Loading...
PlansEQUIPMENT SCHEDULE RTU #1 RRKA024JK08E HEATING = 80 MBTUH INPUT COOLING = 23 MBTUH TOTAL CFM - 800 @.30 WEIGHT = 390 lbs. 208/230 VOLT, 1 ph. MIN. DISCONNECT = 30 MIN. AMP. = 25 • RTU #2.3,4 RKKA048CK10E HEATING = 100 MBTUH INPUT COOLING = 48 MBTUH TOTAL CFM = 1600 @.35 sp WEIGHT = 573 lbs. 208/230 volt, 3 ph. MIN. DISCONNECT = 30 MIN. AMP. 22 FRESH AIR REQUIREMENTS EF -1.23 EXHAUST FAN GROAN, MOD. 671 70 CFM VENTED TO ROOF EF. -,5- 6) C, F, /I RTU #1- 455' - 100'= 5 OCCUPANCY X 20 CFM = 100 CFM OF OSA RTU 92- 1374'- 100'= 14 OCCUPANCY X 20 CFM = 280 CFM OF OSA RTU #3- 1499'- 100'= 15 OCCUPANCY X 20 CFM = 300 CFAI OF OSA RTU 94- 1342'- 100'= 14 OCCUPANCY X 20 CFM = 280 CF1%1 OF OSA ROOFTOP UNIT We" DUCT FLANGE M GASKET 11 1 COUNTER FLASHING' DUCT' NAILER STRIP INSULATION" CANT STRIP* -ROOF ROOFCURB FELT' INSULATION ` ROOF DECK• #loR $c,rsw 11,pe e Jibe a ON «d ROOF STRUCTURAL MEMBER* GENERAL NOTE'S A)ALL UNITS TO HAVE FULLY MODULATING ECONOMIZERS, CAPABLE OF 100% CLOSURE DURING UN -OCCUPIED MODE USING HONEYWELL T7300 CONTROLS. ECONOMIZER WILL ALSO DELIVER REQUIRED OSA TO SPECIFIC ZONE AS SHOWN ON FRESH AIR SCHEDULE. BALL UNITS TO HAVE DUCTS SMOKE DETECTORS FOR SMOKE SHUT DOWN. SYSTEM TO BE INTERFACED WITH FIRE PROTECTION SYSTEM BY ELECTRICAL CONTRACTOR. L,_—.__..._.._ rr.. ,............... RXRD-CBM10 (Fully Modulating Economizers from 0-100°!x) Controlled by enthalpy sensor, senses outside air enthalpy, adjustable minimum Position. :� r 13'331 .x' 14% mm; ALL DOWNFLOW 15M ^m; MODELS INCLUDE STANDARD RELIEF DAMPER j6 MMV. V I4r>4 mri! EIDNOW ZER. 6 SCREWS REOJIREJ RETURN AIR FILLER ECONOFAtZER — BAS£ ASSEMBLY GAS DIAGRAM & SIZING 11,4. >CqN Cd rO LOEVE��f `m r O 1 NpPi°`��` 1!T��` NO see Uetor to Attaoi�. Sob,du cess �� �,� •:.�