Report Electrical Equipment Test Report
WHISKEY HILL ELECTRIC/GREENWAY
GROUND FAULT TEST
33945534-002
2o /
0) 65 ?
Schneider Electric Services:
life-cycle solutions for any
manufacturers' electrical
distribution equipment.
Sch,neider
Make the most of your energy=" Electric
Table of Contents Schneider
Job #33945534-002 O E l e c t r i c
Customer REXEL TAYLOR (RDC)
End User WHISKEY HILL ELECTRIC/GREENWAY
Site Location Designation Device PAGE
Substation NO.
Cover Letter
GREENWAY TOWN CENTER main breaker Main breaker
main switch board
Schneider
, Electric
February 24, 2014
WHISKEY HILL ELECTRIC/GREENWAY
Jon Davis
12220 SW SCHOLLS FERRY RD
TIGARD, OR 97223
Customer PO.: S105956270
Project #: 33945534-002
Subject: Service Report
Dear Jon Davis,
Enclosed please find the project documentation for the work performed by
SchneiderElectric Services at your GREENWAY TOWN CENTER facility on 2/12/14.
Scope of Work Summary
Schneider Electric Services performed ground fault testing on main switch board.
Report Organization
This report has been organized as follows:
•Table of Contents
•Deficiency Summary: Includes all items that require priority attention prior to
the next outage
•Comment Summary: Includes general comments and lower priority action
items that may be scheduled during future maintenance outages
•Test Data Sheets: Includes detailed inspection data and test results for all
equipment serviced during this service activity
Thank you for allowing Schneider Electric Services to assist you with this project. If you
have any questions or concerns regarding this report or work performed please contact
MARK YOKUBAITIS at 503-498-4500
Respectfully,
JOSEPH KROL
Field Service Representative
Low Voltage Ground Fault Relay Schneider
9Electric
CUSTOMER REXEL TAYLOR (RDC) JOB# 33945534-002 PAGE
END USER WHISKEY HILL ELECTRIC/GREENWAY DATE 2/12/2014 TEMPERATURE 45 F HUMIDITY 30 %
SITE LOCATION GREENWAY TOWN CENTER 0610 09-180530
SUBSTATION main switch board END USER ASSET/ID
DESIGNATION main breaker DEVICE Main breaker
TESTED BY Joseph Krol EQUIPMENT USED
I 1
RELAY NAMEPLATE GROUND FAULT SYSTEM TYPE
MANUFACTURER Square 0 SN/SO NO. 06415283670001 @ RESIDUAL GROUND
TYPE RK2000 RATED CURRENT 2000 A t^ ZERO-SEQUENCE
CATALOG NO. RKF36200044A4P INT. RATING 65 KA C' SOURCE GROUND
RATED VOLTAGE 600 V MANUF. DATE 13273
i 1
INSPECTION
DESCRIPTION CONDITION CLEAN/LUBE DESCRIPTION CONDITION CLEAN/LUBE DESCRIPTION CONDITION CLEAN/LUBE
OVERALL CONDITION Acceptable Cleaned MATCHES DWG OR SPEC Acceptable N/A CT WINDOW TYPE Solid N/A
MONITOR/TEST PANEL New N/A MAIN BONDING JUMPER Acceptable N/A CT WINDOW SHAPE Round N/A
MULTIPLE SOURCE SCHEM N/A N/A GROUND CONNECTION Acceptable N/A ZONE INTERLOCKS N/A N/A
■
CONTROL POWER XFMR N/A N/A CONDUCTOR ROUTING Acceptable N/A N/A N/A
I 1
TESTS SETTINGS
DESCRIPTION DESCRIPTION
POLARITY TEST N/A ] PICK-UP SETTING 500 A
OPTIONAL: CONTROL TEST AT 55%VOLTAGE N/A TIME DELAY SETTING 0.1 off
I 1
INJECTION TEST DATA
PICK-UP CURRENT I A PHASE 1 492 I B PHASE 1493 1 C PHASE 1494 1 NEUTRAL I N/A INSULATION
PRIMARY INJECTION TESTING RESISTANCE
NEU.TO GND.
CURVE LIMITS(time) TIME DELAY 01kV D.C.
PICK-UP TEST TEST _
CURRENT % CURRENT
MINIMUM MAXIMUM SECONDS CYCLES BEFORE TEST
629 I amps 150 943.5 amps 0.09 0.11 0.1 .N/A 19.6 G
200 1,258 amps 0.09 0.11 0.1 N/A AFTER TEST
'
300 1,887 amps 0.09 0.11 0.1 N/A 19.6 G
I
TECH NOTE(S):
COMMENTS:
DEFICIENCIES:
(888) 778-2733 www.schneider-electric.us 08001, REVISED 03/15/2013