Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
RECEIVED "25 20 1 3 . 00° 103 MAY 2 2 2013 Simplex TrueAlarm® Fire Alarm Controls p CITY OF TIGAR UL, ULC, CSFM Listed; FM Approved, G DW Model 4010 Fire Alarm Control Panel for TrueAlarm MEA (NYC) Acceptance* Analog Sensors and IDNetTM Addressable Devices Features Standard features include: • Up to 250 addressable TrueAlarm sensor or addressable device points using IDNet communications that operate with either shielded or unshielded twisted pair wiring** • Four,2 A notification appliance circuits(NACs)with solid state current protection • Power supply/battery charger with 4 A available for NACs and auxiliary power • Internal event reporting DACT module(standard on models 4010-9101,4010-9102,&4010-9150) • UL listed to Standard 864 Installation convenience features: • Power-limited design provides electronic modules on a one-piece chassis with up-front terminal blocks for 4010 Fire Alarm Control Panel(with standard door) wiring access Descri•tion • Compact NEMA 1 rated cabinet is available in beige or red and can be pre-shipped for early installation TrueAlarm fire alarm control panels have the ability Setup, programming, and maintenance features: to provide location accuracy for monitoring and control. • Device level ground fault search,locate,and isolate When equipped with TrueAlarm analog sensing for smoke and heat detection,the processing power of the control • Auto Program for general alarm operation panel also has the ability to analyze conditions at each • TrueAlarm individual analog sensing with front panel location to provide accurate detection with significantly information and selection access reduced maintenance costs. • "Dirty"TrueAlarm sensor maintenance alerts,service The 4010 TrueAlarm Fire Alarm Control Panel has been and status reports including"almost dirty" specifically designed to provide addressable operation and • Default TrueAlarm sensor device type operation analog detection in a cost-effective package for application • TrueAlarm sensor peak value performance report sizes that previously were considered only appropriate for • Duplicate address error detection conventional zoned monitoring. • Front panel or PC programming Installation and Service Ease. The 4010 mounts on a • WALKTESTTM silent or audible system tests single chassis for quick installation and removal.Terminal • Software verification simulation mode blocks are large and up-front for easy access and inspection. Supports the following IDNet devices: Optional modules are easily and quickly installed,and programmed as required. • Addressable manual stations;TrueAlarm sensor bases, duct housings,and isolator bases The 4010 cabinet provides convenient stud markers for • Quad-state zone adapter modules(ZAMs)for initiating drywall thickness and nail-hole knockouts for quicker device monitoring mounting. Smooth cabinet surfaces are provided for locally cutting conduit entrance holes exactly where required.4010 • Quad-state line powered individual addressable modules cabinets and electronics can be ordered separately,allowing (IAMB)for initiating device monitoring and relay control early cabinet installation. • 4009 IDNet NAC Extenders and TrueAlertl) Addressable Controllers and accessories Ground Fault Assistance. Ground fault problems often occur during installation.The 4010 provides isolating Available option modules include: circuitry,control of isolator bases,and software-controlled • Door mounted 24 LED annunciator(std.on ULC models) sequencing to isolate ground faults to specific identified • Network connection,or Point Reporting DACT locations.This assistance helps the installer to accurately • Class A,NAC adapter module locate the wiring problem for quicker repair. • RS-232 ports for printer and maintenance PC • Refer to page 6 for listing details.This product has been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code. • Expansion power supply;Auxiliary Relay Module or See CSFM Listing 7170-0026:226 for allowable values and/or conditions concerning City Interface material presented in this document.It is subject to re-examination,revision.and possible cancellation.Accepted for use—City of New York Department of Buildings—MEA35-93E. • Equipment for Suppression Release Applications Additional listings may be applicable;contact your local Simplex product supplier for the (refer to data sheet 54010-0003) latest status Listings and approvals under Simplex Time Recorder Co.are the property of Tyco Safety Products Westminster. Compatible with Simplex®auxiliary panels: "TrueAlarm analog smoke detection and IDNet addressable devices are protected by one or 4003 Voice Control Panel more of the following U S.Patents:5,155,468;5,173,683;5,543,777;5400,014;5,552,765; • 5,552,763,DES.377,460;4,796,025;5,966,002;and 6,034.601. • 4081 Battery Cabinet with charger for 50 Ah batteries t WALKTEST system test is protected under U.S.patent#4,725,818. S4010-0001-12 8/2009 4010 Operator Control Summary 4010 Display Panel and Diagnostic Mode Extensive Feature List. The 4010 Fire Alarm Control Convenient Status Information. With the locking Panel provides access to an extensive feature list that door closed,a window allows viewing of the status includes: display.The 4010 status panel provides a two line by 40 character,super-twist LCD information display and eight • Providing easy and powerful operator information with status LED indicators as shown in the illustration below. a logical, menu-driven display • Extensive and automatic diagnostics for maintenance From this display,the LED indicators will describe the reduction general category of activity being displayed with the LCD History Logs available from the LCD or capable of providing more detail. For the authorized user,unlocking • (optionally)being printed the door will provide access to the control switches and allow further inquiry by scrolling the display for • Software Verification,allowing detailed logic additional detail. (Refer to control panel functional programming simulation to be conducted without illustration below.) activating connected outputs • Control Panel(or service PC) label editing WALKTEST Diagnostic Operation Mode.The patented WALKTEST process allows a single person to • Password access control perform system test.The system records test inputs such • Auto Program Quick Configuration(Quick-CFIG)of as intentional alarms or trouble and either logs the connected modules and IDNet devices for general alarm response(silent WALKTEST operation)or outputs a operation to quickly get the system up and running brief,recognizable audible notification signal(audible WALKTEST operation). Extended Operator Control Panel Functions `FIVE STATUS INDICATOR LEDs provide system status indications in addition to LCD information,LEDs flash to indicate the condition and then when acknowledged,remain on until reset THREE PROGRAMMABLE LEDs `2 X 40 LCD READOUT,LED backlighted during normal conditions and abnormal ' provide custom labeling(labels insert into operating conditions,provides up to 40 characters for custom label information a pocket),the top two LEDs are FIRST ALARM DISPLAY:Operation can be selected for maintained display of first selectable as red or y reen the bottom `alarm until acknowledged , `ED is selectable as green or yellow / '=:Y'=TEM PE: NORMAL_ \ 1 :02: 15c n Mork 17—Auci—lZl9 A / I� EIRE SYSTEM SYSTEM ALARM AC CONTROL` ALARM SUPERVISORY TROUBLE SILENCED POWER PANEL VIEW with • • 1/ • SYSTEM RESET restores 4010 door closed control panel to normal when ' all alarmed inputs are ALARM SUPS TROUBLE ALARM SYSTEM returned to normal ACK ACK ACK SILENCE RESET • `--_ FUNCTION • • , óód ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge and silences the operator NINE EXTENDED FUNCTION KEYS (accessible with door panel and all annunciator tone-alerts open)select and scroll through display prompts for locating • • additional system information,performing maintenance functions,or for front panel programming • SUPV ACK acknowledges system supervisory ALARM SILENCE causes audible notification appliances conditions,logs the acknowledge,and silences the operator panel and all annunciator tone-alerts to be silenced,used after evacuation is complete and while alarm source is being investigated • • ,TROUBLE ACK acknowledges system troubles, logs the acknowledge,and silences the operator panel and all annunciator tone-alerts 2 S4010-0001-12 8/2009 • IDNet Addressable Interface TrueAlarm Analog Sensors (Continued) Overview. The 4010 provides IDNet addressable device TrueAlarm heat sensors can be selected for communications. Using a two-wire circuit,individual rate-of-rise detection as either 15°F(8.3°C)or 20°F devices such as manual fire alarm stations,TrueAlarm (11.1°C)per minute with an independent fixed limit of sensors,and sprinkler waterflow switches can be directly 135°F(57°C)or 155°F(68°C).TrueAlarm heat sensors connected(or interfaced)to the IDNet controller to can also be programmed as a utility device to monitor for communicate their identity and status.This addressability temperature extremes in the range from 32°F to 155°F allows the location and condition of the connected device (0°C to 68°C).This feature can provide freeze warnings to be displayed on the 4010 panel LCD and on system or alert to HVAC system problems. annunciators.Additionally,control circuits(fans, dampers,etc.)may be individual) controlled by using a Toes,up to 250 total P ) Y Y Y g devices,up to 250 total relay IAM(individual addressable module).The 4009 IDNet NAC Extender or the TrueAlert Addressable controller can be controlled for local or remote I ! Ill notification appliance expansion.(Refer to compatible device lists on document S4090-0011 and to individual - device documentation for further details.) TIMM--- Modular TrueAlarm Capacity. A total of 250 addressable monitor and control TrueAlert Addressable Controller sensor with base points may be intermixed on the same pair of wires.By using Zone Adaptor Modules(ZAMs)or Individual Addressable Modules(IAMs),conventional initiating der ices can be connected to the IDNet circuit. IDNet Addressable Operation. The IDNet controller Supervised IAM Modular TrueAlarm sensor continuously interrogates each addressable device on the with IDNet isolator base communication channel for status condition such as: m w= H10111111 normal,off-normal,alarm,supervisory,or trouble. wir Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping"of the circuit for Class operation. Addressable station f Cl B i P 4009 IDNet NAC Wiring Requirements. Refer to the specifications chart Extender below. Distances are for shielded or unshielded wire. Shielded wire may provide protection from unexpected ---z- sources of interference and may be required for some rueAlaIn sensor Monitory IAMs and Y q TrueAlarm sensor Relay IAMB applications. — --- BRi®Iliiiielitiiali _ Wiring Specifications Size 18 AWG(0.82 mm2) 4010 Fire Alarm Preferred Shielded twisted pair(STP) Control Panel with •-=-- Wire annunciator door Acceptable Unshielded twisted pair(UTP) e a Farthest Distance from Control 1$ Up to 2500 feet(762 m) Panel to Device uuluuWNmui'u wnmw!umn�omlimgN Total Wire Length Allowed With Up to 10,000 ft(3 km). `T"Taps for Class B Wiring 4010 Control Panel with Typical IDNet Devices TrueAlarm Analo. Sensors Diagnostics and Default Device Type TrueAlarm System Operation. IDNet communications TrueAlarm operation gives the 4010 system the ability to are used for TrueAlarm smoke and temperature sensors. automatically indicate when a sensor is almost dirty,dirty, Every four seconds,smoke sensors transmit an output and excessively dirty.The NFPA 72(National Fire Alarm value based on their smoke chamber condition.The 4010 Code)requirement for a test of the sensitivity range of the CPU maintains a current value,peak value,and an average sensors is fulfilled by the TrueAlarm ability to maintain value of each sensor's output. Status is determined by the sensitivity level of each sensor. comparing the current sensor value to its average value. Modular TrueAlarm sensors use the same base and diffe rent • Tracking this average value as a continuously shifting sensor types(photoelectric smoke sensor,or heat sensor) reference point filters out environmental factors that cause can be easily interchanged to meet specific location shifts in sensitivity. requirements.This feature also allows intentional sensor Programmable Sensitivity. The sensitivity of each substitution during building construction. When conditions sensor can be field programmed at the 4010 Control Panel are temporarily dusty,instead of covering the smoke sensors for different levels of smoke obscuration(in percent)or (causing them to be disabled),heat sensors may be installed for specific heat detection levels.In order to evaluate without reprogramming the control panel. Although the whether the sensitivity should be revised,the peak value control panel will indicate an incorrect sensor type,the heat is stored in memory and can be easily read and compared sensor will operate at a default sensitivity to provide heat to the alarm threshold directly in percent. detection for building protection at that location. 3 84010-0001-12 8/2009 TrueAlarm Information Details Printer(Simplex True Alarm sensor data can be displayed on the model 4190-9013) 9 • system LCD,on a remote maintenance PC,or printed on a remote printer. With the proper operator access,a - — TrueAlarm Service Report can be generated to list the . specific details of each TrueAlarm device.This report,as Local well as the Status Report can either be displayed on the 11113 maintenance remote maintenance PC or captured permanently by using computer • a remote 80 character printer. _______ ______ _.+.n" J= Status and Service Reports. The report samples \, below illustrate the format provided on either the remote printer.This information is available 4010 Fire Alarm One connection type per 4010, maintenance PC or a p Control Panel selected by module choice;max. at the system LCD by identifying the specific point of .:� wiring distance is 300 ft(91 m) interest and reading one point at a time. @ 9600 baud 101 Compatible Printer. Model 4190-9013 is a UL / Standard 864 listed 80 column,24 pin dot matrix printer (refer to data sheet S4190-0011). -- ' Remote authorized maintenance ..tiff.4. computer connected via dial-up 4". ve. Service Modem Connection RS-232 Connection Options (refer to module selection on page 6) TrueAlarm Status and Service Re•ort Sam•les . Simplex 4010 Fire Alarm System Page 1 REPORT 3 : TrueAlarm Status Report 2:43:03 pm Mon 09-Mar-09 Zone Sensi- Almost Name Custom Label tivity Device Status Dirty M1-1 ANALOG PHOTO CLEAN ROOM 0.5 % NORMAL M1-2 ANALOG ION CLEAN ROOM 1.3 % NORMAL M1-3 ANALOG PHOTO MAIN LOBBY 2.5 % NORMAL *YES* M1-4 ANALOG PHOTO CONFERENCE ROOM 1 2.5 % NORMAL M1-10 HEAT DETECTOR GARAGE 135 F NORMAL M1-11 ANALOG PHOTO KITCHEN 3.7 % NORMAL *YES* END OF REPORT Typical TrueAlarm Status Report Information Printout and/or Maintenance PC Screen Simplex 4010 Fire Alarm System Page 1 REPORT 4 : TrueAlarm Service Report 2:56:09 pm Mon 09-Mar-09 Dev Alarm Avg Current/ Peak/ State Num Custom Label at: val % alarm % alarm 1 ANALOG PHOTO - CLEAN ROOM 0.5/ 83 67 68/ 1% 72/ 10% NOR 2 ANALOG ION - CLEAN ROOM 1.3/209 94 97/ 2% 101/ 1% NOR 3 ANALOG PHOTO - MAIN LOBBY 2.5/185 117 117/ 0% 125/ 42% NOR 4 ANALOG PHOTO - CONFERENCE ROOM 1 2.5/161 93 93/ 0% 93/ 0% NOR 10 HEAT DETECTOR - GARAGE 135F/253 --- 63/-67F 66/ 69F NOR 11 ANALOG PHOTO - KITCHEN 3.7/216 116 116/ 1% 110/ 36% NOR END OF REPORT Typical TrueAlarm Service Report Information Printout and/or Maintenance PC Screen 4 84010-0001-12 8/2009 Standard Panel Features Optional Expansion Slot Modules (Cont'd) N2 Communications for Serial Annunciator Control. Network Interface,Fixed Media.Available for wired Control for up to 6 remote Simplex Annunciator products applications. including 24 Point I/O Module,and LCD Annunciator. DACT,Point Reporting Module. Provides serial output Includes extensive troubleshooting diagnostics.(See list in information that can send location details to a remote next column for compatible devices.) receiving station. Access Port. RS-232 service port for connecting PC tools DACT,Event Reporting Module. For applications where for service diagnostics and for programming the CPU Flash simple event status information is required(Alarm,Trouble, EPROM memory. Supervisory,and AC power failure). IDNet Addressable Communications Channel. Dual RS-232 Module.Available for interfacing to a printer Addressable channel provides communications for up to 250 and a maintenance PC. remote addressable devices,including TrueAlarm analog Single RS-232 Module with Service Modem Connection. sensors and isolator bases(see details on page 3). Provides one port dedicated for connection to a printer,and Four NACs.Class B output is standard,rated for 2 A @ a second port dedicated for dial-in from a service computer, 24 VDC nominal,with solid state current protection. typically located off-site. With an off-site computer, Class A operation is optional with the addition of an adapter programming changes and system diagnostics can be module. performed remotely,reducing service time for repair or NAC operation can be selected for"on-until-Silence"or reprogram. Security is maintained by password protection. "on-until-Reset,"and can be Continuous,Temporal pattern, Optional Chassis Mount Modules or March Time pattern. (March Time is selectable for p 20 bpm or 120 bpm for conventional appliances;or 4 A Expansion Power Supply provides two taps of 2 A 60 bpm for SmarlSyncTm appliances.)NACs are each,28 VDC,filtered,non-regulated.Output rating is 4 A individually selectable to control Simplex synchronized for auxiliary power,4 A for"Special Application" strobes or for Simplex SmartSync control that provides appliances and 2 A for"Regulated 24 DC"appliance power. separate horn and synchronized strobe control using a 2-wire circuit. (SmartSync hom/strobe operation is Battery Meter Module provides panel mounted ammeter • protected under U.S. Patent No.6,281,789.) and voltmeter for power supply monitoring. Two Auxiliary Output Circuits. Operation is programmable Dual Circuit Class A NAC Adapter Module mounts on the for trouble,alarm,supervisory,or other fire response main 4010 printed circuit assembly and provides the • functions.Output is one Form"C"dry contact each,rated 2 additional circuitry needed for Class A operation. A @ 24 VDC. An optional relay kit is available for Dual Circuit City Connect Module provides the interface switching up to 0.5 A at 120 VAC. required for direct wired reporting to conventional city Standard Power Supply. Output is rated 4 A for"Special connection circuits.(Available with or without disconnect Application"appliances and for"Regulated 24 DC" switches.) appliance power. (Special Application appliances include Expansion Power Distribution Module provides two Simplex 4901,4903,4904,and 4906 Series horns,strobes, additional termination points for the 0.5 A auxiliary power horn/strobes,and speaker/strobes.See page 7 for output,or for one tap of the expansion power supply. additional information.) Internal system power is provided separately,allowing the 4 A to be available for NAC and Relay Option Module provides three relays,one each for auxiliary power tap functions.Over-current protection is Alarm,Supervisory,and Trouble. Relay contacts are solid state and self-resetting. selectable for normally open or normally closed and are Auxiliary Power Tap. Provides up to 0.5 A of the standard rated 2 A @ 32 VDC maximum. power supply voltage,over-current protected.Compatible N2 Communications Modules uses include power for:remote LCD annunciators, 24 Point I/O modules,sensor bases and duct housings that require Up to six of the following modules may be connected to external power,and addressable devices requiring external the Simplex N2 serial communications bus. power. 4606-9101 LCD Annunciators provide remote Battery Charger.Capable of charging up to 25 Ah sealed acknowledge,reset,and alphanumeric status display.First lead-acid batteries(4010 cabinet mounted).A recharge time Alarm display will work same as for the panel when of 24 hours is typical with stable 120 VAC input. For selected(see page 2).(Refer to data sheet S4606-0001.) applications requiring larger batteries,external 24 LED Annunciator Doors are standard on ULC listed charger/cabinet assemblies are available. models and are available as door-only assemblies for A depleted battery cutout feature is programmable to advise electronics only packages or other aftermarket applications. and/or to reduce current when battery voltage is low. This option uses the 24 Point I/O module with all points pre-assembled as LED outputs,with individual labels and Optional Expansion Slot Modules each LED is selectable as red or yellow. (The 4010 is available with a Simplex Network Interface. 4605 Series 24 Point I/0 Modules are available for remote 4010 points can be declared"public.") mounting and provide 24 points that can be programmed as either general purpose switch inputs or system controlled Network Interface,Modular Media.Available for wired outputs.Typical applications are for remote annunciators connections or fiber optic. Require separate media modules. and monitoring and control of other related processes. May be both wired,both fiber optic,or one of each. (Refer to data sheet S4010-0002.) 5 84010-0001-12 8/2009 4010 Fire Alarm Control Selection Chart and Module Location Rules (refer to diagrams on page 8) Category Model Description Voltage Color 4010-9101 UL Listed 4010 Fire Alarm Control Panel with:door,cabinet,power 120 VAC Beige 4010-9102 supply/battery charger,IDNet interface,4 NACs,2 programmable Red 4010-9201 auxiliary relays,and external N2 communications interface;4010-9101 Beige reporting 4010-9102 include internal common event ting DACT 240 VAC g Control Panel 4010-9202 Red Assembly 4010-9101C English ULC Listed 4010 Fire Alarm Control Panel;same as above 120 VAC Beige (select one) 4010-9101CF French except:with 24 LED Annunciator door;and without DACT 4010-9150 UL Listed 4010 Fire Alarm Control Panel, Electronics Only;for pre-shipped 4010-9150C ULC English cabinets,requires door and cabinet ordered separately; 120 VAC input; 4010-9150CF Listed French 4010-9150 has event reporting DACT;C&CF suffix models delete DACT Optional Expansion Slot Features (two slots are available, select modules as required) Category Model Description 4010-9810 DACT Module(Common Event Reporting) Reporting and 4010-9816 DACT Module(Point Reporting) Includes two,7 ft(2.1 m)long RJ45 cables Network Modules (select one) 4010-9821 Network Interface Module with fixed,wired connections 4010-9817 Network Interface Module,Modular;requires 2(In/Out)media modules(see below) Media Modules 4010-9818 Network Wired Media Module Media modules mount on the 4010-9817 module 4010-9819 Network Fiber Optic Media Module without impact to slot allocation space. RS-232 4010-9811 Dual RS-232 Interface Module Communications (select one) 4010-9812 Single RS-232 Interface Module with Service Modem connection Chassis Mounted Expansion Modules (select as required) I Category Model Description Expansion Power 4010-9813 120 VAC input 4 A Expansion Power Supply; rated 4 A for"Special Application"appliances; Supply one) 2 A for"Regulated 24 DC"appliance power (select one) 4010-9823 240 VAC input 9 PP P Optional Features 4010-9820 Battery Meter Module(ammeter and voltmeter) (select one) 4010-9825 24 VDC Expansion Power Distribution Module,provides two additional termination points for an expansion power supply tap or the auxiliary power output 4010-9806 Dual Circuit Class A NAC Adapter Module, two maximum Optional Features 4010-9809 Dual Circuit City Connect Module (select as Select one indicated) 4010-9829` Dual Circuit City Connect Module w/o disconnect switches . maximum 4010-9803 Relay Option Module Accessories Category Model Description 4010-9826 120 VAC Auxiliary Relay Kit,allows one auxiliary relay to control up to 0.5 A @120 VAC, select as required; 2 maximum Optional Features 4010-9830 Suppression Release Appliqué,required for suppression release applications;suffix CAF (CAF) selects a French appliqué 2975-9801 Semi-flush trim,beige, 1-7/16"(37 mm)wide 2975-9802 Semi-flush trim,red, 1-7/16"(37 mm)wide Batteries 2081-9272 6.2 Ah Battery, 12 VDC (required if 2081-9274 10.0 Ah Battery,12 VDC batteries are 2081-9288 12.7 Ah Battery,12 VDC internal;select one ry size;two batteries 2081-9275 18 Ah Battery, 12 VDC; NOTE:This battery size will not allow bottom entry conduit are required) 2081-9287 25 Ah Battery, 12 VDC Cabinets(select 2975-9215 Red Cabinet Dimensions:22"H x 18"W x 5-3/8"D one if pre-shipped) 2975-9214(CF) Beige Cabinet;CF suffix has French labels (559 mm x 457 mm x 137 mm) 4010-9858 Red Door with dress panel Dimensions:22"H x 18"W x 5/8"D Doors(select one 4010-9857(CF) Beige Door with dress panel;CF has French labels (559 mm x 457 mm x 16 mm) if pre-shipped or for use with 4010-9860" Beige Door with 24 LED Annunciator and dress panel Dimensions:22"H x 18"W x 4010-9150) 1-23/32"D(559 mm x 457 mm x 4010-9881" Red Door with 24 LED Annunciator and dress panel 44 mm)[see also 54010-0002] As of document revision date:4010-9829 is not ULC listed; 4010-9860 and 4010-9861 are listed by UL,ULC,and CSFM; and FM approved; 6 S4010-0001-12 8/2009 4010 O•eratin• S•ecifications Input Power Requirements Voltage Range Frequency Maximum Current AC Input, 120 VAC base models 102 to 132 VAC 60 Hz 2 A AC Input,240 VAC base models 204 to 264 VAC 50/60 Hz 1 A AC Input with 120 VAC expansion power supply 102 to 132 VAC 60 Hz 4 A AC Input with 240 VAC expansion power supply 204 to 264 VAC 50/60 Hz 2 A Environmental Operating Temperature Range 32°to 120°F(0°to 49°C) Operating Humidity Range up to 93%RH,non-condensing @ 100.4°F(38°C)maximum Output Ratings Rated 4 A for"Special Application"appliances and for Standard Power Supply Output "Regulated 24 DC"appliance power;Battery charger for up to 25 Ah sealed lead-acid batteries Simplex 4901,4903,4904,and 4906 Series horns,strobes,and Special Application combination horn/strobes and speaker/strobes(contact your Simplex Notification Appliance Reference product representative for compatible appliances) Regulated 24 DC Power for other UL listed appliances;use associated external synchronization modules where required Auxiliary Power Output Tap from Standard Power Rated 0.5 A maximum @ 19.4 to 32 VDC; Supply subtract current used from standard power supply output Rated 4 A for"Special Application"appliances and auxiliary power; Expansion Power Supply Output Rated 2 A for"Regulated 24 DC"appliance power; Two output taps of 2 A each are provided NAC Ratings 2 A each maximum;up to 33 synchronized strobes maximum per NAC Current Ratings for Optional Modules and Rem ote LCD Annunciator Model Module Supervisory Alarm Current Current 4010-9810 DACT(Common Event Reporting) 40 mA 40 mA 4010-9816 DACT(Point Reporting) 40 mA 40 mA 4010-9821 Network,wired communications 125 mA 125 mA 4010-9817 Network Modular,add media cards separately 24 mA 24 mA 4010-9818 Network Wired Media 47 mA 47 mA 4010-9819 Network Fiber Optic Media 36 mA 36 mA 4010-9811 Dual RS-232 75 mA 75 mA 4010-9812 Single RS-232 with Service Modem 100 mA 100 mA 4010-9806 Dual Class A NAC Adapter 0 mA 0 mA 4010-9809 Dual Circuit City Connect 20 mA 36 mA 4010-9829 Dual Circuit City Connect w/o disconnect switches 20 mA 36 mA 4010-9803 Relay Option Module 10 mA 37 mA 4010-9860 83 mA 4010-9861 24 LED Annunciator door 60 mA &ULC 4010s (all LEDs on) 4606-9101 Remote LCD Annunciator(refer to data sheet S4606-0001) 65 mA 140 mA System Current(supplied separate from power supply output) Base System with: Supervisory Alarm Current" Current*' no IDNet devices 195 mA 295 mA 50 IDNet devices 230 mA 330 mA 100 IDNet devices 265 mA 365 mA 150 IDNet devices 300 mA 400 mA 200 IDNet devices 335 mA 435 mA 250 IDNet devices 370 mA 470 mA **Current Calculation Information: 1. To determine total supervisory current,add currents of modules in panel to base system value and all auxiliary loads. 2. To determine total alarm current,add currents of modules in panel to base system alarm current and add all panel NAC loads and all auxiliary loads. 7 S4010-0001-12 8/2009 4010 Module La out Reference CET RY u owl NEC I 3lAC 2-, NBC a RAC I o 9 0 ",—— ' - 1.1 O O — Iwlwlwlw• llll " ••• • 4010-9820 8 0 0 0 0 `P' Al r 4010-9809 Meter Module 4010-9806 : 4010-9806 - ' °r-9829 or City Module Expansion Gass A Gass A 4010-9825 Slots 1 8 2 Module • Module or 24 VOC Power 4010-9803 Distribution - Relay Module Block a Oo ® ® . ° ° r a0 0 0 0 0 0 o O( ) O( ) 4010-9813 O ( () "/ O I r. ) or ^ 000 @00000 4010-9823 I© O Expansion Power Supply 9 - - III • r• O..k. .(.1.1,, ,_.09. 14.1, 1 © II_ ,,,,,,,.:,. i• . ..,. :- LJIB ; -IIK ; .I AUX AUXI AUX2 BATTERY POWER Mountin. Information - 1 7-3/32" Typical conduit entry area (180 mm) (cut holes as required) o Standard 1-19132"—a- door profile (40 mm) 6-1/4" (159 mm) 3/4" 5-1/2" I+ 18"(457 mm) ►I Annunciator (19 mm) (140 mm) A door profile 4„----------Wall thickness guides for 1/2"(13 mm)wall board 0 T alia.u.9'��unw a __ w` Standard Door,�i_ _ [ I Ltp a?!' " - 5/8"(16 mm)thick T1 Wall thickness guides for II 5/8"(16 mm)wall board) i 1 1 Internal straps are Annunciator Door, .g 1} r 1-23/32"(44 mm)thick �� provided for wiring i_=rmi _. -) _ management -- - (2 each side) 21" a e--��*+y ss (533 mm) t�.�.� ca ( +r, Door and exposed �—�.` - T—=- I cabinet dimension '-" for semi-flush mount - I 2-15/32"(63 mm) a 14.1/2"(368 mm) /Knockout screw/nail holes Battery Area No conduit e (for semi-flush mount) I ntry or wiring in this area • •• f o " C I Wall board position reference----_____� Shaded area is for non-power limited wiring for semi-flush mount Tyco is a registered trademark of Tyco International Services GmbH and is used under license.Simplex.the Simplex logo.TrueAlarm.WALKTEST.IDNet.Smart Sync,and TrueAlert are trademarks of Tyco International Ltd.and its affiliates and are used under license.NFPA 71 and National Fire Alarm Code are trademarks of the National Fire Protection Association(NEPA). fj Ctm Tyco Safety Products Westminster•Westminster,MA•01441-0001•USA S4010-0001-12 8/2009 �1®•7 www.tycosafetyproducts-usa-wm.corn ©2009 Tyco Safety Products Westminster.All rights reserved All specifications and other information shorn here current as ofdocument revision date and are subject to change Ittihad notice. Simplex Fire Alarm Control Panel Accessories Listings* System Batteries, Sealed Lead-Acid; with Applications Reference for Battery Cabinets, and Battery Cabinets with Charger Features Rechargeable, sealed lead-acid batteries: tltltttlttttlttllttlt81MMI tt infl • Lead-calcium grid structure with immobilized ,"""`"""""'"'"""'°""""""""'""'"""'"""'1 electrolyte in absorbent separator • Low maintenance with no need to add water • Low self-discharge characteristics • One-piece,high impact polystyrene cell cover with high reliability dual seal construction • UL 924 recognized pressure relief valves Available in a variety of capacities: • Batteries for internal mounting range from 6.2 Ah up to 50 Ah,depending on control panel cabinet size • Larger batteries,up to 110 Ah,mount in external battery cabinets that are available with internal chargers • Includes battery chargers with communications — compatibility for use with 4010 Series fire alarm control -- panels and with 4100U Series fire alarm control panels Descri•tion Simplex"' rechargeable sealed-lead acid batteries provide Compatible Sealed Lead Acid Batteries can be Installed Inside Fire Alarm Control Panel Cabin ets reliable and repeatable discharge and recharge characteristics for use in fire alarm and other systems applications. They are designed with immobilized electrolyte in an absorbent separator,allowing them to provide rated capacity on the first cycle. Because of their sealed construction,packaging is allowed within the system electronics enclosure(see illustration on page 2). When this is applicable,the quantity of system cabinets and the battery wiring distances are both minimized. Where required,external battery cabinets can be close-nippled to the control panel to house larger Remote Battery Cabinets are Available for batteries with battery chargers available in some battery Larger Battery Requirements cabinet sizes. Batter Details Battery Details (Continued) Charging.These batteries are intended to be used with Shipping. Sealed lead-acid batteries are shipped via compatible Simplex battery chargers. ground or sea transportation only.They are not shipped Series Connections. These batteries are required to be via air. connected in series to produce 24 V system voltage. Disposal. Battery chemicals and materials can be Battery sets must be of identical voltage,model number, recycled. Refer to information shipped with the battery or appearance,and approximately the same date of on its case. Return to the battery manufacturer or to a manufacture for proper operation. similarly qualified battery processing facility for proper Testing.Battery capacity testing is recommended to be disposal. performed by using a sealed lead-acid battery tester designed to withdraw a minimum of battery charge.The • Refer to details on page 4 and to the referenced individual product data preferred tester applies a variety of amplitude and sheets for agency listing status of battery cabinets and chargers.The batteries duration controlled test pulses that compares terminal detailed in this document meet the requirements of UL,ULC,and Factory Mutual for use with respective equipment battery chargers as listed on page 3. voltage against those predicted for the specific battery Contact your local Simplex product supplier for proper battery selection per size. (Testing is available through your local Simplex system requirements,Listings and approvals under Simplex Time Recorder product supplier.) Co.are the property of Tyco Safety Products Westminster. S2081-0006-19 10/2008 Batte Construction Reference Actual appearance will vary with battery size. Sealed outer cover Quick connect or post type terminal Vent hole (type varies with battery size) Potting material,black for negative,red for positive 1 o ivi_ (polarity is also clearly laJ� marked with+and-) Aill1111111 Pressure relief valve Inner cover Absorbent separator used to immobilize electrolyte 1111111prill Semi-permeable Lead-calcium grids membrane separator Cell group Cell case(high impact polystyrene) Batte Size Specifications Battery Model Capacity @ 20 Hour Width* Depth, Height with Approximate Discharge Rate Terminals Weight* 2081-9272 6.2 Ah 6-1/8"(156 mm) 2-5/8"(67 mm) 4"(102 mm) 5.75 lbs(2.6 kg) 2081-9274 10 Ah 6"(153 mm) 4-1/16"(103 mm) 4"(102 mm) 9.2 lbs(4.2 kg) 2081-9288 12.7 Ah 6"(153 mm) 4"(102 mm) 4"(102 mm) 9 lbs(4.1 kg) 2081-9275 18 Ah 7-1/4"(184 mm) 3-3/8"(86 mm) 6-5/8"(168 mm) 14.3 lbs(6.5 kg) 2081-9287 25 Ah 6-5/8"(168 mm) 5"(127 mm) 7"(178 mm) 19.4 lbs(8.8 kg) 2081-9271 (rectangular case, 33 Ah 12-1/2"(318 mm) 3-3/8"(86 mm) 7-1/16"(179 mm) 26.6 lbs(12.1 kg) typically for service) 2081-9276 ("square"case, 33 Ah 7-3/4"(197 mm) 5-1/4"(133 mm) 6-3/4"(171 mm) 26.5 lbs(12 kg) use for new) 2081-9296 50 Ah 9-1/2"(241 mm) 5-1/2"(140 mm) 8-7/8"(225 mm) 41.8 lbs(19 kg) 2081-9279 110 Ah 11-3/16"(284 mm) 10-1/2"(267 mm) 9"(230 mm) 82 Lbs(37 kg) • Dimensions and weight are per battery and are for reference only.Exact size may vary.Refer to the tables on page 3 mounting compatibility.These batteries are 12 V each and series connected for 24 V system use. NOTE: When wired in series for 24 V output,these batteries are to be of identical voltage,appearance,model number,and approximately the same date of manufacture. General Batte S•ecifications Nominal Voltage Rating 12 Volts per battery Discharge Rating 20 Hour Rate Typical Charge/Discharge Cycles 100 to 150 Preferred Charge Temperature Range 60°F to 90°F(15.6°C to 32.2°C) 2 S2081-0006-19 10/2008 Battery Compatibility for Fire Alarm Control Panel Mounting NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information Battery I Simplex Control Panel Model Series (see legend and notes below) Model Capacity 4003 4004 4004R 4005 4006 8 4009 4010 4100U 4100 8 4120 4020 4008 (all models) (2,4 or 6-Unit) (2,4 or 6-Unit) 2081-9272 6.2 Ah ✓ ✓ ✓ ✓ ✓ ✓ ✓ 1,2,or 3 bay ✓ ✓ 2081-9274 10 Ah ✓ ✓ ✓ ✓ ✓ ✓ ✓ 1,2,or 3 bay ✓ ✓ 2081-9288 12.7 Ah ✓ NA ✓ ✓ ✓ ✓ ✓ 1,2,or 3 bay ✓ ✓ 2081-9275 18 Ah ✓ NA Note 3 ✓ Ext Ext Note 2 1,2,or 3 bay ✓ ✓ 2081-9287 25 Ah NA NA Note 3 Ext Ext NA ✓ 1,2,or 3 bay ✓ Ext 2081-9271 33 Ah NA NA Note 3 Ext NA NA Note 3 1,2,or 3 bay Ext Note 4 (rectangular) 2081-9276 33 Ah NA NA Note 3 Ext NA NA Note 3 1,2,or 3 bay ✓ Ext ("square") 2081-9296 50 Ah NA NA Note 3 NA NA NA Note 3 2 or 3 bay Ext Ext 2081-9279 110 Ah Requires external battery cabinet ✓ =Can be placed in the respective equipment cabinet Ext=External battery cabinet is required,refer to selection chart on page 4 NA=Not applicable/not compatible NOTES: 1. These batteries meet the requirements of UL, ULC,and Factory Mutual for use with respective eq uipment battery chargers listed above.Contact your local Simplex product supplier for proper battery selection per system requirements. 2. 4010 Cabinets will accommodate 2081-9275, 18 Ah batteries,but will not allow bottom entry conduit. 3. Use 4081 series companion cabinet and charger,refer to page 4. 4. 4020 Cabinets will accommodate 2081-9271,33 Ah batteries,but will not allow bottom entry conduit. 5. Some control panel models are listed for battery replacement reference only. External Battery Cabinet Compatibility Reference Battery Cabinets without Chargers(connects to charger in panel) 2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279 Cabinet Panel Compatibility 18 Ah' 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah 2081-9270 multiple ✓ ✓ ✓ ✓ ✓ NA 2081-9280 4100U/4100+ NA NA NA NA NA ✓ 2081-9281 multiple ✓ ✓ ✓ ✓ ✓ NA 2081-9282 4009-9801 multiple ✓ ✓"• NA NA NA NA 4009-9802 multiple ✓ NA ✓ NA NA NA Battery Cabinets with Chargers 2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279 Cabinet Panel Compatibility 18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah 4081-9301 4004R and 4010 ✓ ✓ ✓ ✓ ✓ NA 4081-9302 • 4081-9306 4100U NA NA NA NA ✓ ✓ 4081-9308 "Batteries smaller than those listed are normally mounted in the product cabinet ""25 Ah capacity was effective as of 7/2005. ✓=Can be placed in the respective equipment cabinet NA=Not applicable/not compatible 3 S2081-0006-19 10/2008 External Battery Cabinet Specification Reference Battery Cabinets Without Chargers; Shallow Design with Front Door Model Color Listings Description Dimensions 2081-9281 Beige UL and 2-Unit,4100 style cabinet without charger;with locking 25-3/4"W x 20-3/4"H x 6-3/4"D FM solid door and battery shelf,primarily for use with 50 Ah 654 mm x 527 mm x 171 mm • 2081-9282 Red batteries (654 UL and For up to 25 Ah External battery cabinet without charger, 16-1/4"W x 13-1/2"H x 5-3/4"D 4009-9801' Beige FM batteries* (413 mm x 343 mm x 146 mm' • with locking solid door and battery ( ) For up to 33 Ah harness;for close-nippled mounting to 25-3/4"W x 20-3/4"H x 4-1/8"D 4009-9802 Beige UL batteries fire alarm control panel cabinet (654 mm x 527 mm x 105 mm) *Depth increased for 25 Ah batteries effective 7/2005. Battery Cabinet Without Charger; Deep Design with Hinged Lid Model Color Listings Description Dimensions 2081-9270 Red Not listed Battery cabinet without charger; cabinet has vented front, 26-1/2"W x 12"H x 12"D and hinged lid with support rod and lock on top (673 mm x 305 mm x 305 mm) Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems (refer to data sheet S4081-0001) Model Color Input Voltage Description Dimensions 4081 9301 Beige Battery cabinet with charger for the 4010 and 4004R fire alarm control panel; for up to 50 Ah 120 VAC batteries;with front door 22-1/2"W x16-3/4"H x 8-3/8"D 4081-9302 Red Listings include:UL, ULC,FM, CSFM,and MEA (572 mm x 425 mm x 213 mm) (NYC),see data sheet for details • Battery Cabinet Without Charger for 110 Ah Batteries;for use with compatible panel mounted chargers (refer to data sheet S2081-0012) Model& Color Cabinet Description Compatible Charger Description Dimensions Listings Chargers 4100-9xxx 4100U System Power Supplies Series (SPS) 4100-5111 Battery cabinet for 4100-5112 4100U Additional SPS 2081-9279, 110 Ah 4100-5113 2081-9280 batteries;includes 4100-5125 4100U Remote Power Supply Listings Red 80 A battery fuse, 4100-5126 (RPS))RPS 26-1/2"W x 12"H x 12"D include:UL terminals and 4100-5127 (673 mm x 305 mm x 305 mm) and CSFM battery connection 4100-5120 cables;see data 4100-5121 4100U TrueAlert Addressable sheet for details 4100-5122 Power Supply(TPS) 4100-0104 4100-0114 4100 Legacy power supplies 4100-0124 41000 Compatible Battery Cabinet With Charger for 110 Ah Batteries(for ULC listed systems and for other applications unable to use panel mounted power supply charger; refer to data sheet S4081-0002) Model Color input Voltage Description Dimensions 4081-9306 Red 120 VAC Battery cabinet with charger for up to 110 Ah batteries; 220/230/240 VAC, NOTE: Required for ULC listed charging of 27-7/8"W x 13-1/2"H x 14-5/8"D 4081-9308 Red multi-tapped 110 Ah batteries;Listings include:UL, ULC, FM, (708 mm x 343 mm x 371 mm) CSFM,and MEA(NYC),see data sheet for details 4100-9837 Green LED Power-on Indicator Kit, required for ULC listing, mounts above access panel using knockout provided Tvco is a registered trademark of Tyco International Services GmbH and is used under license.Simplex.and the Simplex logo are trademarks of Tyco International Ltd.and its affiliates and are used under license. £kSimplex Tyco Safety Products Westminster•Westminster, MA•01441-0001 •USA w S2081-0006-19 10/2008 ww.tycosafetyproducts-usa-wm.corn -2()(m W)',Tu a.Gih n Products Westminster.All rights reserved.All specifications and other information shorn acre current as of document revision date and are subject to change without notice. gSimplex Multi-Application Peripherals UL, ULC, CSFM Listed; FM Approved; IDNetTM or MAPNET II® Communicating Devices MEA (NYC)Acceptance* Addressable Manual Stations REIM Individually addressable manual fire alarm FIRE ALARM stations with: • Power and data supplied via IDNet or MAPNET H addressable communications using a single wire PULL DOWN pair** • Operation that complies with ADA requirements • Pull lever that protrudes when alarmed ttts • Break-rod supplied(use is optional) 0smpiex • Models are available with single or double action (breakglass or push)operation 4099-9001 Addressable Manual Station • UL listed to Standard 38 (front and side view) Compatible with the following Simplex®control panels: FIRE ALARM FIRE ,AI AkM f FE ALARM • Model Series 4008,4010,4100U,4020,4100,and BREAK GLASS PUSH 4120 fire alarm control panels equipped with either 631 PULL _ ANN IDNet or MAPNET II communications l KEY rit • OPERATED • • • Model Series 2120 Communicating Device .-, ONLY Transponders(CDTs)equipped with MAPNET II communications s "'k" rss.Y,Ptex Simplex Compact construction: 4099-9002 4099-9003 With 2099-9828 • Electronics module enclosure minimizes dust Breakglass Push Institutional infiltration Cover kit EM • Allows mounting in standard electrical boxes ' • Screw terminals for wiring connections Activation of the Simplex 4099-9001 single manual station requires a firm downward pull to activate the Tamper resistant reset key lock (keyed same as alarm switch.Completing the action breaks an internal Simplex fire alarm cabinets) plastic break-rod(visible below the pull lever,use is Multiple mounting options: optional).The use of a break-rod can be a deterrent to vandalism without interfering with the minimum pull • Surface or semi-flush with standard boxes or requirements needed for easy activation. The pull lever matching Simplex boxes latches into the alarm position and remains extended out • Flush mount adapter kit of the housing to provide a visible indication. • Adapters are available for retrofitting to commonly Double Action Stations(Breakglass) require the available existing boxes operator to strike the front mounted hammer to break the Description glass and expose the recessed pull lever.The pull lever then operates as a single action station. The Simplex model 4099-9001 addressable station Double Action Stations(Push Type) require that a combines the familiar Simplex manual station housing spring loaded interference plate(marked PUSH)be with a compact communication module that is easily pushed back to access the pull lever of the single action installed to satisfy demanding applications. Its integral station. individual addressable module(IAM)constantly monitors Station reset requires the use of a key to reset the status and communicates changes to the connected control manual station lever and deactivate the alarm switch.(If panel via IDNet or MAPNET II communications wiring. the break-rod is used,it must be replaced.) • Refer to page 2 for specific model listings.This product has been approved by the Station testing is performed by physical activation of California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health the pull lever.Electrical testing can be also performed b and Safety Code.See CSFM Listing 7150-0026:224 for abwable values and for conditions p g P by concerning material presented In this document.It is subject to re-examination,revision, unlocking the station housing to activate the alarm switch. and possible canceiatbn.Accepted for use—City of New York Department of Buildings— MEA35-93E.Additional listings may be appicable:contact your bcal Simplex product "IDNet and MAPNET II addressable communications designs are protected by U.S. suppler for the latest status.Listings and approvals under Simplex Time Recorder Co.are Patent No.4,796,025;5,966,002;and 6,034,601. g y the property of Tyco Safety Products Westminster S4099-0001-7 5/2006 Addressable Manual Station Product Selection Addressable Manual Stations,Red Housing with White Letters and White Pull Lever Model Description Housing Pull Lever Listings 4099-9001 Single action,English FIRE ALARM PULL DOWN UL,ULC, FM,CSFM,MEA 4099-9001CB Single action,Bilingual English and French FEU FIRE TIREZ PULL ULC,FM 4099-9001CF Single action,French ALARME FEU ABAISSEZ 4099-9002 Double action,Breakglass operation, English FIRE ALARM PULL DOWN UL, ULC, FM,CSFM,MEA 4099-9003 Double action,Push operation,English Accessories Model Description 2975-9178 Surface mount steel box,red 2975-9022 Cast aluminum surface mount box,red Refer to page 3 for dimensions 2099-9813 Semi-flush trim plate for double gang switch box,red Typically for retrofit, refer to page 4 2099-9814 Surface trim plate for Wiremold box V5744-2.red 2099-9819 Flush mount adapter kit,black Refer to page 4 for details 2099-9820 Flush mount adapter kit,beige 2099-9803 Replacement breakglass 2099-9804 Replacement break-rod 2099-9828 Institutional cover kit for field installation on 4099-9001 rimmem Power and Communications IDNet or MAPNET II communications, 1 address per station Address Means Dipswitch,8 position Wire Connections Screw terminal for in/out wiring,for 18 to 14 AWG wire UL Listed Temperature Range 32°to 120°F(0°to 49°C)intended for indoor operation Humidity Range Up to 93%RH at 100°F(38°F) Housing Color Red with white raised lettering Material Housing and pull lever are Lexan®polycarbonate or equal Pull Lever Color White with red raised lettering Housing Dimensions 5"H x 3-3/4"W x 1"D(127 mm x 95 mm x 25 mm) • • - • • - u • , • S '• , Semi-Fl h t o 1 . • Single Gang Box Mount 4"Square Box Mount Single gang box,2-1/2"deep 4"(102 mm)square box,2-1/8"(54 mm)minimum (64 mm),RACO#500 or equal depth,RACO#231 or equal(supplied by others) (supplied by others) I Mount flush or with ■ 1/16"(2 mm) maximum extension 11° DO NOT RECESS 4"Square box with cover plate Station FIRE ALARM side view Single gang cover plate,3/4" (19 mm)extension,RACO#773 • L PULL DOWN or equal(supplied by others) Single gang box outline Wall surface Semi-Flush Mount Side View pampa* 2 S4099-0001-7 5/2006 .. . - • . • 11 . 1 .I t• .oi ■ • • 11 . a 'sq 2975-9178 Box 2975-9022 Cast Box Preferred Mounting. For 5-3/16"H x 4"W x 2-3/16"D 5"H x 3-7/8"W x 2-3/16"D (132 mm x 102 mm x 56 mm) (127 mm x 98 mm x 56 mm) surface mounting of these (ordered separately) (ordered separately) addressable manual stations, the preferred electrical boxes are shown in the illustration to the right. o 0 Additional Mounting Knockouts located Reference. Refer to page 4 for top and bottom Wiremold box mounting compatibility. '. 1ALARM 0 PULL DOWN ■ o 1 Acc s for 3/4"threaded 5" conduit located top and bottom (127 mm) 0 Simplex v 1"(25.4 mm) 4099 Series Addressable Manual Station Surface Mount Side View with Internal Detail Application Reference Refer to NFPA 72,the National Fire Alarm Code,and all applicable local 1-1/4" codes for complete requirements for (32 mm) Simplex 2975-9178 box Field wiring / (shown for reference) manual stations.The following (shown for reference)\I summarizes the basic requirements. 1. Stations shall be located in the normal path of exit and distributed in the protected area such that they Address setting under t are unobstructed and readily resealable label(accessible accessible. with cover open) 2-5/8" 2. Mounting shall be with the (67 mm) operable part not less than 3-1/2 ft (1.1 m)and not more than 4-1/2 ft Station cover ` (1.37 m)above floor level. 11 III hinges open for installation access 3. At least one station shall be - \ provided on each floor.Additional Switch wiring stations shall be provided to obtain / (prewired) a travel distance not more than 200 ft(61 m)to the nearest station from any point in the building. 4. When manual station coverage appears limited in any way, additional stations should be installed. 3 S4099-0001-7 5/2006 Addressable Manual Station, Additional Mounting Information For retrofit and new installations, additional • ` ' ' Wiremold compatible mounting boxes sc cog receptacle box and the required adapter plates 2099-9814 Surface trim model V5744-2 for Wiremold box (supplied by are shown in the illustration to 5-1/8"H x 5"W others) the right. (130 mm x 127 mm) O ) 9 O Two gang switch box,each 3"H x 2"W x 2-3/4"D FIRE (0 ALARM (76 mm x 51 mm x 70 mm) (supplied by others) 4099-9001 IDNet PULL DOWN (al pp addressable station l ®O oA U � 59Ynpha �o 2099-9813 Semi-flush trim for 2 gang ) E "J switch box,6"H x 4-1/2"W (152 mm x 114 mm) Addressable Manual Station, Flush Mounting Information Flush mount adapter kit 2099-9819,Black 2099-9820,Beige N Box must be recessed into wall 1"to 1-118"(25.4 mm to 29 mm) FIRE I�4:a ALARM / 8" (203 mm) Hole cutout must be a 6" PULL DOWN minimum of 6"H by 5"W (152 mm by 127 mm) (152 mm) i Sl nplex 4-11116"(119 mm) square box,2-1/8" (54 mm)minimum Wall depth(by others) • 4-3/4"(121 mm) 6-3/4"(171 mm) 6.1 surface Front View Side View 7}•co.Simplex,the Simplex logo.MAPNET II.and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S.and/or other countries.NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association(NFPA). Lexan is a trademark of the General Electric Co.Wiremold is a trademark of the Wiremold Company. El Simplex Tyco Safety Products Westminster•Westminster,MA•01441-0001 •USA S4099-0001-7 5/2006 www.tycosafetyproducts-usa-wm.corn ;2006 Tyco Safety Products Westminster.All rights reserved.All specifications and other information shown were current as ofdocument revision date and are subject to change without notice. f3_,Simplex True Alarm Analog Sensing UL, ULC, CSFM Listed; FM Approved; TrueAlarm Analog Sensors — Photoelectric, MEA (NYC) Acceptance* Ionization, and Heat; Standard Bases and Accessories Features TrueAlarm®analog sensing provides: • Digital transmission of analog sensor values via IDNetTM or MAPNET II®two-wire communications** For use with the following Simplex®products: • 4010 and 4100U Series control panels;and 4008 Series I Ig control panels with reduced feature set(refer to data sheet S4008-0001 for details) • 4020,4100,and 4120 Series control panels,Universal Transponders and 2120 TrueAlarm CDTs equipped for 4098-9714 TrueAlarm Photoelectric MAPNET II operation Sensor Mounted in Base Fire alarm control panel provides: • Peak value logging allowing accurate analysis of each Descri stion sensor for individual sensitivity selection Sensitivity monitoring satisfying NFPA 72®sensitivity Digital Communication of Analog Sensing. • it TrueAlarm analog sensors provide an analog testing requirements;automatic individual sensor measurement digitally communicated to the host control calibration check verifies sensor integrity panel using Simplex addressable communications.At the • Automatic environmental compensation,multi-stage control panel,the data is analyzed and an average value is • alarm operation,and display of sensitivity directly in determined and stored.An alarm or other abnormal percent per foot condition is determined by comparing the sensor's present • Ability to display and print detailed sensor information value against its average value and time. in plain English language Intelligent Data Evaluation.Monitoring each sensor's Photoelectric smoke sensors provide: average value provides a continuously shifting reference Seven levels of sensitivity from 0.2%to 3.7% point.This software filtering process compensates for • environmental factors(dust,dirt,etc.)and component Heat sensors provide: aging,providing an accurate reference for evaluating new • Fixed temperature sensing activity. With this filtering,there is a significant reduction • Rate-of-rise temperature sensing in the probability of false or nuisance alarms caused by • Utility temperature sensing shifts in sensitivity,either up or down. Ionization smoke sensors provide: Control Panel Selection.Peak activity per sensor is • Three levels of sensitivity;0.5%,0.9%,and 1.3% stored to assist in evaluating specific locations.The alarm set point for each TrueAlarm sensor is determined at the General features: host control panel,selectable as more or less sensitive as • UL listed to Standard 268 the individual application requires. • Louvered smoke sensor design enhances smoke Timed/Multi-Stage Selection. Sensor alarm set points capture by directing flow to chamber;entrance areas can be programmed for timed automatic sensitivity are minimally visible when ceiling mounted selection(such as more sensitive at night,less sensitive • Designed for EMI compatibility during day). Control panel programming can also provide multi-stage operation per sensor. For example,a 0.2% • Magnetic test feature is provided level may cause a warning to prompt investigation while a • Optional accessories include remote LED alarm 2.5%level may initiate an alarm. indicator and output relays Sensor Alarm and Trouble LED Indication. Each Additional base reference: sensor base's LED pulses to indicate communications • For isolator bases,refer to data sheet S4098-0025 with the panel.If the control panel determines a sensor is • For sounder bases,refer to data sheet 54098-0028 in alarm,or is dirty or has some other type of trouble,the • For photo/heat sensors,refer to data sheet S4098-0024 details are annunciated at the control panel and that sensor (single address)and S4098-0033(dual address) base's LED will be turned on steadily.During a system These products have been approved by the California State Fire Marshal(CSFM)pursuant to alarm,the control panel will control the LEDs such that Section 13144.1 of the California Health and Safety Code.See CSFM Listings an LED indicating a trouble will return to pulsing to help 7272-0026:218,7271-0026:231,7270-0026:216,and 7300-0026217 for allowable values identify the alarmed sensors. and/or conditions concerning material presented in this document It is subject to reexamination,revision,and possible cancellation.Accepted for use—City of New York "TrueAlarm analog sensors are protected by one or more of the following U S Patents Department of Buildings—MEA35-93E.Additional listings may be applicable.contact your 5,155,468;5,173,683;5400,014;5,543,777;5,710,541;0383,407:13388.352,0392,573. local Simplex product supplier for the latest status.Listings and approvals under Simplex MAPNET II and IDNet addressable communications designs are protected by U S Patent Time Recorder Co.are the property of Tyco Safety Products Westminster No 4,796,025. S4098-0019-12 8/2008 TrueAlarm Sensor Bases and Accessories Descri•tion Sensor Base Features TrueAlarm sensor bases contain integral addressable - electronics that constantly monitor the status of the Base mounted address selection: detachable photoelectric,ionization,or heat sensors. Each • Address remains with its programmed location sensor's output is digitized and transmitted to the system - • Accessible from front(DIP switch under sensor) fire alarm control panel every four seconds. General features: Since TrueAlarm sensors use the same base,different • Automatic identification provides default sensitivity sensor types can be easily interchanged to meet specific when substituting sensor types location requirements.This feature also allows intentional • Integral red LED for power-on(pulsing),or alarm or sensor substitution during building construction. When trouble(steady on) conditions are temporarily dusty,instead of covering the • Locking anti-tamper design mounts on standard outlet smoke sensors(causing them to be disabled),heat sensors box may be installed without reprogramming the control panel. Although the control panel will indicate an • Magnetically operated functional test incorrect sensor type,the heat sensor will operate at a Sensor Bases default sensitivity providing heat detection for building protection at that location. 4098-9792,Standard sensor base 4098-9789,Sensor base with wired connections for: Mountln• Reference • 2098-9808 Remote LED alarm indicator or 4098-9822 relay(unsupervised) Electrical Box Requirements:(boxes are by others) 4098-9791,Sensor base with supervised relay driver Without relay:4"octagonal or 4'square,1-1/2'deep: output(not compatible with 2120 CDT): single gang,2"deep • Relay operation is programmable and can be manually With relay:4"octagonal or 4"square,1-1/2"deep, operated from control panel with 1-1/2"extension ring • Use with remote mount 2098-9737 relay 4"(102 mm)Square Box 4"(102 mm)Octagonal Box • Also includes wired connections for remote LED alarm Surface mount reference i indicator or 4098-9822 relay Sensor Base O•tions 2098-9737,Remote or local mount supervised relay: - f ` 1 • DPDT contacts for resistive/suppressed loads,power 1-1/2"(38 mm) minimum box depth limited rating of 3 A @ 28 VDC;non-power limited Flush mount reference,mount even with final rating of 3 A @ 120 VAC(requires external 24 VDC surface,or with up to 1/4"(6.4 mm)maximum recess Coil power) 2098-9737 Relay(mounts in 4098-9822 Relay(mounts 4098-9822,LED Annunciation Relay: base electrical box or remotely) in base electrical box) • Activates when base LED is on steady,indicating local alarm or trouble 11111110 IMO • DPDT contacts for resistive/suppressed loads,power ■ I 11� limited rating of 2 A @ 28 VDC;non-power limited III �i�� ���'�' rating of 1/2 A @ 120 VAC,(requires external 24 VDC coil power) 4098-9832,Adapter plate: Relay Size: 2-1/2"X 1-1/2"X 1"(3.75 cubic inches) (64 mm X 38 mm X 25.4 mm) • Required for surface or semi-flush mounting to NOTE:Review total wire count,wire size,and accessories 4"square electrical box and for surface mounting to being wired to determine required box volume. 4"octagonal box • Can be used for cosmetic retrofitting to existing 6-3/8- I• 6-3/8"(162 mm) •i diameter base product --' - 2098-9808,Remote red LED Alarm \ 4098-9832 Adapter Plate,required for 1/4" mounting to surface mounted boxes Indicator: n (6.4 mm) and 4 mama flush box • Mounts on single gang box ALARM- (shown in illustration to right) 4a/a•(124 mm) .1 15/16" (24 mm) 0 J 03lmplosr TrueAlarm Bases 4098-9789,-9791,&-9792 2 S4098-0019-12 8/2008 TrueAlarm Sensors 4098-9714 Photoelectric Sensor Features TrueAlarm photoelectric sensors use a stable,pulsed Sealed against rear air flow entry infrared LED light source and a silicon photodiode Interchangeable mounting receiver to provide consistent and accurate low power smoke sensing. Seven levels of sensitivity are available EMI/RFI shielded electronics for each individual sensor,ranging from 0.2%to 3.7%per Heat sensors: foot of smoke obscuration. Sensitivity is selected and • Selectable rate compensated,fixed temperature monitored at the fire alarm control panel. sensing with or without rate-of-rise operation The sensor head design provides 360°smoke entry for • Rated spacing distance between sensors: optimum response to smoke from any direction. Due to its Fixed Temp. UL&ULC FM Spacing,Either Fixed photoelectric operation,air velocity is not normally a Setting Spacing Temperature Setting factor,except for impact on area smoke flow. 135°F 80 ft x 60 ft 20 ft x 20 ft(6.1 m)for fixed (57.2°C) (18.3 m) temperature only;RTI=Quick . 4-718'(124 mm) 0,' - 50 ft x 50 ft(15.2 m)for fixed I I 155°F 40 ft x 40 ft temperature with either rate-of-rise _ (68°C) (12.2 m) selection;RTI=Ultra Fast LED status Indicator - Smoke Sensors: 2-1/8'' (54 mm) • Photoelectric or ionization technology sensing ), • 360°smoke entry for optimum response • Built-in insect screens 4098-9733 Heat Sensor 4098-9714 Photoelectric Sensor with Base TrueAlarm heat sensors are self-restoring and provide rate 4098-9717 Ionization Sensor compensated,fixed temperature sensing,selectable with . Due to its TrueAlarm Ionization sensors use a single radioactive or without rate-of-rise temperature sensing small thermal mass,the sensor accurately and quickly source with an outer sampling ionization chamber and an measures the local temperature for analysis at the fire inner reference ionization chamber t o provide stable alarm control panel. operation under fluctuations in environmental conditions . such as temperature and humidity. Smoke and invisible Rate-of-rise temperature detection is selectable at the combustion gases can freely penetrate the outer chamber. control panel for either 15°F(8.3°C)or 20°F(11.1°C) With both chambers ionized by a small radioactive source per minute. Fixed temperature sensing is independent of [Am 241 (Americium)],a very small current flows in the rate-of-rise sensing and programmable to operate at circuit.The presence of particles of combustion will cause 135°F(57.2°C)or 155°F(68°C). In a slow developing a change in the voltage ratio between chambers.This fire,the temperature may not increase rapidly enough to difference is measured by the electronics in the sensor operate the rate-of-rise feature. However,an alarm will be base and digitally transmitted back to the control panel for initiated when the temperature reaches its rated fixed processing. temperature setting. Three levels of sensitivity are available for each TrueAlarm heat sensors can be programmed as a utility ionization sensor: 0.5,0.9,and 1.3%per foot of smoke device to monitor for temperature extremes in the range obscuration. from 32°F to 155°F(0°C to 68°C).This feature can provide freeze warnings or alert to HVAC system 4-716•(124 mm) problems.Refer to specific panels for availability. A 4-7/8'(124 mm) • 0"1---LED status indicator 2-1/8" j (54 mm) � - I � 1 I "1---LED Status Indicator - 2-3/8' V (BO mm) .I„IIIIII' 4098-9717 Ionization Sensor with Base I �' Application Reference Sensor locations should be determined only a fter careful 4098-9733 Heat Sensor with Base consideration of the physical layout and contents of the area to be protected.Refer to NFPA 72,the National Fire Alarm Codes.On smooth ceilings,smoke sensor spacing WARNING: In most fires, hazardous levels of smoke of 30 ft(9.1 m)may be used as a guide. For detailed and toxic gas can build up before a heat detection application information,refer to 4098 Detectors, Sensors, device would initiate an alarm. In cases where Life Safety is a factor, the use of smoke detection is highly and Bases Application Manual(574-709). recommended. 3 S4098-0019-12 8/2008 TrueAlarm Analog Sensing Product Selection Chart TrueAlarm Sensor Bases* Model Description Compatibility Mounting Requirements 4098-9792 Standard Sensor Base,no options Sensors 4098-9714,-9733,&-9717 4"octagonal h: r in single gang square box,min.depth min. depth;or single gang box,2"min.depth Sensor Base with connections for Sensors 4098-9714,-9733,&-9717 4098-9789 Remote LED Alarm Indicator or 2098-9808 remote LED alarm Unsupervised Relay indicator or 4098-9822 relay 4"octagonal or 4"square box Sensor Base with connections for Sensors 4098-9714,-9733,&-9717 Note:Box depth requirements depend Supervised Remote Relay and 2098-9737 remote relay(supervised) on total wire count and wire size,refer to 4098-9791 connections for Remote Alarm accessories list below for reference. connections n for Remote Alarm rm 2098-9808 remote alarm indicator or 4098-9822 relay(unsupervised) TrueAlarm Sensors Model Description Compatibility Mounting Requirements 4098-9714 Photoelectric Smoke Sensor 4098-9717 Ionization Smoke Sensor Bases 4098-9792,4098-9789, Refer to base requirements and 4098-9791 4098-9733 Heat Sensor TrueAlarm Sensor/Base Accessories Model Description Compatibility Mounting Requirements Remote Mounting requires 4"octagonal or Supervised Relay.mounts remote 4"square box, 1-1/2"minimum depth 2098-9737 or in base electrical box For use with 4098-9791 base Base Mounting requires 4"octagonal box, 2-1/8"deep with 1-1/2"extension ring 2098-9808 Remote Red LED Alarm Indicator Single gang box, 1-1/2"minimum depth on single gang stainless steel plate Relay,tracks base LED status Bases 4098-9789 and 4098-9791 4098-9822 (unsupervised,mounts only in base 4"octagonal box,2-1/8"deep with 1-1/2" electrical box) extension ring Required for surface or semi-flush 4098-9832 Adapter Plate Bases 4098-9792,-9789,&-9791 mounted 4"square box and for surface mounted 4"octagonal box •Refer to Installation Instructions 574-707 and Application Manual 574-709 for additional information. S•ecifications General Operating Specifications Communications and Sensor Supervisory Power MAPNET II or IDNet,auto-select,24-40 VDC w/data,400 uA typical, 1 address per base Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG(0.82 mm 2 to 2.08 mm2) Remote LED Alarm Indicator Current 1 mA typical,no impact to alarm current Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG(0.82 mm 2) UL Listed Temperature Range 32°to 100°F(0°to 38°C) Operating with 4098-9717 or 4098-9733 32°to 122°F(0°to 50°C) Temperature Range with 4098-9714 15°to 122'F(-9°to 50°C) Humidity Range 10 to 95%RH Smoke Sensor 4098-9714, Photoelectric Sensor Air velocity=0-2000 ft/min(0-610 m/min) Ambient Ratings 4098-9717. Ionization Sensor Air velocity=0-200 ft/min(0-61 m/min),Altitude is up to 8000 ft(2.4 km) Housing Color Frost White 4098.9791 Base With Supervised Remote Relay 2098-9737(see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC(nominal 24 VDC) Supervisory Current 270 fiA,from 24 VDC supply Alarm Current with 2098-9737 Relay 28 mA,from 24 VDC supply 4098-9822 Unsupervised Relay,Requirements for Bases 4098-9789 and 4098-9791 (see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC(nominal 24 VDC) Supervisory Current Supplied from communications Alarm Current 13 mA from separate 24 VDC supply Two is a registered trademark of Tyco International Services GMBN and is used under license. Simplex,the Simplex logo, TrueAlarm,IDNet.and MAPNET II are trademarks of Tyco International Ltd.and its affiliates and are used under license.NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA) f3 Simplex Tyco Safety Products Westminster•Westminster, MA •01441-0001 •USA S4098-0019-12 8/2008 ® www.tycosafetyproducts-usa-wm.com 2005 Tyco Safety Products Westminster.All rights reserved.All specifications and other information shown were cu rent as of document revision date and are subject to charge without notice. .Simplex Multi-Application Peripherals UL, ULC Listed; FM, CSFM, IDNetTM Communicating Devices and MEA (NYC) Approved* Model 4090-9002 Relay IAM MIMI -oo�-rau IDNet addressable interface modules**for use �Cr Qo , "°N, Qo with Simplex- models 4010 and 4100U fire alarm �� L j ' ' control panels , 4090-9002, Individual Addressable Relay Module (Relay IAM): • A single addressable point provides control and 0 .Y.I Cam XJ status tracking of a Form "C" contact ", • Low power latching relay design allows IDNet ~,''` communications to supply both data and module r \ r I power ` U ©° 0 J Compact, sealed construction: • Enclosed design minimizes dust infiltration 4090 Series IDNet Relay IAM Package (shown approximately 1/2 size) • Mounts in standard 4"square electrical box • Screw terminals for wiring connections • Visible LED flashes to indicate communications PISTREPREI • Optional covers are available to allow LED to be (Refer to Installation Instructions 574-184 for additional viewed after installation information.) UL listed to Standard 864 Communications 4010 or 4100U IDNet,1 address per device rinallAIMI Relay IAM Power Supplied by IDNet communications IDNet Relay IAMs allow fire alarm control panels to Type Form C,SPDT control a remotely located Form"C"contact using 1DNet 2 A @ 24 VDC,for transient addressable communications for both data and module Contact Power-Limited suppressed loads power. Typical applications would be for switching local Ratings 1 A @ 24 VDC for inductive loads power for control functions such as elevator capture,or 1/2 A @ 120 VAC,for transient control of HVAC components,pressurization fans, Nonpower-Limited suppressed loads dampers,etc. Relay status is also communicated requiring only one device address. Wire Connections Screw terminals for in/out wiring, 18 to 14 AWG wire(0.82 to 2.08 mm2) MINTIMBEll Up to 2500 ft(762 m)from fire alarm Model I Description control panel 4090-9002 11 Relay IAM IDNet Wiring Reference Up to 10,000 ft(3048 m)total wiring distance(including T-Taps) Optional Trim Plates Compatible with Simplex 2081-9044 Model Description Overvoltage Protectors 4090-9801 Trim plate with LED For semi-flush 4-1/8'H x 4-1/8"W x 1-3/8"D viewing window,includes mounted box Dimensions (105 mm x 105 mm x 35 mm) mounting screws; For surface 4090-9802 galvanized steel mounted box Housing Material Black thermoplastic Mounting Plate Material Sheet metal,galvanized Temperature Range 32°to 120°F(0°to 49°C), ' This product has been approved by the California Slate Fire Marshal(CSFM)pursuant to intended for indoor operation Section 13144.1 of the California Health and Safety Code.See CSFM Listing Humidity Range Up to 93%RH at 100°F(38°C 7300-0026:223 for allowable values and/or conditions concerning material presented in this ty g P ( C) document It is subject to re-examination,revision,and possible cancellation.Accepted for use—City of New York Department of Buildings—MFA35-93E.Additional listings may be °°IDNet addressable communications are protected by U.S.Patent No.4,796,025. applicable;contact your local Simplex product supplier for the latest status.Ustings and approvals under Simplex lime Recorder Co.are the property of Tyco Safety Products Westminster. S4090-0002-6 2/2004 C• SI1 11 • S • • • - 0 0 bAddress setting under resealable label ' � ,.ko 1 ,,,, ,.._ m O. ...„,.., ,......,,,,,,,2#00„,.., WI ^� tom. �I�► i i 4"(102 mm)square box,2-1/8" N' - li "-� (54 mm)minimum depth,RACO \ I t:› I 232 or equal(supplied by others) i 4090-9002 Relay IAM Double gang blank cover plate and mounting screws,for use when LED is not required to be externally viewed (supplied by others) Mounting Reference, Double Gang Blank Cover Plate /- © © O © Light pipe for LED viewing 4-9/16" 4-5/16" (118 mm) 1 8I (109 mm) omicT Pole 1 C 4EC DOWER BEFORE SERVING BEFORE*MG 0 Q 0 0 . `, / 14 4-9/16"(116 mm) Id F 4-5/16"(109 mm) •1 4090-9801,Trim plate for 4090-9802,Trim plate for semi-flush mounted box surface mounted box - Optional Trim Plates for Visible LED 71'co,Simplex.the Simplex logo,and ID Net are trademarks of Tyco International AG or its affiliates in the U.S and'or other countries. f3 Simplex Tyco Safety Products Westminster•Westminster,MA•01441-0001 •USA S4090-0002-6 2/2004 www.tycosafetyproducts-usa-wm.com ©2004 Tyco Safety Products Westminster.All rights reserved All specifications and other information shoran Isere current as of document revision date and are subject to change„ithma notice. 511'1''1X Multi-Application Peripherals UL, ULC, CSFM Listed; FM Approved; IDNetTM or MAPNET II®Communicating Devices MEA (NYC)Acceptance* 4090-9101 and 4090-9106, Zone Adapter Modules Features IDNet or MAPNET II communications**compatible n (� Monitor ZAMs(Zone Adapter Modules) provide an O O v addressable interface to a conventional initiating device circuit(IDC) L J Available for Class B or Class A IDCs: 6 • 4090-9101, Class B (Style B)monitoring for 2-wire iiithr or 4-wire initiating devices,with power reset na connections for 4-wire devices • 4090-9106,Class A(Style D)monitoring for 2-wire r ° , initiating devices • Zone device power is supplied separately(typically 0 0 C from fire alarm control panel) • Refer to device compatibility list on page 2 4090 Series ZAM Package For use with following Simplex control panels: (shown approximately 1/2 size) • Model Series 4008,4010,and 4100U fire alarm control panels for IDNet communications • Model Series 4100/4100U,4120,4020,and 2120 Communicating Device Transponders(CDTs) S•ecifications equipped with MAPNET II communications IDNet or MAPNET II,1 address per Communications device Compact, sealed construction: • Enclosed design minimizes dust infiltration ZAM Input Voltage 18,9 to 32 VDC(nominal 24 VDC) • Mounts in standard 4"square electrical box Supervisory=16 mA maximum Alarm=72 ZAM Current @ 24 VDC tnA maximum • Screw terminals for wiring connections (actual current is determined by total • Visible LED flashes to indicate communications device requirements) • Optional covers are available to allow LED to be 4090-9101 ZAM,Zone 3.3 ko, 1 W viewed after installation Supervision Resistor Screw terminals for in/out wiring, • UL listed to Standard 864 Wire Connections 18 to 14 AWG wire(0.82 to 2.08 mm2) Up to 2500 ft(762 m)from fire alarm Description control panel IDNet/MAPNET II Monitor ZAMs allow a single IDNet or MAPNET II Up to 10,000 ft(3048 m)total wiring addressable point to monitor a conventional initiating Wiring distance(including T-Taps) device circuit(IDC)populated with 2-wire or 4-wire Compatible with Simplex 2081-9044 initiating devices. Refer to page two for compatible Overvoltage Protectors devices. 4-1/8"H x 4-1/8"W x 1-3/8"D Dimensions (105 mm x 105 mm x 35 mm) • This product has been approved by the California Stale Fire Marshal(CSFM)pursuant to Housing Material Black thermoplastic Section 13144.1 of the California Heath and Safely Code.See CSFM Listing Mounting Plate Material Sheet metal,galvanized 7300-0026:223 for alowable values and/or conditions concerning material presented In this document.It is subject to re-examination,revision,and possible cancelatlon.Accepted for 32°to 120°F(0°to 49°C) use—City of New York Department of Buitlings—MEA3S-93E.Additional Istings may be Temperature Range intended for indoor operation applicable;contact your local Simplex product supplier for the latest status.Listings and p approvals under Simplex Time Recorder Co.are the property of Tyco Safety Products Humidity Range Up to 93%RH at 100°F (38°C) Westminster. • IDNet and MAPNET II addressable communications are protected under U.S.Patent Nos.4,796,025;5,966,002;and 6,034,601. 54090-0003-2 2/2006 Product Selection ZAM Modules Model Number Description 4090-9101 Zone Adapter Module for Class B monitoring of 2-wire or 4-wire initiating devices;with power reset connections for 4-wire devices 4090-9106 Zone Adapter Module for Class A monitoring of 2-wire initiating devices Optional Trim Plates Model Number Description 4090-9801 For semi-flush mounted box Trim plate with LED viewing window, includes mounting screws; 4090-9802 For surface mounted box galvanized steel End-of-Line Resistor Harness Model Number Reference No. Description 4081-9002 733-893 3.3 kc, 1 End-of-Line Resistor Harness for 4090-9101, Class B zone monitoring Monitor ZAM Two-Wire Initiating Device Compatibility Reference Chart Description Model Number Compatible Maximum Bases Quantity Direct connect photoelectric smoke detector 2098-9209 4098-9401 No base 4098-9402 required 20 4098-9403 4098-9404 Electronic heat detectors 4098-9612 4098-9788 4098-9613 — 20 4098-9614 4098-9684 4098-9615 4098-9683 1 4098-9601 4098-9788 20 Photoelectric smoke detectors 4098-9602 4098-9605 4098-9683 1 Ionization smoke detector 4098-9603 4098-9788 20 4098-9683 1 Duct detector housing with 4098-9601 detector 4098-9685 N.A. 20 Reference for Existing Equipment 2098-9201 2098-9211 20 Smoke detectors 2098-9202 2098-9203 2098-9576 2098-9637 1 4098-9407 Electronic heat detectors 4098-9408 2098-9211 20 4098-9409 4098-9410 NOTES: 1. Four-wire detector operation is compatible with conventional listed contact closure initiating devices. 2. Four-wire detectors require detector voltage to be connected to resettable power terminals. 3. Refer to installation instructions 574-183,and field wiring diagram 842-073 for additional information. 4. Contact your local Simplex product supplier for additional compatible devices. 2 S4090-0003-2 2/2006 ZAM Mountin• Information }`i IP 110000111 0 Address setting under i\� 0 resealable label ' o, , i iii„ , ,'t.4, 0 . 0 0 J 4”(102 mm)square box,2-1/8" t I (54 mm)minimum depth,RACO 1 1 232 or equal(supplied by others) 4090-9101/9106 ZAM ) Double gang blank cover plate and mounting screws,for use when LED is not required to be externally viewed s ' (supplied by others) Mounting Reference, Double Gang Blank Cover Plate • i • O © 1 © © Light pipe for LED viewing 4-9/16" 4-5/16" (116 mm) (109 mm) 0 O O O O w - _ 'J , V l• 4-9/16"(116 mm) 01 • 4-5/16"(109 mm) •1 4090-9801,Trim plate for 4090-9802,Trim plate for semi-flush mounted box surface mounted box Optional Trim Plates for Visible LED 3 S4090-0003-2 2/2006 Tyco.Simplex,the Simplex logo,MAPNET ll.and 1DNet are trademarks of Tyco International Services AG or its affiliates in the U.S.and/or other countries. !'i S' Tyco Safety Products Westminster•Westminster,MA•01441-0001 •USA S4090-0003-2 2/2006 ® m x www.tycosafetyproducts-usa-wm.corn ©2006 Tyco Safety Products Westminster All rights reserved All specifications and oilier information shogun here current as of document revision date and are subject to change without notice. f3.Simplex Multi-Application Peripherals • UL, ULC, CSFM Listed; FM Approved; IDNetTM and MAPNET Il`' Communicating Devices, MEA (NYC) Acceptance* Individual Addressable Modules (IAMs) Features IDNet or MAPNET II addressable communications supply both data and power over a single wire pair Iniirnpiex x**. id.to provide .• Supervised Class B monitoring of normally open,dry contacts• Total wiring distance from IAM to supervision resistor(s)of up to 500 ft(152 m) • Monitored connection is compatible with Simplex® 2081-9044 Overvoltage Protectors for outdoor wiring or electrically noisy applications 4090-9001 Supervised IAM • For use in indoor locations up to 158°F(70°C)such as (shown approximately 3/4 size) attic spaces or similar applications For use with following Simplex control panels: • Model Series 4008,4010,and 4100U fire alarm control panels for IDNet communications • Model Series 4100/4100U,4120,4020,and 2120 - Communicating Device Transponders(CDTs)equipped with MAPNET II communications Model 4090-9001: • Enclosed design minimizes dust infiltration • Mounts in standard single gang electrical box • Screw terminals for wiring connections -r • Visible LED flashes to indicate communications • Optional covers are available to allow LED to be 4090-9051 Supervised IAM viewed after installation(requires mounting bracket, (shown approximately 3/4 size) ordered separately) Model 4090-9051: • Encapsulated design for extended exposure to high Descri.tion humidity(LED is not present on this model) • Color coded 18 AWG leads for wiring Individual addressable modules(IAMs) receive IDNet communications provides current limited both power and communications from a two-wire monitoring: MAPNET II or 1DNet circuit.They provide location • Provides monitoring of tamper switch(supervisory) specific addressability to a single initiating device(such as single station smoke detector alarm contacts or heat and waterflow switch(alarm)on same circuit using detector contacts)or multiple devices at the same location one point by monitoring normally open dry contacts and the wiring • Available with IDNet communications only to an end-of-line resistor. Multiple operation modes are available and are selectable at the control panel: Model 4090-9001 is packaged in a thermoplastic • Contact closure status can be tracked housing and provides screw terminal connections and a status indicating LED. • Momentary contact closure conditions can be selected at the panel to be latched or tracked(not available with the Model 4090-9051 is an encapsulated package with wire 2120 CDT) leads.It does not provide a status indicating LED. UL listed to Standard 864 • These products have been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code.See CSFM Listing 7300-0026:223 for allowable values and/or conditions concerning material presented in this document It is subject to re-examination,revision,and possible cancellation.Accepted for ** IDNet and MAPNET II addressable communications are protected under U.S.Patent use—City of New York Department of Buildings—MEA35-93E.Additional listings may be Nos.4,796,025;5,966,002;and 6,034,601. applicable;contact your local Simplex product supplier for the latest status.Listings and approvals under Simplex Time Recorder Co.we the property of Tyco Safety Products Westminster. S4090-0001-9 8/2010 Operation Current Limited Operation Applications Contact Closure. Closure of the monitored contact(s) For use with IDNet communications only,these initiates an alarm or other response as programmed at the IAMB can provide quad-state sensing of normal,open fire alarm control panel. An open in the monitored circuit circuit,short circuit,and current limited conditions. wiring will cause a trouble to be reported. (Program type is"T-sense.")With the proper end-of-line Panel Selections. Selections can be made at the control and current limiting resistors,dual functions such as panel to maintain the alarm condition if the initiating tamper switch and waterflow switch monitoring can be device contacts are momentary,such as from a determined and communicated by a single addressable rate-of-rise heat detector,or to track the device contact point. status(not available with the 2120 CDT). IAM Product Selection Model Description 4090-9001 Supervised IAM,mounted in thermoplastic housing with screw terminals;see applicable options below 4090-9051 Supervised IAM,encapsulated with wire leads Optional Trim Plates and Mounting Bracket for Model 4090-9001 Model Description 4090-9806 For semi-flush mounted box Trim plate with LED viewing window,requires 4090-9810 mounting bracket, 4090-9807 For surface mounted box includes mounting screws;galvanized steel 4090-9810 Mounting bracket,mounts IAM to electrical box and provides screw holes for trim plate, required for optional trim plates End-of-Line Resistor Harnesses (ordered separately as required) Model Reference No. Description 4081-9004 733-886 6.8 kit, 1/2 W;Standard end-of-line resistor harness for N.O.contact supervision 4081-9003 733-896 4.7 kc2, 1/2 W Use for current limited monitoring applications 4081-9005 733-984 1.8 k12, 1/2 W S•ecifications Electrical Power and Communications MAPNET II or IDNet,auto selected, 1 address per IAM Input Requirements Normally open,dry contacts Screw terminals for in/out wiring, 18 to 14 AWG wire Wire Connections 4090-9001 (0.82 mm2 to 2.08 mm2) 4090-9051 Color coded wire leads, 18 AWG(0.82 mm2),8"long(203 mm) Installation Instructions 574-331 for 4090-9001;579-572 for 4090-9151 Reference Documents Field Wiring Diagrams 842-073 for IDNet operation;841-804 for MAPNET II operation Wiring Distances 500 ft(152 m)maximum without protectors Distance from IAM to Contacts 400 ft(122 m)maximum with 2081-9044 Overvoltage Protectors Wiring Distance Reference per channel,MAPNET II or 2500 ft(762 m)maximum from fire alarm control pa nel IDNet Communications 10,000 ft(3048 m)maximum total wiring distance(including T-Taps) Mechanical 4090-9001 1-9/16"W x 1-3/4"H x 1-1/4"D(40 mm x 44 mm x 32 mm) Dimensions 4090-9051 1-9/16"W x 1-9/16"H x 9/16"D(40 mm x 40 mm x 14 mm) Housing Material,4090-9001 Black thermoplastic Encapsulation Material,4090-9051 Epoxy,beige Temperature Range 32°to 158°F(0°to 70°C);intended for indoor operation Humidity Range Up to 93%RH at 100°F(38°C) 2 54090-0001-9 8/2010 Mountin• Information 4090-9001 IDNet =_� Field wiring shown supervised IAM mi. for reference T4! ø!JO ■ �i _ I�_ LED viewing port til {0 w ' •! �� ��� Single gang electrical ���'�0 box 2-1/2"(64mm) minimum depth (supplied by others) Address setting under resealable label Single gang blank cover plate and mounting screws,for use when LED is not required to be externally viewed(supplied by others) Mounting Reference, Single Gang Blank Cover Plate • _ .1 1 © 0 �o� O Light pipe for 0 3 LED viewing 4-1/4" 0 4-1/2" (108 mm) ; ! (114 mm) [ "I} C T r l'I �h�'r'EC_:`n 1ER EEC,iE S_kr_[\,c, t ) E 7 \.- i T \ `� y 2-1/2" i 2-13/16" �JI 41 00- (64 mm) E (72 mm) I 4090-9806,Trim plate for 4090-9807,Trim plate for 4090-9810 Mounting semi-flush mounted box surface mounted box bracket,ordered separately NOTE:These mounting plates require mounting bracket 4090-9810. Optional Trim Plates and Mounting Bracket for Visible LED 3 S4090-0001-9 8/2010 4090-9051 Mountin• Information Address setting is at rear of housing � . 4090-9051 I Encapsulated Supervised IAM I 0 Single gang electrical box 2-1/2"(64mm) minimum depth (supplied by others) Single gang blank cover plate and mounting screws(supplied by others) Tyco is a registered trademark of 7yco International Services GmbH and is used under license.Simplex,the Simplex logo.IDNet,and MAPNET I/are trademarks of Tyco International Ltd.and its affiliates and are used under license. g Simplex Tyco Safety Products Westminster•Westminster,MA•01441-0001 •USA S4090 0001-9 8/2010 www.tycosafetyproducts-usa-wm.com 2010 Two Safety Products Westminster.All rights reserved All specifications and other information shown acre current as ofdocu mem reruion date and are subject to change without notice. E Simplex TrueAlarm® Analog Sensing UL, ULC, CSFM Listed; FM Approved; Addressable Duct Sensor Housings with TrueAlarm MEA (NYC)Acceptance* Photoelectric Sensor; Available with Multiple Relay Control Features © �, Compact air duct sensor housing with clear cover to monitor for the presence of smoke** Includes factory installed TrueAlarm I : photoelectric smoke sensor and features: . • Individual sensor information processed by the host control panel to determine sensor status 0 0 • Digital transmission of analog sensor values via IDNetTM or MAPNET II®,2-wire communicationst • Programmable sensitivity,consistent accuracy, am_ t environmental compensation,status testing,and . monitoring of sensor dirt accumulation Model 4098-9755: • Basic duct sensor housing(no relay output)powered • by IDNet/MAPNET II communications Duct Sensor Housing, Front and Bottom View Model 4098-9756: • Duct sensor housing with supervised output for r multiple remote relays;requires separate 24 VDC; !'� includes one relay - • Relay output is under panel control •�"` • At the panel,relay output can be activated manually or ! �' in response to a separate alarm or other input 2098-9808 2098-9806 General features: Remote Status/Alarm Indicator and Test Station • UL listed to Standard 268A Introduction • Clear cover allows visual inspection Operation. Simplex'compact air duct smoke sensor • Test ports provide functional smoke testing access housings provide TrueAlarm operation for the detection of with cover in place smoke in air conditioning or ventilating ducts.Sampling • Mounts to rectangular ducts or round ducts; minimum tubes are installed into the duct allowing air to be directed to size is 8"(203 mm)square or 18"(457 mm)diameter the smoke sensor mounted in the housing. • Magnetic test feature for alarm initiation at housing TrueAlarm Sensor Operation • Optional weatherproof enclosure is available Digital Communication of Analog Sensing. separately(refer to data sheet S4098-0032) Analog information from the sensor is digitally Diagnostic LEDs(on interface board): communicated to the control panel where it is analyzed. • Red Alarm/Trouble LED for sensor status and Sensor input is stored and tracked as an average value communications polling display with an alarm or abnormal condition being determined by • Yellow LED for open or shorted trouble indication of comparing the sensor's present value against its average. supervised relay control(4098-9756 only) Intelligent Data Evaluation.Monitoring each Sampling tubes (ordered separately): photoelectric sensor's average value provides a software filtering process that compensates for environmental • Available in multiple lengths to match duct size factors(dust,dirt,etc.)and component aging,providing • Installed and serviced with housing in place an accurate reference for evaluating new activity.The Remote module options(ordered separately): result is a significant reduction in the probability of false • Remote red status/alarm LED(2098-9808) or nuisance alarms caused by shifts in sensitivity,either up or down. • Remote test station with LED(2098-9806) • 4098-9843 remote relays(refer to page 2 for details) ** Please note that smoke detection in air ducts is intended to provide Y ( P g ) notification of the presence of smoke in the duct.It is not intended • These products have been approved by the California State Fire Marshal(CSFM)pursuant to to,and will not,replace smoke detection requirements for open Section 13144.1 of the California Health and Safety Code See CSFM Listing 3240-0026 241 areas or other non-duct applications. for allowable values and/or conditions concerning material presented in this doc ument.It is subject to re-examination,revision,and possible cancellation.Accepted for use—City of New t TrueAlarm sensors and IDNet and MAPNET II communications are protected by one or York Department of Buildings—MEA35-93E.Additional listings may be applicable.contact more of the following U.S.Patents:5,155,468;5,173,683;5,543,777;5,400,014; your local Simplex product supplier for the latest status.Listings and approvals under Simplex 5,543,777;5,710,541;0383,407;D388,352;D392,573;4,796,025. Time Recorder Co.are the property of Tyco Safety Products Westminster S4098-0030-6 1/2009 TrueAlarm Sensor Operation (Continued) Photoelectric Sensing (Continued) Control Panel Selection. Peak activity per sensor is Typically duct sensor applications require less sensitive stored to assist in evaluating specific locations.The alarm settings(such as 2.5%per foot obscuration)due to the set point for each sensor is determined at the control ducts being a relative dirty environment. However,the panel,selectable as the individual application requires. standard seven levels of TrueAlarm sensor sensitivity are Sensor Status LED. Each sensor housing's red status available for each individual sensor,ranging from 0.2%to LED(located on the electrical interface board)pulses to 3.7/o per foot of smoke obscuration. Sensitivity is indicate communications with the panel. If the control selected and monitored at the fire alarm control panel. panel determines that a sensor is in alarm,or that it is Fire Alarm Control Panel Features dirty or has some other type of trouble,the details are annunciated at the control panel and that sensor housing's • Individual smoke sensitivity selection status LED will he turned on steadily. During a system • Sensitivity monitoring that satisfies NFPA 72 alarm,the control panel will control the LEDs such that sensitivity testing requirements an LED indicating a trouble will return to pulsing to help • Peak value logging allows accurate analysis for identify any alarmed sensors. (Remote Status/Alarm sensitivity selection LEDs track the operation of the sensor housing LED.) • Automatic,once per minute individual sensor Photoelectric Sensin s calibration check verifies sensor integrity TrueAlarm photoelectric sensors use a stable,pulsed • Automatic environmental compensation infrared LED light source and a silicon photodiode • Smoke sensitivity is displayed in percent per foot receiver to provide consistent and accurate low power • Ability to display and print detailed sensor smoke sensing. information in plain English language • Relays of model 4098-9756 are under panel control Duct Sensor Selection Chart for ON,OFF,or override Duct Smoke Sensor Housing with Photoelectric Sensor* Model Description Compatibility Simplex fire alarm control panel models 4008, 4098 9755 Basic Duct Sensor Housing;operating power is supplied by 4010,4100U,and legacy products 4020, either IDNet or MAPNET II communications(no relay output) 4100/4100+,and 4120.Also 2120 CDT if configured for MAPNET II,TrueAlarm operation Duct Sensor Housing with supervised multiple relay output, Same as above except relay operation is not 4098-9756 requires separate 24 VDC fire alarm power and 4081-9008 compatible with 2120 CDT; end-of-line resistor harness;includes one 4098-9843 relay Relay output is for up to 15 total 4098-9843 Relays(additional relays are ordered separately) Remote LED Indicator and Test Station, Select One if Required Model Description Compatibility Mounting 2098-9808 Red LED status indicator on single-gang stainless steel plate 4098 9755 Use single gang box, Test Station with keyswitch and red LED status indicator,on 3"H x 2"W x 2"D 2098-9806 single-gang stainless steel plate;(turning switch to"TEST" 4098-9756 (76 mm x 51 mm x 51 mm) initiates alarm for system testing) Epoxy Encapsulated Remote Relay and End-of-Line Resistor Model Description Compatibility Location Relay;single Form C(7 A @ 120 VAC);refer to pages 3 and 4 4098-9756 only; Locate relays within 3 ft 4098-9843 for additional relay information;one included with 4098-9756; (1 m)of device being wiring is 18 AWG(0.82 mm2)color coded wire leads connect up to 15 controlled per NFPA 72 4081 9008 End-of-Line Resistor Harness; 10 kf2,1/2 W;(ref.733-894); 4098-9756 At last relay location required to supervise remote relay coil connection 'Each duct housing includes an internally mounted model 4098-9714 TrueAlarm photoelectric sensor and an exhaust tube.A correctly sized sampling tube(ordered per application)is required,refer to chart below. Sampling Tube Selection Chart, Ordered Separately Per Duct Width, Select One Overall Duct Width Tube Required Suggested Cut Length 12"(305 mm) 2098-9796 1/2"(12.7 mm)longer than duct width 13"to 23"(330 mm to 584 mm) 2098-9804 1/2"(12.7 mm)longer than duct width 24"to 46"(610 mm to 1168 mm) 2098-9797 2"(51 mm)longer than duct width 46"to 71"(1168 mm to 1803 mm) 2098-9798 2"(51 mm)longer than duct width 71"to 95"(1803 mm to 2413 mm) 2098.9799 2"(51 mm)longer than duct width 2 S4098-0030-6 1/2009 Duct Sensor Housin. Detail Reference NOTE: Refer to Installation Instructions 574-776 for additional installation detail and maintenance information. 11-3/8"(289 mm) Exhaust tube access hole) .4—(Conduit(by others)) en O 0 ' 4098-9714 Smoke sensor,mounted • 6-3/4" in special interface base(supplied .. Y• Metal plate with dual holes (171 mm) ' �\�-- 0 for 3/4"(19 mm)conduit,plug T, .,_„ supplied for unused hole• 1 ill 11111 1 Front View . : 1 Iimi Yellow LED,relay control trouble indicator(4098-9756 only) Sampling tube access hole , I 0 ' Red sensor status LED (Side of duct 0 o Ci Wiring terminals (Stationary baffle(built-in) (Captive fastening screws(4) Magnetic test area NOTE:Orientation shown is for reference (Transparent c over) (Gasketed sensor area) only,refer to General Location Notes and / End View illustration below for alternate mounting reference. — 3-3/8" 1R� !_ I_____ ■(86 mm) ► Bottom view (Duct wall V 13/16" (21 mm) 11.1 Exhaust tube 4098-9843 Remote Relay 410\ ( (supplied) 4 // (7 A @ 120 VAC,for use with 4098-9756 only) Test ports(2)provided NOTE: Mount in separate electrical box within Sampling tube,ordered (Gaskets lied 3 ft(1 m)of device being controlled per (supplied)) for measuring airflow separately per duct width ( pp ) NFPA 72 and for aerosol injection --� 1-3/16" v;,(30 mm) 1-1/2" 13/16" f Square duct Alternate location (38 mm) (21 mm) reference outline �(if aoorooriate) a I • I 18"Round duct outline J (minimum diameter) Sampling tube,keyed for proper hole alignment with holes facing' into airflow(template is provided for proper tube installation). (Housing is shown as position 2 per note 2 below.) (General Location Notes: • • • • I 1.Testing performed under the auspices of the Fire Detection Institute(FDI)recommended when sampling tubes are not Duct , • located vertically,that they be positioned horizontally in the housing End View with upper half of the duct to account for possible stratification. Ducts and Tubes 2.Three duct side mounting options are available as shown below. Mount housing at 90°to airflow for all orientations. A Arrows indicate allowed airflow directions. V . _ , A a 1: 2 3 Exhaust tube �. a.;'-C f 8"Square duct outline • ( ''' 0 minimum width) ♦ ♦ ■ 3 54098-0030-6 1/2009 Duct Sensor Location Reference Duct Sensor Location Considerations: 1. Proper duct smoke detection location must ensure Exhaust Damper Sensor OK adequate airflow within the duct housing. Exhaust- • Return Air 2. Duct air velocity rating is 300 to 4000 ft/min(91 to 1220 m/min). Pressure differential between intake and Do not locate exhaust tubes is required to be between 0.015 to 1.55 sensor here l inches of water(0.381 to 39.37 mm). Return air damper _ 3. To avoid air turbulence,a location of six duct widths downstream from bends or inlets is desirable. Ensure accessibility for test and service. Fresh air • .' •Supply Air 4. Proper Locations: downstream side of filters to detect fires in the filters; in return ducts,ahead of mixing Do not locate Filter bank Sensor OK areas;upstream of air humidifier and cooling coil. sensor here 5. Other locations and orientations may be required for Bend or other Top mount,if appropriate proper duct smoke detection depending on duct access, obstruction ' system design,and duct airflow testing. Contact your • • Return . local Simplex product supplier for assistance. 6 Duct air inlet • 6 Duct widths widNs Locations to Avoid: '• desirable • desirable 1. Where dampers closed for comfort control would Additional Information. Refer to NFPA 90A,Standard for interfere with airflow. the Installation of Air Conditioning and Ventilating Systems; 2. Next to outside air inlets(unless the intent is to monitor NFPA 72°,the National Fire Alarm Coder;and the NEMA smoke entry from that area). Guide for Proper Use of Smoke Detectors in Duct 3. In return air damper branch ducts and mixing areas Applications,and Installation Instructions 574-776. where airflow may be restricted. S•ecifications General Mechanical and Environmental Air Velocity Range(linear ft/min) 300 to 4000 ft/min(91 to 1220 m/min) Sensor Sensitivity Range 0.2%to 3.7%per foot of obscuration,selectable at host control panel UL Listed Temperature Range 32°F to 100°F(0°C to 38°C) Operating Temperature Range 32°F to 122°F(0°C to 50°C) Storage Temperature Range 0°F to 140°F(-18°C to 60°C) Humidity Range 10%to 95%RH,non-condensing Wiring Connections Terminal blocks, 18 to 12 AWG(0.82 mm2 to 3.31 mm2) Housing Color Black base with clear cover Remote Status/Alarm LED and Test Station with Remote Status/Alarm LED Remote Alarm LED Current 1.2 mA,no impact to 24 VDC alarm current(2098-9808 or 2098-9806) Test Station Keyswitch Current 3.3 mA,no impact to 24 VDC alarm current(2098-9806) Remote Alarm LED and Test Station Distance 250 ft(76 m)maximum Addressable Operation Data Communications IDNet or MAPNET II communications,auto-select,one address per housing; provides operating power to model 4098-9755 Model 4098-9756 with Supervised Multiple Relay Control,Requires Separate Fused 24 VDC from Fire Alarm Power Supply Input Voltage 18-32 VDC(24 VDC nominal) Standby Current 3 mA @ 24 VDC Alarm Current(one relay activated) 15 mA @ 24 VDC;add 15 mA for each additional remote 4098-9843 relay For use with 4098-9843 relay only,quantity of 15 maximum;distance of 500 ft Supervised Remote Relay Control Output (152 m)maximum;requires 4081-9008(ref.733-894) 10 kI2, 1/2 W end-of-line resistor 4098-9843 Relay Output Ratings,Single Form C,use with Model 4098-9756 Only Coil Current 15 mA @ 24 VDC,up to 15 maximum per relay control output Relay Contacts 7 A at 0.35 PF @ 28 VDC&120 VAC;250 to @ 5 VDC Location Distance 500 ft(152 m)maximum to relay coils;locate relays within 3 ft (1 m)of device being controlled per NFPA 72 Tyco.Simplex.the Simplex logo.TrueAlarm,lDNet,and MAPNET Il are trademarks of Tyco international Services AG or its affiliates an the U.S.and,or other countries.NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association(NFPA). ®Simplex Tyco Safety Products Westminster•Westminster,MA•01441-0001 •USA S4098-0030-6 1/2009 www.tycosafetyproducts-use-wm.com 02009 Tyco Safety Products IVesoninster.All rights reserved.All specifications and other information shone,,ere current as of document revision date and are subject to c hange nitliout notice. B®Simplex LifeAlarm® Fire Alarm Controls • UL, ULC, CSFM Listed; FM Approved; 4009 IDNetTM NAC Extender for Control from 4010 or MEA (NYC)Acceptance* 4100ES/4100U IDNet Communications, or Conventional NACs Features L_ _ Provides additional notification appliance circuit ,rte. (NAC) capacity with flexible operation modes and '° power-limited design Upto8 NACs Four, Class B (Style Y) NACs are standard: It-1 • Rated 2 A each for conventional reverse polarity 4009 IDNet 24 VDC notification appliances and providing NAC Extender multiple operation modes ! 1 • Can be selected to provide synchronization for Simplex.)visible notification strobe flashes I Optional IDNeI • Capable of controlling TrueAlert®non-addressable Channel Repeater . notification appliances operating with SmartSyncTM I two-wire control mode** •� .�. Input control options: ; • IDNet addressable communications from a Simplex 2-Wire IDNet �� • model 4010,4100ES,or 4100U Fire Alarm Control Communications • . Fiber Optic IDNet \ Panel** r Communications Cif \ • Or from one or two conventional 24 VDC NACs with NAC Control multiple output control options �= n..,. _ • IDNet communications control benefits: ® IDNet Fiber • Provides status monitoring and individual NAC control Optic Transmitter using a single address per 4009 IDNet NAC Extender - • Supports IDNet"Device Level"earth fault location 4010(shown)or WALKTESTTm operation is available with either 4100ES/4100U Fire input choice Alarm Control Panel Fire Alarm Control Panel with Internal 8 A power supply/battery charger: Conv entional NACs • Charges internal batteries up to 12.7 Ah or up to 18 Ah batteries in external cabinet 4009 IDNet NAC Extender Connection Reference Drawing • Provides status monitoring of battery,input power,and Introduction earth faults • Rated 8 A for"Special Application"appliances; ADA Compliance. Complying with the notification including Simplex 4901,4903,4904,and 4906 Series requirements of ADA(Americans with Disabilities Act) horns,strobes,horn/strobes,and speaker/strobes may require more notification appliance power than is Rated 6 A for"Regulated 24 DC"appliance power available within the fire alarm control panel. When • additional power is required,a Simplex 4009 IDNet NAC Optional 4009 IDNet NAC Extender modules: Extender can provide up to 8 A of NAC power with up to • IDNet Communications Repeater provides Class B eight,supervised reverse polarity NACs. (Style 4)or Class A(Style 6)output Location Flexibility.The 4009 IDNet NAC Extender • IDNet Communications Fiber Optic Receiver/Repeater, can be mounted close to a compatible dedicated host available as Class B or Class A panel or can be located remotely for convenient power • Four additional Class B NACs,rated 1.5 A for Special distribution. Multiple operation modes and multiple Application appliances; 1 A for Regulated 24 DC connection options further increase location flexibility. appliance power Additional Information. For additional operation detail • Class A(Style Z),Two Circuit Adapter Module and application information,refer to Installation UL Listed to Standard 864 Instructions 574-181 and field wiring diagram 842-068. External Accessories • ULC listed model is 4009-9202CA.This product has been approved by the California State Fire Marsha(CSFM)pursuant to Section 13144.1 al the California Health and Safety Code.See CSFM Listing 7300-0026:214 for allowable values and/or conditions IDNet communication fiber optic transmitters: concerning material presented in this document It is subject to re-ex aminabon,revision, • For applications requiring the data integrity available and possible cancellation.Accepted for use-City of New York Department of Buildings -MEA35-93E.Additional listings may be applicable:contact your local Simplex product with fiber optic communications supplier for the latest status.Listings and approvals under Simplex Time Recorder Co. • Available as Class B(Style 4)or Class A(Style 7) are the property of Tyco Safety Products Westminster. • Mounts in standard six-gang electrical box ••4100U requires revision 11 software or higher for compatibility.4010 requires revision 2 External battery cabinet for 18 Ah batteries software or higher facompatit>ility. S4009-0002-8 Application and Operation Information IDNet Addressable Communications Compatible. Hardwire Control Applications. For applications Up to ten(10),4009 IDNet NAC Extenders can be where an existing(or new)conventional NAC needs controlled per 4100ES/41000 IDNet communications additional power,the 4009 lDNet NAC Extender can be channel; up to five(5)can be controlled on the 4010 controlled directly from the NAC. Either one or two IDNet communications channel. Each output NAC can be NACs, from either the same,or from different host fire individually controlled for general alarm or selective area alarm control panels,can be connected to control the 4009 notification requiring only one point address per Extender. IDNet NAC Extender output NACs. Multiple control Individual Extender NACs can also be manually selections provide flexible operation. (Refer to page 4 for controlled from the host panel. 1DNet controlled more detail.) Alarms from the host panel will activate the extenders will inform the host panel of troubles via IDNet four,4009 IDNet NAC Extender NACs(or optionally, communications. 4100ES and 4100U control panels eight NACs)to extend the alarm. control using multi-point rules,refer to data sheet The 4009 IDNet Extender monitors itself and each of its S4090-0011 for details. output NACs for trouble conditions, including earth Optional IDNet Repeaters. IDNet communications can faults. Extenders wired to conventional NACs will be repeated with the optional IDNet Repeater Module or indicate a trouble by opening the path to the NAC's with the optional Fiber Optic Receiver Module. Up to 100 end-of-line resistor,but retaining the ability to respond to of the IDNet channel points can be repeated once(refer to alarms. Individual troubles are also annunciated by LEDs pages 3 and 5 for details). Repeated IDNet communications located on the 4009 IDNet NAC Extender main circuit also support the"device level"earth fault location utility of board. (Refer to page 7 for more diagnostic information.) the host panel. Product Selection Standard Models Model Description 4009-9201 4009-9202CA' 120 VAC input 4009 IDNet NAC Extender with 4,Class B(Style Y)NACs and 8 A power supply 4009-9301 240 VAC input *ULC listed model Optional Modules (for on-site installation) Model Description Comments Additional four point NAC module,rated 1.5 A Special 4009-9807 Application appliances; 1 A for Regulated 24 DC appliance One maximum power,Class B(Style Y), 4009-9808 Dual Class A(Style Z)adapter(for two NAC outputs) Select as required(4 maximum) 4009-9809 IDNet Repeater,output is Class A(Style 6)or Class B(Style 4) Select either an IDNet Repeater or a Fiber 4009-9810 Class B(Style 4) Optic Receiver as required 4009-9811 Fiber Optic Receiver Class A(Style 7 fiber,Style 6 IDNet) 4009-9805 Red Appliqué for door Select if required 2975-9801 Beige trim 1-7/16"wide(78 mm),use if required for 2975-9802 Semi-Flush Trim Kit Red trim semi-flush installations Battery Selection (select battery size per system requirements) Model Description Comments 2081-9272 6.2 Ah Battery,12 VDC 2081-9274 10 Ah Battery, 12 VDC Two batteries are required,24 VDC operation 2081-9288 12.7 Ah Battery, 12 VDC • 2081-9275 18 Ah Battery, 12 VDC Requires external battery cabinet,two batteries are required,24 VDC operation External Accessories (select per system requirements) Model Description Comments 4090-9105 IDNet Fiber Optic Class B(Style 4)operation Mounts in six-gang electrical box,refer to 4090-9107 Transmitter Class A(Style 7)operation page 4 for mounting details 4009-9801 External battery cabinet for up to 18 Ah batteries,beige 16-1/4"W x 13-1/2"H x 5-3/4"D (413 mm x 343 mm x 146 mm) 4081 Series End-of-Line Resistor Harnesses;see data sheet S4081-0003 for details 2 S4009-0002-8 Typical IDNet Connection Example Typical IDNet compatible devices (Refer to individual devices for actual wiring requirements,some wiring is not shown.) -r >_. . , I IDNet addressable communications channel, .4_,./shown Class B(Style 4) Output NACs,four standard, Conventional NAC operation (horns) —- eight with expansion option � r —Select conventional or SmartSync 11111111111 1 operation per NAC 4100ES(shown) r—�—L--1. r---w or 41000/4010 Fire T, I AP:, , JI ID ,s/ Alarm Control Panel I SmartSync operation(horns and strobes) 4009 IDNet NAC Extender with I 1 IIIIII1 ==4..optional internal IDNet Repeater 111 J Conventional NAC ` ,, operation(strobes) Repeated IDNet Channel: 1 111111N1/1 up to 100 devices maximum on repeater output, ! t 250 devices total on IDNet Channel IDNet devices and additional 4009 IDNet NAC Extender(s) NOTE: Up to ten(10)4009 IDNet NAC Extenders may be connected per 4100 ES or 4100U IDNet channel, up to five(5)on the 4010 IDNet channel. IDNet communications can be repeated only once(can pass through only one series connected repeater or one fiber optic receiver). Typical Fiber Optic System Connections Two fiber cables,3000 ft Output NACs 4090-9105,Class B (914 m)maximum distance - _ (Style 4)Output Fiber I 1!!I!l11ii1 i • 1111011111111111111111111111111111111111111111111111111111 Optic Transmitter tf_. 8 ; 1 . 7 , , I IDNet addressable communications channel Class B(Style 4)or Class A (Style 6),Class B shown Repeated IDNet Channel:up to 100 devices maximum on repeater output,250 devices total on IDNet Channel IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII Four fiber cables,3000 ft 4010 or 4100ES/41000 (914 m)maximum distance Fire Alarm Control Panel / --- i iii- I ► 24 VDC power for ( �l��MIIII fiber optic transmitters /—*"�/— IMME 4090-9107,Class A(Style 7) ��41 Output Fiber Optic Transmitter 7111111111111_[ ' J 4009 IDNet NAC Extenders with optional Output NACs internal IDNet Fiber Receivers NOTE: Up to ten(10)4009 IDNet NAC Extenders may be connected per 4100 ES or 41000 IDNet channel, up to five(5) on the 4010 IDNet channel. IDNet communications can be repeated only once(can pass through only one series connected repeater or one fiber optic receiver). Fiber optic transmitters connect to only one 4009 IDNet NAC Extender. 3 S4009-0002-8 Hardwire Control Connection Information Smart Sync Notification Appliance Control NAC Input Selections. The 4009 IDNet NAC The TrueAlert Notification Appliance product line Extender can be selected to: includes addressable and non-addressable operation. • Track input NAC operation or to provide a locally Non-addressable models are available with 2-wire generated code,selectable per NAC input Smart Sync operation or conventional 4-wire operation. If selected for local coding,NAC outputs can be either The following details apply to use with the 4009 IDNet • NAC Extender: Temporal Coded or 60 Beats/min March Time Coded, one code selection per extender(input NACs must be on • TrueAlert non-addressable models with SmartSync continuous with Alarm) operation allow audible notification to be separately • Additionally,NAC outputs can be selected to provide controlled over the same wire pair that controls visible the Simplex strobe synchronization signal.This signal notification will synchronize the flashes of synchronized strobes but • 4009 IDNet NAC Extenders can be selected to provide will be ignored by free-run strobes and audible devices. SmartSync operation whether controlled by IDNet (Strobes are for operation by noncoded NACs.) communications or conventional NACs NAC input to NAC output control can be selected for • IDNet control allows output NACs to be individually standard and optional NACs per the following table: selected for conventional or SmartSync operation Conventional NAC Output Operation Options • With NAC input control, all output NACs are selected Input A B C for either conventional or SmartSync operation NAC 1 NACs 1 &2,5&6 NACs 1-4 NACs 1-8 • Refer to data sheet S4009-0003 for TrueAlert NAC 2 NACs 3&4,7&8 NACs 5-8 None Addressable operation details,contact your loca I SmartSync NAC Output Operation Simplex product supplier for further information on Input NAC Control Function specific TrueAlert notification appliances NAC 1 Strobe Control All NAC outputs(1-8) NAC 2 Horn Control Hardwire Control NAC Connection One-Line Reference Diagram Up to eight(8)output NACs total;hardwire control can be selected to map NAC inputs to different combinations of NAC outputs depending on system requirements NAC 1 input (see Note 1) • � ' �I Conventional NACs -l With hardwire control, ~ „ r j — NAC outputs are all Output conventional or am ' NACs SmartSync operation - -- 4009 IDNet NAC _ _ Extender Fire Alarm Control Panel with Conventional NACs SmartSync operation Class A operation,either mode,requires NAC 2 input 4009-9808 Dual Class A Adapter (optional,see Note 1) To additional 4009 IDNet NAC Extenders(up to four(4), 4009 IDNet NAC Extenders per NAC);see Note 2 Notes: 1.For separate audible and visible output NAC control,or SmartSync NAC output operation,two(2)input NACs are required. NAC 1 is"on-until-reset"and NAC 2 is"on-until-silenced." 2.To synchronize strobe flash outputs for up to four(4)4009 IDNet NAC Extenders,use the synchronized strobe output from a Synchronized Flash Module (4905-9914 for Class B operation,4905-9922 for Class A operation)or, if available,from a NAC selected to provide synchronized strobe flash output. NOTE:DO NOT USE a NAC selected for SmartSync operation for this function. Refer to Installation Instructions 574-181 for additional information and application guidance 4 S4009-0002-8 4009 IDNet NAC Extender S•ecifications 120 VAC Input(4009-9201) 3A @ 102-132 VAC,60 Hz Input 240 VAC Input(4009-9301) 1.5A @ 204-264 VAC, 50/60 Hz Ratings Hardwire Control from External Conventional reverse polarity operation NACs,Input Requirements 5 mA maximum; 16 to 33 VDC Total Rating 8 A,Special Application appliances 6 A,Regulated 24 DC appliance power Standard NACs 2 A each,Special Application or Regulated 24 DC appliance power Optional NACs 1.5 A each,Special Application appliances (requires 4009-9807) 1 A each,Regulated 24 DC appliance power Special Application Simplex 4901,4903,4904,and 4906 Series non-addressable horns,strobes, Output Ratings Appliances and combination horn/strobes and speaker/strobes(contact your Simplex product representative for compatible appliances) Regulated 24 DC Power for other UL listed appliances;use associated external synchronization Appliances modules where required Strobe Operation Up to 33 strobes per NAC can be synchronized;output NACs configured for Simplex synchronized strobe operation are synchronized to each other Auxiliary Output 500 mA @ 24 VDC nominal Optional Modules Ratings Input Power 70 mA @ 24 VDC,system supplied IDNet Input,One Address Maximum distance from IDNet source is 2500 ft(762 m) IDNet Repeater Repeated IDNet output for up to 100 devices(total IDNet devices not to exceed Module 250 per channel) (4009-9809) IDNet Output Specifications Maximum distance to farthest device is 2500 ft(762 m) Total distance including"T-taps"is 10,000 ft(3048 m) Class A(Style 6)loop maximum distance is 2500 ft(762 m), no"T"taps Fiber Optic Receiver Modules Input Current 4009-9810,Class B(Style 4),65 mA @ 24 VDC,system supplied 4009-9811,Class A(Style 7),80 mA©24 VDC,system supplied IDNet Output Specifications Same as those for Repeater Module(see above) Fiber Optic Transmission Distance 3000 ft(914 m)maximum General(LED status indicators are listed on page 7,dimensions and mounting details are on page 6) Operating Temperature 32°to 120°F(0°to 49°C) Operating Humidity Range 10%to 90%RH from 32°F to 104°F(0°C to 40°C) Wiring Connections` Terminal blocks for 18 AWG(stranded)to 12 AWG(solid) Fiber Optic Transmitter Specifications Input Voltage 18.9-32 VDC from compatible listed fire alarm supply Input Current 4090-9105,Class B(Style 4),30 mA @ 24 VDC 4090-9107,Class A(Style 7),35 mA @ 24 VDC Multimode,graded index,50/125pm,62.5/125 pm, 100/40 pm,or 200 pm Fiber Optic Connections and cable Type ST connectors requirements 4090-9105,Class B(Style 4)operation,two fiber cables required 4090-9107,Class A(Style 6)operation,four fiber cables required Module Size(with mounting bracket) 6-13/16"W x 3-3/4"H x 1-1/8"D(173 mm x 95 mm x 29 mm) Green LED flashing=transmit On-board Status Indicators Red LED flashing=receive Separate red LED on 4090-9107=Class A(Style 7)receive Communications Simplex IDNet Fiber Optic Transmission Distance 3000 ft(914 m)maximum Wiring Connections° Terminal blocks for 18 AWG(stranded)to 12 AWG(solid) Operating Humidity 10%to 90%RH from 32°to 104°F(0°to 40°C) Operating Temperature 32°F to 120°F(0°to 49°C) Metric wire equivalents: 18 AWG=0.82 mm 2; 12 AWG=3.31 mm2 5 S4009-0002-8 4009 IDNet NAC Extender Mounting and Module Placement I nformation ice— 16-1/4°(413 mm) 1..._ Cabinet depth 4-1/4°(108 mm) –I I 161– 10-29/32"(277 mm) I Door,5/8" ® ® ® ® (16 mm)thick�' [ n V © I:�i:�l:�l�l I_I __I �� ®® ® 8® oR Optional Class A 4009-9807 Additional Four 13-1/2" adapter modules point module(shown with (343 mm) 0 Class A 0 Exposed cabinet I I dimension for—Po I I System Module ® '' semi-flush mount Fa / (25.4 mm (1" mm), Knockouts for screw IDNet repeater gr 1-3/8"(35 mm)with or nail mounting holes 8 Fiber optic receiver D n semi-flush trim ® ®L lJ —© 0 — �.4 12"(305 mm) r.1 i I o 7-------------- Battery location,no conduit entry or wiring in i this area(12.7 Ah battery outline shown) ' CI I 0' r Semi-flush trim option Non-power limited wiring area(AC input) 1-3/16"wide(30 mm), — 3/8"(9.5 mm)thick At- - Wall surface reference for semi-flush mount NOTE: Recommended conduit entrance varies with module selection. Refer to general installation instructions 574-181, specific module installation instructions, and to field wiring diagrams 842-068 before locating conduit entrance. 4009 IDNet NAC Extender Cabinet with Door Detail Optional red appliqué (4009-9805) 0 _ 4009 IDNet"' NAC EXTENDER simplex 6 S4009-0002-8 4090-9105/9107 IDNet Fiber Optic Transmitter Mounting Information Surface mount box: _1,, Simplex model 2975-9217 (ordered separately) • • • . a c:=> o o o o o ' I Flush mount masonry box: use 6-gang box,RACO#960,2-1/2"deep 0 0 (64 mm),or RACO#965,3-1/2"(89 mm) pi • • • • 'purl deep,or equal(supplied by others) Flush mount ganged boxes: ` . ■i • • ' use 6-gang box,1-1/2"(38 mm) minimum depth;six,RACO#400 t;1 • I • O O or equal,(supplied by others) t,1 - •� ups 0 o 0 0 0 0 IDNet fiber optic transmitter: 4090-9107,Shown,Class A(Style 7)output 4090-9105,Not shown,Class B(Style 4)output INSTALLATION NOTE: Fiber optic cable bend radius should be 2"(51 mm) minimum,or per Manufacturer's specification. 0 0 0 0 0 0� Six-gang blank cover plate Mulberry Metal Products 97156 or equal(by others) Service Diagnostic Features Power-up Self-Diagnostics. Upon power-up,the LED Status Indicators are provided for the following: 4009 IDNet NAC Extender tests each module and • Each NAC (standard and optional)has a dedicated performs earth fault diagnostics. Trouble conditions are yellow LED that: communicated to the host control panel and are also — During supervision provides a slow flash to indicate displayed on diagnostic status LEDs in the 4009 IDNet a short circuit condition and a fast flash to indicate NAC Extender. When connected via 1DNet communications, detailed status information is available an open circuit at the host. When controlled with conventional NAC — During an alarm,the LED follows the NAC output inputs,common troubles are signaled by providing a (on steady or flashing with coded output) polarized open circuit that disconnects the NAC wiring • Four,general status yellow LEDs provide nine from its end-of-line resistor but still allows a reversed separate indications listed in priority of urgency. As a polarity alarm to be received. trouble is eliminated,any remaining trouble(s)will Door Mounted Reference Label. The 4009 IDNet then be indicated until the 4009 IDNet NAC Extender NAC Extender has a detailed programming and is returned to normal operation. diagnostic label inside the front door that provides a quick • AC power status is indicated by a green LED that is reference for both installation and checkout. on when AC is normal. During low AC(brownout) conditions or with no AC,the LED is off. Additional power and battery status is indicated by the general status LEDs. 7 S4009-0002-8 4009 IDNet NAC Extender Current Chart Panel Module Selection (shaded model numbers are optional modules) Model Description Supervisory Actual Alarm Current Actual Alarm Current Supervisory 4009-9201 120 VAC input Basic Panel 85 mA 85 mA 185 mA 185 mA 4009-9301 240 VAC input 4009-9807 Additional Four Point NAC 40 mA + +NAC loads +NAC loads (add below) (add below) 4009-9808 Dual Class A Adapter(current — included in basic panel value) 4009-9809* IDNet Repeater 70 mA 70 mA 4009-9810*t Fiber Optic Receiver,Class B 65 mA + 65 mA + 4009-9811*t Fiber Optic Receiver,Class A 80 mA 80 mA IDNet Devices, 0.7 mA each,maximum of 100 Total devices + Total devices (A1) + (see note 5) x 0.7 mA each x 0.7 mA each Auxiliary Power Output, calculate per total 500 mA + 500 mA (A2) + device requirements(see note 5) maximum maximum Total Supervisory Current= (A) + Total 4009 IDNet NAC Extender Panel Alarm Current= (B1) *Only one of these three modules can be chosen for a single 4009 IDNet NAC Extender. t NOTE: IDNet Fiber Optic Transmitter current is supplied from the host fire alarm control panel. NAC Loads NAC Type NAC Circuit# NAC Alarm Current Circuit 1 + Circuit 2 + Standard Panel NACS,2 A maximum per NAC(see note 5) Circuit 3 + Circuit 4 + Circuit 5 + Circuit 6 + Optional Four Point NAC Module, 1.5 A maximum per NAC(see note 5) Circuit 7 + Circuit 8 + Total NAC Loads Alarm Current= (C) Total 4009 IDNet NAC Extender Panel Alarm Current(enter B1 from above)= (B2) + Procedure: Total Alarm Current= (D) 1. Calculate total panel supervisory current(A). 2. Calculate total panel alarm current(B1)[convert mA to A,example:350 mA=0.35 A].Copy(B1)into block(B2). 3. Calculate total NAC loads alarm current from notification appliance ratings(C). 4. Add(C)+(B2)to determine total alarm current(D). 5. Total of IDNet Device Current(Al)+Auxiliary Power Output Current(A2)+NAC Loads Alarm Current(C)is 8 A maximum. 6. Refer to Simplex battery selection document 900-012 for recommended battery size for specific standby requirements (i.e.24 hours supervisory,5 minutes of alarm).Internal cabinet space is provided for batteries up to 12.7 Ah. Tyco is a registered trademark of Tvco International Services GmbH and is used under license.Simplex.the Simplex logo.Life Alarm.!Wier.WALKTEST,SmartSync.and TT rueAlert are trademarks of Tyco International Ltd.and its affiliates and are used under license. S i m p I Ex Tyco Safety Products Westminster•Westminster,MA•01441-0001•USA S4009-0002-8 JB www.tycosafetyproducts-usa-wm.corn © 20/0 Tyco Safety Products Westminster.All rights reserved All specifications and other information sham acre current as of document revision date and are subject to change ttithout notice. Wheelock' ExcederTM Series 00 COOPER Notification Ejerriti517 Finally, Design and Safety Meet... t n.1- /111\ Ceiling Wall Description: The Wheelock®ExcederTM'Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. up 14% ** - Save u to cost of installation The Wheelock ExcederTM'Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single 0 Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings,can be set without the use of a tool and are located behind the appliance to prevent tampering. ej Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTM' Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting 12/ 4 Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a so,95,99 d6 shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while 8 Candela Settings"* it is on the UMB. When the Contact Cover is removed the circuit Wall-15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows Ceiling-15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if }„ required. Wall models provide an optional locking screw for extra �jg,o� Universal Mounting Base secure installation, while the ceiling models provide a captivated v Ceiling and Wall Mounts to 5 Backbox Types screw to prevent the screw from falling during installation. Co) Environmentally Friendly Low Current Draw Compatibility and Requirements -Synchronize using the Wheelock"Sync Modules or panels with built-in Wheelock®Patented Sync Protocol -Compatible with UL"Regulated Voltage"using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage"range Compared to competitive models "' Patented "Compared to previous models NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION ANDIOR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: •Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. •Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%)UL 464(85%UL 19711. •Series Exceder horns are under UL Standard 464 for audible signal appliances(Indoor use only). Low Current Draw = Fewer Power Supplies Strobe Ratings per UL Standard 1971 UL Max Current` 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 &UL 464 at 24 VDC UL Max Current*at 99 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.082 0.095 0.102 -0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125 UL Max Current'at 95 dBA 24 VDC 12 VDC Model Regulated Voltaae 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122 UL Max Current*at 90 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC •HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL 464 /k Model Regulated Voltage 99 dB 95 dB 90 dB , 't'"- . 4CZ--" Range VDC HN 16-33.0 0.064 0.044 0.022 •/ - HNC 16-33.0 0.084 0.044 0.022 _`-- HN 8.0-17.5 0.047 0.026 0.017 y f \ ; 1 HNC 8.0 17.5 0.047 0.026 0.017 r *UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. Specification & Ordering Information Sync w/SM, Model Strobe DSM or 12/24 VDC* Mounting Candela PS-6&PS-8 H Options 5 Horn Strobes o . d HSR 15/1575/30/75/95/110/135/185 X X 73 UMB** O HSW 15/1575/30/75/95/110/135/185 X X 7.1 UMB** C) HSRC 15/30/60/75/95/115/150/177 X X "v UMB** C) HSWC 15/30/60/75/95/115/1501177 X X 05 UMB** o ',frnbes u U STR 7 15/1575/30/75195/110/135/185 X X UMB** L Q) ul d STW "O 15/1575/30/75/95/110/135/185 X X m UMB** E STRC r 15/30/60/75/95/115/150/177 X X Q UMB** IDSTWC o 15/30/60/75/95/115/150/177 X X 4 UMB**Horn w rn CV co O HNR y X X cn UMB** N HNW C X X UMB** HNRC U X X rn t0 UMB** W HNWC CO . X X r UMB** *12 VDC models feature 15&15/75 settings **UMB=Universal Mounting Base Model Legend HN = Horn � J ST = Strobe HS = Horn Strobe � A C = Ceiling Mount / y `-'- W =White i, ' P = s �` �` R = Red .N/`// Example 1: STRC=Strobe, Red,Ceiling Mount - Example 2: HSR = Horn Strobe, Red,Wall Mount ' Example 3: HSW= Horn Strobe, White,Wall Mount Example. Example. HSWC c , I: cc . *UMB Contact Cover Voltage test points for quick 8 candela settings Common base for wall and ceiling with 5 troubleshooting and easy spot mounting options checking (wall models only) NOTE:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance l with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. d • Architects and Engineers Specifications The notification appliances shall be Wheelock'® Exceder TM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. • Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135. 185 candela for wall mount and 15, 30. 60. 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3)audible outputs. The Series HS Audible Strobe,ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal. 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP). The mounting base shall be the same base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24"H x 4.58"W x 2.19"D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series HNC ceiling shall have a diameter of 6.68"x 1.50" D. When synchronization is required, the appliance shall be compatible with Wheelock®'s SM, DSM Sync Modules,Wheelock®Power Supplies or other manufacturer's panels with built-in Wheelock®Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1)flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock®synchronization protocol. Wall Appliances—UL Standard 1971, UL Standard 464..California State Fire Marshal(CSFM), ULC, FM Ceiling Appliances—UL Standard 1971, UL Standard 464,California State Fire Marshal(CSFM), ULC. FM NOM WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder- Spec Sheet 10/10 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. 4401 Wilson Boulevard,Suite 220 Long Branch,NJ 07740 Sarasota,FL 34243 Arlington,VA 22203 P:800-631-2148 P:941-487-2300 P:877-459-7726 F:732-222-8707 F:941-487-2389 F:703-294-6560 www.coopernotification.com Cooper Notification is Wheelock` (MEDC1 SAFEPATH' WAVEV "WO Sec re COOPER Notification