 100% EXHAUST CAPABILITY - 2" SPRING ISOLATORS - SUPPLY AIR TEMPERATURE CONTROL WITH VFD AND BYPASS - HIGH EFFICIENCY THROW AWAY FILTERS - TRANE COMMUNICATION INTERFACE MODULE - HIGH EFFICIENCY MOTORS - 0-100% ECONOMIZER - ACCESS DOORS - NONFUSED DISCONNECT SWITCH - RETURN AIR TEMPERATURE SENSOR - FACTORY WIRED 15A GFCI CONVENIENCE OUTLET 2. 2 HP EXHAUST FAN MOTOR 3. PROVIDE WITH DUCT SMOKE DETECTOR. 4. EXISTING UNIT UNIT NO. -PACKAGED GAS ELEC AIR CONDITIONING UNIT SCHEDULE KITCHEN GREENHECK KSU-112 3420 0.75 460/3 2 14/ 120 UNIT NO. AREA SERVED TRANE MODEL NOM GAS HEAT TONS IN MBH CFM OUT MBH ESP FAN OA HP CFM EER/ SEER ELECTRICAL VOLT PH MCA WT LBS NOTES AC -B-1 SOUTH AREA SFHFC604 60 500 400 19290 2.5 30 3960 9.0 460/3 190 10700 4 AC -8-2 NORTH AREA SFHFC604 60 500 400 1 21605 2.5 40 4600 9.0 460/3 210 10700 4 AC -8-3 CENTRAL AREA SFHFC204 20 235 190 7120 2.5 10 2080 9.0 460/3 66 5800 123 NOTES: 1. PROVIDE WITH THE FOLLOWING FEATURES: - 2 -STAGE LOW GAS HEAT - 100% EXHAUST CAPABILITY - 2" SPRING ISOLATORS - SUPPLY AIR TEMPERATURE CONTROL WITH VFD AND BYPASS - HIGH EFFICIENCY THROW AWAY FILTERS - TRANE COMMUNICATION INTERFACE MODULE - HIGH EFFICIENCY MOTORS - 0-100% ECONOMIZER - ACCESS DOORS - NONFUSED DISCONNECT SWITCH - RETURN AIR TEMPERATURE SENSOR - FACTORY WIRED 15A GFCI CONVENIENCE OUTLET 2. 2 HP EXHAUST FAN MOTOR 3. PROVIDE WITH DUCT SMOKE DETECTOR. 4. EXISTING UNIT NOTES: 1. EXISTING UNIT 3. DISCONNECT AND MOTOR STARTER BY ELECTRICAL CONTRACTOR. 4. SET ON CURB WITH MUA-1. OAS ASCE--ESP AIR UNIT SCHEDULE UNIT NO. AREA SERVED FAN ' MBH MFG. & MODEL NO. CFM ESP VOLT PH HP INPUT OUTPUT EXHAUST FAN SCHEDULE KITCHEN GREENHECK KSU-112 3420 0.75 460/3 2 14/ 120 840 1, 2 a. The supply fan sholl operate continuously during EMS scheduled occupied periods, and UNIT NO. SERVICE 8c LOCATION MFR.. & MODEL NO. TYPE CFM ESP V/PH FAN SPEED RPM MAX NOISE SONES MOTOR HP DRIVE BDD WT CONTROL NOTES EF -1 TOILET ROOMS COOK 150C-56 ROOFTOP 1900 .6 120/1 1092 9.9 1/2 BELT Y 85 SEE NOTES 1 EF -6-2 COPY ROOM - B162 GEMINI GN -340 IN-LINE 200 .1 120/1 1625 3.3 137 W DIRECT Y 25 CONTINUOUS 1 EF -B-3 COPY ROOM - 6151 GEMINI GN -340 IN-LINE 200 .1 120/1 1625 3.3 137 W DIRECT Y 25 CONTINUOUS 1 EF -6-4 COPY ROOM - 6263 GEMINI GN -340 IN-LINE 200 .1 120/1 162'5 3.3 137 W DIRECT Y 25 CONTINUOUS 1 EF -B-5 COPY ROOM - 8252 GEMINI GN -340 IN-LINE 200 .1 120/1 1625 3.3 == 137 W DIRECT Y 25 CONTINUOUS 1 EF -6-6 IDF ROOM - B168 GREENHECK CSP -255 IN-LINE 500 .1 120/1 1080 5.0 325 W DIRECT Y 36 T -STAT 1 EF -6-7 KITCHEN HGOD 1&3 GREENHECK CUBE-180HP-15 ROOFTOP 2500 2 460/3 1530 19.:; 1 1 /02 BELT N 104 W/ HOODS 3,4 EF -6-8 KITCHEN HOOD 2 IGREENHECK CUE -140-8 I ROOFTOP 1350 .65 120/1 t 1140 1 10.5 1/4/00 1 DIRECT Y 1 66 1 W/ HOOD 3 NOTES: 1. EXISTING UNIT 3. DISCONNECT AND MOTOR STARTER BY ELECTRICAL CONTRACTOR. 4. SET ON CURB WITH MUA-1. OAS ASCE--ESP AIR UNIT SCHEDULE UNIT NO. AREA SERVED FAN ' MBH MFG. & MODEL NO. CFM ESP VOLT PH HP INPUT OUTPUT WT LBS NOTES MUA-1 KITCHEN GREENHECK KSU-112 3420 0.75 460/3 2 14/ 120 840 1, 2 NOTES: 1. ARRANGEMENT 'F' 2. DISCONNECT BY ELECTRICAL ELECTRIC WALL HEATER SCHEDULE UNIT NO. SERVICE & LOCATION MFR & MODEL NO. WATTS VOLTS/PHASE -FLA NOTES WH -1 JANITOR 202 MARKEL E4002 -TA -RP 750 120/1 6.3 1 WH -B-2 FIRE SPR 118 MARKEL E4002 -TA -RP 750 120/1 6.3 1 NOTES: 1. EXISTING UNIT SEQUENCE OF OPERATIONS PART 1 GENERAL 2.02 HVAC SYSTEMS 1.01 SECTION INCLUDES A. VAV Rooftop Air Handler A. Sequence of operation descriptions for all HVAC systems 1. Programming: a. The supply fan sholl operate continuously during EMS scheduled occupied periods, and PART 2 DESCRIPTIONS E optimal start cool -down and worm -up periods. The supply fons shall remain off during unoccupied periods. 2.01 AUTOMATION ENERGY MANAGEMENT SYSTEM 2. Temperature Control a. The equipment manufacturer provides: A. Systems Programming 1. A discharge air sensor and electronic controls to operate refrigeration capacity regulation devices to maintain the supply air temperature setpoint. 1. The systems ore programmed for unoccupied, warm-up mode, cool -dawn and occupied mode by 2. The electronic control to be capable of receiving a remote signal from EMS to the energy management system, "EMS". reset the supply air temperature set point from 50'F to 75'F 3. Internal interlock to allow remote E��!S signal to prevent refrigeration 2. The systems independently programmed ore: operation. a. HVAC systems per specific tenant occupancy. 4. Compressor status, each compressor, run/stop, dry contact for EMS. 5. Compressor alarm, foil -shutdown, single dry contact for EMS. 3. Unoccupied Schedule EMS/equipment interface requirements to be coordinated with selected a. Heating and cooling systems are signaled to maintain unoccupied program space controls contractor. temperature setpoints. b. The control contractor provides: Heoting - 65'F (adjustable) 1. Discharge air temperature set point reset signal from EMS. Discharge set point Cooling = 80'F (adjustable) shall be reset based on a poll of zone temperature controllers' calculated b. VAV box heaters and fons ore cycled as required to maintain the heoting setpoint. cooling or heating demand. Cooling and economizer outside air intake operation is prevented. VAV box and 2. Economizer electric actuators and corKrols. EMS signals economizer damper terminal unit dampers remain closed. actuators to maintain required mixed air temperature. Actuators provided by c. Cooling equipment, economizers and VAV dampers ore cycled as required to maintain controls contractor. the cooling setpoint. Heating operation is prevented. 3. EMS prevention of refrigeration operation when outdoor temperature is below d. Exhaust Eons remain off. 59F. 4. Minimum outside air override (see below) of economizer function when 4. Worm -Up Start Schedule outdoor temperature is greater thor, economizer changeover set point (78'F a. Outside air and space temperatures are monitored for a program calculation to adjustable). determine on earlier start time of heating systems to provide the space comfort set point 5. EMS automatic reset of econo ;- zer minimum outside air position, 0-100%. prior to the scheduled occupied start time. 6. EMS remote enoble/disable for efrigerotion cycle. b. Cos heat is energized. System supply fan operates continuously. AC units remain off. Enable: Permits automatic control start/stop and capacity regulation. Ensure c. The VAV unit dampers initially modulate full open and fons remain off until 80 percent compressors start in unloaded condition. of the zones achieve their setpoints. VAV zone sensors modulate dampers to maintain Disable: Lockout, prevents compressor operation. zone setpoint. d. VAV box electric heat remains off. 9. EMS monitoring of run/stop status, eoch compressor. e. Gas heat shuts down upon 80% of zone sensors achieving setpoint. 10. EMS monitoring of alarm fail, singlF alarm for all compressors. EMS/equipment interface requirements to be coordinated with equipment manufacturer. f. The programmed exhaust fons remain off. 5. Cool -Down Start Schedule 3. Minimum Outside Air Volume a. Outside air and space temperatures ore monitored for a program calculation to a. Percent outside air shall be calculated based on the following equation: determine on earlier start time of cooling systems to provide the space comfort set point %OA = ((MAT-tZ4T)/(OAT-RAT)) x 100 prior to the scheduled occupied start time. b. System supply fons operate continuously with cooling and economizer domper controls where %OA percent outside air = enabled to maintain occupied cycle setpoints. c. The VAV units ore signaled to maintain occupied set points with local heating enabled. MAT = mixed air temperature d. The programmed exhaust fons remain off. OAT outside air temperatureRAT = return air temperature 6. Occupied Schedule a. Heating and cooling systems ore signaled to maintain occupied program space b. Outside air cfm shall be calculated based on the following equation: temperature setpoints. b. System supply fans operate continuously. Economizer and cooling cycles ore operated OACFM = (%OA/100) x SCFM to maintain occupied comfort setpoints. c. Rooftop unit exhaust fons ore activated to maintain building static pressure setpoints. where %OA = percent outside air d. Exhaust systems operate continuously. OACFM = outside air CFM SCFM = supply CFM S. Clock Overrides SCFM sholl be the instantaneous sum of ail VAV terminal unit primary CFMs 1. The programming systems shall be provided with override capability via manual push buttons of zone room temperature sensors. downstream of the unit. c. If the outside air temperature is equal to or less than the economizer changeover set point: a. When the override is activated, occupied set points ore provided for the activated zone 1. The economizer function operates normally. for a timed (adjustable) period. The main air handler will be activated, and the terminal 2. The economizer dampers ore not ohowed to close to below the %OA (30% unit will provide heating or cooling to maintain set point for the timed period. EMS adjustable) or minimum OACFM (adjustable) setpoints. shall be capable of logging duration of timed override. d. If the outside air temperature is O'F to SF (adjustable) greater than the economizer changeover set point: b. The EMS sholl hove the capability of programming zone manual push buttons for floor 1. The economizer function is disabled. (or EMS selectable area) timed overrides. When the push-button is activated, the 2. The outside air and return oir dampers ore automatically set to the 50% following functions occur for a timed (adjustable) period. physical position. 1. VAV terminal zones for the activated floor operate at occupied setpoints. e. If the outside air temperature is more than 5'F- (adjustable) greater than the economizer 2. Corresponding AC unit operates as in occupied cycle (cooling and heating ore changeover set point: enabled). 1. The economizer function is disabled. 3. VAV terminal zones on non -override floors remain in unoccupied cycle with 2. The economizer dampers 'control to the %OA (30% adjustable) or minimum dampers remaining in the closed position. OACFM (adjustable) set point that provides the greatest outside air damper 4. EMS sholl be capable of logging duration of timed override. position. 4. Supply Air Static Pressure Control 2. The system shall also have the capability of scheduling zone or floor overrides through the a. The equipment manufacturer provides: operator workstation. 1. Fan motor starter and pilot relay suitable for fon start/stop signals, for remote operation by EMS. 2. Airflow modulation control sholl be capable of 3 -point floating control for fan from remote EMS. Controller shoal modulate from 0-100% in 60 seconds. 3. Feedback of flow-moduloting device (position or speed) for monitoring by remote EMS. EMS/equipment interface requirements to be coordinated with selected controls contractor. b. The control contractor provides: 1. Supply duct static probe mounted 2/3 down the main supply duct. The supply duct pressure sensor is referenced to the occupied space pressure. 2. EMS control of, supply fon and fon capacity regulation device to maintain the design pressure setpoint. Fan must start in the unloaded condition. 3. EMS monitoring of static pressure. 4. EMS remote start/stop for supply fon. 5. EMS modulation of copocity reguloti-:�n device for supply fon. 6. EMS monitoring of fon run/stop status through use of current sensitive relay on motor load wire. Current sensitive relay provided by controls contractor. 7. EMS monitoring of 0-100% position or speed of the VAV modulating device. EMS/equipment interface requirements to be coordinated with equipment manufacturer. 2.03 VAV TERMINAL UNITS A. VAV Fon Terminal Unit ..; th Electric Heat 1. General a. Room temperature sensors with a lo^otion shown sholl be installed with approved _plenum rated cable connections. Temperature controls shall be completely operational. b. Units shown installed without o room temperature sensor location sholl hove a temperature sensor temporarily attached to the terminal unit with a 20' spool of control wire. Temperature controls sholl be completely operational. 2. Control Criteria a. Pressure independent controls. A volume sensor measures primary airflow quantity. b. The room temperature control modulates the variable volume damper between minimum and maximum volume positions as required to maintain the cooling setpoint. c. The room temperature 'control sequence operates the unit fan and heating stages as required to maintain the heoting setpoint. Volume damper is set to minimum position through heating` stoges during normal occupancy. d. The room temperature control sholl provide separate occupied and unoccupied setpoints. e. Room.. temperature sensors specified shall have an integral override push-button to signal EMS override functions listed in paragraph 2.01.6 of this specification section. f. EMS provides: 1. Space temperature indication. 2. Air volume indication. 3. Air volume set point indication: minimum and maximum. 4. Temperature set point indication: Heating occupied and unoccupied. 5. Temperature set point indication: Cooling occupied and unoccupied. 6. Mode indication: Occupied/Unoccupied/Override 7. Adjust set points, all, command. 8. Adjust mode, oil, command. 9. Adjust override timing command. 10. Heating enoble/disoble command. 2.05 OUTDOOR ATMOSPHERIC STATIC PRESSURE REFERENCE A. System Description 1. This system shall consist of a 1" minimum copper riser open at street level and available to all space static. supply air duct, and return air shaft reference sensors, suitable for providing a stable and constant outside air reference. Riser shall be fitted with valved stub outs at each floor level. B. Reference Location 1. The outdoor reference location point shall be concealed outside the west first floor lobby. END OF SECTION i Miller MacDonald ofOregon 6711 S.W. ..• Portland, �Ea P RoF 5 o O C�RIEGON k1,25119 g� (.•x•01 /2\ 24/7 ROOMS ADDED. 12/27/99 REVISIONS: DATE CENTERTIGARD CORPORAT-t ,. RENAISSANCE TI 12259 SW 69TH AVE TIGARD, OREGON Hvac NOTES 8 LEGENDS BUILT UP ROOF ROOF SUSPEND EXHAUST FAN FROM STRUCTURE. INSULATED FLEX --: HUNG AS STRAIGHT AS POSSIBLE 6'-0" MAX. ROUND TO RECTANGULAR TRANSITION �- DIFFUSER IN T -BAR CEILING CONNECTION PER MANUFACTURER REQUIREMENTS HN'- L I E EXHAUST SAN ll"NIMFALLATION DETAIL AC UNIT --� NEOPRENE WEATHER SEAL BY RAIL MFR. INSULATION STRIP BY G.C. ROOFING BY G.C.--,,,, CANT STRIP BY G.C.-----, /— fSLEEPER CAP WELD CURB TO STEEL------- BY MECH. CONTR. PLATES BY MECH CONTR. J < Y2" x 4" LONG STEEL PLATE EMBEDDED IN---" CONCRETE ON 8'-0" CENTERS BY G.C. 4x4 CANT STRIP (TYP) 4 tv SEE STRUCTURAL DRAWINGS FOR `' EXACT CONSTRUCTION OF X48 CONCRETE CURB. ROOFING 4" CONC SLAB a •« Ad RVV� LJL�.n REBAR PER STRUCTURAL REQUIREMENTS IR DUCT ENCLOSURE UR IN TYPES I AND II zESISTIVE BUILDINGS) NERAL CONTRACTOR AI R FLOW ING AND EXTENDED BY GENERAL ACTOR NOTES: 1. EXHAUST FAN MUST BE A UL LISTED FOR USE WITH RESTAURANT EXHAUST APPLIANCES. 2. ALL DUCT JOINTS SHALL HAVE A LIQUID TIGHT, CONTINUOUS EXTERNAL WELD. /0-�8 TYPE I HOOD EXHAUST FAN IL �-o W SLE CRIP & E _----------_ -- DIFFUSER NECK SIZE PERFORATED METAL Y2 DUCT SIZE + 3" 1" NO SCALE AC UNIT MFR.'S CURB AND SPRING RAILS INSTALLED BY M -M. 2 LAYERS OF 2" DUCT LINER, STICK PIN & GLUE, BY MECH CONTRACTOR, FOR SOUND ATTENUATION NOTES: 1. CURB BY GENERAL CONTRACTOR 2. TOP OF CURB TO BE LEVEL AROUND PERIMETER OF UNIT. 3. TO MINIMIZE NOISE AND VIBRATION THE ROOF FRAMING SHALL BE DESIGNED FOR A MAX. STRUCTURAL DEFLECTION OF Y8" DUE TO AC UNIT WEIGHT. SEE EQUIP SCHEDULE. S H 3 z OW v10 - Z O W —J m� C)o (w �O Q W U z NO SCALE GG V/� J Il111�ILL JJ STEEL FLASHING I \ \ \ INSULATED FLEX `-` ` TAKE OFF WITH y < HUNG AS STRAIGHT �,w� VOLUME DAMPER AS POSSIBLE 12'- 0" MAX-_..--' DIFFUSER CAN / T -BAR CEILING \ / h \ / DIFFUSER \ / y / \ CONNECTION PER MANUFACTURER REQUIREMENTS NO SCALE \ \ \ INSULATED FLEX r� .�1 � ` y <\ I HUNG AS STRAIGHT AS POSSIBLE�� ` \ / TAKE OFF WITH 12'-0" MAX VOLUME DAMPER ` J \- DIFFUSER IN GYP BD CEILING CONNECTION PER MANUFACTURER REOUiREMENTS DIES" U SEER I NSTALLATION DrEm"NIFOA I L Ys" NON - ABSORB GASKET ACCESS PANEL Y4" WING -NT AROUND PERIME 1 1 Ll:1rVL NOTE: GENERAL CONTRACTOR TO INSTALL GWB 2HR RATED OR EQUAL ACCESS PANEL CENTERED OVER DUCT CLEAN-OUT TYPICAL OF ALL SHOWN. o CLEAN—OUT DETAIL NO SCALE a (su C (St DUCT COMBINATION FE/OEDAMPE LISTED AND LABELLED RATED BY: [KIST TION INSTRUCTIONS DAMPERS SHALL BE SECURED TO COLLAR WITH NO: 10 SHEET METAL SCREWS fi ON CENTER, 1/4' DIA. NUTS AND BOLTS, WELDING, OR 3/16" STEEL POP RIVETS. SEE NOTES 2 AND 3 FOR JOINT DETAIL. ANGLES SHALL BE A MINIMUM OR 1 1/2" X 1 1/2" X 16 GAUGE. FASTEN TO COLLAR WITH 1/4- DIAMETER NUTS AND BOLTS, WELDING 6" ON CENTER, NO. 10 SHEET METAL SCREWS 6" ON CENTER, OR 3/16r STEEL POP RIVETS. (SEE NOTE 4 FOR CLEARANCE AND OVERLAP.) NoTmo 1. COLLARS SHALL BE OF THE SAME GAUGE OR HEAVIER AS THE DUCT TO WHICH IT IS ATTACHED. GAUGES SHALL CONFORM TO SMACNA OR ASHRAE DUCT STANDARDS. COLLARS SHALL EXTEND APPROXIMATELY 5' ON EITHER SIDE OF WALL OR FLOOR TO FACILITATE THE JOINING OF THE COLLAR TO THE DUCT. IN CASES WHERE THE WIDTH OF THE RETAINING ANGLE IS SUCH THAT IT WOULD INHIBIT JOINING THE COLLAR TO THE DUCT. THE COLLAR MAY EXTEND APPROXIMATELY 2" BEYOND THE EDGE OF THE ANGLES. SEE NOTE 3. 2. THE FOLLOWING DUCT—COLLAR CONNECTIONS MAY BE USED ON ALL SYSTEMS: — INSIDE SUP — ANGLE SUP — PLAIN SLIP — DOUBLE 'S' SLIP — HEMMED 'S' SLIP — CUP SLIP — BAR SLIP — DRIVE SLIP — ALTERNATE BAR SLIP — POCKET LOCK (STANDING SLIP) — REINFORCED BAR SLIP (CLEAT) 3. WHEN THE DUCT WORK TERMINATES AT THE DAMPER. RETAINING ANGLES ON THE OPPOSITE SIDE OF THE OPENING MAY BE REVERSED PROVIDED THE SIZE OF THE OPENING IS INCREASED BY AN AMOUNT EQUAL TO TWICE THE COMBINED THICKNESS OF THE ANGLE AND THE HEIGHT OF THE SCREW OR BOLTHEAD TO MAINTAIN EXPANSION CLEARANCE. (SEE NOTE 4.) IN THIS CASE THE COLLAR AT THE OPEN END MAY BE MADE FLUSH WITH THE EDGE OF THE RETAINING ANGLE. 4. CLEARANCE BETWEEN THE COLLAR AND WALL/FLOOR OPENING SHALL BE 1/8" PER FOOT ON HEIGHT AND WIDTH OF COLLAR TO A MAXIMUM OF 1/2" (E.G. DAMPER 47 3/4" X 47 3/4 COLLAR 48" X 48", OPENING 48 1/2- X 48 1/2-). PERIMETER ANGLES SHALL OVERLAP THE WALL/FLOOR BY A MINIMUM OF 1". 5. MAXIMUM SINGLE DAMPER OF A MULTIPLE ASSEMBLY SHALL BE 36"X48". MAXIMUM MULTIPLE ASSEMBLY SHALL BE 72"X48". 6. IN CASES WHERE THE OPENINGS ARE LARGER THAN SPECIFIED IN NOTE -5, A 12" WIDE BRICK OR REINFORCED CONCRETE MULLION MUST BE PROVIDED BETWEEN ADJACENT ASSEMBLIES. 7. AS WITH ALL JOINTS, CONTRACTOR MUST SEAL DUCT—COLLAR CONNECTIONS, IN FfELD, AFTER INSTALLATION. TYPEE C VERTCAL MOUNTING NOTE: CAUTION — HEAVY SPRING USED TO LOAD SPRINT LINK ACTUATOR. USE CARE IN RESETTING LINK. 6 FIRE/SMOKE Ml -01 NO SCALE 18" MIN CLEARANCE FROM COMBUSTIBLES IMPORTANT. — DO NOT CAST DAMPER IN PLACE. DO NOT FASTEN RETAINING ANGLES OR DAMPER DIRECTLY TO WALL OR FLOOR. — CYCLE DAMPER AFTER INSTALLATION TO INSURE FREE MOVEMENT. — DO NOT INSTALL DAMPER OUT OF SQUARE OR OUT OF FLAT. — INSTALL DAMPER IN PLANE OF FIRE SEPARATION. SUITABLE ACCESS SERVICE OPENINGS MUST BE PROVIDED TO MAKE FIRE DAMPERS ACCESSIBLE FOR INSPECTION AND SERVICING. DAMPER INSTALLATION 3" MIN -� FLASHING / `♦ CANOPY TYPE RANGE HOOD BY KITCHEN CONTRACTOR It RANGE NOTES: 1. HOODS FURNISHED BY OTHERS 2. FIRE SPRINKLER AND SUPPRESION SYSTEMS PROVIDED BY OTHERS. 1 -HR SHAFT DUCT ENCLOSURE (2 -HR IN TYPES I AND II FR BUILDINGS) 16 GA WELDED DUCT UP NON-COMBUSTIBLE CEILING CONSTRUCTION FLASHING WELDED DUCT CONNECTION NON-COMBUSTIBLE WALL CONSTRUCTION 22 GA STAINLESS STEEL FLASHING (TYP) 3" MIN RANGE HOCA INSTALLATION E REVISIONS DATE T6GARD CORPORATE CENTER BLDG -B RENAISSANCE TI NO SCALE 12259 SW 69TH AVE TIGARD, OREGON HVAC DETAILS 1 ST FLOOR PLAN — HVAC Crnla VP — 1'—n M 0 W a�a SHEET NOTES: Ot VENT HOOD #1. PROVIDED BY KALBERER. SEE KALBERER SUBMITTAL DRAWINGS FOR CONNECTION SIZES AND LOCATIONS. OZ GREASE HOOD #2. PROVIDED BY KALBERER. SEE KALBERER SUBMITTAL DRAWINGS FOR CONNECTION SIZES AND LOCATIONS. O GREASE HOOD #3. PROVIDED BY KALBERER. SEE KALBERER SUBMITTAL DRAWINGS FOR CONNECTION SIZES AND LOCATIONS. AW MacDonald Miller of Oregon 5711 S.W. Hood St, Portland, OR 97201 Rumm- (503) 230-8981 Fcz: (503) 230-9238 0INFF cz 15 3 2 OREGON r- ✓ G�Y251990 ?2 24/7 ROOMS ADDED. 12/27/99 �1 CORE EXHAUST REV'S. 12/1/99 REVISIONS: DATE TIGARD CORPORATE CENTER BLDG -B RENAISSANCE TI 12259 SW 69TH AVE TIGARD, OREGON IST FLOOR HVAC PLAN ENGINEER: LhS1 REMEP. N. SCOTT 04—T8-00 CHECKED W.- DATE PLOTF]EX J. KIRK 04-18-00 CM- ISSUE DATE: J. SANFORD 04-18-00 FW FILE NI '. im NUMBER 263 279-1016 ISSUED FOR PERMIT SHEET NUMBER: M2.11 f 0 W rz O J d G ��r,r,•s O /A CORE EXHAUST REV'S. 12/1/99 REVISIONS: DATE TIGARD CORPORATE CENTER BLDG -R RENAISSANCE TI 2nd FLOOR PLAN — VAC 12259 SSV 69TH AVE N Scale: Y8 = 1'-0 i'IGAR®, OREGON 2nd FLOOR HVAC FLAN ENGINEER: LAST REVISED: N. SCOTT 04-18-00 CHECKED BY: DATE PLOTTED: J. KIRK 04-18-00 CAD: ISSUE DATE: J. MILLER 04-18-00 FLAT FILE INDEX: JOB NUMBER: 263 289-2000-54 rn ISSUED FOOR N N Puft E FEZ M IT m w Q SHEET NUMBER: z W LL ® U (3; ROOF PLAN —HVAC Scole: Y8" =V=0 E 66 N 66 4. MacDonald Miller of Oregon 5711 S.W. Hood St. r.Portland, OR 97201 phom: (5503) =—N!9 1 Fcx: (W3) 2W -92W P Ro LLJ OREGON & 25, COL. 0 REVISION DATE TIGARD CORPORATE CENTER BLDG -B RENAISSANCE TI 12269 SW 69th AVE TIGARD, OREGON ROOF HVAC PLAN f } AC -B-3 { 18/18 ELEVATOR SHAFT RELIEF ROOF VENT. (EXISTING) LIZ 0/—(E) 50 FLUE. I —IJ (E)AC-B-2 %-12/12 mmBusli AIR INLET ROOF (EXISTING) IVENT. EF -B- EF -6-8 t 1141414 MUA-B- 1. 4 ROOF PLAN —HVAC Scole: Y8" =V=0 E 66 N 66 4. MacDonald Miller of Oregon 5711 S.W. Hood St. r.Portland, OR 97201 phom: (5503) =—N!9 1 Fcx: (W3) 2W -92W P Ro LLJ OREGON & 25, COL. 0 REVISION DATE TIGARD CORPORATE CENTER BLDG -B RENAISSANCE TI 12269 SW 69th AVE TIGARD, OREGON ROOF HVAC PLAN