WAC GENERAL NOTES
1. THE HVAC SYSTEM FOR THIS PROJECT IS BASED ON THE FOLLOWING CRITERIA:
ROOF "U" VALUE (BTUH/S.F: F) = 0.05
WALL "U" VALUE (BTUH/S.F:F) = 0.10
FLOOR "U" VALUE (BTUH/S.F: F) = N/A -
GLASS "U" VALUE (BTUH/S.F: F) = 0.57
GLASS SHADE COEFF. = 0.56
LIGHTING (WATTS/S.F.) = 1.2
MISC. EQUIP. (WATTS/S.F.) = 1..8
PEOPLE DENSITY (S.F./PERSON) = 142
COOLING INDOOR DESIGN TEMP ('F) = 75
COOLING OUTDOOR DESIGN TEMP ('F) = 95
HEATING INDOOR DESIGN TEMP ('F) = 70
HEATING OUTDOOR DESIGN TEMP ('F) = 18
2. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. THE HVAC CONTRACTOR IS
TO COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK.
3. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 1997 EDITIONS OF THE UNIFORM MECHANICAL
CODE, UNIFORM BUILDING CODE, UNIFORM FIRE CODE AND LOCAL CODES AND ORDINANCES WITH 1998 OREGON AMENDMENTS.
4. DUCT CONSTRUCTION AND HANGING SHALL COMPLY WITH CHAPTER 6 OF THE 1996 GMSC AND WITH CURRENT SMACNA STANDARDS.
EARTHQUAKE BRACE ALL DUCTS 28" DIA AND LARGER WHICH ARE SUSPENDED MORE THAN 12" BELOW STRUCTURAL SYSTEM.
5. JOINTS OF MEDIUM AND HIGH VELOCITY DUCT SYSTEMS SHALL BE SEALED WITH GASKETS OR LISTED MASTIC TYPE DUCT SEALANT.
6. DUCTS SHALL BE INSULATED AS INDICATED ON PLANS.
- SOUND LINING, WHERE INDICATED, SHALL BE 1" 1.5 LB/CU FT FIBERGLASS DUCT LINING COATED TO PREVENT FIBER EROSION AT
VELOCITIES UP TO 4000 FPM.
7. FLEXIBLE DUCTS SHALL CONSIST OF A REINFORCED VAPOR BARRIER, 1 1/2" FIBERGLASS INSULATION, AND NON -PERFORATED
INTERIOR LINER WITH WIRE HELIX. DUCT SHALL BE A UL 181 LISTED CLASS 1 AIR DUCT. FLEXIBLE DUCTS SHALL ONLY BE USED
WHERE SHOWN AND SHALL NOT EXCEED 12' IN LENGTH UNLESS NOTED OTHERWISE.
8. PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH SECTION 1630 OF THE 1998 OSSC.
9. PROVIDE FIRE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 713.11 OF THE 1998 OSSC. PROVIDE CEILING
FIRE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 710.2 OF THE 1998 OSSC. INSTALL FIRE DAMPERS AND
CEILING FIRE DAMPERS IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS, THE TERMS OF THEIR LISTING, AND THE REQ'MENTS
OF THE CODE.
10. PROVIDE SUPPLY DUCT SMOKE DETECTOR AUTOMATIC SHUT DOWN OF ALL HEATING, COOLING, OR VENTILATION EQUIPMENT DELIVERING
IN EXCESS OF 2000 CFM IN ACCORDANCE WITH SECTION 608 OF THE 1996 GMSC. POWER WIRING AND INTERLOCK WIRING WITH THE
BUILDING FIRE ALARM SYSTEM IS BY THE ELECTRICAL CONTRACTOR.
11. HVAC EQUIPMENT, VALVES AND DAMPERS SHALL BE LOCATED IN EASILY ACCESSIBLE LOCATIONS. UNLESS SHOWN ON ARCHITECTURAL
DRAWINGS, REQUIRED ACCESS PANELS SHALL BE PROVIDED BY THE HVAC CONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR.
12. ALL MOTOR STARTERS NOT LISTED AS BEING PROVIDED IN THE HVAC EQUIPMENT SCHEDULES ARE TO BE
PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
13. ALL DUCT DIMENSIONS SHOWN ON PLANS ARE INSIDE CLEAR DIMENSIONS.
DRAWING SHEET INDEX
SHEET NUMBER DESCRIPTION
MO.01 SCHEDULES - HVAC
M1.01 DETAILS - HVAC
M2.11 FIRST FLOOR PLAN - HVAC
M2.12 FIRST FLOOR PLAN - ZONING PLAN
M2.21 SECOND FLOOR PLAN - HVAC
M2.22 SECOND FLOOR PLAN - ZONING PLAN
DIFFUSER/GRILLE SCHEDULE
SYMBOL
WAC AR TIONS
LEGEND
TYPE
ABBV
FULL NAME
ABBV
FULL NAME
ABBY
FULL NAME
AC
AIR CONDITIONING UNIT
ESP
EXTERNAL STATIC PRESSURE
NOM
NOMINAL
AFF
ABOVE FINISHED FLOOR
EXH
EXHAUST
OA
OUTSIDE AIR
BDD
BACKDRAFT DAMPER
EXTR
EXTRACTOR
OBD
OPPOSED BLADE DAMPER
BOD
BOTTOM OF DUCT
FDf
FIRE DAMPER
OD
OUTSIDE DIMENSION
BOTT
BOTTOM
FLA
FULL LOAD AMPS
RA
RETURN AIR
BTU
BRITISH THERMAL UNITS
FOB
FLAT ON BOTTOM
REG
REGISTER (GRILLE WITH DAMPER)
BTUH
BRITISH THERMAL UNITS PER HOUR
FOT
FLAT ON TOP
REQ'D
REQUIRED
CAP
CAPACITY
GALV
GALVANIZED
RIO
ROUGH IN ONLY
CFM
CUBIC FEET PER MINUTE
GC
GENERAL CONTRACTOR
SA
SUPPLY AIR
CONN
CONNECT
GR
GRILLE
SL
SOUND LINING
DIFF
DIFFUSER
GWB
GYPSUM WALL BOARD
SM
SHEET METAL
DMPR
DAMPER
HP
HORSE POWER
SP
STATIC PRESSURE
DN
DOWN
ID
INSIDE DIMENSION
STL
STEEL
EC
EGGCRATE
M -M
MACDONALD-MILLER
SUSP
SUSPENDED
EER
ENERGY EFFICIENCY RATIO
MBH
ONE THOUSAND BTUH
TOD
TOP OF DUCT
ELEV
ELEVATION
MCA
MINIMUM CIRCUIT AMPACITY
TV
TURN VANES
277/1
500
MIN
MINIMUM
TYP
TYPICAL
10
390
MT
MOUNT
UNO
UNLESS NOTED OTHERWISE
330
KITCHEN HGOD 1&3
MUA
MAKE-UP AIR
VD
VOLUME DAMPER
460/3
277/1
19.:;
LOW
00
VOLTAGE PHASE & DUCT DIAM �R
VPEE-PAR-1111
8
590
180
310
3.5
DRAWING SHEET INDEX
SHEET NUMBER DESCRIPTION
MO.01 SCHEDULES - HVAC
M1.01 DETAILS - HVAC
M2.11 FIRST FLOOR PLAN - HVAC
M2.12 FIRST FLOOR PLAN - ZONING PLAN
M2.21 SECOND FLOOR PLAN - HVAC
M2.22 SECOND FLOOR PLAN - ZONING PLAN
DIFFUSER/GRILLE SCHEDULE
SYMBOL
DAMPER
LEGEND
TYPE
SYMBOL
DESCRIPTION
& MODEL NUMBER
SYMBOL
DESCRIPTION
FLEX CONNECTOR
1 Y2 HOUR VERTICAL COMBINATION FIRE/SMOKE
DAMPER
FD t Y2
1 Y2 HOUR CURTAIN STYLE VERTICAL FIRE DAMPER
< �
FSD1&Y2
CESCO FSD(x) OR EQUAL
10640
10640
CESCO 75A -V OR EQUAL
t2AJ
DUCT ACCESS - BY MECHANICAL CONTRACTOR
TITUS MCD BORDER 6
BDD
BACKDRAFT DAMPER
CESCO BDA OR EQUAL
T
CFM
VOLTS
PH
STGS
FAN
HP
ACCESS DOOR - 18" x 18" MINIMUM THROUGH
BUILDING
AS NOTED
SURFACE MT RET/EXH
AD
CONSTRUCTION - BY GENERAL CONTRACTOR
10
1165
350
VDI
VOLUME DAMPER
TITUS TDCA BORDER 6
AS NOTED
SURFACE MT DIFFUSER
PROVIDE WITH PATTERN CONTROLLER
SHOP FABRICATED, CESCO CDS-OB OR EQUAL
2
1/3
CENTRAL AREA
AND RADIAL OPPOSED BLADE DAMPER.
o-IZ
GENERAL NOTES:
AS NOTED
LAY -IN RET/EXH
COMBINATION FIRE/SMOKE DAMPER
FM
1200
FIRE DAMPER REQUIREMENTS:
630
REQUIREMENTS (UNLESS OTHERWISE NOTED):
25
M -M METAL EGGCRATE
12/24
- CLASS II
PROVIDE 12/24 ACOUSTICAL BOOT.
2
- BLADES
OUT OF AIRSTREAM ON MEDIUM PRESSURE DUCTS
- 1657 FUSIBLE
LINK
LOW
- 1657 FUSIBLE LINK
- FAIL -CLOSE, 120V ACTUATOR (MA230 OR MA418 STD)
VPEE-PAR- 1715
- CLASS II
1250
- ACTUATOR
BY MECHANICAL CONTRACTOR,
6.0
18
1035
WIRING BY
ELECTRICAL CONTRACTOR.
DIRECT
2
1/3
- INTERLOCK
TO FIRE ALARM SYSTEM BY
EF -B-5
LOW
3
ELECTRICAL
CONTRACTOR
10
520
160
DRAWING SHEET INDEX
SHEET NUMBER DESCRIPTION
MO.01 SCHEDULES - HVAC
M1.01 DETAILS - HVAC
M2.11 FIRST FLOOR PLAN - HVAC
M2.12 FIRST FLOOR PLAN - ZONING PLAN
M2.21 SECOND FLOOR PLAN - HVAC
M2.22 SECOND FLOOR PLAN - ZONING PLAN
DIFFUSER/GRILLE SCHEDULE
SYMBOL
MANUFACTUER
SIZE
TYPE
NOTES
14/12 SM
& MODEL NUMBER
SOUNDLINE SHEETMETAL (1" LINING)
14/12 SLSM
FLEX CONNECTOR
A-SSIZ
TITUS MGD BORDER 3
AS NOTED
LAY -IN DIFFUSER
120W
BUILDING TOTAL
10640
10640
TRANE
MODEL NO.
INLET
SIZE
B SIZE RFM
TITUS MCD BORDER 6
AS NOTED
SURFACE MT DIFFUSER
T
CFM
VOLTS
PH
STGS
FAN
HP
SIZ
TITUS 350RL
AS NOTED
SURFACE MT RET/EXH
PROVIDE WITH OBD
CCFM
10
1165
350
610
DD -CSM
TITUS TDCA BORDER 6
AS NOTED
SURFACE MT DIFFUSER
PROVIDE WITH PATTERN CONTROLLER
10700
2
1/3
CENTRAL AREA
AND RADIAL OPPOSED BLADE DAMPER.
o-IZ
TITUS PAR
AS NOTED
LAY -IN RET/EXH
VPEE-PAR-2415
FM
1200
360
630
8.0
25
M -M METAL EGGCRATE
12/24
RETURN/EXH
PROVIDE 12/24 ACOUSTICAL BOOT.
2
M -M METAL EGGCRATE
24/24
RETURN/EXH
PROVIDE 24/24 ACOUSTICAL BOOT.
OUTSIDE AIR PROVISION
DUCT LEGEND
DESCRIPTION
SYMBOL
DESCRIPTION SYMBOL
BARE SHEETMETAL
14/12 SM
FLEX DUCT 120
SOUNDLINE SHEETMETAL (1" LINING)
14/12 SLSM
FLEX CONNECTOR
BARE ROUND SHEETMETAL
120
1 20
WRAPPED ROUND SHEETMETAL
120W
BUILDING TOTAL
OUTSIDE AIR PROVISION
Project: TIGARD CORPORATE CENTER
Room
Use
Area Code Occupancy
Load
(sf/person)
Ave. Vent.
Occupancy Load
(# people)
Outside Air
Required/Person
Total Room
Outside Air
Required
Outside Air
Provided
Building
[Office
1 35,774 100
532
1 20
10640
10640
BUILDING TOTAL
10640
10640
NOTES:
1. PARALLEL FAN POWERED TERMINAL UNIT WITH HEAT - PRESSURE INDEPENDENT, SIZE AS LISTED W/DDC CONTROL CARD. DAMPER
ACTUATOR, AND INLET VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. DISCONNECT BY ELECTRICAL CONTRACTOR.
FACTORY OPTIONS INCLUDE:
- FAN CONTROL THROUGH FACTORY WIRED RELAYS
- 24V TRANSFORMER, 50VA MIN RATED
- FILTER RACK WITH 1" 20% EFFICIENT PLEATED FILTER
- FOIL FACED INTERNAL INSULATION
2. COOLING ONLY TERMINAL UNIT - PRESSURE INDEPENDENT, SIZE AS LISTED, W/DDC CONTROL CARD, DAMPER ACTUATOR, AND INLET
E VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. CONTROL POWER PROVIDED BY CONTROL CONTRACTOR.
a FACTORY OPTIONS INCLUDE:
00
- FOIL FACED INTERNAL INSULATION
66 3. EXISTING UNIT
6 4. DISCONNECT THE SECOND STAGE OF HEAT IN EXISTING PARALLEL FAN POWERED TERMINAL. EXISTING HEATER KW SIZE AND # OF STAGES SHOWN IN PARENTHESIS (#).
5. USE EXISTING VAV-B-226 FROM THE SECOND FLOOR.
o
w
r NOTE TO ELECTRICAL ENGINEER:
O - 46OV/3PH TERMINAL UNITS REQUIRE FOUR WIRE POWER FEED TO SUPPLY 277V/1 PH POWER TO FAN.
J
a
UNIT
NO.
-PACKAGED
GAS
ELEC
VAV BOX
SCHEDULE
-
SUILDiNC B
2 14/ 120
UNIT
NO.
AREA
SERVED
TRANE
MODEL
NOM GAS HEAT
TONS IN MBH
CFM
OUT MBH
ESP
FAN OA
HP CFM
EER/
SEER
UNIT
NO.
TRANE
MODEL NO.
INLET
SIZE
COOL
CFM
MIN
CFM
FAN
CFM
HEATER
KW
T
CFM
VOLTS
PH
STGS
FAN
HP
VOLTS
PH
SPD
NOTES
VAV-6-101
VPEE-PAR-1711
10
1165
350
610
5.0
16
960
460/3
460/3
10700
2
1/3
CENTRAL AREA
277/1
20
LOW
3
VAV-8-102
VPEE-PAR-2415
12
1200
360
630
8.0
25
990
200
460/3
120/1
2
1/3
137 W
277/1
Y
LOW
3
VAV-B-103
VPEE-PAR- 1715
10
1250
375
660
6.0
18
1035
3.3
460/3
DIRECT
2
1/3
CONTINUOUS
277/1
EF -B-5
LOW
3
VAV-13-104
VPEE- PAR -1715
10
520
160
270
3.0
21
430
25
460/3
1
2
1/3
GREENHECK CSP -255
277/1
500
LOW
3, 4 6
VAV-B-105
VPEE- PAR -1715
10
390
120
210
3.0
28
330
KITCHEN HGOD 1&3
460/3
ROOFTOP
2
1/3
460/3
277/1
19.:;
LOW
3, 4 6
VAV-6-106
VPEE-PAR-1111
8
590
180
310
3.5
22
490
.65
460/3
t 1140 1
1
1/3
1 DIRECT
277/1
1 66
LOW
3, 4 7
VAV-B-107
VPEE-PAR-2415
12
1270
380
670
8.0
23
1050
460/3
set point:
2
1/3
1. The economizer function operates normally.
277/1
LOW
3
VAV-13-108
VPEE-PAR-2415
12
1415
430
750
7.5
19
1180
460/3
(or EMS selectable area) timed overrides. When the push-button is activated, the
2
1/3
following functions occur for a timed (adjustable) period.
277/1
physical position.
MED
3
VAV-B-109
VPEE-PAR-2415
12
1160
350
610
7.5
24
960
2. The economizer dampers 'control to the %OA (30% adjustable) or minimum
460/3
2
1/3
277/1
LOW
3
VAV-6-110
VPEE-PAR-2415
12
1320
390
690
9.0
26
1080
460/3
2
1/3
277/1
LOW
3
VAV-B-11 1
VPEE-PAR- 1111
8
750
230
390
5.0
25
620
460/3
2
1
3
277/1
LOW
3
VAV-B-112
VCCE-17
10
870
260
3
VAV-B-113
VCCE-17
10
835
250
3
VAV-B-114
VCCE-24
12
1400
420
3
VAV-B-115
VPEE- PAR- 1107
8
550
160
290
2.0
14
450
277/1
2
1/8
277/1
LOW
3
VAV-6-116
VPEE-PAR-0604
6
370
110
200
1.5
15
310
277/1
2
1/15
277/1
LOW
3
VAV- B-117
VCCE-17
10
970
290
3
VAV-B-118
VCCE-24
12
1280
390
3
VAV-B-119
VPEE-PAR-0604
6
300
90
160
2.0
24
250
277/1
2
1/15
277/1
LOW
3
VAV-B-120
VPEE-PAR-1107
8
700 1
_21 0
370
2.5
13
580
277/1
2
1 1/8
277/1
LOW
3
VAV-B-121
VPEE-PAR-1104
8
360
110
190
2.0
20
300
277/1
2
1/15
277/1
MED
3
VAV-8-122
VPEE-PAR- 1104
8
500
140
260
2.0
15
400
277/1
2
1, 1/15
277/1
MED
3, 5
VAV-B-123
VPEE-PAR-2415
12
1680
510
880
5.5
12
1390
460/3
2
1
3
277/1
MED
1
VAV-B-124
VPEE-PAR-2415
8
1680
510
880
6.5
14
1390
460/3
2
1/3
277/1
MED
1
VAV-B-201
VPEE-PAR-2415
12
1060
320
560
9.0
31
880
460/3
2
1/3
277/1
LOW
3
VAV-6-202
VPEE-PAR-2415
12
1220
370
640
8.0
24
1010
460/3
2
1/3
277/1
LOW
3
VAV-B-203
VPEE-PAR-1715
10
1500
450
790
6.5
16
1240
460/3
2
1/3
277/1
LOW
3
VAV-B-204
VPEE-PAR-3220
14
2560
770
1340
13.0
19
2110
460/3
3
1/2
277/1
MED
3
VAV-B-205
VPEE-PAR-1715
10
1200
360
630
6.5
20
990
460/3
2
--1/3
277
1
LOW
3
VAV-6-206
VPEE-PAR-1715
10
1125
340
590
6.0
20
930
460/3
2:
1/3
277/1
LOW
3
VAV-8-207
VPEE-PAR-1111
8
830
250
440
7.5
33
690
460/3
2
1/3
277/1
LOW
3
VAV-6-208
VPEE-PAR-2415
12
1360
410
710
9.0
25
1120
460/3
2
= 1/3
277/1
LOW
3
VAV-6-209
VPEE-PAR-2415
12
1540
460
810
8.0
19
1270
460/3
1 '
%1/3
277
1
LOW
3
VAV-B-210
VPEE-PAR-2415
12
1380
410
730
8.0
21
1140
460/3
2
1/3
277/1
LOW
3
VAV-B-211
VPEE-PAR-2415
12
1260
380
660
11.0
32
1040
460/3
2 .
' 1/3
277/1
LOW
3
VAV-B-212
VCCE-17
10
890
270
3
VAV-B-213
VCCE-03
5
160
50
3
VAV-6-214
VCCE-03
5
160
50
3
VAV-B-215
VCCE-11
8
730
220
3
VAV-6-216
VCCE-17
10
1000
300
3
VAV-B-217
VCCE-17
10
660 1
200
3
VAV-B-218
VCCE-06
NOT
USED
VAV-B-219
VCCE-24
12--T
1080
320
3
VAV-B-220
VPEE-PAR-0604
NOT
USED
VAV-8-221
VPEE-PAR-0604
NOT
USED
VAV-B-222
VCCE-17
10
1040 1
310
1
1
IF
T3
VAV-15-223
VCCE-03
NOT
USED
VAV-B-224
VCCE-03
5
160
50
1
1
1
1 3
VAV-B-225
VPEE-PAR-1707
10
1060
320
560
1 2.0 1
7
1 880
1
277/1
1
2
1/8
277/1
1 HIGH
3
VAV-B-226
VPEE-PAR-1107
NOT
USED
VAV-8-227
VPEE-PAR-1104
8
550
170
290
2.0
13
460.
277/1
2
1/15
277/1
MED
3
VAV-8-228
VCCE-24
12
1505
450
2
VAV-B-229
VCCE-24
12
1460
440
2
NOTES:
1. PARALLEL FAN POWERED TERMINAL UNIT WITH HEAT - PRESSURE INDEPENDENT, SIZE AS LISTED W/DDC CONTROL CARD. DAMPER
ACTUATOR, AND INLET VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. DISCONNECT BY ELECTRICAL CONTRACTOR.
FACTORY OPTIONS INCLUDE:
- FAN CONTROL THROUGH FACTORY WIRED RELAYS
- 24V TRANSFORMER, 50VA MIN RATED
- FILTER RACK WITH 1" 20% EFFICIENT PLEATED FILTER
- FOIL FACED INTERNAL INSULATION
2. COOLING ONLY TERMINAL UNIT - PRESSURE INDEPENDENT, SIZE AS LISTED, W/DDC CONTROL CARD, DAMPER ACTUATOR, AND INLET
E VELOCITY PROBE PROVIDED BY CONTROL CONTRACTOR. CONTROL POWER PROVIDED BY CONTROL CONTRACTOR.
a FACTORY OPTIONS INCLUDE:
00
- FOIL FACED INTERNAL INSULATION
66 3. EXISTING UNIT
6 4. DISCONNECT THE SECOND STAGE OF HEAT IN EXISTING PARALLEL FAN POWERED TERMINAL. EXISTING HEATER KW SIZE AND # OF STAGES SHOWN IN PARENTHESIS (#).
5. USE EXISTING VAV-B-226 FROM THE SECOND FLOOR.
o
w
r NOTE TO ELECTRICAL ENGINEER:
O - 46OV/3PH TERMINAL UNITS REQUIRE FOUR WIRE POWER FEED TO SUPPLY 277V/1 PH POWER TO FAN.
J
a
NOTES:
1. PROVIDE WITH THE FOLLOWING FEATURES:
- 2 -STAGE LOW GAS HEAT
- 100% EXHAUST CAPABILITY
- 2" SPRING ISOLATORS
- SUPPLY AIR TEMPERATURE CONTROL WITH VFD AND BYPASS
- HIGH EFFICIENCY THROW AWAY FILTERS
- TRANE COMMUNICATION INTERFACE MODULE
- HIGH EFFICIENCY MOTORS
- 0-100% ECONOMIZER
- ACCESS DOORS
- NONFUSED DISCONNECT SWITCH
- RETURN AIR TEMPERATURE SENSOR
- FACTORY WIRED 15A GFCI CONVENIENCE OUTLET
2. 2 HP EXHAUST FAN MOTOR
3. PROVIDE WITH DUCT SMOKE DETECTOR.
4. EXISTING UNIT
UNIT
NO.
-PACKAGED
GAS
ELEC
AIR CONDITIONING
UNIT SCHEDULE
KITCHEN
GREENHECK KSU-112 3420 0.75 460/3
2 14/ 120
UNIT
NO.
AREA
SERVED
TRANE
MODEL
NOM GAS HEAT
TONS IN MBH
CFM
OUT MBH
ESP
FAN OA
HP CFM
EER/
SEER
ELECTRICAL
VOLT PH
MCA
WT
LBS
NOTES
AC -B-1
SOUTH AREA
SFHFC604
60
500
400 19290
2.5
30 3960
9.0
460/3
190
10700
4
AC -8-2
NORTH AREA
SFHFC604
60
500
400 1 21605
2.5
40 4600
9.0
460/3
210
10700
4
AC -8-3
CENTRAL AREA
SFHFC204
20
235
190 7120
2.5
10 2080
9.0
460/3
66
5800
123
NOTES:
1. PROVIDE WITH THE FOLLOWING FEATURES:
- 2 -STAGE LOW GAS HEAT
- 100% EXHAUST CAPABILITY
- 2" SPRING ISOLATORS
- SUPPLY AIR TEMPERATURE CONTROL WITH VFD AND BYPASS
- HIGH EFFICIENCY THROW AWAY FILTERS
- TRANE COMMUNICATION INTERFACE MODULE
- HIGH EFFICIENCY MOTORS
- 0-100% ECONOMIZER
- ACCESS DOORS
- NONFUSED DISCONNECT SWITCH
- RETURN AIR TEMPERATURE SENSOR
- FACTORY WIRED 15A GFCI CONVENIENCE OUTLET
2. 2 HP EXHAUST FAN MOTOR
3. PROVIDE WITH DUCT SMOKE DETECTOR.
4. EXISTING UNIT
NOTES:
1. EXISTING UNIT
3. DISCONNECT AND MOTOR STARTER BY ELECTRICAL CONTRACTOR.
4. SET ON CURB WITH MUA-1.
OAS ASCE--ESP AIR UNIT SCHEDULE
UNIT
NO.
AREA SERVED
FAN ' MBH
MFG. & MODEL NO. CFM ESP VOLT PH HP INPUT OUTPUT
EXHAUST
FAN
SCHEDULE
KITCHEN
GREENHECK KSU-112 3420 0.75 460/3
2 14/ 120
840
1, 2
a. The supply fan sholl operate continuously during EMS scheduled occupied periods, and
UNIT NO.
SERVICE 8c LOCATION
MFR.. & MODEL NO.
TYPE
CFM
ESP
V/PH
FAN SPEED
RPM
MAX NOISE
SONES
MOTOR
HP
DRIVE
BDD
WT
CONTROL
NOTES
EF -1
TOILET ROOMS
COOK 150C-56
ROOFTOP
1900
.6
120/1
1092
9.9
1/2
BELT
Y
85
SEE NOTES
1
EF -6-2
COPY ROOM - B162
GEMINI GN -340
IN-LINE
200
.1
120/1
1625
3.3
137 W
DIRECT
Y
25
CONTINUOUS
1
EF -B-3
COPY ROOM - 6151
GEMINI GN -340
IN-LINE
200
.1
120/1
1625
3.3
137 W
DIRECT
Y
25
CONTINUOUS
1
EF -6-4
COPY ROOM - 6263
GEMINI GN -340
IN-LINE
200
.1
120/1
162'5
3.3
137 W
DIRECT
Y
25
CONTINUOUS
1
EF -B-5
COPY ROOM - 8252
GEMINI GN -340
IN-LINE
200
.1
120/1
1625
3.3 ==
137 W
DIRECT
Y
25
CONTINUOUS
1
EF -6-6
IDF ROOM - B168
GREENHECK CSP -255
IN-LINE
500
.1
120/1
1080
5.0
325 W
DIRECT
Y
36
T -STAT
1
EF -6-7
KITCHEN HGOD 1&3
GREENHECK CUBE-180HP-15
ROOFTOP
2500
2
460/3
1530
19.:;
1 1 /02
BELT
N
104
W/ HOODS
3,4
EF -6-8
KITCHEN HOOD 2
IGREENHECK CUE -140-8 I
ROOFTOP
1350
.65
120/1
t 1140 1
10.5
1/4/00
1 DIRECT
Y
1 66
1 W/ HOOD
3
NOTES:
1. EXISTING UNIT
3. DISCONNECT AND MOTOR STARTER BY ELECTRICAL CONTRACTOR.
4. SET ON CURB WITH MUA-1.
OAS ASCE--ESP AIR UNIT SCHEDULE
UNIT
NO.
AREA SERVED
FAN ' MBH
MFG. & MODEL NO. CFM ESP VOLT PH HP INPUT OUTPUT
WT
LBS
NOTES
MUA-1
KITCHEN
GREENHECK KSU-112 3420 0.75 460/3
2 14/ 120
840
1, 2
NOTES:
1. ARRANGEMENT 'F'
2. DISCONNECT BY ELECTRICAL
ELECTRIC WALL HEATER SCHEDULE
UNIT NO. SERVICE & LOCATION MFR & MODEL NO. WATTS VOLTS/PHASE -FLA NOTES
WH -1 JANITOR 202 MARKEL E4002 -TA -RP 750 120/1 6.3 1
WH -B-2 FIRE SPR 118 MARKEL E4002 -TA -RP 750 120/1 6.3 1
NOTES:
1. EXISTING UNIT
SEQUENCE
OF OPERATIONS
PART 1 GENERAL
2.02 HVAC SYSTEMS
1.01 SECTION INCLUDES
A. VAV Rooftop Air Handler
A. Sequence of operation descriptions for all HVAC systems
1. Programming:
a. The supply fan sholl operate continuously during EMS scheduled occupied periods, and
PART 2 DESCRIPTIONS E
optimal start cool -down and worm -up periods. The supply fons shall remain off during
unoccupied periods.
2.01 AUTOMATION ENERGY MANAGEMENT SYSTEM
2. Temperature Control
a. The equipment manufacturer provides:
A. Systems Programming
1. A discharge air sensor and electronic controls to operate refrigeration capacity
regulation devices to maintain the supply air temperature setpoint.
1. The systems ore programmed for unoccupied, warm-up mode, cool -dawn and occupied mode by
2. The electronic control to be capable of receiving a remote signal from EMS to
the energy management system, "EMS".
reset the supply air temperature set point from 50'F to 75'F
3. Internal interlock to allow remote E��!S signal to prevent refrigeration
2. The systems independently programmed ore:
operation.
a. HVAC systems per specific tenant occupancy.
4. Compressor status, each compressor, run/stop, dry contact for EMS.
5. Compressor alarm, foil -shutdown, single dry contact for EMS.
3. Unoccupied Schedule
EMS/equipment interface requirements to be coordinated with selected
a. Heating and cooling systems are signaled to maintain unoccupied program space
controls contractor.
temperature setpoints.
b. The control contractor provides:
Heoting - 65'F (adjustable)
1. Discharge air temperature set point reset signal from EMS. Discharge set point
Cooling = 80'F (adjustable)
shall be reset based on a poll of zone temperature controllers' calculated
b. VAV box heaters and fons ore cycled as required to maintain the heoting setpoint.
cooling or heating demand.
Cooling and economizer outside air intake operation is prevented. VAV box and
2. Economizer electric actuators and corKrols. EMS signals economizer damper
terminal unit dampers remain closed.
actuators to maintain required mixed air temperature. Actuators provided by
c. Cooling equipment, economizers and VAV dampers ore cycled as required to maintain
controls contractor.
the cooling setpoint. Heating operation is prevented.
3. EMS prevention of refrigeration operation when outdoor temperature is below
d. Exhaust Eons remain off.
59F.
4. Minimum outside air override (see below) of economizer function when
4. Worm -Up Start Schedule
outdoor temperature is greater thor, economizer changeover set point (78'F
a. Outside air and space temperatures are monitored for a program calculation to
adjustable).
determine on earlier start time of heating systems to provide the space comfort set point
5. EMS automatic reset of econo ;- zer minimum outside air position, 0-100%.
prior to the scheduled occupied start time.
6. EMS remote enoble/disable for efrigerotion cycle.
b. Cos heat is energized. System supply fan operates continuously. AC units remain off.
Enable: Permits automatic control start/stop and capacity regulation. Ensure
c. The VAV unit dampers initially modulate full open and fons remain off until 80 percent
compressors start in unloaded condition.
of the zones achieve their setpoints. VAV zone sensors modulate dampers to maintain
Disable: Lockout, prevents compressor operation.
zone setpoint.
d. VAV box electric heat remains off.
9. EMS monitoring of run/stop status, eoch compressor.
e. Gas heat shuts down upon 80% of zone sensors achieving setpoint.
10. EMS monitoring of alarm fail, singlF alarm for all compressors.
EMS/equipment interface requirements to be coordinated with equipment manufacturer.
f. The programmed exhaust fons remain off.
5. Cool -Down Start Schedule
3. Minimum Outside Air Volume
a. Outside air and space temperatures ore monitored for a program calculation to
a. Percent outside air shall be calculated based on the following equation:
determine on earlier start time of cooling systems to provide the space comfort set point
%OA = ((MAT-tZ4T)/(OAT-RAT)) x 100
prior to the scheduled occupied start time.
b. System supply fons operate continuously with cooling and economizer domper controls
where %OA percent outside air
=
enabled to maintain occupied cycle setpoints.
c. The VAV units ore signaled to maintain occupied set points with local heating enabled.
MAT = mixed air temperature
d. The programmed exhaust fons remain off.
OAT outside air temperatureRAT
= return air temperature
6. Occupied Schedule
a. Heating and cooling systems ore signaled to maintain occupied program space
b. Outside air cfm shall be calculated based on the following equation:
temperature setpoints.
b. System supply fans operate continuously. Economizer and cooling cycles ore operated
OACFM = (%OA/100) x SCFM
to maintain occupied comfort setpoints.
c. Rooftop unit exhaust fons ore activated to maintain building static pressure setpoints.
where %OA = percent outside air
d. Exhaust systems operate continuously.
OACFM = outside air CFM
SCFM = supply CFM
S. Clock Overrides
SCFM sholl be the instantaneous sum of ail VAV terminal unit primary CFMs
1. The programming systems shall be provided with override capability via manual push buttons of
zone room temperature sensors.
downstream of the unit.
c. If the outside air temperature is equal to or less than the economizer changeover
set point:
a. When the override is activated, occupied set points ore provided for the activated zone
1. The economizer function operates normally.
for a timed (adjustable) period. The main air handler will be activated, and the terminal
2. The economizer dampers ore not ohowed to close to below the %OA (30%
unit will provide heating or cooling to maintain set point for the timed period. EMS
adjustable) or minimum OACFM (adjustable) setpoints.
shall be capable of logging duration of timed override.
d. If the outside air temperature is O'F to SF (adjustable) greater than the economizer
changeover set point:
b. The EMS sholl hove the capability of programming zone manual push buttons for floor
1. The economizer function is disabled.
(or EMS selectable area) timed overrides. When the push-button is activated, the
2. The outside air and return oir dampers ore automatically set to the 50%
following functions occur for a timed (adjustable) period.
physical position.
1. VAV terminal zones for the activated floor operate at occupied setpoints.
e. If the outside air temperature is more than 5'F- (adjustable) greater than the economizer
2. Corresponding AC unit operates as in occupied cycle (cooling and heating ore
changeover set point:
enabled).
1. The economizer function is disabled.
3. VAV terminal zones on non -override floors remain in unoccupied cycle with
2. The economizer dampers 'control to the %OA (30% adjustable) or minimum
dampers remaining in the closed position.
OACFM (adjustable) set point that provides the greatest outside air damper
4. EMS sholl be capable of logging duration of timed override.
position.
4. Supply Air Static Pressure Control
2. The system shall also have the capability of scheduling zone or floor overrides through the
a. The equipment manufacturer provides:
operator workstation.
1. Fan motor starter and pilot relay suitable for fon start/stop signals, for remote
operation by EMS.
2. Airflow modulation control sholl be capable of 3 -point floating control for fan
from remote EMS. Controller shoal modulate from 0-100% in 60 seconds.
3. Feedback of flow-moduloting device (position or speed) for monitoring by
remote EMS.
EMS/equipment interface requirements to be coordinated with selected controls
contractor.
b. The control contractor provides:
1. Supply duct static probe mounted 2/3 down the main supply duct. The supply
duct pressure sensor is referenced to the occupied space pressure.
2. EMS control of, supply fon and fon capacity regulation device to maintain the
design pressure setpoint. Fan must start in the unloaded condition.
3. EMS monitoring of static pressure.
4. EMS remote start/stop for supply fon.
5. EMS modulation of copocity reguloti-:�n device for supply fon.
6. EMS monitoring of fon run/stop status through use of current sensitive relay
on motor load wire. Current sensitive relay provided by controls contractor.
7. EMS monitoring of 0-100% position or speed of the VAV modulating device.
EMS/equipment interface requirements to be coordinated with equipment manufacturer.
2.03 VAV TERMINAL UNITS
A. VAV Fon Terminal Unit ..; th Electric Heat
1. General
a. Room temperature sensors with a lo^otion shown sholl be installed with approved
_plenum rated cable connections. Temperature controls shall be completely operational.
b. Units shown installed without o room temperature sensor location sholl hove a
temperature sensor temporarily attached to the terminal unit with a 20' spool of control
wire. Temperature controls sholl be completely operational.
2. Control Criteria
a. Pressure independent controls. A volume sensor measures primary airflow quantity.
b. The room temperature control modulates the variable volume damper between
minimum and maximum volume positions as required to maintain the cooling setpoint.
c. The room temperature 'control sequence operates the unit fan and heating stages as
required to maintain the heoting setpoint. Volume damper is set to minimum position
through heating` stoges during normal occupancy.
d. The room temperature control sholl provide separate occupied and unoccupied
setpoints.
e. Room.. temperature sensors specified shall have an integral override push-button to signal
EMS override functions listed in paragraph 2.01.6 of this specification section.
f. EMS provides:
1. Space temperature indication.
2. Air volume indication.
3. Air volume set point indication: minimum and maximum.
4. Temperature set point indication: Heating occupied and unoccupied.
5. Temperature set point indication: Cooling occupied and unoccupied.
6. Mode indication: Occupied/Unoccupied/Override
7. Adjust set points, all, command.
8. Adjust mode, oil, command.
9. Adjust override timing command.
10. Heating enoble/disoble command.
2.05 OUTDOOR ATMOSPHERIC STATIC PRESSURE REFERENCE
A. System Description
1. This system shall consist of a 1" minimum copper riser open at street level and available to all
space static. supply air duct, and return air shaft reference sensors, suitable for providing a
stable and constant outside air reference. Riser shall be fitted with valved stub outs at each floor
level.
B. Reference Location
1. The outdoor reference location point shall be concealed outside the west first floor lobby.
END OF SECTION
i
Miller MacDonald
ofOregon
6711 S.W. ..•
Portland,
�Ea P RoF
5 o O
C�RIEGON
k1,25119
g�
(.•x•01
/2\ 24/7 ROOMS ADDED. 12/27/99
REVISIONS: DATE
CENTERTIGARD CORPORAT-t
,.
RENAISSANCE TI
12259 SW 69TH AVE
TIGARD, OREGON
Hvac NOTES
8 LEGENDS
BUILT UP ROOF
ROOF
SUSPEND EXHAUST
FAN FROM STRUCTURE.
INSULATED FLEX --:
HUNG AS STRAIGHT
AS POSSIBLE
6'-0" MAX.
ROUND TO
RECTANGULAR
TRANSITION
�- DIFFUSER IN T -BAR CEILING
CONNECTION PER
MANUFACTURER REQUIREMENTS
HN'- L I E EXHAUST SAN ll"NIMFALLATION DETAIL
AC UNIT --�
NEOPRENE WEATHER SEAL BY RAIL MFR.
INSULATION STRIP BY G.C.
ROOFING BY G.C.--,,,,
CANT STRIP BY G.C.-----,
/— fSLEEPER CAP WELD CURB TO STEEL-------
BY MECH. CONTR. PLATES BY MECH CONTR.
J <
Y2" x 4" LONG STEEL PLATE EMBEDDED IN---"
CONCRETE ON 8'-0" CENTERS BY G.C.
4x4 CANT STRIP (TYP)
4
tv SEE STRUCTURAL DRAWINGS FOR
`' EXACT CONSTRUCTION OF
X48 CONCRETE CURB. ROOFING
4" CONC SLAB
a •«
Ad
RVV� LJL�.n
REBAR PER STRUCTURAL REQUIREMENTS
IR DUCT ENCLOSURE
UR IN TYPES I AND II
zESISTIVE BUILDINGS)
NERAL CONTRACTOR
AI R FLOW
ING AND EXTENDED
BY GENERAL
ACTOR
NOTES: 1. EXHAUST FAN MUST BE A UL LISTED FOR USE
WITH RESTAURANT EXHAUST APPLIANCES.
2. ALL DUCT JOINTS SHALL HAVE A LIQUID TIGHT,
CONTINUOUS EXTERNAL WELD.
/0-�8 TYPE I HOOD EXHAUST FAN IL
�-o
W SLE
CRIP
& E
_----------_ --
DIFFUSER
NECK SIZE
PERFORATED METAL
Y2 DUCT SIZE + 3"
1"
NO SCALE
AC UNIT MFR.'S CURB
AND SPRING RAILS
INSTALLED BY M -M.
2 LAYERS OF 2"
DUCT LINER, STICK
PIN & GLUE, BY MECH
CONTRACTOR, FOR
SOUND ATTENUATION
NOTES:
1. CURB BY GENERAL CONTRACTOR
2. TOP OF CURB TO BE LEVEL
AROUND PERIMETER OF UNIT.
3. TO MINIMIZE NOISE AND VIBRATION
THE ROOF FRAMING SHALL BE
DESIGNED FOR A MAX. STRUCTURAL
DEFLECTION OF Y8" DUE TO
AC UNIT WEIGHT. SEE EQUIP
SCHEDULE.
S
H
3
z
OW
v10 -
Z O
W —J
m�
C)o
(w �O
Q
W
U
z
NO SCALE
GG V/� J Il111�ILL JJ
STEEL FLASHING
I \ \
\
INSULATED FLEX `-` ` TAKE OFF WITH
y <
HUNG AS STRAIGHT �,w� VOLUME DAMPER
AS POSSIBLE
12'- 0" MAX-_..--'
DIFFUSER CAN
/
T -BAR CEILING
\ /
h \ / DIFFUSER
\ /
y
/ \ CONNECTION PER
MANUFACTURER REQUIREMENTS
NO SCALE
\ \
\
INSULATED FLEX r� .�1 � ` y <\ I
HUNG AS STRAIGHT
AS POSSIBLE�� ` \ / TAKE OFF WITH
12'-0" MAX VOLUME DAMPER
` J
\- DIFFUSER IN GYP BD CEILING
CONNECTION PER
MANUFACTURER REOUiREMENTS
DIES" U SEER I NSTALLATION DrEm"NIFOA I L
Ys" NON -
ABSORB GASKET
ACCESS PANEL
Y4" WING -NT
AROUND PERIME
1 1 Ll:1rVL
NOTE: GENERAL CONTRACTOR TO INSTALL GWB 2HR RATED
OR EQUAL ACCESS PANEL CENTERED OVER
DUCT CLEAN-OUT TYPICAL OF ALL SHOWN.
o CLEAN—OUT DETAIL
NO SCALE
a
(su
C
(St
DUCT
COMBINATION FE/OEDAMPE
LISTED AND LABELLED RATED
BY:
[KIST TION INSTRUCTIONS
DAMPERS SHALL BE SECURED TO COLLAR WITH NO: 10 SHEET METAL
SCREWS fi ON CENTER, 1/4' DIA. NUTS AND BOLTS, WELDING, OR 3/16"
STEEL POP RIVETS.
SEE NOTES 2 AND 3 FOR JOINT DETAIL.
ANGLES SHALL BE A MINIMUM OR 1 1/2" X 1 1/2" X 16 GAUGE. FASTEN TO
COLLAR WITH 1/4- DIAMETER NUTS AND BOLTS, WELDING 6" ON CENTER,
NO. 10 SHEET METAL SCREWS 6" ON CENTER, OR 3/16r STEEL POP RIVETS.
(SEE NOTE 4 FOR CLEARANCE AND OVERLAP.)
NoTmo
1. COLLARS SHALL BE OF THE SAME GAUGE OR HEAVIER AS THE DUCT TO
WHICH IT IS ATTACHED. GAUGES SHALL CONFORM TO SMACNA OR ASHRAE
DUCT STANDARDS. COLLARS SHALL EXTEND APPROXIMATELY 5' ON
EITHER SIDE OF WALL OR FLOOR TO FACILITATE THE JOINING OF THE
COLLAR TO THE DUCT. IN CASES WHERE THE WIDTH OF THE RETAINING
ANGLE IS SUCH THAT IT WOULD INHIBIT JOINING THE COLLAR TO THE
DUCT. THE COLLAR MAY EXTEND APPROXIMATELY 2" BEYOND THE EDGE OF
THE ANGLES. SEE NOTE 3.
2. THE FOLLOWING DUCT—COLLAR CONNECTIONS MAY BE
USED ON ALL SYSTEMS:
— INSIDE SUP — ANGLE SUP
— PLAIN SLIP — DOUBLE 'S' SLIP
— HEMMED 'S' SLIP — CUP SLIP
— BAR SLIP — DRIVE SLIP
— ALTERNATE BAR SLIP — POCKET LOCK
(STANDING SLIP)
— REINFORCED BAR SLIP (CLEAT)
3. WHEN THE DUCT WORK TERMINATES AT THE DAMPER. RETAINING ANGLES
ON THE OPPOSITE SIDE OF THE OPENING MAY BE REVERSED PROVIDED
THE SIZE OF THE OPENING IS INCREASED BY AN AMOUNT EQUAL TO
TWICE THE COMBINED THICKNESS OF THE ANGLE AND THE HEIGHT OF
THE SCREW OR BOLTHEAD TO MAINTAIN EXPANSION CLEARANCE. (SEE
NOTE 4.) IN THIS CASE THE COLLAR AT THE OPEN END MAY BE MADE
FLUSH WITH THE EDGE OF THE RETAINING ANGLE.
4. CLEARANCE BETWEEN THE COLLAR AND WALL/FLOOR OPENING SHALL BE
1/8" PER FOOT ON HEIGHT AND WIDTH OF COLLAR TO A MAXIMUM OF
1/2" (E.G. DAMPER 47 3/4" X 47 3/4 COLLAR 48" X 48", OPENING
48 1/2- X 48 1/2-). PERIMETER ANGLES SHALL OVERLAP THE
WALL/FLOOR BY A MINIMUM OF 1".
5. MAXIMUM SINGLE DAMPER OF A MULTIPLE ASSEMBLY SHALL BE 36"X48".
MAXIMUM MULTIPLE ASSEMBLY SHALL BE 72"X48".
6. IN CASES WHERE THE OPENINGS ARE LARGER THAN SPECIFIED IN NOTE
-5, A 12" WIDE BRICK OR REINFORCED CONCRETE MULLION MUST BE
PROVIDED BETWEEN ADJACENT ASSEMBLIES.
7. AS WITH ALL JOINTS, CONTRACTOR MUST SEAL DUCT—COLLAR
CONNECTIONS, IN FfELD, AFTER INSTALLATION.
TYPEE C VERTCAL MOUNTING
NOTE:
CAUTION — HEAVY SPRING USED
TO LOAD SPRINT LINK ACTUATOR.
USE CARE IN RESETTING LINK.
6 FIRE/SMOKE
Ml -01 NO SCALE
18" MIN CLEARANCE
FROM COMBUSTIBLES
IMPORTANT.
— DO NOT CAST DAMPER IN PLACE.
DO NOT FASTEN RETAINING ANGLES OR DAMPER DIRECTLY TO WALL OR
FLOOR.
— CYCLE DAMPER AFTER INSTALLATION TO INSURE FREE MOVEMENT.
— DO NOT INSTALL DAMPER OUT OF SQUARE OR OUT OF FLAT.
— INSTALL DAMPER IN PLANE OF FIRE SEPARATION.
SUITABLE ACCESS SERVICE OPENINGS MUST BE PROVIDED TO MAKE FIRE
DAMPERS ACCESSIBLE FOR INSPECTION AND SERVICING.
DAMPER INSTALLATION
3" MIN
-�
FLASHING / `♦
CANOPY TYPE RANGE HOOD
BY KITCHEN CONTRACTOR
It
RANGE
NOTES:
1. HOODS FURNISHED BY OTHERS
2. FIRE SPRINKLER AND SUPPRESION SYSTEMS
PROVIDED BY OTHERS.
1 -HR SHAFT DUCT ENCLOSURE
(2 -HR IN TYPES I AND II FR BUILDINGS)
16 GA WELDED DUCT UP
NON-COMBUSTIBLE CEILING CONSTRUCTION
FLASHING
WELDED DUCT CONNECTION
NON-COMBUSTIBLE
WALL CONSTRUCTION
22 GA STAINLESS STEEL FLASHING (TYP)
3" MIN
RANGE HOCA INSTALLATION
E
REVISIONS DATE
T6GARD CORPORATE
CENTER BLDG -B
RENAISSANCE TI
NO SCALE
12259 SW 69TH AVE
TIGARD, OREGON
HVAC DETAILS
1 ST FLOOR PLAN — HVAC
Crnla VP — 1'—n
M
0
W
a�a
SHEET NOTES:
Ot VENT HOOD #1. PROVIDED BY KALBERER. SEE KALBERER
SUBMITTAL DRAWINGS FOR CONNECTION SIZES AND LOCATIONS.
OZ GREASE HOOD #2. PROVIDED BY KALBERER. SEE KALBERER
SUBMITTAL DRAWINGS FOR CONNECTION SIZES AND LOCATIONS.
O GREASE HOOD #3. PROVIDED BY KALBERER. SEE KALBERER
SUBMITTAL DRAWINGS FOR CONNECTION SIZES AND LOCATIONS.
AW
MacDonald Miller
of Oregon
5711 S.W. Hood St,
Portland, OR 97201
Rumm- (503) 230-8981
Fcz: (503) 230-9238
0INFF
cz 15 3 2
OREGON r-
✓ G�Y251990
?2 24/7 ROOMS ADDED. 12/27/99
�1 CORE EXHAUST REV'S. 12/1/99
REVISIONS: DATE
TIGARD CORPORATE
CENTER BLDG -B
RENAISSANCE TI
12259 SW 69TH AVE
TIGARD, OREGON
IST FLOOR
HVAC PLAN
ENGINEER: LhS1 REMEP.
N. SCOTT 04—T8-00
CHECKED W.- DATE PLOTF]EX
J. KIRK 04-18-00
CM- ISSUE DATE:
J. SANFORD 04-18-00
FW FILE NI '. im NUMBER
263 279-1016
ISSUED FOR
PERMIT
SHEET NUMBER:
M2.11
f
0
W
rz
O
J
d
G ��r,r,•s O
/A CORE EXHAUST REV'S. 12/1/99
REVISIONS: DATE
TIGARD CORPORATE
CENTER BLDG -R
RENAISSANCE TI
2nd FLOOR PLAN — VAC 12259 SSV 69TH AVE
N Scale: Y8 = 1'-0
i'IGAR®, OREGON
2nd FLOOR
HVAC FLAN
ENGINEER: LAST REVISED:
N. SCOTT 04-18-00
CHECKED BY: DATE PLOTTED:
J. KIRK 04-18-00
CAD: ISSUE DATE:
J. MILLER 04-18-00
FLAT FILE INDEX: JOB NUMBER:
263 289-2000-54
rn
ISSUED FOOR
N
N
Puft E FEZ M IT m
w
Q
SHEET NUMBER: z
W
LL
® U
(3;
ROOF PLAN —HVAC
Scole: Y8" =V=0
E
66
N
66
4.
MacDonald Miller
of Oregon
5711 S.W. Hood St.
r.Portland, OR 97201
phom: (5503) =—N!9 1
Fcx: (W3) 2W -92W
P Ro
LLJ
OREGON
&
25,
COL.
0
REVISION DATE
TIGARD CORPORATE
CENTER BLDG -B
RENAISSANCE TI
12269 SW 69th AVE
TIGARD, OREGON
ROOF HVAC PLAN
f
}
AC -B-3
{
18/18 ELEVATOR
SHAFT RELIEF
ROOF VENT.
(EXISTING)
LIZ
0/—(E) 50 FLUE.
I
—IJ
(E)AC-B-2
%-12/12 mmBusli
AIR INLET ROOF
(EXISTING)
IVENT.
EF -B-
EF -6-8
t
1141414
MUA-B- 1.
4
ROOF PLAN —HVAC
Scole: Y8" =V=0
E
66
N
66
4.
MacDonald Miller
of Oregon
5711 S.W. Hood St.
r.Portland, OR 97201
phom: (5503) =—N!9 1
Fcx: (W3) 2W -92W
P Ro
LLJ
OREGON
&
25,
COL.
0
REVISION DATE
TIGARD CORPORATE
CENTER BLDG -B
RENAISSANCE TI
12269 SW 69th AVE
TIGARD, OREGON
ROOF HVAC PLAN