JO COSCO FIRE PROTECTION, INC. 11800 NE 95th STREET, SUITE 240 VANCOUVER, WA 98682 HYDRAULIC CALCULATIONS FOR ORCHARD SUPPLY HARDWARE NURSERY CANOPIES FILE NUMBER: PD5103-1 DATE: DEC 10, 2012 -DESIGN DATA- OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP II DENSITY: . 20 gpm/sq. ft . AREA OF APPLICATION: 1950 sq. ft . COVERAGE PER SPRINKLER: 120 sq. ft . NUMBER OF SPRINKLERS CALCULATED: 17 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 467 . 2 gpm TOTAL WATER REQUIRED (including hose) : 717 . 2 gpm FLOW AND PRESSURE (gi BOR) : 467 . 2 gpm @ 71.2 psi SPRINKLER ORIFICE SIZE: 3/4 inch/8 . 0 K NAME OF CONTRACTOR: ENGINEERED STRUCTURES, INC. DESIGN/LAYOUT BY: JEFF HALSTEAD AUTHORITY HAVING JURISDICTION: CITY OF TIGARD CONTRACTOR CERTIFICATION NUMBER: 67508 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4903012830) HRS SYSTEMS, INC. City of Tigard Approve Plans B y Date D 12-7-11'3 OFFICE COPY SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 12/10/2012 5103 ORCHARD SUPPLY HARDWARE - TIGARD\CALCS\PD5103-1 .SDF 1 JOB TITLE: Orchard Supply Hardware PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe : 1 -24 . 1 2 . 067 PL 9 . 33 PF 0 . 1 1 19 . 9 8 . 0 9 . 1 24 . 1 2 . 3 100 FTG ---- PE 0 . 0 2 19 . 9 8 . 0 9 . 2 24 . 2 0 . 009 TL 9 . 33 PV Pipe: 2 -48 . 3 2 . 067 PL 9 . 33 PF 0 . 3 2 19 . 9 8 . 0 9 . 2 24 . 2 4 . 6 100 FTG ---- PE 0 . 0 3 19 . 9 8 . 0 9 . 5 24 . 6 0 . 034 TL 9 . 33 PV Pipe: 3 -73 . 0 2 . 067 PL 9 . 33 PF 0 . 7 3 19 . 9 8 . 0 9 . 5 24 . 6 7 . 0 100 FTG ---- PE 0 . 0 4 19 . 9 8 . 0 10 . 2 25 . 5 0 . 073 TL 9 . 33 PV Pipe : 4 -98 . 5 2 . 067 PL 3 . 83 PF 0 . 9 4 19 . 9 8 . 0 10 . 2 25 . 5 9 .4 100 FTG E PE 0 . 0 T1 19 . 9 0 . 0 11 . 1 0 . 0 0 .128 TL 7 . 40 PV Pipe : 5 -98 . 5 2 . 067 PL 4 . 88 PF 1 . 5 T1 19 . 9 0 . 0 11 . 1 0 . 0 9 .4 100 FTG T PE 2 . 1 81 15 . 0 0 . 0 14 . 8 0 . 0 0 . 128 TL 12 . 02 PV Pipe : 6 -24 .2 2 . 067 PL 9 . 33 PF 0 . 1 5 19 . 9 8 . 0 9 .2 24 . 2 2 .3 100 FTG -- -- PE 0 . 0 6 19 . 9 8 . 0 9 .3 24 .4 0 . 010 TL 9 . 33 PV Pipe : 7 -48 . 6 2 . 067 PL 9 . 33 PF 0 . 3 6 19 . 9 8 . 0 9 . 3 24 . 4 4 . 6 100 FTG -- -- PE 0 . 0 7 19 . 9 8 . 0 9 . 6 24 . 8 0 . 035 TL 9 . 33 PV Pipe: 8 -73 .4 2 . 067 PL 9 . 33 PF 0 . 7 7 19 . 9 8 . 0 9 . 6 24 . 8 7 . 0 100 FTG --- - PE 0 . 0 8 19 . 9 8 . 0 10 . 3 25 . 7 0 . 074 TL 9 . 33 PV Pipe : 9 -99 . 0 2 . 067 PL 3 . 83 PF 1 . 0 8 19 . 9 8 . 0 10 . 3 25 . 7 9 . 5 100 FTG E PE 0 . 0 T2 19 . 9 0 . 0 11 . 2 0 . 0 0 . 129 TL 7 . 40 PV Pipe : 10 -99 . 0 2 . 067 PL 4 . 88 PF 1 . 6 T2 19 . 9 0 . 0 11 . 2 0 . 0 9 . 5 100 FTG T PE 2 . 1 B2 15 . 0 0 . 0 14 . 9 0 . 0 0 . 129 TL 12 . 02 PV Pipe : 11 -26 . 7 1 . 380 PL 9 . 00 PF 0 . 7 9 15 . 9 8 . 0 11 . 2 26 . 7 5 . 7 100 FTG ---- PE 0 . 0 10 15 . 9 8 . 0 11 . 9 27 . 6 0 . 082 TL 9 . 00 PV Pipe : 12 -54 . 3 1 . 380 PL 3 . 67 PF 1 . 8 10 15 . 9 8 . 0 11 . 9 27 . 6 11 .6 100 FTG E PE 0 . 0 T3 15 . 9 0 . 0 13 . 7 0 . 0 0 . 304 TL 5 . 81 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE : 12/10/2012 5103 ORCHARD SUPPLY HARDWARE - TIGARD\CALCS\PD5103-1 .SDF JOB TITLE: Orchard Supply Hardware PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ . PT DISC. VEL (FPS) HW (C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe : 13 -54 . 3 1 . 380 PL 0 . 88 PF 1 . 6 T3 15 . 9 0 . 0 13 . 7 0 . 0 11 . 6 100 FTG T PE 0 .4 B3 15 . 0 0 . 0 15 .6 0 . 0 0 . 304 TL 5 . 16 PV Pipe : 14 -27 . 7 1 . 380 PL 9 . 00 PF 0 . 8 11 15 . 9 8 . 0 12 . 0 27 . 7 5 . 9 100 FTG --- - PE 0 . 0 12 15 . 9 8 . 0 12 . 8 28 . 6 0 . 088 TL 9 . 00 PV Pipe : 15 -56 . 3 1 . 380 PL 3 . 67 PF 1 . 9 12 15 . 9 8 . 0 12 . 8 28 . 6 12 . 1 100 FTG E PE 0 . 0 T4 15 . 9 0 . 0 14 . 7 0 . 0 0 . 325 TL 5 . 81 PV Pipe : 16 -56 . 3 1 . 380 PL 0 . 88 PF 1 . 7 T4 15 . 9 0 . 0 14 . 7 0 . 0 12 . 1 100 FTG T PE 0 .4 B4 15 . 0 0 . 0 16 . 7 0 . 0 0 . 325 TL 5 . 16 PV Pipe : 17 -29 . 1 1 . 380 PL 9 . 00 PF 0 . 9 13 15 . 9 8 . 0 13 . 2 29 . 1 6 . 2 100 FTG - --- PE 0 . 0 14 15 . 9 8 . 0 14 . 1 30 .0 0 . 096 TL 9 . 00 PV Pipe : 18 -59 . 1 1 . 380 PL 3 . 67 PF 2 . 1 14 15 . 9 8 . 0 14 . 1 30 . 0 12 . 7 100 FTG E PE 0 . 0 T5 15 . 9 0 . 0 16 . 2 0 . 0 0 . 356 TL 5 . 81 PV Pipe : 19 -59 . 1 1 . 380 PL 0 . 88 PF 1 . 8 T5 15 . 9 0 . 0 16 . 2 0 . 0 12 . 7 100 FTG T PE 0 .4 B5 15 . 0 0 . 0 18 . 4 0 . 0 0 . 356 TL 5 . 16 PV Pipe : 20 -30 . 9 1 . 380 PL 9 . 00 PF 1 . 0 15 15 . 9 8 . 0 14 . 9 30 . 9 6 . 6 100 FTG - --- PE 0 . 0 16 15 . 9 8 . 0 15 . 9 31 . 9 0 . 107 TL 9 . 00 PV Pipe : 21 -62 . 7 1 . 380 PL 3 . 67 PF 2 . 3 16 15 . 9 8 . 0 15 . 9 31 . 9 13 . 5 100 FTG E PE 0 . 0 T6 15 . 9 0 . 0 18 . 2 0 . 0 0 . 397 TL 5 .81 PV Pipe : 22 -62 . 7 1 . 380 PL 0 . 88 PF 2 . 1 T6 15 . 9 0 . 0 18 . 2 0 . 0 13 . 5 100 FTG T PE 0 .4 B6 15 . 0 0 . 0 20 . 6 0 . 0 0 . 397 TL 5 . 16 PV Pipe : 23 -37 . 2 1 . 380 PL 3 . 67 PF 0 . 9 17 15 . 9 8 . 0 21 . 6 37 . 2 8 . 0 100 FTG E PE 0 . 0 T7 15 . 9 0 . 0 22 . 5 0 . 0 0 . 151 TL 5 . 81 PV Pipe : 24 -37 . 2 1 . 380 PL 0 . 88 PF 0 . 8 T7 15 . 9 0 . 0 22 . 5 0 . 0 8 . 0 100 FTG T PE 0 .4 B7 15 . 0 0 . 0 23 . 7 0 . 0 0 . 151 TL 5 . 16 PV Pipe : 25 -98 . 5 3 . 260 PL 9 . 75 PF 0 . 1 B1 15 . 0 0 . 0 14 . 8 0 . 0 3 . 8 100 FTG -- - - PE 0 . 0 B2 15 . 0 0 . 0 14 . 9 0 . 0 0 . 014 TL 9 . 75 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 12/10/2012 5103 ORCHARD SUPPLY HARDWARE - TIGARD\CALCS\PD5103-1 . SDF JOB TITLE: Orchard Supply Hardware WATER SUPPLY CURVE 96+ 1 1 88*\\\\\\\\\ 0\\\\\\\\ \\\\\\\\\ 1 \\\\\\\\\ 80+ \\\\\\\\\ 1 \\\\\\\\\ 1 \\\\\\\\\ 1 74 . 0 psi @ 1986 gpm-> * 72+ X Flow Test Point 1 1 1 P 64+ R E S S 56+ U I R I E I 48+ ( 1 P S I 40+ 1 1 32+ 24+ 1 1 1 16+ LEGEND 1 I X = Required Water Supply " 1 71 . 86 psi @ 717 .2 gpm 8+ I 0 = Available Water Supply " 85 . 02 psi @ 717 . 2 gpm 0++ +- --+ 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) COSCO •��•' Fire Protection • MATERIAL SUBMITTAL FOR Orchard Supply Hardware 10031 SW Cascade Avenue Tigard, Oregon 97223 COSCO Fire Protection Inc. Job # 24PD5103 11800 NE 95th St., Suite 240 Vancouver,WA 98682 Phone:360-883-6383 Fax: 360-883-6390 Toll Free:800-983-6383 , Material Submittal Orchard Supply Hardware Tigard, Oregon Item Manufacturer Model Size Comments Sprinklers QR Upright Viking VK350 "18.0 K 200° F, Brass QR Pendent Viking VK302 Y,,"/5.6 K 155° F, Chrome Valves Butterfly Valve Firelock Series 705 4" x 60 Grooved with tamper Dry Pipe Valve Reliable D 4" With trim Pipe & Fittings Grooved Pipe State Pipe &Supply Schedule 10 1'/" - 6" Or equal Screwed Pipe State Pipe & Supply Schedule 40 1" - 2" Or equal Grooved Fittings Victaulic Varies 11/4" - 8" Or equal D.I. Threaded Fittings Smith Cooper Varies 1" - 2" Or equal Flexible Drop Flexhead 2036 %" x 36" Electrical Devices Pressure switch Potter PS-10 Or equal Low Air Switch Potter PS-40 Or equal Air Compressor Emglo F13-S-30UMS Or equal Hangers Sidewinder for wood Speedy Products SWG 20 %" Top Beam Clamp Afcon Fig. 105 %" Or equal Hanger Ring Afcon Fig. 300 1" - 6" Or equal Seismic Bracing In-line Clamp Tolco Fig. 4A Bar Joist Attachment Tolco Fig. 825 EQ Ear Tolco Fig. 980 Fast Clamp Tolco Fig. 1000 January 22, 2010 Sprinkler 51 a NIKNG MICROFASP AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND ■ CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Microfast' and MicrofastHP' Quick Response Upright and Conventional (Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers 1*rr_ available in several different finishes, temperature ratings, and K-Factors to /. meet design requirements. The special Polyester and Teflon' coatings .,i' can be used in decorative applications where colors are desired. In addi- /!C Lion, these coatings have been investigated for installation in corrosive atmos- pheres and are cULus listed as corrosion resistant as indicated in Approval Chart 1. (Note: FM Global has no approval classification for Teflon" and Polyester °i y coatings as corrosion resistant.) 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Classes 2002 and 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984B-PDA VdS Approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 LPC Approved: Ref. No. 096e/03,TE30401, and TE30872 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, and 0786-CPD-40171 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- http://www.vikinggroupinc.com. sure (HP) sprinklers can be identified by locating "250" stamped on The Web site may include a more recent the deflector. All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: Refer to the Approval Charts "cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06661B, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 06661B and 12281. Copper UNS-C19500 for Sprinklers 06665B, 06764B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Form No. F_080488 Replaces page 51a-e, dated April 25, 2008. (Updated for Sprinkler 14817. Added VdS to Sprinklers 06665B, 06764B, and 14817. Updated FM Approvals and split the Approval Charts to separate UL Listing requirements from FM Approval requirements. Changed the metric K-factor for K4.2 sprinklers to 57.) Sprinkler 51 b January 22, 2010 MICROFAST®AND VIKING TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Teflon®Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon®Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Microfast®and MicrofastHP®Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, Chrome-Enloy®= F,White Polyester= M-/W, Black Polyester= M-/B, and Black Teflon®= N Temperature Suffix(°F/°C): 135°157° =A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2" thread, Brass finish and a 155°F/68°C temperature rating = Part No. 06661BAB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrench: Standard Wrench: Part No. 10896W/B(available since 2000) Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B.Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast®and MicrofastHP®Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature' Ordinary 135°F(57 °C) 100 °F(38 °C) Orange Ordinary 155 °F(68 °C) 100 °F(38 °C) Red Intermediate 175 °F(79 °C) 150 °F(65 °C) Yellow Intermediate 200 °F(93 °C) 150 °F(65 °C) Green High 286 °F(141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon® Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon® Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 'The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compatible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only.Note that the spring is exposed on sprinklers with Polyester and Teflon®coatings. January 22, 2010 Sprinkler 51c MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND r I N KI CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) _ Temperature KEY Microfast"'and MicrofastHP�Quick Response �F.nlsn Upright and Conventional Sprinklers A1x•-Escutcheon tifapplicable) Maximum 175 PSI (12 bar)WWP Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metric' Inches mm cULus4 NYC' VdS LPCB CE I O Upright-Standard Orifice 06661B VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- -- -- -- 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- -- A3 A3 B3" B3" Conventional-Standard Orifice 06766B VK310 1/2" 15 mm 5.6 80.6 2-3/16 56 A3 A3 I -- A3 B3" I B3'3 Upright-Large Orifice 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 A2 A2 A3 A3 B3" -- 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2 A2 A3 A3 B3" -- 06764B VK350 1/2" 15 mm 8.0 115.2 2-5/16 59 A2 A2 A3 -- -- -- Conventional-Large Orifice 06768B VK354 3/4" 20 mm 8.0 115.2 2-5/16 I 59 A2 A3 -- A3 B3" -- Upright-Small Orifice10 06717810 VK325 1/2' 15 mm 2.8 40.3 2-3/16 56 A2 A2 -- -- -- -- 06719B10 VK327 1/2' 15 mm 4.2 57 2-3/16 56 A2 A2 0693181° VK327 -- 10 mm 4.2 57 2-3/16 56 -- -- A3 -- C112 -- Maximum 250 PSI (17 bar)WWP Upright-Standard Orifice Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN (Refer also to Design Criteria on page 51d.) Number' NPT BSP U.S. metric' Inches mm cUlus° NYC' VdS LPCB (E O 12281 VK315 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- -- -- -- Upright-Small Orifice° 122867° VK340 1/2" 15 mm 2.8 40.3 2-3/16 56 A2 A2 -- -- -- -- Approved Temperature Ratings Approved Finishes A- 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 1 Brass and Chrome Enloy 286 °F(141°C) 2-Brass, Chrome-Enloy ,White PolyesterJ6,Black Polyesters", B- 155 °F(68 °C), 175 'F (79 'C), 200 'F(93°C), and 286 °F (141°C) and Black Teflon C 155 °F(68 °C) 3 - Brass, Chrome-Enloy", White Polyester", and Black Polyesters 6 Footnotes 'Base part number is shown. For complete part number, refer to Viking's current price schedule. 2Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 'Listed by Underwriters Laboratories Inc. for use in the U.S.and Canada. 'cULus Listed as corrosion resistant. o Other colors are available on request with the same Listings and Approvals as the standard colors. 'Accepted for use. City of New York Board of Standards and Appeals, Calendar Number 219-76-SA. s Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16. Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. '°The sprinkler orifice is bushed. "(E Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. 12(E Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131. ' p MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. Sprinkler 51d January 22, 2010 • MICROFAST® AND VIKING TECHNICAL DATA MicrofastHP" QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRITERIA - UL< (Also refer to Approval Chart 1 on page 51c) cULus Listing Requirements: Microfast and MicrofastHP• Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers,or old style(conventional)sprinklers. • Designed for use in Light and Ordinary Hazard occupancies(exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style(conventional)sprinklers. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Protective `drench Sprinkler Flat ►. Cap 10896 Figure 1: Standard Sprinkler Wrench 10896W/B January 22, 2010 Sprinkler 51e MICROFASP AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) Temperature KEY Microfase Quick Response Upright Sprinklers FI"ISn Al X 4-Escutcheon Of applicable) Maximum 175 PSI(12 bar)WWP Base Part SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Number' NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.) Standard Orifice 06661B VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 A2 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A2 Large Orifice 06665B VK350 3/4" — 8.0 115.2 2-5/16 59 A2 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2 Small Orifice" 0671786 VK325 1/2" 15 mm 2.8 40.3 2-3/16 56 Al Approved Finishes Approved Temperature Ratings 1 -Brass and Chrome-Enloy® A- 135°F (57 °C), 155°F(68 °C), 175 °F(79°C), 200°F(93°C), and 286°F(141°C) 2 - Brass, Chrome-Enloy®, White Polyesters, and Black Polyesters Footnotes 'Base part number is shown. For complete part number, refer to Viking's current price schedule. z Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3This table shows the FM Approvals available at the time of printing.Check with the manufacturer for any additional approvals. ° FM Approved as quick response Non-Storage pendent sprinklers. For specific application and installation requirements, reference the latest appli- cable FM Loss Prevention Data Sheets(including Data Sheet 2-0). Other colors are available on request with the same Approvals as the standard colors. The sprinkler orifice is bushed. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Aoproval Requirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-Storage upright sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements,hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. THIS PAGE INTENTIONALLY LEFT BLANK Form No. F_080488 Replaces page 51a-e, dated April 25, 2008. (Updated for Sprinkler 14817. Added VdS to Sprinklers 06665B,067646,and 14817. Updated FM Approvals and split the Approval Charts to separate UL Listing reauirements from FM Approval reauirements. Changed the metric K-factor for K4.2 sprinklers to 57.1 October 8, 2010 Sprinkler 41a MICROFAST AND NIKING TECHNICAL DATA MicrofastHP' QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Microfast" and MicrofastHP' Quick Response Pendent Sprinklers are small, thermosensitive,glass-bulb spray sprinklers available in several different finishes and temperature ratings and K-Factors to meet design requirements.The special Polyester and Teflon"coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive at- mospheres and are cULus listed as corrosion resistant as indicated in the Approval Chart. (Note: FM Global has no approval classification for Teflon"'and Polyester coat- ings as corrosion resistant.) 2. LISTINGS AND APPROVALS ft).7-7: cULus Listed: Category VNIV FM Approved: Class 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984C-PDA VdS Approved: Certificates G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021 LPC Approved: Ref. Nos. 096e/03 and 096e104 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40130, and 0786-CPD-40170 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on page 41d for cULus Listing requirements and refer to Approval Chart 2 and Design Criteria on page 41e for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for Viking Technical Data may be found on use with water working pressures ranging from the minimum 7 psi The Viking Corporation's Web site at (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres- http://www.vikinggroupinc.com. sure (HP) sprinklers can be identified by locating "250" stamped on The Web site may include a more recent the deflector. All other Part Nos. not mentioned above are rated to a edition of this Technical Data Page. maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: Refer to the Approval Charts 'cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06662B and 12282. Brass UNS-C84400 for all other sprinklers. Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 06662B, 06666B, and 06765B. Copper UNS- C19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Form No. F_081296 Replaces page 41a-f, dated May 7, 2010. (Clarified FM Approval.) Sprinkler 41 b October 8, 2010 MICROFAST®AND VIKING TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com For Teflon®Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon®Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Microfast®and MicrofastHP®Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin- ish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, Chrome-Enloy®= F, White Polyester= M-/W, Black Polyester= M-/B, and Black Teflon®= N Temperature Suffix(°F/°C): 1352/57° =A, 1550/68° = B, 1750/79° = D,200°/93° = E, and 286 0/141° =G For example, sprinkler VK302 with a 1/2"thread, Brass finish and a 155°F168 °C temperature rating = Part No. 06662BAB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B.Wrench for Coated and/or Recessed Sprinklers: Part No. 12144W/B*(available since 2003) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool**Part No. 15915(available since 2010.) NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B. *A'/2"ratchet is required(not available from Viking). **Allows use from the floor by attaching a length of 1"diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A(available since 1971) B.Twelve-head capacity: Part No. 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements. 7. AVAILABILITY Wrench The Viking Microfast®and MicrofastHP®Quick Response Pendent Flats Sprinklers are available through a network of domestic and Protective international distributors. See The Viking Corporation web site for 1_=:1 9 rP � 1 Sprinkler the closest distributor or contact The Viking Corporation. Cop 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. 10896 (6)) Figure 1: Standard Sprinkler Wrench 10896W/B • October 8, 2010 Sprinkler 41c MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK i RESPONSE PENDENT SPRINKLERS The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal=: Maximum Ambient Bulb Color Classification Temperature Rating' ■' Ceiling Temperature2 Ordinary 135 °F (57°C) 100 °F (38 °C) Orange Ordinary 155 °F (68°C) 100 °F (38 °C) Red Intermediate 175 °F (79°C) 150 °F (65°C) Yellow Intermediate 200 °F (93°C) 150 °F (65°C) Green — High 286 °F (141 °C) 1 225 °F(107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon® Corrosion-Resistant Coatings': White Polyester, Black Polyester, and Black Teflon® Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments.Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon coatings. 1 f I ! 1 1 I I Li --E] IS 1.- 1.-1A- Al p-i in Ij Or--L thin III +- ., I� i .,,.r,----r _, ..Sprinkler Wrench 12144W/Bww for installing coated ��� and/or recessed _.....____ pendent sprinklers ii . Carefully slide the 1 l with protective caps. wrench sideways i. r� ;i around the protective cap, ensuring engage- =1 ment with the sprinkler =i **A 1/2' ratchet is required wrench flats. I (not available from Viking). Figure 2: Wrench 12144W1B for Coated and/or Recessed Pendent Sprinklers • Sprinkler 41d October 8, 2010 MICROFAST®AND TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) Temperature KEY Flnish and MicrofastHP°Quick Response Pendent Sprinklers A7 X�-Escutcheon(if applicable) Maximum 175 PSI(12 bar)WWP Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No.' NPT BSP U.S. metric' Inches mm cULus4 NYC° VdS LPCB (E 0 Standard Orifice 06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A1X,B1Y AI X,B1Y A3 A3X,B3Y C3X, E3Y" C3X, E3Y13 Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 A1X, B1Y A1X,B1Y A3 A3X C3" -- 06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 A1X, B1Y A1X,B1Y A3 -- -- -- Small Orifice° 06718B9 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 A1X,B1Y A1X,B1Y -- -- -- -- 06720B9 VK331 1/2" 15 mm 4.2 57 2-1/4" 58 AI X,B1Y A1X,B1Y -- -- -- -- 06932B VK331 -- 10 mm 4.2 57 2-3/8" 60 -- -- A3 -- G2" -- Maximum 250 PSI(17 bar)WWP Standard Orifice Sprinkler Thread Size Nominal Overall Listings and Approvals' Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.) Part No' NPT BSP U.S. metric' Inches mm cULus° NYC10 VdS LPCB E a 12282 VK317 1/2" 15 mm 5.6 80.6 2-1/4" 58 A1X, B1Y A1X -- -- -- -- Maximum 250 PSI(17 bar)WWP Small Orifice' 1229010 VK342 1/2" 15 mm 2.8 40.3 2-3/16" 56 Al X, B1Y A1X -- -- -- -- Approved Temperature Ratings A-135°F(57°C),155°F(68°C),175°F(79°C),200°F(93°C), Approved Escutcheons and 286°F(141 °C) Approved Finishes X - Standard surface-mounted escutcheon or B-135°F(57°C), 155°F(68°C), 175°F(79°C),and 200°F 1 - Brass, Chrome-Enloy®, White the Viking Microfast® Model F-1 Adjustable 9 °C) C- 155 F(68°C), 175°F(79°C), 200°F(93°C),and 286°F Polyester°', Black Polyester°•', Escutcheon (141 °C) and Black Teflon®' Y - Standard surface-mounted escutcheon or D 135°F(57°C), 155°F(68°C), 175°F(79°C),and 286°F 2-Brass and Chrome-Enloy® the Viking Microfast® Model F-1 Adjustable (141 °C) 3 - Brass, Chrome-Enloy®, White Escutcheon or recessed with the Viking E-155°F(68°C), 175°F(79°C),and 200°F(93°C) Polyester',and Black Polyester' Micromatic' Model E-1 or E-2 Recessed F- 155°F(68°C), 175°F(79°C),and 286°F(141 °C) Escutcheon G- 155°F(68°C) Footnotes ' Base part number is shown. For complete part number,refer to Viking's current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. d Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 'Accepted for use,City of New York Board of Standards and Appeals,Calendar Number 219-76-SA. °cULus Listed as corrosion resistant. 'Other colors are available on request with the same Listings and Approvals as the standard colors. °Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 'The sprinkler orifice is bushed. 10Acgepted for use,City of New York Department of Buildings, MEA Number 89-92-E,Vol. 16. Certified,Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. " Certified,Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40130 and 0786-CPD-40170. 13 $MED Certified,Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. October 8, 2010 Sprinkler 41e MICROFAST®AND\ilium TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT • SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRITERIA- UL (Also refer to Approval Chart 1 on page 41d) gULus Listing Requirements: Microfast'and MicrofastHP"Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies(exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Ceiling Opening Size: 2-5/16' (58.7 mm) minimum 2-1/8' 2-1/2' (63.5 mm) maximum (54 rim) 1/2' (15 mm) —\ — tii -• NPT _- � : -------- IdlaalltX1 f-----1 IR.. .)--.L. rI 1-3/4" �`l t 2-1 (44.5 mm) 2' . 1-1/2' (38.1 mm) 1-5/8' (58 mm) (50.8 mm) / Minimum (41mm) l j i Maximum ! 1 1 . 1 _i__ ..........Installed with a Pendent Sprinkler' standard 1/8' surface- 06662B (VK302) mounted escutcheon. Installed with a Microfast Model F-1 Adjustable Escutcheon Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon 2-1/8" 1 Ceiling Opening Size: 2-1/8' (54 mm) 2-5/16' (58.7 mm) minimum (54 mm) 2-1/2' (63.5 mm) maximum t��!1 ilii 1� m..... TI I�� . uI 1-3/4' 1-1/8' (28.6 mm)(44.5 mm) Minimum 2' 1-1/8' (28.6 mm) Maximum = _ $ (50,8 mm) S Minimum Maximum }1 Installed with a Micromatic Model E-1 Recessed Escutcheon Installed with a thread on Model E-2 Recessed Escutcheon Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons Sprinkler 41f October 8, 2010 MICROFAST®AND VIKING TECHNICAL DATA MicrofastHP® QUICK RESPONSE PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) ( --Temperature KEY Microfast Quick Response Pendent Sprinklers Finish Maximum 175 PSI(12 bar)WWP Al x.-Escutcheon(if applicable) Sprinkler SIN Thread Size Nominal K-Factor Overall Length FM Approvals' Base Part No.' NPT BSP U.S. metric' Inches mm (Refer also to Design Criteria below.) Standard Orifice 06662B VK302 1/2" 15 mm 5.6 80.6 2-1/4" 58 A2X,B2Y Large Orifice 06666B VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 A1X,B1Y Small Orifice" 06718B6 VK329 1/2" 15 mm 2.8 40.3 2-3/16" 56 Al X Approved Escutcheons Approved Temperature Ratings Approved Finishes X-Standard surface-mounted escutcheon or the Viking A-135°F(57°C), 155°F(68°C), 175°F(79°C), 1 -Brass and Chrome-Enloy Microfast"Model F-1 Adjustable Escutcheon 200°F(93°C),and 286°F(141 °C) Y - Standard surface-mounted escutcheon or the 2 grass,Chrome Enloy,White Polyesters, B- 135°F(57°C), 155°F(68°C), 175°F(79°C), and Black Polyesters Viking Microfast" Model F-1 Adjustable Escutcheon and 200°F(93°C) or recessed with the Viking Micromatic"Model E-1 or E-2 Recessed Escutcheon Footnotes ' Base part number is shown. For complete part number,refer to Viking's current price schedule. Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 'FM Approved as standard response control mode standard spray Non-storage sprinklers. For specific application and installation requirements,refer- ence the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). 'Other colors are available on request with the same Listings and Approvals as the standard colors. 'The sprinkler orifice is bushed. DESIGN CRITERIA- FM (Also refer to Approval Chart 2 above.) FM Approval Reauirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-storage standard spray pendent sprinklers as indicated in the FM Approval Guidet. For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheets 2-0 and 8-9).FM Global Loss Prevention Data Sheets contain guidelines relating to,but not limited to:minimum water supply requirements, hydraulic design,ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. 1-Sprinklers VK302 and VK352 are also FM Approved as quick response Rack Storage standard spray pendent sprinklers. Refer to technical data page 131a-e for Intermediate Level In-Rack Sprinklers, IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_081296 Replaces page 41a-f, dated May 7, 2010. (Clarified FM Approval.) • ,.• • • , •,• •x ILIK•1111■111114 FireLock® Butterfly Valve °' 410, VdS i.pcs uar•• SERIES 705 WITH WEATHERPROOF ACTUATOR The Series 705 Butterfly Valve features a weatherproof actuator housing Approved for - it indoor or outdoor use,a ductile iron body and disc with Nitrite seats. Designed for fire i' protection services only.Victaulic FireLock Series 705 Butterfly Valve is cULus Listed, • LPCB Listed, FM and VdS Approved for 300 psi/2068 kPa service.Contact Victaulic for details of agency approvals. APPROVALS AND LISTINGS Approval/Listing Service Pressures Series 705 Butterfly Valve cUlus FM VdS LPCB 2750mm up to 300psi/2068kPa n/a u•to 300.si/2068kPa u•to 300•si/2068kPa 2 1/2765mm u.to 300psi/2068kPa u.to 300•si/2068kPa n/a u•to 300•si/2068kPa 76.1mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa u•to 300.si/2068kPa 3780mm up to 300•si/2068kPa u•to 300•si/2068kPa up to 300ps1/2068kPa u•to 300•si/2068kPa 4"/100mm u.to 300.si/2068kPa u•to 300•si/2068kPa up to 300.s1/2068kPa u•to 300ps1/2068kPa 57125mm up to 300psi/2068kPa up to 300psi/2068kPa n/a u•to 300•si/2068kPa 139.7mm up to 300psi/2068kPa up to 300.sl/2068kPa u.to 300•si/2068kPa up to 300.si/2068kPa 67150mm U.to 300psi/2068kPa u•to 300•s1/2068kPa u.to 300.si/2068kPa up to 300•si/2068kPa 165.1mm up to 300psi/2068kPa u.to 300psi/2068kPa n/a u•to300•si/2068kPa 8/200mm up to 300psi/2068kPa up to 300•si/2068kPa up to 300psi/2068kPa up to 300•si/2068kPa 107250mm u•to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 127300mm u.to 300.si/2068kPa u•to 300•si/2068kPa n/a u•to 300•s1/2068kPa JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. sctaUliild REV C 10.81 1 IPS CARBON STEEL PIPE-FIRE PROTECTION VALVES .L U.01 FireLock® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR MATERIAL SPECIFICATIONS Body: Ductile iron conforming to ASTM A-536,grade 65-45-12 End Face, 2—6750— 150 mm: Ductile iron conforming to ASTM A-536,grade 65-45-12 Seal Retainer, 8— 12"/200—300mm: Ductile iron conforming to ASTM A-536,grade 65-45-12 Coating: Black alkyd enamel Disc: Ductile iron conforming to ASTM A-536,grade 65-45-12,with electroless nickel coating con- forming to ASTM B-733 Seat: • Grade"T3" Nitrile Stems: 416 stainless steel conforming to ASTM A-582 Stem Seal Cartridge:C36000 brass Bearings:Stainless Steel with TFE lining Stem Seals: Nitrile Stem Retaining Ring:Carbon steel Actuator: • 2-8"/50-200mm: Brass or bronze traveling nut on a steel lead screw, in a ductile iron housing • 10- 12 7250-300mm:Steel worm and cast iron quadrant gear, in a cast iron housing www.victaulic.com Ctaulic° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.81 2 REV C IPS CARBON STEEL PIPE-FIRE PROTECTION VALVES I U■01 FireLock® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR DIMENSIONS- II liraMIUM11 Outside End to Size Diameter End A B C D E F G DIA H J 2' 2.375 4.25 2.28 6.41 _ 4.00 4.22 4.50 2.12 s .3��1 60 mm 60.3 108.0 57.9 162.8 - 101.6 107.2 114.3 53.8 2W 2.875 3.77 2.28 7.54 _ 4.00 4.22 4.50 1.77 ■ 73 mm 73.0 95.8 57.9 191.5 101.6 107.2 114.3 45.0 ,•,ItH 3.000 3.77 2.28 7.54 - - 4.00 4.22 4.50 1.77 76.1 mm 76.1 95.8 57.9 191.5 101.6 107.2 114.3 45.0 F 3' 3.500 3.77 2.53 7.79 _ _ 4.50 4.22 4.50 1.77 88.9 mm 88.9 95.8 643 197.9 114.3 107.2 114.3 45.0 4.250 4.63 2.88 8.81 _ _ 5.50 4.22 4.50 2.20 108 mm 108.0 117.6 73.2 223.8 139.7 107.2 114.3 55.9 4' 4.500 4.63 2.88 8.81 _ _ 5.50 4.22 4.50 2.20 /,IVI� 114.3 mm 114.3 117.6 73.2 223.8 139.7 107.2 114.3 55.9 • 0H 5.250 5.88 3.35 10.88 6.56 6.19 6.30 2.58 =1fjpJ 133 mm 133.0 149.4 85.1 276.4 - - 166.6 157.2 160.0 65.5 7 5.500 5.88 3.35 10.88 _ _ 6.56 6.19 6.30 2.58 1 139.7 mm 139.7 149.4 85.1 276.4 166.6 157.2 160.0 65.6 -6--- 5' 5.563 5.88 3.35 10.88 6.56 6.19 6.30 2.58 1 141.3 mm 141.3 149,4 85.1 276.4 - - 166.6 157,2 160.0 65.5 6.250 5.88 3.84 11.38 - 0.41 7.52 6.19 6.30 2.58 } 159 mm 159.0 149.4 97.5 289.1 10.4 191.0 157.2 160.0 65.5 6.500 5.88 3.84 11.38 0.41 7.52 6.19 6.30 2.58 -J-, 165.1 mm 165.1 149.4 97.5 289.1 - 10.4 191.0 157.2 160.0 65.5 E- -A t-D -- 6' 6.625 5.88 3.84 11.38 _ 0.41 7.52 6.19 6.30 1.90 Note:Optional 1/2"/l5mm tap available. 168.3 168.3 149.4 97.5 289.1 10.4 191.0 157.2 160.0 48.3 Contact Victaulic for details. 8' 8.625 5.33 5.07 13.53 0.80 1.47 10.00 6.19 8.10 2.33 219.1 mm 219.1 135.4 128.8 343.6 20.3 37.3 254.0 157.2 205.7 59.2 10' 10.750 1 6.40 6.37 I1 15.64 1.41 1.81 12.25 8.10 I` 9.00 Ir _ 273 12'm 12.750 1 6.50 161.8 .36 ! 16.64 1 2.30 2 80 f 14 25 8.0 1 9.00 I _ 323.9 mm 323.9 1 165.1 1 186.9 1 422.7 I 58.4 I 71.1 1 362.0 1 205.7 1 228.6 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jetau1ia REV C 10.81 3 IPS CARBON STEEL PIPE-FIRE PROTECTION VALVES I U.0 I FireLock® Butterfly Valve SERIES 705 - WITH WEATHERPROOF ACTUATOR PERFORMANCE The chart expresses the frictional resistance of Victaulic Series 705 Butterfly Valve in equivalent feet/ meters of straight pipe. Size Size Actual Actual Nominal Outside Nominal Outside Size Diameter Equiv. Size Diameter Equiv. Inches Inches Feet/m Inches Inches Feet/m t, mm mm of Pipe mm mm of Pipe 2 2.375 6 6 6.625 14 50 60.3 1.8 150 168.3 4.2 21/2 2.875 6 14 159 mm 159 mm 65 73.0 1.8 4.3 76.1 mm 3.000 6 165.1 mm 6.500 14 76.1 1.8 165.1 4.2 3 3.500 7 8 8.625 16 80 88.9 2.1 200 219.1 4.9 4 4.500 8 10 10.750 18 100 114.3 2.4 250 273.0 5.5 1 8 12 12.750 19 08 mm 108 mm 2.4 300 323.9 5.8 5 5.563 12 125 141.3 3.7 133 mm 133 mm 12 3.7 139.7 mm 5.500 ! 12 139.7 3.7 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2010 VICTAULIC COMPANY,ALL RIGHTS RESERVED. sCtaul1C' 10.81 4 REV C IPS CARBON STEEL PIPE-FIRE PROTECTION VALVES 1 V.8 1 FireLock® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR PERFORMANCE Cv values for flow of water at+60°F/+16°C with a fully open valve are shown in the table below. For additional details,contact Victaulic. Formulas for Cv Values: AP = Q2 Where: zz Q=Flow(GPM) AP=Pressure Drop(psi) Q = C., x �P C,=Flow Coefficient Size C, Si'i I c, Actual _ - Actual Actual Nominal Outside Nominal Outside Nominal Outside Size Diameter Size Diameter Size Diameter Inches Inches Inches Inches Inches Inches mm mm (Full Open) mm mm (Full Open) mm mm (Full Open) 1.375 5 5.563 8 8.625 2 60.3 170 125 141.3 1200 200 219.1 3400 2'h 2.875 260 133 mm 133 mm 1200 10 10.750 5800 65 73.0 250 273.0 76.1 mm 3.000 260 139.7 mm 5.500 1200 12 12.750 9000 76.1 139.7 300 323.9 3 3.500 440 6 6.625 1800 80 88.9 150 168.3 4 4.500 100 114.3 820 159 mm 159 mm 1800 108 mm 108 mm 820 165.1 mm 6'S� 1800 165.1 Formulas for Kv Values: ,P = Q2 Where: \ K Q=Flow( Q = K x ...,FCP AP Pressure(bar) K =Flow Factor .i., K„ Sivr a, Stn K; Actual Actual Actual 1 Nominal Outside Nommal Outside Nominal Outside I Size Diameter Size Diameter Size Diameter Inches Inches Inches Inches Inches Inches 1 rem mm (Full Open) nim mm (Full Open) mm mm I (Full Open) 2 147 2.375 5 5.563 1040 8 8.625 2940 60.3 125 141.3 200 219.1 21/2 2.875 225 133 mm 133 mm 1040 tO 10.750 5020 65 73.0 250 273.0 76.1 mm 3.000 225 139.7 mm 5.500 1040 12 12.750 7790 76.1 139.7 300 323.9 3 3.500 380 6 6.625 1560 80 88.9 150 168.3 4 4.500 710 159 mm 159 mm 1560 100 114.3 _ 108 mm 108 mm 710 165.1 mm 6'S� 1560 165.1 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. htaiullc° REV C 10.81 5 IPS CARBON STEEL PIPE-FIRE PROTECTION VALVES 10.0 1 FireLock® Butterfly Valve SERIES 705 - WITH WEATHERPROOF ACTUATOR SWITCH AND WIRING 1. The supervisory switch contains two single pole,double throw, pre-wired switches. 2.Switches are rated: 10 amps @ 125 or 250 VAC/60 Hz 0.50 amps @ 125 VDC 0.25 amps CO 250 VDC 3.Switches supervise the valve in the"OPEN"position. 4.One switch has two#18 insulated wires per terminal,which permit complete supervision of leads (refer to diagrams and notes below). The second switch has one#18 insulated wire per termi- nal.This double circuit provides flexibility to operate two electrical devices at separate locations, such as an indicating light and an audible alarm, in the area that the valve is installed. 5.A#14 insulated ground lead (green)is provided. Switch#1 =51 For connection to the supervisory circuit of a UL Listed alarm control panel Switch#2=S2 Auxiliary switch that may be connected to auxiliary devices, per the authority having jurisdiction Normally Closed:(2)Blue S1 Common:(2)Yellow Normally Closed: Blue with Orange Stripe S2 Normally Open:Brown with Orange Stripe Common:Yellow with Orange Stripe s ` Jt- nx FFF aI ARUM i) Ci Flit 1�57ri e / 71,0 i1,0 A`+f� lE l 1.1 4St5 Ol1. `/ tIPFRVIS!ORV ��U ilia a AtA 1:, ruy 1119 ICI o t COV. r vt>I rACtr Switch 1:2 leads pet terminal Switch 3:1 lead per terminal NOTE: The above diagram shows a connection between the common terminal(yellow-S1 and yellow-with-orange stripe-S2)and the normally closed terminal (blue-Si and blue-with-orange stripe-S2). In this example, the indicator light and alarm will stay on until the valve is fully open. When the valve is fully open, the indicator light and alarm will go out.Cap off any unused wires (e.g. brown with orange stripe). Only S1 (two leads per terminal) may be connected to the fire alarm control panel. The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary switch per NFPA 70(NEC). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUI1Ca 10.81 6 REV C . . - : • •, U,R•" FireLock® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the installation sheet included with the valve.Verify you have the latest revision by visiting our website at www.victaulic.com. Further reference can be found in the 1-100 Victaulic Field Installation Handbook. For complete contact information,visit www.victaulic.com 10.81 5662 REV C UPDATED 12/2010 ictauloc VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.81 Bulletin 351 Rev.Q Mo del D Reliabl ° 5. Dry Pipe Valve 4"(100mm) & 6"(150mm) 0 Features 1. Differential Type...simple...light weight construction. r AL 2. Screwed in one piece air and water • seat—eases maintenance. sf 3. Bronze seat with "O"-Ring seals— prevents corrosion and leakage. r ,, r 6® VATICI 4. Single hinge pin and latch design — no ION 4 CO • complicated levers. lJ , 5. Simple to reset— no special tools required. 6.Tapered air and water seats—induces p �•- iv a. J or- hairline differential operation. s 7. One piece rubber facing—provides more reliable rubber-to-metal water seal. - Y 8.Three connections styles available: • ANSI flanged inlet and outlet ANSI flanged inlet and grooved outlet The Reliable Model D Dry Pipe Valve makes pos- • g g roove sible the installation of automatic sprinkler sys- • Metric flanged inlet and outlet tems in buildings in which freezing temperatures prevail. This type of system, called a Dry Pipe Sys- tem, has air under pressure instead of water in the piping above the dry pipe valve. When one or Listings & Approvals more automatic sprinklers operate due to fire, the 1. Listed by Underwriters Laboratories, Inc. (UL) air pressure in the system is reduced — the dry 2. Listed by Underwriters Laboratories of Canada.(ULC) pipe valve opens and water under pressure flows 3. Certified by FM Approvals in the activated sprinkler(s) and is then distributed 4. Loss Prevention Council. (LPC, UK) on the fire. 5. NYC BS&A No. 587-75-SA. 6. Scientific Services Laboratories (SSL, Australia) The Reliable Automatic Sprinkler Co.,Inc., 525 North MacQuesten Parkway, Mount Vernon, New York, 10552 • Operation The Reliable Model D Dry Pipe Valve in its closed When an automatic sprinkler operates, the result- and open positions is shown in Figures 1 and 2. ing air pressure decay is inversely proportional to - The closed position is maintained as long as the air the size of the dry system - the larger the system, pressure in the system piping above the dry pipe the slower the air pressure decays which slows the valve is sufficient to exert a greater force on the top operation of the Dry Pipe Valve. NFPA 13, Installa- - side of the clapper than is exerted on its underside tion of Sprinkler Systems, specifies that quick by the pressure of the water supply. Since the area opening devices may be required in dry systems included by the air seat is approximately six times having capacities of more than 500 gallons. that of the water seat(The Differential Principle)the Reliable's Model B1 Accelerator is an approved air pressure needed to keep the dry pipe valve quick opening device that is easily attached to Reli- closed is only a fraction of that of the water supply. able's Dry Pipe Valves. The accelerator is sensitive Table 1 gives the recommended air pressure for to small drops in system pressure and it's quick op- various water supply pressures for both sizes of eration allows the system air to pass through to the Model D Dry Pipe Valves. alarm outlet and the underside of the clapper. Here Table 1 the air pressure build-up, coupled with the pres- sure of the water supply, opens the dry pipe valve Water Pressure Air Pressure psi (bar) clapper permitting the water to flow instantly to the in Supply Line psi (bar) To be Pumped into System _ operated sprinkler(s). Maximum Not less than Not more than Reliable's Model B1 Accelerator is described in 20 (1,38) 10(0,68) 20(1,37) greater detail in Bulletins 320 and 322. 50 (3,44) 15 (1,03) 25 (1,72) 75 (5,17) 20(1,37) 30(2,06) Valve Description 100 (6,89) 25 (1,72) 35 (2,41) 1. Rated working pressure 175 psi (12.1 bar). 125 (8,62) 30 (2,06) 40 (2,75) 2. Factory hydrostatic test pressure:350 psi(24.1 bar). 150 (10,34) 35 (2,41) 45 (3,10) 3. End and trim connections: Three valve connec- 175 (12,06) 40 (2,75) 50 (3,44) tion styles are available: a. US Standard Flanged Inlet and Outlet: • Flanges mate with ANSI B 16.1 (125 lb.) Flange. When one or more automatic sprinklers operate due to fire, the air pressure in the system piping U.S. Flange Dimensions in inches above the dry pipe valve is reduced. The pressure Bolt Bolt Flange Y p p P Valve Circle Hole Outside Flange No. of the water supply, now by exerting the greater Size Dia. Dia. Dia. Thickness Bolts _ force, raises and rotates the clapper to its open po- 4° 7/2 Y4 9 ' s 8 sition, permitting the water to flow to the operated 6" 9/2 % 11 1 8 sprinkler(s). Water also flows from the alarm outlet • Threaded openings per ANSI B 2.1. of the dry pipe valve through a strainer to the Reli- • Reliable's standard trim sets are compati- able Mechanical Sprinkler Alarm and Electric ble with US Flanged Valves. Alarm Switch to automatically actuate mechanical • Color — Black. Y b. US Standard Flanged Inlet and Grooved Out- and electrical alarms. let (Fig. 3): Reliable Model D Dry Pipe Valves can be reset • Inlet flange mates with ANSI B 16.1 quickly and easily without the use of special tools. ((125 lb.)flange. • Outlet Groove per ANSI/AWWA C606. SYSTEM AIR PRESSURE AIR INLET 0\\ � \"`, ::::::-.?..--_-?t, \y\i PRIMING Ni \�;..,_. PRIMING _______________��.... WATER LEVEL WATER INLET :Y ' o 1 /- } CLAPPER �,. i," �WAT£R SEAT •� -_- ?- V l_ LATCH j� ��\ /,-AIR SEAT `�_ _ i -{ ;�' DRAIN -� a I t A- 'J Sri <;�® % ALARM OUTLEr I vi ALARM TEST 0- __ o i% ! - - iM :�� Tai , �.r.. � ,., . .,..- SUPPLY WAFER p,ny, PRESSURE SUPPLY WATER PRESSURE Figure 1—Closed Figure 2—Open 2. U.S. Groove Dimensions in Inches Trim Description Valve T Outlet I Groove Groove Outlet Face The trimmings for Reliable Model D Dry Pipe Size Dia. Dia. Width to Groove Valves (Fig 4) are arranged for rapid, easy and 4" 4.500 4.334 % % compact attachment and serve as connection 6" 6.625 6.455 3e % - points to Reliable Alarm and other devices. They • • Threaded opening per ANSI B 2.1. also serve as a means of setting and resetting the • Reliable's standard trim sets are compati- dry pipe valve prior to and after operation as well ble with US Flanged and Grooved Valves. • Color— Black. as allowing testing of the alarm devices without c. Metric Flanged Inlet and Outlet: causing the system to operate. • Flanges mate with EN 1092-2, The Model D Basic Trim Set is shown in Fig.4(The NF-E-29-282 and BS 4504 PN16 Flanges. electric sprinkler alarm switch is not part of the trim Metric Flange Dimensions in Millimeters set and must be separately ordered.) This trim set Bolt Bolt Flange provides the air supply, drain, priming level and Valve Circle Hole Outside Flange Number alarm connections. An alarm test valve, which al- Size Dia. Dia. Dia. Thickness,- Bolts lows the alarm devices to be tested without operat- 100 180 18.3 229 23.8 8 ing the dry pipe valve, is included. The basic trim 150 241 22.2 279 25.4 8 set includes all items such as ball drip valves, pres- • Threaded openings per ISO 7/1 Rp. sure gauges, etc which are needed to enable • Reliable's standard trim sets may,be used proper dry pipe valve operation. with Metric Valves providing trim is assem- bled The basic trim set is available in either black or al carefully and extra thread sealant is gal- applied to connections between valves vanized in one of three forms: loose, segmentally as- and trim. sembled trim or factory trimmed on the valve. • Color— Blue. Two additional trimming attachments are offered: 4. Face to Face Dimension: the priming chamber attachment and the fill line at- • The 4" (100 mm) Valve— 16"(406 mm) tachment. The priming chamber attachment al- • The 6" (150 mm) Valve- 19"(482 mm) lows the priming level to be maintained while the 5. Shipping Weight: system remains pressurized. The fill line attach- Flanged Flanged Inlet Flanged Inlet ment provides a source of water for maintaining the Valve and Outlet and Grooved prime level. Outlet The trimmings, connection, operation and main- 4" (100 mm) 120 lb. (54.5 kg) 110 Ib. (49.83 kg) tenance of the additional items which comprise a 6" (150 mm) 242 lb. (109.5 kg) 228 lb.(103.28 kg) dry pipe valve system, such as air maintenance de- vices, air compressors, accelerators, electric 6.Friction Loss Expressed in Equivalent Length of Pipe, alarm switches, mechanical sprinkler alarms, etc., based on Hazen-Williams formula with C = 120: are described in detail in the individual bulletins for these products. Size Equiv. Length All valves are listed and approved by Under- 4"(100 mm) 28ft (8.51 m) writers Laboratories, Inc. and Factory Mutual 6"(150 mm) 47ft(14.29 m) Research Corp. only when used with the valve 7. Installation Position: Vertical j manufacturers trim sets. I 1998 AIR CONTROL VALVE CONNECNUN FOR A'R R£L(E VALVE-.)4 INCH AvrJMATrc'IPRxNKLER rN MODEL D N D.F.Y. ENCLOSURE PRMrN {burp vAtVE DRY �-PIPE VALVE �' - EL£irR/ ALARM .► i 4 E iwrrc" OR IJ MEC'4N1C4L REUABLE* AUTOMATIC �, i__`ipmNr(LER AGV7M 1 r SPRINKLER CO. �1. Yr.SAWN��pQ��,, NEM YOWL \ t ,•M . Noon 0 ' ®TED MAIN OPAIN VALVE '' t% i[u. --- its *yr',ist ®4 F M D 0 4- IVIFr r a Prsty i rurt vs PSI liZ),;: r � rev 0 • i?• r tLE�`TRI�'�yp/y �rLE�LtAE A ALARM PRfSiURE SlttTCH• N ^\ 175 PSI ` JO?PCr59 LOEAALW 1l ?JTF(:cSB TES' ALARM TEST VALVE $/N-I d+U LIMP VALVE 351FIG3 Figure 3 Figure 4—Model D Dry Pipe Valve Model D Basic Trimming 3. Ordering Information Specify • Valve Size: Either 4"(100 mm) or 6"(150 mm). • Style of Trim - Loose Individual part trim or seg- - When size is specified in mm, a metric valve mentally assembled trim or factory trimmed valve. per 3(c)will be supplied. • Additional Equipment—Air Maintenance De- • Inlet and Outlet Connection — Either vices, Air Compressors, Accelerators, Electric - Flanged/Flanged or Flanged/Grooved. Sprinkler Alarm Switches and Mechanical • Trim - Basic Trim Sprinkler Alarms must be separately ordered. Priming Chamber Attachment Fill Line Attachment • Galvanized or Black Trim. Installation Measurement In Inches Valve A B C D E F G H I J 4"(100mm) 16 6% 5 17 10 11 15 4% 2% 3/ 6" (150mm) 19 8% 6% 18% 11% 11 15% 4% — 3% Installation Dimensions of 4" (100mm) & 6" (150mm) sizes I 7 f 8 ___ .. 1-L . =— I I■� MI III ) ICI - p 1998 ((� )) • O j INCA I,I 0 NODES U F-,� ." N I�11�(C )� _mri uvE - •i w I I / `/ './ i , ^ REUAELE-AUTOMATIC,C Ili 4 �� ^Q,Pill NKLER ' \ 11 l L .ua o.;eIP•ss r-co EML'J� V „� (' )) „ L lq IMAM t O �O ■ `I I � __ it MB ®m t °L-a:c:'I I I In I I —,_ C .� - F — H C I' _550Dat The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances,whenever applicable. Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by - The Reliable Automatic Sprinkler Co., Inc. ® er eliab' R � 800.431.1588 Sales Office p 800.848.6051 Sales Fax 914.668.3470 Corporate Office Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address PG.Printed in U.S 1/03 P/N 9999970045 40, State Pipe & Supply, Inc. THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE,AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 10 " Black and Galvanized Steel ERW Pipe Pipe Size _ Test Pressure Nominal O.D. I.D. Weight/Foot psi 1" 1.315 1.097 1.410 700 1-1/4" 1.660 1.442 1.810 1200 1-1/2" 1.900 1.682 2.090 1200 2" 2.375 2.157 2.640 2300 2-1/2" 2.875 2.635 3.530 2500 3" 3.500 3.260 4.340 1290 4" 4.500 4.260 5.620 1000 5" 5.563 5.295 7.780 1010 6" 6.625 6.357 9.300 1020 8.625 8_249 16.960 780 "8"wall thickness is 0.188, not SCH10 or 0.148"wall thickness. COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements, Percent(Product) C Mn P S Other Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 1 Residual elements max:Cu-0.40,Ni-0.40,Cr-0.40,Mo-0 15 and V-.08. These live elements combined shall not exceed 1%. Mechanical Properties-Tensile Requirements Strength-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 A 30,000 - 48,000 - NOTE: Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade. 961 5 S. Norwalk Blvd., Santa Fe Springs, CA 90670 • (562)695-5555 • FAX: (562) 692-1054 • www.statepipe.com 0. • State Pipe & Supply, Inc• THIS INFORMATION PROVIDED IS BASED ON ASTM GUIDELINES FOR WELDED PIPE SPECIFICATIONS AND ASTM REQUIREMENTS. ACTUAL PIPE AND MATERIAL TEST REPORTS PROVIDED WOULD MEET OR EXCEED THESE GUIDELINES. TEST REPORTS WOULD PROVIDE SPECIFIC AND ACTUAL DETAILS CONCERNING THE MECHANICAL AND CHEMICAL PROPERTIES OF THE ACTUAL PIPE, AS WELL AS ADDITIONAL TESTS RESULTS REQUIRED BY ASTM. SCHEDULE 40 Black and Galvanized Steel ERW Pipe Pipe Size Test Pressure Nominal O.D. I.D. Weight/Foot psi 1" 1.315 1.049 1.680 700 1-1/4" 1.660 1.380 2.270 1200 1-1/2" 1.900 1.610 2.720 1200 2" 2.375 2.067 3.660 2300 2-1/2" 2.875 2.469 5.800 2500 3" 3.500 3.068 7.580 2220 4" 4.500 4.026 10.800 1900 5" 5.563 5.047 14.630 1670 6" 6.625 6.065 18.990 1520 8" 8.625 7.981 28.580 1340 COMPOSITION AND PROPERTIES Chemical and mechanical properties requirements are as prescribed by applicable ASTM standards edition January 2006. Chemical Requirements, Percent(Product) C Mn P S Other Specification Grade max max max max ASTM A53 A 0.250 0.950 0.05 0.045 - 1 Residual elements max:Cu-0.40,Ni-0.40,Cr-0.40,Mo-0.15 and V-.0B. These live elements combined shall not exceed 1%. Mechanical Properties-Tensile Requirements Stren th-psi. Yield Tensile Specification Grade Min Max Min Max ASTM A53 A 30,000 - 48,000 - NOTE. Elongation requirements vary with nominal area of test specimen and specified minimum tensile strength of the steel grade. 9615 S. Norwalk Blvd., Santa Fe Springs, CA 90670 •(562)695-5555 • FAX: (562)692-1 054 •www.statepipe.com • :; :s k • • — . •:s 1 1 •;•0 t•111.•1• 11114 FireLock EZTM Rigid Coupling 1 t US ® LPCB VdS SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • STYLE 009 (UL, FM) STYLE 009V (UL, FM, VdS, LPCB) �:.- The FireLock EZ Style 009 and Style 009V couplings are rigid, installation-ready couplings for fire protection pipe joining. The coupling's unique design eliminates loose parts, insures consis- tent installation and provides substantial gains in productivity. IMPORTANT •• _ All FireLock EZ Style 009 and Style 009V couplings are recommended for use ONLY on fire protection systems. PATENTED STYLE 009 LISTINGS/APPROVALS t#§ The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Pipe Size Pressure Rating-psi Pipe Size Pressure Rating-psi Pipe Size Pressure Rating-psi 5 1%-2 1 175 ' 175 j 175 EZ T 114-2 300 ' 300 ' 300 MT 1 V.-2 1 300 1 300 300 10,40 154-4 300 300 300 FF 1 V.-4 300 300 300 MLT 1%.-2 300 300 300 BLT 1 r/4-2 300 300 300 ELF 1 V.-4 N/A N/A 300 ST 1 1/4-2 N/A N/A 300 DF 1 V.-4 300 300 300 FLT 1'/.-2 N/A N/A 300 STF 1 V.-4 N/A N/A 300 DT 1 IA-2 300 300 300 FLTL 1 V.-2 N/A N/A 300 TF 2 V.-4 N/A N/A 300 EF 1 V.-4 175 175 175 GL 1 V.-2 300 300 300 W L5 1 V.-2 300 300 300 EL 1 44-2 300 300 300 G5 11/4-2 175 175 175 WST 1V.-2 175 175 175 ET40 1 U.-2 300 300 300 G7 1 V.-2 300 300 300 XL 1 V.-2 300 300 300 EZF 3-4 300 300 300 _ MF 11/4-4 300 1 300 1 300 STYLE 009V LISTINGS/APPROVALS tt§ Pipe Schedule Size Pressure Rating v• Nominal Size f Inches i mm VdS LPC UL FM IIM 76.1 mm — 168ar 16 Bar 232 psi 232 psi 1 76.1 mm 16Bar 168ar 32 100 232 psi 232 psi 1 V. 16 Bar 20.7Bar 32 232psi 300 psi 11/2 16Bar 20.7 Bar 40 232psi 300 psi 10,40 2 — I — 16Bar 20.7 Bar 50 232psi 300psi 3 _ _ 16 Bar 20.7 Bar 80 232psi 300 psi 4 _ — 16 Bar 20.7 Bar 100 232psi 300 psi t Listed/Approved for wet and dry pipe systems(>-40°F/-40°C).For rigid pipe connections in systems operating below 0°F/-18°C Victaulic recommends Style 005 FireLock rigid couplings with Grade•C silicone gaskets. t Please refer to the Victaulic Field Installation Handbook(I-100)for details concerning when supplemental lubrication is required. §Style 009V couplings are VdS and LPC approved to 16 Bar/232 psi for wet and dry Fire protection systems. • JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com jctaulid VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. REV H 10.60 1 IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS .1.V.DU FireLock EZTM Rigid Coupling STYLE 009(UL, FM) STYLE 009V(UL, FM,VdS,LPCB) STYLE 009 DIMENSIONS Max. Max. Allow. Work. End Pipe End W Bolt/Nut Aprx. Press.• Load• Sep. t No.-Size Dimensions-Inches/mm Wgt.Ea. _ ' Actual ' '7 ' '.• - Pre assent „1 Y • Size Uia. psi __condition) 14' -..:J_ ._... .. �Z1 Numeral Outside C (Stab in Joint Assembled Inches Inches rsi Lhs. Inches Lbs. iL I*. w mm mm i kP.-, N mm Inches i X I Y X l Y 1 Z kg �� r� ►'1" Iv. 1.660 300 649 0.10 2-r/s x 2 3.13 4.93 2.86 4.83 1.93 1.5 J 32 42.4 2068 2888 2.54 80 125 73 123 49 0.7 U 1 y 1.900 300 851 0.10 2-%x 2 3.38 5.16 3.11 5.07 1.86 1.7 40 48.3 2068 3787 2.54 86 131 79 129 47 0.8 STYLE 009 PRE-ASSEMBLED 2 2.375 300 1329 0.12 2_y,x 21/2 3.88 5.81 3.59 5.68 1.86 1.9 (STAB IN CONDITION) 50 60.3 2068 5914 3.05 99 148 91 144 47 0.9 2 1 2.875 300 1948 0.12 4.38 6.21 4.08 6.10 1.87 2.0 Y r_Z 1 65 73.0 2068 8668 3.05 2 '/'x 2'h 111 1 SS 104 155 48 0.9 3 3.500 300 2886 0.12 2_,h x 2�fi 5.06 6.68 4.73 6.43 1.90 4.3 _� 80 88.9 2068 12842 3.05 129 170 120 163 48 2.0 �� Cu ��1 4 4.500 300 4771 0.17 2-�.x2rh 6.46 8.64 6.00 8.34 2.10 2.3 �_ 100 114.3 2068 21230 4.32 164 220 152 212 53 0 ` =11 • •@ t Refer to notes below. STYLE 009 JOINT ASSEMBLED STYLE 009V DIMENSIONS Max. Max. Allow. Work. End Pipe End ®Bolt/Nut Apra. Size Press. • Load• Sep.t Nor-Size Dimensions-Inches/mm Wgt.Ea. ActuaF' Pie-dssembted Y 11 r Z-x{ Nominal Outside (Stab in Size Dia. condition) Joint Assembled Inches Inches psi Lbs. Inche Lbs. [4 iii w mm mm kPa N mm s X Y x Y 2 kg �� r� ►t1 1 VI 1.660 300 649 0.10 2-M10 x 57 3.14 4.84 2.85 4.65 1.91 1.6 _ _• _ 32 42.4 2068 2888 2.54 80 123 72 118 49 0.7 1 1 1.900 300 851 0.10 2-M10 x 57 3.34 5.06 3.13 4.85 1.92 1.7 40 48.3 2068 3787 2.54 85 129 80 123 49 0.8 STYLE 009 PRE-ASSEMBLED 2 2.375 300 1329 0.12 2-M10 x 64 3.61 5.47 1.94 2.1 (STAB IN CONDITION) 50 60.3 2068 5914 3.05 92 139 49 0.9 3.000 300 1948 0.12 4.57 6.46 4.17 6.18 1.96 2.3 4 Y r-11 76.1 mm 76.1 2068 8668 3.05 2-M10 x64 116 164 106 157 50 1.1 13�i 3 3.500 300 2886 0.12 5.15 7.12 4.73 6.67 1.94 2.6 1 5t _ 80 88.9 2068 12842 3.05 2-M10 x64 131 181 120 169 49 1.2 ��; ri �'� 4 4.500 300 4771 0.17 2-M10 x64 6.39 8.74 6.05 8.46 EMI J: _ 100 114.3 2068 21230 4.32 162 222 154 215 Working Pressure and End Load are total,from all internal and external loads, based on STYLE 009 JOINT ASSEMBLED standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.See pages 3 and 4 of this document for Listed/Approved ratings on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t The allowable pipe separation dimension shown is for system layout purposes only. FireLock EZ couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 0 Number of bolts required equals number of housing segments. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. jct.aulie 10.60 2 REV H IPS CARBON STEEL PIPE—FIRE PROTECTION PRODUCTS I V.DU FireLock EZTM Rigid Coupling • STYLE 009 (UL, FM) STYLE 009V(UL, FM, VdS, LPCB) MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: • Orange enamel(North America) • Red enamel (Europe) Optional Coatings: • Hot dipped galvanized Gasket: • Grade"E"EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited,and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services within the rated working pressure. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. iCtauIIC.� REV H 10.60 • FireLock EZTM Rigid Coupling STYLE 009(UL, FM) STYLE 009V(UL, FM, VdS, LPCB) GENERAL NOTES NOTE:When assembling FireLock EZ couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009 and Style 009V couplings, use FireLock No. 006 end caps containing the"EZ" marking on the inside face or No. 60 end caps containing the"QV EZ"marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V couplings. • INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. III II11I III I IIIIIIIIIIII I1111I1111 WCAS-78KHHG For complete contact information,visit www.victaulic.com _ 10.60 3999 REV H UPDATED 11/2007 V Ictaulic• VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. - -•- 10.60 :: :.1 • • - :II f II 0 • 1, 1111110/411111.11114 Reducing Coupling cL 44> Is vds LPCB BE VMIPO SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS . STYLE 750 :l -- The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed F'• ,, to replace two couplings and a reducing fitting,the Style 750 features a special reducing , gasket for pressure responsive sealing.A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. *Ai.., UN 1Mil 101 Exaggerated for clarity MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel • Optional:Hot dipped galvanized and others Gasket: (Specify choice*): • Grade"E" EPDM (All other sizes) EPDM(Green color code). Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional:Assembly Washer:Galvanized,carbon steel Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. /CtSaUliC' REV I 06.08 1 CARBON STEEL PIPE -GROOVED COUPLINGS UO.UO ISO: ii1r.if1g3 ' ) '°)i-=', STYLE 750 - DIMENSIONS Max.Work Allow.Pipe Bolt/Nut@ Approx. Size Pressure' Max.End Load ' End Sep. r Deflect.Fr.Ci t No-Size Dimensions-Inches/mm Wgt.Each Nominal Per Pipe I Size psi Lbs. Cpig. In./Ft. Lbs. ., Inches/1nm kPa N Inches/mm Deg. mm/m Inches X Y Z kg 2 x 1 350 500 0-0.07 0°-57' 0.20 2-3/8 x 2 3.38 5.28 1.88 2.7 50 25 2410 2225 0-1.8 17 85 134 48 1.2 11/2 350 1000 0-0.07 0.20 3.38 5.28 1.88 2.0 40 2410 4450 0-1.8 0°-5T 17 2-3/8 x 2 85 134 48 1.0 21/2 2 500 2215 0-0.07 0.16 4.00 5.93 1.88 3.1 65 x 50 3450 9850 0-1.8 0 -47 14 2-3/8 x 2 102 151 48 1.4 76.1 mm x 2 350 1550 0-0.07 0.16 4.38 6.63 1.88 4,6 50 2410 6900 0-1.8 0'-4T 14 2-''/z x 2z1a 111 168 48 2,1 3 2 350 1550 0-0.07 0.13 4.75 7.13 1.88 4.9 80 x 50 2410 6900 0-1.8 0° 39' 11 2-'h x 2�a 121 181 48 2.2 21/2 500 3250 0-0.07 0.13 4.75 7.13 1.88 4.3 65 3450 14460 0-1.8 0'-39' 11 2-''/z x 2'k 121 181 48 2.0 350 2275 0-0.07 0.13 4.75 7.13 1.88 4.2 88.9mm x 76.1mm 2410 10125 0-1.8 0°-39' 11 2-'/x23//4 121 181 48 1.9 4 2 350 I 1550 0-0.13 0.28 6.25 8.90 2.25 8.1 100 x 50 2410 6900 0-3.2 1'-19' 25 2-5/8 x 3'/a 159 226 57 3.7 21/2 350 2275 0-0.13 1°-19' 0.28 2-5/8 x 3'/a 6.25 8.90 2.25 8.6 65 2410 10125 0-3.2 25 159 226 57 3.9 3 500 4810 0-0.13 1'-19' 0.28 2-5/8 x 3'/a 6.00 1 8.90 2.25 6.7 80 3450 21400 0-3.2 25 152 226 57 3.0 350 2475 0-0.13 0.28 6.25 8.90 2.25 6.9 114.3mm x 76.1mm r-19' 2-5/8x3'/, 2410 I 11014 0-3.2 25 159 226 57 I 3.1 5 x 4 350 5565 0-0.13 r 3' 0.22 2_3 x 4'/e 7.18 10.70 2.13 I 11.2 125 100 2410 24765 0-3.2 19 182 272 54 5.1 6 4 350 5565 0-0.13 0.18 I 8.63 11.90 2.25 16.7 '-52' 2-1/2x41/2 150 100 2410 24765 j 0-3.2 15 i 181 302 57 7.6 5 350 8500 0-0.13 0.18 8.31 11.90 2.25 12.9 0'-52' j 2-14x41/2 125 2410 37825 0-3.2 15 211 302 57 5.9 165.1 mm x 4 350 5565 0-0.13 0. S5, 0.19 ! 2_/4 x 4'/a 8.63 1 1.90 2.25 15.2 100 1 2410 24765 j 0-3.2 16 219 L 302 57 6.9 8 6 350 12000 0-0.13 0.13 10.81 14.88 2.50 22.4 200 x 150 2410 53400 0-3.2 ! 0'-38' 11 2-7/8 x 5 275 378 64 10.2 350 1625 0-0.13 0.13 10.75 14.88 2.50 23.2 219.1 mm x 165.1 mm 0'-38' . 2-7/8 x 5 2410 0-3.2 11 273 378 64 10.5 10 8 350 20450 0-0.13 0.9 13.12 17.26 2.62 31.4 x 0°-25' 2-1 x5 273 219.1 2410 0-3.2 8 1/2 333 438 67 i 14.2 Style 750 Reducing couplings should not be used with end caps(t/60)in systems where a vacuum may be developed.Contact Victaulic for details. *Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1'/z times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4-31/2720"/20-90 mm;25%for 4%100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. Y le-Z� < /YY rZ-• ti��:t� I (ril tit/�`\tti 11t�,l (� � „I ejli,ll ru � A v www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.8 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ICtaIU I tC 06.082 CARBON STEEL PIPE-GROOVED COUPLINGS V O.U8 Reducing Coupling STYLE 750 FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables. All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Equiv.Pipe Size Length Site Ieni;lh Nominal Nominal Size I Sm.Dia. Size Sm.Dia. Inches/rim I Fee Um Incheslmm Feethn 2 1 5.9 1 2 2.7 50 x 25 1.8 25 x 50 0.8 11 2.0 11 2 1.9 40 0.6 40 x 50 0.6 214 2 1.9 2 21 1.0 65 x 50 0.6 _ 50 x 65 0.3 76.1 mm x 50 0.6 76.1mm p0 3 2 5.5 3 3.5 80 X 50 1.7 80 1.1 21 3.8 4 3.0 65 1.2 100 0.9 88.9mm x 76.1 mm 3.2 65� x _ 80 0.8 4 2 6.0 4 3.0 100 x 50 1.8 100 0.9 65 b,g 76.1 mm x 88.9mm 0.8 3 6.0 114.3mm 09 114.3mm x 76.1 mm 6.8 &31 x 100 0.8 5 4 3.0 4 5 33 125 x 100 0.9 100 x 125 1.0 6 4 6.0 6 4.6 150 x 100 1.8 150 1.4 125 1.4 165.1 mm 4.4 165.1mm x 4 6.0 5 x 6 2.3 100 1.8 125 150 0.7 8 6 7.3 6 8 6.0 200 X 150 2.2 150 x 200 1.8 219.1 mm x 165.1 mm 123 165.1 mm x 219.1 mm 1.565 10 8 8.7 8 10 6.3 273 x 219.1 2.65 219.1 x 273 19.2 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. sCtaVIl i RFVI O6.OR3 • • • - ; IO . • , ,l.PIuI. Reducing Coupling STYLE 750 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 1111111111111111I IIIIIIU III IIIUII III WCAS-6UPKD7 For complete contact information,visit www.victaulic.com 06.08 1536 REV I UPDATED 6/2008 uctaauIIC* VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2007 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. 06.08 Flexible Couplin, 0 ® (vds LPCB RE VNIIPO SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • STYLE 75 4 , Style 75 is available where moderate pressures are expected or weight considerations are a factor. Up to 50%lighter in weight than the Style 77, the Style 75 coupling is recommended for service up to 500 psi/3450 kPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. • The Victaulic standard flexible coupling offering for grade"EHP"or"T"gaskets is the Style 177 installation ready flexible coupling. For all available sizes,the Style / 177 is the standard flexible coupling Victaulic supplies in North America for piping in&`�_ systems using Grade"EHP"or"T"gaskets.Contact Victaulic for further details. Exaggerated for clarify MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel. • Optional:Hot dipped galvanized and others. Gasket: (specify choice*) • Grade"E" EPDM EPDM(Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range;except hot,dry air over+140°F/+60°C and water over +150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. NOTE:Additional gasket styles are available.Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com jctaulic' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.. REV M 06.05 1 CARBON STEEL PIPE-GROOVED COUPLINGS V O.V D Flexible Coupling STYLE 75 • DIMENSIONS Max.Work Allow.Pipe Bolt/Nut@ Approx. S ze Pressure" Max.End Load• End Sep.t Deflect.Fr.CO No-Size Dimensions-Inches/mm Wgt.Each Actual ' Nominal Outside Size Diameter Per Pipe Inches Inches psi :"s.' Inches Cplg. In.Ht. Lbs. mm mm kPa N mm Deg. mm/m Inc hr.-. K Y Z kg 1 1.315 500 680 0-0.06 0.57 238 4.27 1.77 1.3 25 33.4 3450 3025 0-1.6 2'-43 48 2-s°x 2 61 108 45 0.6 11/4 1.660 500 1080 0-0.06 0.45 2.68 4.61 1.77 1.4 32 42.2 3450 4805 0-1.6 2'-10 38 2-Vi x 2 68 117 45 0.6 1 K 1.900 500 1420 0-0.06 0.40 2.91 4.82 1,77 1.5 40 483 3450 6320 0-1.6 I'-56' 33 2-Ye x 2 74 122 45 0.6 2 2.375 500 2215 0-0.06 0.32 3.43 5.22 1.88 1.7 50 603 3450 9860 0-1.6 I'-31' 26 2-Ye x 2 87 133 48 0.8 21/2 2.875 500 3245 0-0.06 0.26 3.88 5.68 1.88 1.9 65 73.0 3450 14440 0-1.6 1 -IS 22 2-Vex 2 98 144 48 0.9 3.000 500 3535 0-0.06 0.26 4.00 5.90 1.88 1.9 76.1 mm 76.1 3450 15730 0-1.6 r-12' 22 2-r/i x 2 102 150 48 0.9 3 3.500 500 4800 0-0.06 0.22 4.50 7.00 1.88 2.9 80 88.9 3450 21360 0-1.6 1 -2 18 2 K x 236 114 178 48 1.3 31/2 4.000 500 6300 0-0.06 0.19 5.00 7.50 1.88 2.9 90 101.6 3450 28035 0-1.6 0'-54' t6 2-K x 216 127 191 48 1.3 4 4.500 500 7950 0-0.13 0.34 5.80 8.03 2.13 4.1 100 114.3 3450 35380 0-3.2 1 -36' 28 2-K x 21/i 147 204 54 1.9 4.250 450 6380 0-0.13 0.35 5.55 7.79 2.13 3.7 108.0mm 108.0 3100 28395 0-3.2 1'-41' 29 2 12x70.0 141 198 54 1.7 4 K 5.000 450 8820 0-0.13 0.25 6.13 9.43 2.13 5.5 120 127.0 3100 39250 0-3.2 1'-2b' 21 2-Vex 3 y4 156 240 54 2.5 5 5.563 450 10935 0-0.13 0.27 6.88 10.07 2.13 5.8 125 141.3 3100 48660 0-3.2 I'-18 23 Vex 3% 175 256 54 2.6 5.250 450 9735 0-0.13 0.28 6.55 9.37 2.13 6.0 133.0mm 133.0 3100 43325 0-3.2 I'-21 24 2-16 x 82.5 166 238 54 2.7 5.500 450 10665 0-0.13 0.28 6.80 9.59 2.13 6.3 139.7mm 139.7 3100 47460 0-3.2 1'-18' 24 2-s/a x 3 Vi 173 244 54 2.9 6.000 450 12735 0-0.13 0.21 7.38 10.48 1.88 6.2 15 Z4 mm 152.4 3100 56670 0-3.2 I'-12' 18 2-%x 3 y. 187 266 48 2.8__ 6 6.625 450 15525 0-0.13 0.23 8.00 11.07 2.13 7.0 150 168.3 3100 69085 0-3.2 1 -5 18 2-5/x x 3% 203 281 54 3.2 6.250 450 13800 0-0.13 0.24 7.63 10.49 2.13 6.8 159.0 mm 159.0 3100 61405 0-3.2 I 9 20 2-16x82.5 194 266 54 3.1 8 8.625 450 26280 0-0.13 0.18 1034 13.97 2.32 12.4 200 219.1 3100 116945 0-3.2 0'-50' 14 2-3f x 4 y. 263 355 59 5.6 " Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for Y4-31/2720-90mm;25%for 47100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. ix Y ft-z-1 41 1 iii '''. uTo I gal www.victaulic.com \CteUIiC' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED 06.05 2 REV M 1::Ok " - ; V I • 111.1 01+111 Flexible Couplin5•, STYLE 75 WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. For complete contact information,visit www.victaulic.com 06.05 1470 REV M UPDATED 2/2011 ICtaulicr VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 06.05 IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS 1 0.04 VICIAUIIC' IS AN h000001 f_EanF 1ED('OMPA`JY Style 744 FireLock® Flange Adapter VIC =;_ r r ; ; with Vic-Plus TM Gasket System Gasket System PRODUCT DESCRIPTION Style 744 FireLock Flange adapter is designed for directly incorporating flanged components with ANSI CL. 125 or CL. 150 bolt hole patterns into a grooved pipe system. Sizes 2 -8"(50 - 200 mm)are hinged for easy handling with integral end tabs which facilitate assembly. � The design incorporates small teeth inside the key shoulder I.D.to prevent rotation. L..' ID Because of the outside flange dimension, FireLock Flange adapters should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting,check disc dimensions to - - assure proper clearance. FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. Mating rubber faced flanges,valves, etc., require the use of a FireLock Flange washer. 2.8"Sizes FireLock Flange adapters with Vic-Plus gaskets do not require lubrication.The gasket must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. 4.%_tr-,s. Style 744 FireLock Flange Adapters with the Vic-Plus TM Gasket System are designed and ��I�i�N recommended for use ONLY on fire protection systems. �h,� Vic-Plus Gasket System: Mill Victaulic` now offers a gasket system which requires no field lubrication on wet pipe systems. The Vic- PlusTM System (patented) is dry,clean, and non-toxic. It reduces assembly time substantially and �I II!��I, eliminates the mess and chance of over-lubrication. Please refer to the latest copy of the Victaulic Field ll Installation Handbook(1-100)for supplemental lubrication requirements. ■■ iii See Victaulic (Exaggerated for clarity) publication 10.01 for details. DIMENSIONS Style 744 Sealing Sizes 2-8"(50-200 mm) Surface Dimensions ANSI Class 125 and 150 Flange Pipe Max. Max. Incheslmm Incheslmillimeters Apt Actual Work End WgL Z14-- Nominal Outside Press.' Load' No. Bon Each Diameter Diameter PSI Lbs. Bolts f Size t "A" "B" Lbs. In/mm Inform kPa N Req'd. Inches Max. Min. W X V Z kg Q 2 2.375 175 775 2.38 3.41 6.75 6.00 4.75 0.75 2.7 Pt 50 60.3 1200 3450 4 ''/a X 27/4 60 87 172 152 121 19 1.2 MM Y W 2/2 2.875 175 1135 q le X 3 2.88 3.91 7.88 7.00 5.50 0.88 4.2 65 73,0 1200 5050 73 99 200 178 140 22 7,9 O`�O 3 3.500 175 1685 5 3.50 4.53 8.44 7.50 6.00 0.94 4.8 0 A 80 88.9 1200 7500 4 /a X 3 89 115 214 191 152 24 2.2 4 4.500 175 2780 4.50 5.53 9.94 9.00 7.50 0.94 7.1 100 114.3 1200 11045 8 /8 X 3 114 141 252 229 191 24 3.2 Note:Gray area of mating face must 5 5.563 175 4250 5.56 6.71 11.00 10.00 8.50 1.00 8.3 be free from gouges.undulations or 125 141.3 1200 18920 8 3/4 X 31/z 141 171 279 254 216 25 3,8 deformities of any type for effective scaling. 6# 6.625 175 6030 s 6.63 7.78 12.00 11.00 9.50 1.00 9.3 150 168.3 1200 26840 8 /°X 3/2 168 198 305 279 241 25 4.2 8#200 8.625 1200 45475 8 3/4 X 31/2 8.63 9.94 14.63 13.50 12985 1.13 is 9 Refer to notes below. t Total bolts required to be supplied by installer.Bolt sizes for conventional flange-to-Mange connection.Larger bolts are required when Vic-Flange adapter is utilized with wafer-type valves. #Not available with Vic-Plus gasket system.Lubrication is required. NOTES -working Pressure and End Load are total,from all internal and external loads,based on standard weight steel pipe.standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 112 times the figures shown. Style 744 FireLock Flange adapters provide rigid joints when used on pipe with standard roll or cut groove dimensions and consequently allow no linear or angular movement at the joint. WARNING:Depressurize and drain the piping system before attempting to install.remove,or adjust any Victaulic piping products. •REGISTERED TRADEMARK OF VICTAUUC-C COPYRIGHT 2004 VICTAUUC-PRINTED IN U.SA 1477 REV D Victaulic Company of America•Phone.1-800-PICK-VIC(1-800-742-5842)•Fax:610-250-8817•e-mail:pickvic@victaulic.com Victaulic Company of Canada•Phone:905-884-7444•Fax:905.884-9774•e-mail:viccanada @viclaulic.com Victaulic Europe•Phone:32-9.381 1500•Fax:32-9-380-4438•e-mail:viceuro@victaulic.be Victaulic America Latina•Phone:610-559-3300•Fax:610-559-3608•e-mail:vical@victaulic.com 4tauIac 9 Victaulic Asia Pacific•Phone:65-6235-3035•Fax:65-6235-0535•e-mail:vicap@victaulic.com I 10.04 VIC-FLANGE ADAPTER NOTES The Style 744 (2-8'/50- 200 mm)design incorporates small teeth inside the key shoulder I.D.to prevent rotation. 2 FireLock Flange adapter should not be used on FireLock fittings.When wafer or lug-type valves are used adjoining a Victaulic fitting, check disc dimensions to assure proper clearance. 3 FireLock Flange adapters should not be used as anchor points for tie-rods across nonrestrained joints. Mating rubber faced flanges,valves,etc. require the use of a FireLock Flange washer. 4 Area A-B noted in the above drawing must be free from gouges,undulations or deformities of any type for effective sealing. s FireLock Flange adapter gaskets must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange. o Flange Washers:FireLock Flange adapters require a smooth hard surface at the mating flange face for effective sealing. Some applications for which the Vic-Flange adapter is otherwise well suited do not provide an adequate mating surface.In such cases,it is recommended that a metal Flange Washer be inserted between the FireLock Flange adapter and the mating flange to provide the necessary sealing surface. Typical applications where a Flange Washer should be used are: A When mating to a serrated flange:a standard flat flange gasket should be used adjacent to the serrated flange and then the Flange Washer is inserted between the FireLock Flange adapter and the flange gasket. B When mating to a wafer valve:where typical valves are rubber lined and partially rubber faced(smooth or not),the Flange Washer is placed between the valve and the FireLock Flange adapter. e When mating a rubber faced flange: the Flange Washer is placed between the FireLock Flange adapters and the rubber faced flange. o When mating AWWA cast flanges to IPS flanges:the Flange Washer is placed between two FireLock Flanges. The hinge points must be oriented approximately 90°to each other. If one flange is not a FireLock Flange adapter(e.g.flanged valve),then a standard flat flange gasket must be placed adjacent to that flange and the Flange Washer inserted between the flange gasket and the FireLock Flange adapter. E When mating to components(valves,strainers, etc.)where the component flange face has an insert: follow the same arrangement as in Application 1. F When mating to a Series 705-W Butterfly valve, Style 744 may only be used on one side of the connection. When ordering Flange Washers,always specify product style(Style 744)and size to assure proper Flange Washer is supplied. MATERIAL SPECIFICATIONS Flange Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Coating: Black enamel • Optional: Hot dipped galvanized Bolts/Nuts: Supplied by installer Gasket: • Grade"E"EPDM-Type A Vic-Plus Gasket System A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Ap- proved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated work- ing pressure using the Grade"E"Type A Vic-Plus Gasket System,requiring no field lubrication for most installation conditions. A Standard gasket approved for dry pipe systems to-40°F(-40°C).Based on"typical"pipe surface conditions.supplemental lubricant is recommended for services installed below 0'F(•18°C)and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water.Supplemental lubrication may also be rquired on pipe with raised or undercut weld scams or pipe that has voids and/or cracks at the weld seams. This product shall be manufactured by Victaulic Company.All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications.designs and standard equipment without notice and without incurring obligations. 2 Style 744 FireLock® Flange Adapter ® �� ® �C LPCB Vds Lrj FireLock® Fittings VNIIPO See Victaulic publication 10.01 for details • FireLock®products comprise a unique system specifically designed for fire protection CIA services. FireLock full-flow elbows and tees feature CAD-developed,hydrodynamic design,affording a shorter center-to-end dimension than standard fittings.A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Victaulic IPS-sized couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005 couplings. 0 11 • MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12. Fitting Coating: • Orange enamel. • Red Enamel in EMEA-I. • Optional:Hot dipped galvanized. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.O 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaulic* REV I 10.03 1 IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS I V.V 3 FireLock® Fittings DIMENSIONS CtoE�I _¢ t E __ +_p I CtoE _U 0 _ .-i g ..r.... 13 �` to rr- tom j 1 ���� I-i NO.001 NO.003 NO.002 NO.006 No.001 No.003 No.002 No.006 Sire 90`Elbow 45 Elbow Straig it Tee Cap Nominal Actual Approx. Approx. Approx, Approx. Size Outside Diameter C to E Weight Each C to E Weight Each C to E Weight Each Thickness"T" Weight Each Inches Inches Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs. rem mm mm kg mm 1 kg mm kg mm kg 1'/a 1.660 0.8 0.3 32 42.4 21 0.1 1'/a 1.900 - - - - - - 0.82 0.4 40 48.3 - - - - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 21/2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 57 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 3.30 2.25 2.4 - - - 76.1 76 1.5 57 _ 1.1 _ 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 4.250 4.00 5.7 3.00 5.1 4.00 7.5 108 mm 108.0 102 2.6 76 2.3 102 3.4 4 I 4.500 4.00 6.7 3.00 5.6 4.00 8.7 I 1.00 2.4 100 114.3 102 3.0 I 76 2.5 102 3.9 25 I 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88_ - 15.7 1.00 4.1 125 141.3 124 5.7 83 3.8 124 7.1 25 1.9 - - 159mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 _ 158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 5.3 140 10.3 25 2.7 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iOtaulILe 10.03 2 REV IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS 1.V.V 3 FireLock® Fittings • FLOW DATA Frictional Resistance Size Equivalent Feet/meters of Straight Pipe 1 Actual No.002 Nominal Outside Straight Tee Size Diameter Inches Inches No.001 ( No.003 mm mm 90°Elbow 45°Elbow Branch f Run 1'/a 1.660 1.5 0.8 3.7 1.5 32 42.4 0.5 0.2 1.1 0.5 1Y 1.900 2.2 1.1 5.5 2.2 40 48.3 0.7 0.3 1.7 0.7 2 2.375 3.5 1.8 8.5 3.5 _ 50 60.3 1.1 0.5 2.6 1.1 2' 2.875 4.3 2.2 10.8 4.3 65 73.0 1.3 0.7 3.3 1.3 3.000 4.5 2.3 j 11.0 4.5 76.1 mm 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 08 mm 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 59 mm 6.250 9.4 4.9 25.0 i 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 1.5 7.6 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 t The flow data listed is based upon the pressure drop of Schedule 40 pipe. www.victaulic.com jctaulic° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I 10.033 FireLock® Fittings GENERAL NOTES NOTE:When assembling FireLock EZ couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009/009V/009H couplings, use FireLock No. 006 end caps containing the"EZ" marking on the inside face or No. 60 end caps containing the "QV EZ"marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H couplings. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.03 1539 REV I UPDATED 2/2010 \ictaulic+° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.03 F exHea ' commercia ire sprin er connections . ._ . . . _ , ,, ., -- - . , ', • , - ,-,z.--vi.,,, 1-''''4- ' - .. , •.'-,1 ;444.1! .::- • :.: , •_.:;: jskv......_.. . ,, • , -:,01 ..,, • ... Flk■-• ...,,+-4, --'-. '',.. ,*- •,. • - L', %Ai , ,, - '-V,,, •,,,,'., v,,.. ,.,,,A,,,,,i.,:,:.-. - ',-.4.. ' P . __. -_,.,'-f-.-f--: . '...44.V., ..,,,,„,...1..,,L'4,-, --.- , .....„ '.. ._,. . .-",..--: -„,7-,:..' : -• ...oily ,,'", _,,..,,..:''' 1-.'-'-'.-'7--• '' . • V ; 1. k., ••• •• .., ,-, • .A :, .. ',,,'1400. ;6.6.4- , . . ,1,. - , ... - .-.....-4!•• ., 1 .,,t4w Ili t . . . •-, , .., ■ rj .•.':..' .. . ..•i.4-2:•/•■• 7,..d,.:1, .,.27k.11 . - _........ ..,• .....■•■••••■••—• VII' . I .,...... .'..W■••.'''' . '.. .R • . . 7i/, 1- • .1 A.''' .7.' ; , 10 • ' 1 . . ,i 1 ) :,,;,,j, ' ,'... • , . i 111 • • , . - .. ,—..„„A I, • .. , • ...- 4 / 4111114 I - • , , • , *or..A - . . 411P i . ...........,--__.. ..,_ ... . , ' N, ii I, ■ ,•.„ ■ ix7 1', • A •4-• ' . . ' ',;''• .,■',..',, .! ,, ,.., i • '\li -1-, . .!.: - 4 • .. - .4. ...?.-:.*-:•:_L- '" A . • ..., , :4;',-r, . , •.- ,,. , . . i-- ... 76564*116464,,, .....40-- it FL . XHEA , 1 . ws, • INDUSTRIES Your connection to • • • The best idea in sprinkler systems since water higher prod., :uctivrt ....' / . ., . And tower costs. , •,,,Iii..,,, . rev •rs- (2 --... (11 ' c(Du ` .0-4 i iirvirrai almwrlii APPROVID ::--j : - '-' '.' ' ':' - ''f'..' ...'''-' ' ."-.. ' - '''1-:. . '' ':'. '''r'' ''' ' I■ N.Y.C. MEA #261-99-E CA: OPA-0672 7 � J , k lil 1s 1r ic io � � as a am Sar , fc io1 FlexHead Outlet Hose Maximum FM/UL Maximum Maximum Maximum Rated Model St Size Assembly Number of Equivalent Length Ambient Pressure in(cm) Length 90-Degree Length of Temperature t ft(m) Bends Schedule 40, Rating (3 in. Nominal 1 in. F(C) 3 1410 Bending Diameter Pipe, ft H-Series i i Radius) FM/UL psi (kPa)/psi (kPa) 2024, 2024H 1/2(1.27) 2(0.6) 3 3.5/11 300°(148°) 175(1205)/300(2068) I 2036, 2036H 1/2(1.27) 3(0.9) 3 4.8/16 300°(148°) 175(1205)/300(2068) 2048, 2048H 1/2(1.27) 4(1.2) 4 6.8/24 300°(148°) 175(1205)/300(2068) ■ f --I 2060, 2060H 1/2(1.27) 5(1.5) 4 8.5/29 300°(148°) 175(1205)/300(2068) 1 2072, 2072H 1/2(1.27) 6(1.8) 4 8.9/35 300°(148°) 175(1205)/300(2068) i Z 2024, 2024H 3/4(1.90) 2(0.6) 3 7.8/12 300°(148°) 175(1205)/300(2068) 2036, 2036H 3/4(1.90) 3(0.9) 3 8.1/18 300 0(148 0) 175(1205)/300(2068) 1 C) 2048, 2048H 3/4(1.90) 4(1.2) 4 17.9/23 300 0(148 0) 175(1205)/300(2068) 1 __ 2060, 2060H 3/4(1.90) 5(1.5) 4 19.9/29 300°(148°) 175(1205)/300(2068) 2072, 2072H 3/4(1.90) 6(1.8) 4 24.3/32 300 0(148 0) 175(1205)/300(2068) 2024E, 2024HE 1/2(1.27) 2(0.6) 3 5.5/19 300°(148°) 175(1205)/300(2068) 2036E, 2036HE 1/2(1.27) 3(0.9) 3 6.8/23 300 0(148 0) 175(1205)/300(2068) t +--1 2048E, 2048HE 1/2(1.27) 4(1.2) 4 8.8/27 300°(148°) 175(1205)/300(2068) 2060E, 2060HE 1/2(1.27) 5(1.5) 4 10.5/32 300°(148°) 175(1205)/300(2068) ce 2072E, 2072HE 1/2(1.27) 6(1.8) 4 10.9/35 300°(148°) 175(1205)/300(2068) 2024E, 2024HE 3/4(1.90) 2(0.6) 3 9.8/18 300°(148°) 175(1205)/300(2068) 2036E, 2036HE 3/4(1.90) 3(0.9) 3 10.1/23 300 0(148 0) 175(1205)/300(2068) 2048E, 2048HE 3/4(1.90) 4(1.2) 4 19.9/23 300°(148°) 175(1205)/300(2068) 2060E, 2060HE 3/4(1.90) 5(1.5) 4 21.9/29 300°(148°) 175(1205)/300(2068) 2072E, 2072HE 3/4(1.90) 6(1.8) 4 26.3/32 300 0(148 0) 175(1205)/300(2068) Model Numbers: The"H"designates high pressure unit rated to 300 psig and the"E"designates elbow style unit. FlexHead products are intended for use in hydraulically designed wet, pre-action, deluge or dry pipe sprinkler connections per NFPA 13, 13R, and 130 guidelines. The hydraulic loss of the FlexHead connector needs to be included in the hydraulic design calculations the same as a valve or fitting.Each FlexHead sprinkler drop has a 3"minimum bend radius per UL guidelines, and a 7" minimum bend radius per FM guidelines. Equivalent lengths are shown with maximum number of 90 degree bends at the minimum bend-radius. Different values were obtained by FM and UL due to the differences in minimum bend radius,testing protocol and calculation methods. Please see individual testing standards for more information relative to friction Pressure surges aren't a risk for FlexHead loss (Equivalent Length of Pipe). 0 connection systems. Our fully braided r J stainless steel hose is rated , , , 'itam 300 psi. tt Let FlexHead make your connection today.. ' Engineers Contractors Owners .14.114,1,1* ~ rte` Stainless steel.quality Lower installation costs Shorter time to occupancy �ii�1,. .,1.;'" . at black iron costs More productive installers Lower reconfiguration cos /mg „' Fast-track construction No p unch list items Cost effective code 0x ," ' ,' Their 1� lr. ' - industrial-grade Simplified project Highest quality available compliance i- �(. . r< 9 P P J 9 q Y � : ,,a. management Lower total costs I.1, � .,;:' * ' construction is■More flexible scheduling /ha Cost-effective code of ownership , ,,h . - all-welded, with Competitive advantage ,_ �. r° compliance - • . no 0-rings. for your company � -I " Seismically qualified ,,"f,�' ° Connect sprinkler heads to sub-mains at • least four times faster. . FlexHead systems connect sprinkler heads to sprinkler sub-mains in about a quarter of the time it takes to install hard pipe. Add in the fact that less-skilled people can do the work, and you're looking at significant productivity gains. Expect even greater savings in retrofits, where Want pinpoint locations? No problem. FlexHead installs six to seven times faster than The design makes it easy to accurately locate hard pipe. sprinkler heads every time. If the spec calls for Everything about FlexHead says "fast installation." center-of-tile placement, you can do it with ease. You don't need to install bracing or hangers. There's In fact, you get center-of-tile placement every no on-site assembly. Every sprinkler connection is a install whether the spec calls for it or not. It takes finished, pre-constructed assembly, from the 1" pipe one more headache out of specifying and bidding. connector to the sprinkler head outlet. Accommodate floor plan changes. You pay a little more for FlexHead connections Need to relocate sprinkler heads? No problem. With compared to black iron armovers. But their labor its built-in flexibility it's much easier to move heads savings far exceed the materials premium. to a new location to accommodate new layouts or Installation is simple uses of the space. It doesn't matter whether the sprinkler head is Retrofits in less time. semi-recessed, full pendant or fully concealed, it's a Need to comply to code in unsprinklered buildings? snap to attach to a FlexHead connection system. In contrast to costly and labor-intensive hard-pipe Q Attach the bracket to t-bar ceiling grid. retrofits, FlexHead connections install in minutes in O Connect the FlexHead sprinkler drop to even the most restrictive spaces. the submain. Shorten your time to occupancy. Q Secure sprinkler drop to the bracket. Faster installation times help get end-users into That's it! No more wasted hours spent hard-piping. No their spaces more quickly—and get installers on more frustration over changes to blueprints. No more their next projects faster. FlexHead connections lost time fixing leaks and other problems common to virtually eliminate punch list items commonly hard-pipe armovers. found with hard-pipe armovers. Each connection is ready to install right out of the box. It comes complete with a mounting bracket— = + + - compatible with any suspended or Sheetrock ceiling Millions of tons of water are drained from system—and a one-piece, leak-tested FlexHead sprinkler piping every year. FlexHead products sprinkler drop. help minimize hydrostatic testing and eliminate the need to drain down the system when relocating sprinkler heads. Three steps to faster installations. inwpwirit of rrt +, IA I Att V ; ; . Attach bracket to t-bar ceiling grid. Connect FlexHead sprinkler drop to submain. Secure FlexHead sprinkler drop to bracket. Connection also compatible with Sheetrock ceilings . .,.._ .._ 1 3 ..i.kkol,, , . ::::b:......, :t,kt. ra.tt:;o.. . _ .,.• it, Elbow style unit used in confined space Adjustable Bracket Design: for use with T-bar applications. grid, metal stud and Chicago grid applications. FM approved and UL listed Fully guaranteed All FlexHead sprinkler connections are Factory FlexHead has always maintained a commitment to Mutual Approved and Underwriters Laboratories quality. We pressure- and leak-test every FlexHead listed for suspended or sheetrock ceiling connection at our FM- and UL-audited factory. Burst installations. Tests include hydrostatic pressure, pressures exceed 3,000 pounds. Every product is vibration, friction loss, fatigue, head deployment, covered by our comprehensive limited warranty. corrosion and water hammer. Choose the length you need Our commercial connections also conform to these FlexHead connections are available in 2', 3', 4', 5' and industry standards: 6' hose lengths, and easily fit any sprinkler head on • Approved for use in suspended ceilings the market Outlets can accommodate both '/z" and '/4" with light, medium, and heavy-load grids sprinkler heads. (ASTM C-635 and C-636) Call, write or visit our website • They're the only flexible sprinkler connection FlexHead Industries offers everything you need to qualified for use in Seismic Design Categories specify, bid and install higher quality fire protection. C, D, E and F Let us make your connection today. Get in touch via • International Building Code (IBC) compliant the method that suits you best: without needing an unsightly oversized ring, • E-mail salesl @flexhead.com with questions and sleeve or adaptor where the ceiling meets the requests. sprinkler head • Call toll-free 800-829-6975 to speak to a • Compatible with BlazeMaster" fire sprinkler representative. systems • Visit www.flexhead.com for data sheets and • Meets all NFPA 13 guidelines and is demonstrations. specifically referenced in the 2007 edition New construction comparison Retrofit comparison 5 �� ( ( 5 � 5 5 T FlexHeads :))SS' )S SSS • FexHeads( ,art ipe 1-11 ril 1 Hard Pipe During a typical installation, a minimum of 4 During a typical installation, a minimum of 6 FlexHeads can be installed in the the same time it FlexHeads can be installed in the the same time it takes to do 1 hard-Bile. takes to do 1 hard-ii se. FlexHead metal stud detail Iii � C' 11' ta��1'/1�y�1 � � -�1t �>�i�, (: <-,,I il�� ��� � (0-6-,(16 ir�[9 t p •# �1�'f{,� �( I,;' ids ' .. .I I., . . Sprinkler 441+ 011 , {• r W ` branchline Pi, . i. 11 ations. Their advanta ! �p FlexHead �11�1111111,14 i.i `- hem cost-effective Sprinkler Drop h�+/�1 , \', , commercial job. (All 304 stainless Ir`'++� steel including 1(111A1 fittings) t1 Metal stud Adjustable hub mounting bracket �" ' ' ► - /l _4 , , ... . , - Metal stud * lions Sheetrock ceiling Sprinkler head (not included) FlexHead suspended ceiling detail 1f , 01 a Ili, 1 Sprinkler branchline 1111 FlexHead III lii '1+1 l Sprinkler Drop lt (All 304 stainless tit 111 steel including fittings) Ceiling grid Imell=511.41k 7.11.1;1'="15114 mounting bracket Adjustable hub I H)� iN. �! I Suspended r---�"` t-bar grid Ceiling tile Sprinkler head ,. -fiL (not included) r � �, "'"'. Each FM approved., IR listed, LPCB certified unit is ready-to-install, pressure- and leak-tested, and comes complete with a flexible stainless steel hose and mounting bracket with adjustable hub. Ffrqr—il ' )1111 ' \ 3 1 1 IL kv.. _ t:_-�j .' O i 4 .. .,.; 't... ;.: ...–..s..–_ ,-7.�Ir.w. ... 'a �^-i.TS+`'r`:. .r,{�c.i .. ., .u, t�c+-i'is�-�1?'t.c� • - .. .- r Y'Fy ,- .A...-y. Your security is our business. FlexHead Industries was founded in 1992 to help engineers, builders and owners increase the safety of their buildings. Our patented sprinkler connection technologies show that it's possible to comply with codes cost-effectively. We're proud to help Y reduce the risks of property damage and "} loss of life in a wide variety of buildings, , domestically and world-wide. .„ , r FlexHead manufactures ' s sprinkler connections for i' 1. all types of applications s., N., including: ,1:: I ; r . Commercial Exhaust ducts Institutions • Government • Aerospace • Concrete penetrations • Hospitals • Automotive for sidewall and Seismically pendant applications y • Offices • Biotechnology • Correctional centers qualified. • Restaurants • Electronics • Retail • Forest products/ • Mental health facilities FlexHead connections allow • Schools paper pulp for independent movement • Laboratories between sub-mains and Cleanrooms ceilings. They're the only • Petrochemical flexible s r nkler connection • Biotechnology P • Electronics • Pharmaceuticals to be qualified for use in • Restaurants Seismic Design Categories • High-end commercial C, D, E and F ceilings • Semiconductors • Pharmaceuticals • Steel manufacturers • Semiconductors . /' f INDUS ; - APPEU1EO LISTED The best idea in sprinkler systems since wate U.S.and international patents pending:#6,123,154, 06,119,784, 56 Lowland #6,752,218,#7,032,680,#6,488,097. Holliston, Massa The FlexHead name and logo are trademarks of FlexHead Industrie' toll-free 800-829 FGG/BM/CP System Compatible indicates this product has been tested and is monitored on an ongoing basis to assure chemical (508) 893-9596 compatibility with FlowGuard Gold', BlazeMaster,and Corzan pipe fax (508) 893-6020 and fittings. FGG/BM',FlowGuard Gold', BlazeMaster',and Corzan'are registered info @flexhead.com trademarks of Noveon IP Holdings Corp. www.ftexhead.com 5M/SDP/03-09 ` P PS10 SERIES 0 The Symbol of Protection PRESSURE SWITCH •- - (UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA Accepted,CE Marked Pending) Dimensions: 3.78"(9,6cm)W x 3.20"(8,lcm)D x 4.22"(10,7cm)H ©POTTER Conduit Entrance:Two knockouts provided for 1/2"conduit. Individual switch compartments and ground screws suitable for P102 (E dissimilar voltages. Enclosure: Cover-Die-cast with textured red powdercoat finish,single cover screw and rain lip. Base-Die-cast Pressure Connection: Nylon 1/2"NPT Male Factory Adjustment: 4-8 PSI(0,27-0,55 BAR) Differential: 2 PSI(0,13 BAR)typical Maximum System Pressure: 300 PSI(20,68 BAR) Patent Pending Switch Contacts: SPDT(Form C) I0.1 Amps at I25/250VAC,2.0 Amps at 30VDC Ordering Information One SPDT in PS 10-I,Two SPDT in PS 10-2 Model Description Stock No. Environmental Specifications: PS 10-I Pressure switch with one set 1340103 NEMA 4/IP55 Rated Enclosure-indoor or outdoor when used SPDT contacts with NEMA 4 conduit fittings. PS I0-2 Pressure switch with two sets 1340104 Temperature range:-40°F to 140°F(-40°C to 60°C) SPDT contacts Service Use: Hex Key 5250062 Automatic Sprinkler NFPA-l3 Cover Tamper Switch Kit 0090200 One or two family dwelling NFPA-13D Tamper Residential Occupancy up to four stories NFPA-I 3R Cover incorporates tamper resistant fastener that requires a special key for National Fire Alarm Code NFPA-72 removal.One key is supplied with each device. For optional cover tamper switch kit,order Stock No.0090200. See bulletin#5401200 PSCTSK. Installation The Potter PS 10 Series Pressure Actuated Switches are designed for the into alarm port piping on the input side of retard chamber and electrically detection of a waterflow condition in automatic fire sprinkler systems of connect PS I0 to control unit that provides a retard to compensate for surges. particular designs such as wet pipe systems with alarm check valves,dry Insure that no unsupervised shut-off valves are present between the alarm pipe, preaction,or deluge valves. The PSIO is also suitable to provide a check valve and PSIO. low pressure supervisory signal;adjustable between 4 and 15 psi(0,27 and Method 2: When using the PS 10 for local bell application or with a control 1,03 BAR). that does not provide a retard feature-the PS 10 must be installed on the alarm I.Apply Teflon tape to the threaded male connection on the device. outlet side of the retard chamber of the sprinkler system. (Do not use pipe dope) Testing: Accomplished by opening the inspector's end-of-line test valve. 2.Device should be mounted in the upright position(threaded connection down). Allow time to compensate for system or control retard. 3.Tighten the device using a wrench on the flats on the device. Note: Method 2 is not applicable for remote station service use,if there is an Wiring Instructions unsupervised shut-off valve between the alarm check valve and the PS10. I. Remove the tamper resistant screw with the special key provided. Wet System With Excess Pressure 2.Carefully place a screwdriver on the edge of the knockout and Connect PS 10 into alarm port piping extending from alarm check valve. sharply apply a force sufficient to dislodge the knockout plug.See Fig 9 Retard provisions are not required. Insure that no unsupervised shut-off 3. Run wires through an approved conduit connector and affix the connector valves are present between the alarm check valve and the PS 10. to the device. Testing: Accomplished by opening the water by-pass test valve or the 4.Connect the wires to the appropriate terminal connections for the inspector's end-of-line test valve. When using end-of-line test,allow time service intended.See Figures 2,4,5,and 6.See Fig 7 for two switch,one for excess pressure to bleed off. conduit wiring. Dry System Testing Connect PSIO into alarm port piping that extends from the intermediate The operation of the pressure alarm switch should be tested upon completion chamber of the alarm check valve. Install on the outlet side of the in-line of installation and periodically thereafter in accordance with the applicable check valve of the alarm port piping. Insure that no unsupervised shut-off NFPA codes and standards and/or the authority having jurisdiction valves are present between the alarm check valve and the PS10. (manufacturer recommends quarterly or more frequently). Testing:Accomplished by opening the water by-pass test valve. Wet System Note: The above tests may also activate any other circuit closer or water Method l: When using PSIO and control unit with retard -connect PSIO motor gongs that are present on the system. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400928-REV D PAGE I OF 3 1(08 P POTTER PS10 SERIES - >9 The Symbol of Protection PRESSURE SWITCH Dimensions Switch Clamping Plate Terminal Fig. 1 Fig.2 r � 00 t i I• GROUND p��SCREWS `�� N`or . 2.87 -./ ADJUSTMENT I I�: I [72.97] I KNOB L■ I'] ® 4.22 m.--- ---.'I =" [107.19] I■■_ _it 4� _ CI I/2"NPT -` I +�` o��O0 uwca 923.3 r 1 2.48 1.60 1 1j 1 V(( [62.87] [40.64] . _ �,..:_i 11_ •\ ' , 3.78 3.20 . An uninsulated section of a single conductor [95.89] [81.28] should not be looped around the terminal and serve as two separate connections. The wire NOTE:To prevent leakage,apply Teflon tape sealant to male threads only. must be severed,thereby providing supervision of the connection in the event that the wire DWO#930-I becomes dislodged from under the terminal. Typical Sprinkler Applications Fig.3 WET SYSTEM WITH WET SYSTEM WITHOUT DRY SYSTEM EXCESS PRESSURE EXCESS PRESSURE PS I II PSIO PSIo WATER WATER WATER MOTOR MOTOR Ilk MOTOR alb GONG GONG GONG RBVS DRY C'HEC'K ROWS WET RIDS VALVE WET SYSTEM •SYSTEM ... SYSTEM. ► ALARM ALARM CHECK ALARM CHECK VALVE • CHECK RETARD VALVE V'ALV'E 101 ►i IVATF.R \VATER WATER OS&Y • 13Y-PASS OS&1' • BYPASS VALE[ • VALVE OS&E • BY-PASS V\LV ♦ VALVE VALVE • VALVE OSLO.=923 2AA A CAUTION Closing of any shutoff valves between the alarm check valve and the PS 10 will render the PS I0 inoperative.To comply with NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model RBVS. Low Pressure Signal Connection Waterflow Signal Connection Local Bell For Waterflow Connection Fig.4 Fig.5 Fig.6 TO FIRE ALARM PANEL TO FIRE ALARM PANEL NEGATIVE DC OR NEUTRAL AC ra ra BELL POSITIVE DC LINE LOAD w■•I_ __mow-- I OR HOT AC _ IFOM=11 0 0 r I ii. 10 0 IL O"WA'lr,l '1 0 0 I! 1 r 1 I 40 0 0 0 110 1 0 O CI 0 0 0 0 PRINTED IN USA MFG.#5400928-REV D PAGE 2 OF 3 1/08 P POTTER • PS10 SERIES The Symbol of Protection PRESSURE SWITCH One Conduit Wiring Switch Operation Removing Knockouts Fig.7 Fig.8 Fig.9 Break out thin section of divider to provide path for wires Terminal W/PRESSURE APPLIED C:Common xr when wiring both switches from one conduit entrance. I: Closed when installed under nonnal system pressure. ik i�,r , 1 ® °� 2: Open when installed hi ilir under normal system pressure.Closes on ,,i h pressure drop.Use for ^j_ jar low pressure )l 1� " Terminal W/O PRESSURE APPLIED-- l: Open with no pressure supplied.of Closes u upon `1� � detection of pressure. `_ �/ Use for waterflow ' indication. \� 2: Closed with no DWC14928-5 1)Wli>4!$4 pressure applied. DWG#93Bb AWARNING& A CAUTION •Instal lation must be performed by qualified personnel and in •Do not tighten by grasping the switch enclosure.Use wrenching accordance with all national and local codes and ordinances. flats on the bushing only.Failure to install properly could damage •Shock hazard.Disconnect power source before servicing. the switch and cause improper operation resulting in damage to Serious injury or death could result. equipment and property. •Read all instructions carefully and understand them before -To seal threads,apply Teflon tape to male threads only. Using starting installation.Save instructions for future use. Failure to joint compounds or cement can obstruct the pressure port inlet read and understand instructions could result in improper and result in improper device operation and damage to equipment. operation of device resulting in serious injury or death. •Do not over tighten the device,standard piping practices apply. •Risk of explosion. Not for use is hazardous locations.Serious injury or death could result. Engineer/Architect Specifications Pressure Type Waterflow Switch Pressure type waterflow switches;shall be a Model PS 10 as Pressure switch shall have one or two form C contacts,switch contact manufactured by Potter Electric Signal Company,St Louis MO., rating 10.1 Amps at 125/250 VAC,2.0 Amps at 30 VDC. and shall be installed on the fire sprinkler system as shown and or Pressure type waterflow switches shall have two conduit entrances specified herein. one for each individual switch compartment to facilitate the use of Switches shall be provided with a'A"NPT male pressure connection dissimilar voltages for each individual switch. and shall be connected to the alarm port outlet of;Wet Pipe Alarm The cover of the pressure type waterflow switch shall be Zinc die-cast Valves,Dry Pipe Valves,Pre-Action Valves,or Deluge Valves.The with rain lip and shall attach with one tamper resistant screw.The pressure switch shall be actuated when the alarm line pressure reaches Pressure type waterflow switch shall be suitable for indoor or outdoor 4-8 PSI(0,27-0,55 BAR). service with a NEMA 4/IP55 rating. Pressure type waterflow switches shall have a maximum service The pressure type waterflow switch shall be UL Ulc and CSFM listed, pressure rating of 300 PSI(20,68 BAR)and shall be factory adjusted FM and LPC approved and NYMEA accepted. to operate on a pressure increase of 4-8 PSI(0,27-0,55 BAR) 1 PRINTED IN USA MFG.#5400928-REV D PAGE 3 OF 1 1/08 P POTTER PS40 SERIES The Symbol of Protection PRESSURE SWITCH • (UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA Accepted,CE Marked Pending) Dimensions:3.78"(9,6cm)W x 3.20"(8,Icm)D x 4.22"(I0,7cm)H ©POP.ER Conduit Entrance: Two knockouts provided for 1/2"conduit.Individual switch compartments and ground screw suitable for _ s_ •;...e u,,:,.___ dissimilar voltages 114. "` C PS40-2 E Enclosure: Cover-Die-cast with textured red powdercoat finish,single cover screw and rain lip. Base-Die-cast Pressure Connection:Nylon 1/2"NPT male Factory Adjustment: PS40-I operates on decrease at 30 PSI(2,1 BAR) PS40-2 operates in increase at 50 PSI(3,5 BAR) and on decrease at 30 PSI(2,1 BAR) Pressure Range: 10-60 PSI(,7-4,1 BAR) Differential: Typical 1 lb.at 10 PSI(,07 at,7 BAR) 4 lbs at 60 PSI(,28 at 4,1 BAR) Maximum System Pressure:300 PSI(20,68 BAR) Switch Contacts: SPDT(Form C) 10.1 Amps at 125/250VAC,2.0 Amps at 30VDC One SPDT in PS40-1,Two SPDT in PS40-2 Environmental Specifications: NEMA 4/IP55 Rated Enclosure-indoor or outdoor when used with NEMA 4 conduit fittings. Temperature range:-40°F to 140°F(-40°C to 60°C) Tamper: Cover incorporates tamper resistant fastener that requires a Ordering Information special key for removal. One key is supplied with each device. For optional cover tamper switch kit,order Stock No.0090200. Model Description Stock No. See bulletin#5401200 PSCTSK. P540-1 Pressure switch with one set SPDT contacts 1340403 Service Use: PS40-2 Pressure switch with two sets SPDT contacts 1340404 Automatic Sprinkler NFPA-13 Hex Key 5250062 One or two family dwelling NFPA-13D Cover Tamper Switch Kit 0090200 Residential Occupancy up to four stories NFPA-13R BVL Bleeder valve 1000018 National Fire Alarm Code NFPA-72 Installation The Potter PS40 Series Pressure Actuated Switches are designed primarily to 4. Connect the wires to the appropriate terminal connections for the detect an increase and/or decrease from normal system pressure in automatic service intended. See Figures 2,4,5,6,and 8 fire sprinkler systems. Typical applications are:Dry pipe system,pre-action Adjustment And Testing air/nitrogen supervision,pressure tanks,air supplies,and water supplies. The operation of the pressure supervisory switch should be tested upon The PS40 switch is factory set for40 PSI(2,8 BAR)normal system pressure. completion of installation and periodically thereafter in accordance with The switch marked with the word LOW is set to operate at a pressure decrease the applicable NFPA codes and standards and/or the authority having of 10 PSI(,7 BAR)at 30 PSI(2,1 BAR). The switch marked with the word jurisdiction(manufacturer recommends quarterly or more frequently). HIGH is set to operate at a pressure increase of 10 PSI(,7 BAR)at 50 PSI Note: Testing the PS40 may activate other system connected devices. (3,5 BAR). See section heading Adjustments and Testing if other than The use of a Potter BVL(see product bulletin 8900067 for details)is factory set point is required. recommended to facilitate setting and testing of the PS40 pressure switch. I. Connect the PS40 to the system side of any shutoff or check valve. When a BVL(bleeder valve)is used,the pressure to the switch can be 2. Apply Teflon tape to the threaded male connection on the device. isolated and bled from the exhaust port on the BVL without effecting the (Do not use pipe dope) supervisory pressure of the entire system. See Fig.3 3. Device should be mounted in the upright position. The operation point of the PS40 Pressure Switch can be adjusted to any (Threaded connection down) point between 10 and 60 PSI(0,7-4,11 BAR)by turning the adjustment 4. Tighten the device using a wrench on the flats on the device. knob(s)clockwise to raise the actuation point and counter clockwise to Wiring Instructions lower the actuation point. In the case of the PS40-2,both switches operate I. Remove the tamper resistant screw with the special key provided. independent of each other. Each switch may be independently adjusted to 2. Carefully place a screwdriver on the edge of the knockout and sharply actuate at any point acrosss the switch adjustment range. Initial adjustment apply a force sufficient to dislodge the knockout plug. See Fig.9 can be made with a visual reference from the top of the adjustment knob 3. Run wires through an approved conduit connector and affix the across to the printed scale on the switch bracket. Final adjustments should connector to the device. A NEMA-4 rated conduit fitting is be verified with a pressure gauge. required for outdoor use. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5401930-REV D PAGE I OF 3 1/08 P POTTER PS40 SERIES 8, The Symbol of Protection PRESSURE SWITCH Dimensions Switch Clamping Plate Terminal Fig. I Fig.2 f'__ 1 O®1 f �-�-� GROUND `uvA`.;i> L�I I 2.87 SCREWS `�� ,/‘,,,,C(3' r ADJUSTMENT F��: �`1 1 [72.971 i �� ,/" KNOB -l� ® 4.22 t 1. i 11 -� �o, [107.191 r --�.- -∎ jJ� l iAr I/2'NPT o- Y.G DWG#921-1 13‘C° 2.48 + I'_ 1.60 [62.87] I [40.641 3.78 .f 3.20 -.,t [95.89] [81.28] A WARNING 1 NOTE To prevent leakage.apply Teflon tape sealant to male threads only. An uninsulated section of a single conductor DWG.9.104 should not be looped around the terminal and serve as two separate connections. The wire must be severed,thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. Typical Sprinkler Applications Fig.3 PS16 A CAUTION AIR LINE SHUT-OFF A HLEEUER P810 Closing of any shutoff valves between the VALVE ALARM TEST PRESSURE • alann check valve and the PS 10 will render CHECK A VALVE SWITCH VALVE BVL the PS 10 inoperative.To comply with NFPA- WATER 72 any such valve shall be electrically GONG supervised with a supervisory switch such as CHECK RBVS DRY PIPE VALVE Potter Model RBVS. VALVE • ►• WATER DWG.#924.1A OS&Y • BY-PASS VALVE • TES I VALVE Typical Connections Fig.4 WITH NORMAL SYSTEM PRES- PS40-I PS40-2 SURE APPLIED LOW-TERMINAL 2 CLOSES ON PRESSURE DROP. TO FIRE ALARM PANEL iPi .l._ HIGH AIR COM N, + a O COM I•111 1W1•l a_ WITH NORMAL SYSTEM II■1111 El "11 IOW PRESSURE APPLIED HIGH I'O FIRE NV AIR -TERMINAL I WILL CLOSE ALARM MMI■IINI\L1 ON PRESSURE INCREASE. PANEL F.OLR DWG#930-2 PRINTED IN USA MFG.#5400930-REV D PAGE 2 OF 3 1;08 P POTTER PS40 SERIES 8 The Symbol of Protection PRESSURE SWITCH • Low Pressure Signal Connection High Pressure Signal Connection One Conduit Wiring Fig.5 Fig.6 Fig.7 TO FIRE ALARM PANE(. TO FIRE ALARM PANEL Break out thin section of divider to provide path for wires _ when wiring both switches from one conduit entrance. 02:1:11 ilow � -- ® o •® ® � � _� 1ILI — 'i .� VIII' r. (MC.9.l I)N'O1(525-I Changing Pressure Removing Knockouts (With normal system pressure) Fig.9 Fig.8 Terminal LOW PRESSURE SWITCH C:Common ,,,c l: Closed when installed o under normal system C pressure. 2: Open when installed Ilk under normal system ■ ^iv_ji IIIP pressure.Closes on c , 'Kg: pressure drop.Use for ,P le l' low air signal. I: Terminal HIGH PRESSURE SWIM!' *, �` ,� l: Open when installed ' ��` under normal system c. �1ii ® 7 pressure.Closes on i �/ /'ter increase in pressure. No ` Use for high air signal. \-� 2: Closed under normal system pressure. DWGft928-5 nwus 971.; Engineer/Architect Specifications Pressure Type Waterflow Switch Pressure type supervisory switches;shall be a Model PS40 as manufactured by A WA R N I N G Potter Electric Signal Company,St.Louis,MO.,and shall be installed on the fire sprinkler system as shown and or specified herein. •Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. Switches shall be provided with a 1/2"NPT male pressure connection to be 'Shock hazard.Disconnect power source before servicing.Serious injury or death connected into the air supply line on the system side of any shut-off valve. A could result. Model BVL bleeder valve as supplied by Potter Electric Signal Company of St. •Read all instructions carefully and understand them before starting installation. Louis,MO.,or equivalent shall be connected in line with the PS40 to provide a Save instructions for future use. Failure to read and understand instructions could means of testing the operation of the supervisory switch.(See Fig.3) result in improper operation of device resulting in serious injury or death. The switch unit shall contain SPDT(Form C) switch(es). One switch shall be 'Risk of explosion.Not for use is hazardous locations.Serious injury or death could result set to operate at a pressure decrease of 10 PSI(0,7 BAR)from normal. If two switches are provided,the second switch shall be set to operate at a pressure increase of 10 PSI(0,7 BAR)from normal. A CAUTION Switch contacts shall be rated at 10.1 Amps at I25/250VAC and 2.0 Amps at 30VDC. The units shall have a maximum pressure rating of 300 PSI(20,68 BAR) 'Do not tighten by grasping the switch enclosure. Use wrenching flats on the bushing and shall be adjustable from 10 to 60 PSI(0,7 to 4,1 BAR). only. Failure to install properly could damage the switch and cause improper operation resulting in damage to equipment and property. Pressure switches shall have two conduit entrances,one for each individual switch 'To seal threads.apply Teflon tape to male threads only. Using joint compounds or compartment to facilitate the use of dissimilar voltages for each individual switch. cement can obstruct the pressure port inlet and result in improper device operation and The cover of the pressure switch shall be zinc die-cast with rain lip and shall attach damage to equipment. with one tamper resistant screw. The pressure switch shall be suitable for indoor or •Do not over tighten the device,standard piping practices apply. outdoor service with a NEMA-4/IP55 rating. The pressure switch shall be UL,ULC,and CSFM listed,FM and LPC approved and NYMEA accepted. PRINTED IN LISA MFG.45400930-REV D PAGE 3 OF 3 1/08 dire rl f �� r � 4 �. 3 r b .� . , s - :_.:_:, --':?.?-,.* _. 4 _ r Base Plate Mounted ■ Directional air shroud for reduced pump temperatures Standard Features •Totally enclosed heavy-duty belt guard • Heavy-duty single stage cast iron compressor pump • Powder coated, extra heavy steel base plate Made in Somerset, PA USA ■ Large canister intake filter with replaceable filter elements • Splash lubricated ■ Magnetic starter is included on all 5HP and larger units • Belt driven with a large flywheel for extra cooling and easier start-up ■ Industrial/Commercial grade UL Listed electric motor • Each unit is filled with Jenny Synthetic Blue Compressor Pump Oil •Thermal overload motor protection Base Mounted System Size Optional Maximum Gallons Auto F12S-30S - II in to 40 PSI in system to be Pum p CFM del'd @ Control in 30 Minutes Model Pump HP Power Supply RPM 40 PSI Group 1 220 F13S-BS 1/3 670 2.9 ,' 290 F12S-BS F 1/2 950 3.8 _, ACGF t ' 350 F34S-BS 115 Volt 1200 4.4 • 3/4 425 K34S-BS K (through 2 HP) 520 5.3 ACGK EI11910 or 480 F1S-BS F 1 p Volt hase 1430 6.0 ACGF 600 K1S-BS 790 7.4 885 K15S-BS K 1-1/2 1140 10.9 ACGK '`� 208, 230, It 985 K2S-BS 2 460 or 1280 12.4 1215 G2S-BS 575 Volt 630 15.1 _ 1775 G3S-BS G 3 3 Phase 950 21.8 ACGD �{ 1950 GC5S-BS 5 1030 24.2 ACGJ •. m 2115 J5S-BS J 830 26.0 ..: ... .t N ' fil, Tank Mounted/30 Gallon .4..o ' 220 F13S-30UMS 1/3 670 2.9 s 290 - F12S-30UMS F 1/2 950 3.8 E1llyl0 350 F34S-30UMS 3/4 115 Volt 1200 4.4 425 K34S-30UMS K (through 2 HP) 520 5.3 230 Volt GC5S-30S 480 F1 S-30UMS F 1 1 Phase 1430 6.0 It 600 K1 S-30UMS 790 7.4 885 K15S-30UMS K 1-1/2 1140 10.9 985 K2S-30UMS 208, 230, 1280 12.4 -- 2 460 or 1215 G2S-30UMS G 575 Volt 630 15.1 1775 G3S-30UMS 3 3 Phase 950 21.8 6 i 1950 GC5S-30UMS GC 5 1030 24.2 1 2115 J5S-30UMS J 830 26.0 Etn910 Tank Mounted Additional Standard Features Options . > •Tanks are powder coated and ASME certified ASME National Board tank ''.s: • Protectively mounted fittings Magnetic starter 1 K15S-30S • Manual tank drain(s) 17 gallon tank•Vertical tank • Large canister intake filter with replaceable filter elements Low oil level switch ■Oil sight glass • Special unloading valves to assist in motor starting ,'',,. Automatic tank drain •Air line filter '° ■Tank gauge • Pressure relief safety valve Aftercooler•Dryer •Auto Start/Stop control with pressure unloader set at 25-40 PSI Control Group l�. R C O M P R E S S O 7' 7 uIJvvII' L, 1' 7 _______ . . , .,::„..„..,,..,,104,, ,:(t41-, ,, _p U .a �, t S pp Rod Screw Box Weight Case cod Approvals Part# Item# Model �( lies Deseons Qty. (per 125) ",Q Jut Driver 1/4" 8018957 4016 SWG 100 1/4 X 1 25 9.38 125 3#14SW Nut Driver 1/4" 8019957 300 SWG 200 1/4 X 2 25 10.00 125 r Sidewinders and /7"Rod Sammys 3/8" 8020957 18 SWG 10 1/4 X 1 25 7.50 125 O 3/8" 8021957 19 SWG 20 1/4 X2 25 8.75 125 3/8" 8022925 26 SWG 25-380 3/8 X 2-1/2 25 12.81 125 3/8" 8023925 25 SWG 30 1/4 X 3 25 10.63 125 t.i Rod Screw Box Weight Case ± steel Approvals Part# Item# Model II Size Descriptions Qty. (per 125) Qty 3/8" 8050957 39 SWD 10 1/4-14 X 1 25 7.50 125 `` " 1 3/8" 8051957 40 SWD 15 1/4-14 X 1-1/2 25 9.38 125 3art#8114910 3/8" 8052957 41 SWD 20 1/4-14 X 2 25 8.13 125 Item#101 3/8" 8053957 42 SWD 516 5/16-18 X 1-1/4 25 8.75 125 3/8" 8054957 46 SWDR 1-1/2" 1/4-20 X 1-1/2 25 9.06 125 3/8" 8055957 43 SWOR 1" 1/4-20 X 1 25 8.75 125 ! 'E 3/8" 8056957 44 SWDR 516 5/16-18 X 1-1/4 25 10.31 125 *+; 3/8" 8057957 45 SWT 15 12-24 X 1-1/2 25 7.81 125 Approvals Rod Part# Item# Model Screw Box Weight Case Concrete Size Descriptions Qty. (per 128) Qty 1/4" 8062957 1900 SWC 200 5/16 X 1-1/2 25 9.38 125 3/8" 8061957 65 SWC 20 5/16 X 1-1/2 25 9.38 125 • Most Items Available in Stainless Steel NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! * Use with 3/8" Sammy Swivel Head Part# Item# Model Screw Box Weight Case • 17°Descriptions Qty. (per 125) Qty 1 U.S.Patent No. 17 deflection from vertical 6,443,680 • Accommodates up to n.' 8139957 4702 SH-GST 20 1/4 x 2 25 9.38 125 3-1/2 x 12 pitch roof Q 8140957 4703 SH-GST 22SS 1/4 x 2 25 9.38 125 • Also available in stainless steel ©' 8141957 4704 SH-GST 30 1/4 x 3 25 10.94 125 • 8142957 4705 SH-GST 30SS 1/4 x 3 25 1094 125 � i{ • Use#14 Nut Driver(black) , • 8137957 4700 SH-DSTR 1 1/4-20 x 1 25 9.38 125 I O 8138957 4701 SH-DSTR 1 -SS 1/4-20 x 1 25 9.38 125 d Directly Patent Pending SAMMY X"PRESS M nod Steel Screw Box Weight Case sang Thread Gauge Metal Part# Item# Model 9 Than '� Ga. Descriptions Qty. (per 125) Qty. from &purlln 1 Deck t 1/4-20 x 1-1/8 l,, 4 € Q, 22-20 8150922 500 XP 20 Sammy X-Press 20 25 10.3 125 1' 1/4-20 x 1-1/8 r,4. -��". 18-16 8153922 503 XP 35 25 10.3 125 Sammy X-Press 35 Uninstalled Sammy X-Press It SAMMY = _ 8151910 501 XPIT Installation Tool 1 1.02 1 /`)^ PRESS T" (Kit includes:Sleeve.Bit Receiver. Ilex Wrench,and 25184"MIN Bit) �' 8152910 502 XPDB 25/64"Drill Bit 1 0.14 1 Installed t ..Z;figOOZ 105 BEAM CLAMP 1 1/4" MOUTH N14 ,,..„,:_\ *_,,,,, Alt SIZE-3/8" and 1/2" rod. MATERIAL-Ductile iron with hardened cup point set screw and jam nut. FINISH- Plain, Electro-Galvanized and H.D.G.and Stainless Steel. LISTINGS- c V us EX 2551 <C> Approval guide-Pipe Hangers CONFORMS WITH: Federal Specification WW-H-171E Type 19 and 23 and Manufactures Standardization Society ANSI/MSS-SP-58 Type 19 and 23. FUNCTION-Hanger assembly attachment to steel flange with thickness of less than 1 1/4". INSTALLATION- Per NFPA-13 with set screw up or down. Install in accordance with ANSI/MSS-SP-69.Torque-3/8"=60 inch pounds.Torque- /2"= 125 inch pounds. In the absence of a torque wrench,engage set bolt finger tight then additionally tighten 1/3 turn. FEATURES * Maintains CONSTANT HANGER CENTER-LINE,with set screw up or down. * Flat throat back prevent twisting during installation. ORDERING-Part#,rod size and finish. 12/03 r grg§UU 300 RING HANGER $ o---- 1 thru 4 inch pipe 1/2 and 314 inch pipe LISTED FOR STEEL/CPVC 5 thru 8 inch pipe SIZE- 1/2 thru 8 inch pipe. MATERIAL-Carbon Steel, Mil. Galvanized to G-90 spec. IMPERIAL MAX REC. METRIC* LISTINGS- PIPE ROD LOAD LBS. PIPE ROD COuS EX 2551 1/2 318 400 10 <> Approval guide-Pipe Hangers 314 318 400 20 10 CONFORMS WITH: Federal Specification WW-H-171 (Type 10, 1 318 400 25 10 Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10). 1 1/4 318 400 32 10 MAXIMUM TEMPERATURE-6500F. 1 1/2 318 400 40 10 FUNCTION-Pipe hanger component for use on steel,CPVC or 2 318 400 50 to copper piping. 21/2 3/8 600 65 10 INSTALLATION - Per NFPA-13, I 3R and I 3D. FEATURES- 3 318 600 80 10 * Sized and listed exclusively for use with#310 Surge Restrainer. 31/2 3/8 600 to * Band edge is offset for EASY pipe insertion. 4 3/8 1000 100 10 * Custom fit swivel nut for better retention in ring body. 5 1/2 1250 t25 12 * Full length knurl on swivel nut for better grip. 6 1/2 1250 150 12 ORDERING-Part#,pipe size. 6 1/2 1250 200 12 •Order Part a300m Note: On Copper-Insulate pipe. Note: iir Ring Hanger not<FM>approved 08/03 € F iii LCS �l„ W.tol�o.coim ,r,,,,,,.,NIBCO Revision 10/15/2008 r Component of State of Fig. 4A - Pipe Clamp for Sway Bracing California OSHPD Approved COOS MN Seismic Restraints System Size Range — 4" thru 8" pipe. For sizes smaller than 4" use TOLCO® Fig. 4. B Material — Carbon Steel Function — For bracing pipe against sway and seismic disturbance. Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada l �` (cUL)4" thru 8". Included in our Seismic Restraints Catalog approved by ,.,' 01 the State of California Office of Statewide Health Planning and Development lb. (OSHPD). / Installation Instructions — The Fig. 4A is the "braced pipe" attachment / A component of a longitudinal, lateral or riser brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO transitional and structural '\ attachment component(s) to form a complete bracing assembly. NFPA 13 .�.., 0 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 4A over the pipe to be braced. Attach TOLCO �` transitional fitting, either Fig. 980, 910 or 909, to the clamp ears. Tighten bolts and nuts; torque requirement is a minimum of 50 ft. lbs. Transitional fit- 0 ting attachment can pivot for adjustment to proper brace angle. C Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, pipe size and finish o _ 0 I 1 • l� 0 Fig. 4A - Longitudinal Brace Fig. 4A - Lateral Brace TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. Dimensions •Weights Pipe Max. Horizontal Approx. Sizes A B C D Bolt Size Design Load WtJ100 4 81/2 9/16 3% 311/i2 1/2 2015 221 5 93/4 9/16 31/2 4% 1/2 2015 253 6 111/2 5/8 5 51/2 1/2 2015 513 8 131/4 3/4 611/16 61/2 1/2 2015 601 ® OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA.CA 92879•PH: 951.737.5599•FAX: 951.737 0330 CUSTOMER SERVICE•800.786.5266 www.tolco.com 4 V FDLCS www.tolco.com a brand of NIBCO' Revision 5/24/2001 Fig. 825 - Bar Joist Sway Brace Attachment Size Range — One size accommodates all TOLCO Fig. 900 Series sway Component of State of brace attachments. Maximum Horizontal Design Load 2015 lbs. California OSHPD apysoved Seismic Restraints System Material — Carbon Steel Function — *To attach sway and hanger assemblies bracing to steel bar 3/8„ joist structural members.. Features —This product's design incorporates a concentric attachment point which is critical to the performance of structural seismic connections. NFPA 13 indicates the importance of concentric loading of connections and fasteners. Permits secure non-friction connection without drilling or welding. �1 Unique design reinforces point of connection to joist. Break off head bolt design assures verification of proper installation. ��f.1b Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the A711i 1111* State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. �((( Important Structural Note: The TOLCO Fig. 825 has significant UL established design loads, however, structural issues related to the steel joist member require restricted location installation for all bracing. Steel Joist Manufacturers require that all earth- Maximum Design Load 2015 Lbs. quake bracing connections be within 6" of the cord panel point. Installation Weight/100 237.5 Lbs. of the Fig. 825 must be limited to the outer third sections of the joist span. For installations within the center third section of the joist span, use UL UL Listed as Hanger Attachment Listed TOLCO Fig. 825A. 6" Pipe Max. Finish — Plain, Electro-Galvanized and HDG Order By — Figure number and finish *Important Note —The Fig. 825 is precision manufactured to perform its function as a critical component of a complete bracing assembly. To ensure performance, the UL Listing requires that the Fig. 825 must be used only with other TOLCO bracing products. Patent #6,098,942 .mr..f ipONMI Mg vuw Z.. ear F.0 Vw.n NN'NO WANT k..l...tNY _., CpisnY*tat Mat•IWN'o1y'M! -_ a Soon re§ -- Ji 1 L 1 rte' '_tgot Rs IV • MIS O.NI n .yanma R9'CO ' - fgQN,VFW Office/Manufacturing Facility•1375 Sampson Ave •Corona,CA 92879•Ph: 909.737.5599•Fax: 909.731.0330 Customer Service•800.786.5266 www.lolco.com TDLCD www.toico.com _ ,r„-r,NIBCO” Revision 4/6/2010 Fig. 980 - Universal Swivel Sway Brace Attachment C O US LISTED Size Range - One size fits bracing pipe 1" thru 2",TOLCO 12 gauge channel, and all 4> structural steel up to 1/4" thick. Material - Carbon Steel Component of State of 1-714‘Function - Multi-functional attachment to structure or California OSHPD Approved Seismic Restraints System braced pipe fitting. Features - This product's design incorporates a concen- tric attachment opening which is critical to the performance Nt. Fi of structural seismic connections. NFPA 13 (2010) 9.3.5.8.4 liKk% indicates clearly that fastener table load values are based i ( 1' only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Installation - The Fig.980 is the structural or transitional A attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the 111.114 B "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install - Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until set bolt head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals - Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note - The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000 , Fig. 2001 or Fig. 4A Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters' Laboratories and the National Fire Protection Association (NFPA) Finish - Plain Note - Available in Electro-Galvanized finish. •. Order By - Figure number and finish. Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174, Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730, Pat. #7,669,806 Lateral Brace Dimensions •Weights Max. Design **Max. Design Approx. A B H* Load Lbs. Load Lbs. Wt./100 (cULus) (FM) 51/4 1'/s 17/32 2765 2800 132 Available with hole sizes to accommodate up to 3/4" fastener. Consult factory. **Load shown is allowable with brace installed, between 30°-90°.No reduction of load based on brace angle is required. TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO®brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA.CA 92879•PH: 951.737.5599•FAX: 951.737.0330 149 CUSTOMER SERVICE•800.786.5266 wwwtolco.com TOLL. www.tolco.com •••NIBCO Revision 5/27/2008 Fig. 1000 - "Fast Clamp" Sway Brace Attachment CaColiforrnia nia O OS tofStateof SHPD Approved Seismic Restraints System Size Range — Pipe size to be braced: 1" thru 6" Schedule 10 thru 40 IPS.* Pipe size used for bracing: 1" and 11/4" Schedule 40 c 0 us uSTEn PS. Additionally(UL) approved for use to brace Schedule 7 sprinkler pipe up to 4" (maximum horizontal design load 655 lbs.) Torque requirement 6 — 8 ft. lbs. Material — Carbon Steel Function — For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace sys- tem: Fig. 1000 is used in conjunction with a TOLCO • Fig. 900 Series Fitting and joined together with bracing pipe per NFPA 13' or TOLCO OSHPD Approved Seismic Manual, forming a complete sway brace assembly. Features — Field adjustable, making critical pre-engineering of i I bracing pipe unnecessary. Unique design requires no threading of bracing pipe. Can be used as a component of a 4-way riser brace. Can be used as longitudinal brace with Fig. 907. Comes assembled - and individually packaged with illustrated installation instructions . " — sizes are clearly marked. Steel leaf spring insert provided to assure installer and inspector necessary minimum torque has been achieved. Installation — The Fig. 1000 is the "braced pipe" attachment component of a lateral sway brace assembly. It is intended to be Maximum Design Load combined with the "bracing pipe" and TOLCO structural attach- 1" thru 4" pipe size — 2015 lbs. ment component, Fig. 980, 910 or 909 to form a complete bracing 6" size — 1265 lbs. assembly. Follow NFPA 13 and/or OSHPD guidelines. To Install — Place the Fig. 1000 over the pipe to be braced, insert bracing pipe through opening leaving a minimum of 1" extension. FM Approved Design Loads* Brace pipe can be installed on top or bottom of pipe to be braced. 1" - 21/2" - 600 lbs. Tighten hex nuts until leaf spring is flat. It is recommended that the 3" - 4" - 700 lbs. brace angle be adjusted before hex nuts are fully tightened. Approvals — Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement informa- tion relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Application Note — Position Fast Clamp and tighten two hex nuts until leaf spring flattens. A minimum of 1" pipe extension beyond the Fig. 1000 is recommended. Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Order first by pipe size to be braced, followed by pipe size used for bracing, figure number and finish. Lateral Brace TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFRCE/MANUFACTURINO FACIUTY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951 737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800 786 5266 155 www.tolcacom