Loading...
Report Electrical Equipment Test Report WHISKEY HILL ELECTRIC/GREENWAY GROUND FAULT TEST 33945534-002 2o / 0) 65 ? Schneider Electric Services: life-cycle solutions for any manufacturers' electrical distribution equipment. Sch,neider Make the most of your energy=" Electric Table of Contents Schneider Job #33945534-002 O E l e c t r i c Customer REXEL TAYLOR (RDC) End User WHISKEY HILL ELECTRIC/GREENWAY Site Location Designation Device PAGE Substation NO. Cover Letter GREENWAY TOWN CENTER main breaker Main breaker main switch board Schneider , Electric February 24, 2014 WHISKEY HILL ELECTRIC/GREENWAY Jon Davis 12220 SW SCHOLLS FERRY RD TIGARD, OR 97223 Customer PO.: S105956270 Project #: 33945534-002 Subject: Service Report Dear Jon Davis, Enclosed please find the project documentation for the work performed by SchneiderElectric Services at your GREENWAY TOWN CENTER facility on 2/12/14. Scope of Work Summary Schneider Electric Services performed ground fault testing on main switch board. Report Organization This report has been organized as follows: •Table of Contents •Deficiency Summary: Includes all items that require priority attention prior to the next outage •Comment Summary: Includes general comments and lower priority action items that may be scheduled during future maintenance outages •Test Data Sheets: Includes detailed inspection data and test results for all equipment serviced during this service activity Thank you for allowing Schneider Electric Services to assist you with this project. If you have any questions or concerns regarding this report or work performed please contact MARK YOKUBAITIS at 503-498-4500 Respectfully, JOSEPH KROL Field Service Representative Low Voltage Ground Fault Relay Schneider 9Electric CUSTOMER REXEL TAYLOR (RDC) JOB# 33945534-002 PAGE END USER WHISKEY HILL ELECTRIC/GREENWAY DATE 2/12/2014 TEMPERATURE 45 F HUMIDITY 30 % SITE LOCATION GREENWAY TOWN CENTER 0610 09-180530 SUBSTATION main switch board END USER ASSET/ID DESIGNATION main breaker DEVICE Main breaker TESTED BY Joseph Krol EQUIPMENT USED I 1 RELAY NAMEPLATE GROUND FAULT SYSTEM TYPE MANUFACTURER Square 0 SN/SO NO. 06415283670001 @ RESIDUAL GROUND TYPE RK2000 RATED CURRENT 2000 A t^ ZERO-SEQUENCE CATALOG NO. RKF36200044A4P INT. RATING 65 KA C' SOURCE GROUND RATED VOLTAGE 600 V MANUF. DATE 13273 i 1 INSPECTION DESCRIPTION CONDITION CLEAN/LUBE DESCRIPTION CONDITION CLEAN/LUBE DESCRIPTION CONDITION CLEAN/LUBE OVERALL CONDITION Acceptable Cleaned MATCHES DWG OR SPEC Acceptable N/A CT WINDOW TYPE Solid N/A MONITOR/TEST PANEL New N/A MAIN BONDING JUMPER Acceptable N/A CT WINDOW SHAPE Round N/A MULTIPLE SOURCE SCHEM N/A N/A GROUND CONNECTION Acceptable N/A ZONE INTERLOCKS N/A N/A ■ CONTROL POWER XFMR N/A N/A CONDUCTOR ROUTING Acceptable N/A N/A N/A I 1 TESTS SETTINGS DESCRIPTION DESCRIPTION POLARITY TEST N/A ] PICK-UP SETTING 500 A OPTIONAL: CONTROL TEST AT 55%VOLTAGE N/A TIME DELAY SETTING 0.1 off I 1 INJECTION TEST DATA PICK-UP CURRENT I A PHASE 1 492 I B PHASE 1493 1 C PHASE 1494 1 NEUTRAL I N/A INSULATION PRIMARY INJECTION TESTING RESISTANCE NEU.TO GND. CURVE LIMITS(time) TIME DELAY 01kV D.C. PICK-UP TEST TEST _ CURRENT % CURRENT MINIMUM MAXIMUM SECONDS CYCLES BEFORE TEST 629 I amps 150 943.5 amps 0.09 0.11 0.1 .N/A 19.6 G 200 1,258 amps 0.09 0.11 0.1 N/A AFTER TEST ' 300 1,887 amps 0.09 0.11 0.1 N/A 19.6 G I TECH NOTE(S): COMMENTS: DEFICIENCIES: (888) 778-2733 www.schneider-electric.us 08001, REVISED 03/15/2013