Specifications ` i-P5Zd13 --C ct RECEIVED Worldwide tqco www.tyco-fire.com JUL 1 0 2013 Contacts CITY()F TIGARI) Series TY--B — 5.6 K fac SING DIViTON Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General the standard corrosion tests of the ap- plicable approval agencies, the test- '�� Description ing is not representative of all possible ` corrosive atmospheres. Consequently, The TYCO Series TY-B, 5.6 K-factor, it is recommended that the end user f Horizontal and Vertical Sidewall Sprin- be consulted with respect to the suit- /.�„�,',,h'' klers described in this data sheet are ability of these coatings for any given ff J �'' standard response standard cover- corrosive environment. The effects of i Ai,. . age,decorative 5 mm glass bulb type ambient temperature,concentration of NC spray sprinklers designed for use in chemicals, and gas/chemical velocity, light and ordinary hazard,commercial should be considered,as a minimum, , occupancies such as banks, hotels, along with the corrosive nature of the - and shopping malls. chemical to which the sprinklers will be exposed. They are designed for installation along a wall or the side of a beam and just NOTICE beneath a smooth ceiling. Sidewall sprinklers are commonly used instead The TYCO Series TY-B Sprinklers de- of pendent or upright sprinklers due to scribed herein must be installed and aesthetics or building construction con- maintained in compliance with this doc- _ siderations, where piping across the ument, as well as with the applicable ceiling is not desirable. standards of the National Fire Protec- ! tion Association, in addition to the stan- The recessed version of the Series dards of any other authorities having ju- +W TY-B Horizontal Sidewall Sprinkler is in- risdiction.Failure to do so may impair tended for use in areas with a finished the performance of these devices. ill wall. It uses a two-piece Style 10 Re- ` - — cessed Escutcheon.The Recessed Es- The owner is responsible for maintain- - cutcheon provides 1/2 inch(12,7 mm)of ing their fire protection system and de- recessed adjustment or up to 3/4 inch vices in proper operating condition. The (19,1 mm)of total adjustment from the installing contractor or sprinkler manu- - flush sidewall position.The adjustment facturer should be contacted with any provided by the Recessed Escutcheon questions. reduces the accuracy to which the fixed Maximum Working Pressure pipe nipples to the sprinklers must be Sprinkler Refer to Table B. cut. Corrosion resistant coatings, where Identification Discharge Coefficient applicable, are utilized to extend K=5.6 GPM/psi1 2(80,6 LPM/bar112) the life of copper alloy sprinklers Numbers Temperature Ratings beyond that which would otherwise be obtained when exposed to corrosive TY3351 Horizontal Refer to Table A. atmospheres. Although corrosion re- TY3451 Vertical Finishes sistant coated sprinklers have passed Sprinkler: Refer to Table A. Technical Recessed Escutcheon: Signal or Pure IMPORTANT White, Jet Black, Chrome Plated, or Always refer to Technical Data Data Natural Brass Sheet TFP700 for the "INSTALLER WARNING" that provides cautions Approvals Physical Characteristics with respect to handling and UL and C-UL Listed Frame Bronze installation of sprinkler systems and Button Brass/Copper components. Improper handling and FM, LPCB,VdS,and NYC Approved Sealing Assembly. . . Beryllium Nickel installation can permanently damage Refer to Table A for complete approval w/TEFLON a sprinkler system or its components information including corrosion resis- Bulb Glass and cause the sprinkler to fail to tant status. Compression Screw Bronze operate in a fire situation or cause it HSW Deflector Bronze to operate prematurely. VSW Deflector Copper Page 1 of 6 MARCH 2013 TFP161 TFP161 Page 2 of 6 • Operation DEFLECTOR 1 - Frame HAT 5 The glass bulb contains a fluid which 2 - Button ,��, ��,� expands when exposed to heat.When 3 - Sealing / _tr,! the rated temperature is reached, the Assembly fluid expands sufficiently to shatter the 4 - Bulb fir' glass bulb,allowing the sprinkler to ac- 5 -Compression I,\' P tivate and water to flow. Screw 6 - Deflector* 6* 4 2 3 1 Design Criteria (14,3 mm) WLATSH NPT** The TYCO Series TY-B, 5.6 K-factor, I Horizontal and Vertical Sidewall Sprin- ��RI I /' klers are intended for fire protection •r r _ + I�_' systems designed in accordance with / 'the standard installation rules recog ... nized by the applicable Listing or Ap- • proval agency(for example, UL Listing 1-13/16" 7/16" is based on the requirements of NFPA (46,0 mm) (11,1 mm) 13, and FM Approval is based on the NOMINAL requirements of the FM Loss Preven- CENTERLINE tion Data Sheets). Only the Style 10 OF SPRINKLER MAKE-IN Recessed Escutcheon,as applicable, WATERWAY 1-1/2" is to be used for recessed horizontal '–(38,1 mm)� installations. *Temperature rating is indicated on 2-3/16" Installation Deflector. (55,6 mm) ESCUTCHEON The TYCO Series TY-B, 5.6 K-factor, ** Pipe thread STYLE 10 — i — PLATE SEATING Horizontal and Vertical Sidewall Sprin- connections per RECESSED SURFACE klers must be installed in accordance ISO 7-1 can be ESCUTCHEON il with this section. provided on special request. General Instructions Do not install any bulb type sprinkler if 2-7/8"DIA. ilargillitil the bulb is cracked or there is a loss (73,0 mm) � of liquid from the bulb.With the sprin- „� III kler held horizontally,a small air bubble should be present.The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) to 3/32 inch(2,4 mm)for the 360°F(182°C)tem- , perature ratings. A leak-tight 1/2 inch NPT sprinkler joint FIGURE 1 should be obtained by applying a mini- SERIES TY-B HORIZONTAL SIDEWALL (TY3351)SPRINKLERS mum-to-maximum torque of 7 to 14 ft.- 5.6 K-FACTOR STANDARD RESPONSE lbs.(9,5 to 19,0 Nm).A maximum of 21 ft.-lbs.(28,5 Nm)of torque may be used Step 1. Horizontal sidewall sprinklers coated sprinklers, use an 8 or 10 inch to install sprinklers with 1/2 NPT con- install in the horizontal position with adjustable Crescent wrench.With refer- nections. Higher levels of torque may their centerline of waterway perpendic- ence to Figure 1 or 2,apply the W-Type distort the sprinkler inlet and cause ular to the back wall and parallel to the 6 Sprinkler Wrench or the Crescent leakage or impairment of the sprinkler. ceiling.The word"TOP"on the Deflec- wrench, as applicable, to the wrench Do not attempt to make-up for insuf- tor is to face towards the ceiling. flats. ficient adjustment in the escutcheon Vertical sidewall sprinklers install in the When installing wax-coated sprinklers plate by under- or over-tightening the pendent or upright position with the ar- with the adjustable Crescent wrench, sprinkler. Readjust the position of the row on the Deflector pointing away from exercise care to prevent damage to the sprinkler fitting to suit. the wall. wax coating on the sprinkler wrench Step 2. With pipe-thread sealant ap flats or frame arms and, consequent Vertical Sidewall Sprinklers plied to the pipe threads, hand tighten ly,exposure of bare metal to the corro- The Series TY-B Horizontal and Ver- the sprinkler into the sprinkler fitting. sive environment.Open the jaws of the tical Sidewall Sprinklers must be in- wrench sufficiently wide to pass over stalled in accordance with the follow- Step 3. Tighten the sprinkler into the the wrench flats without damaging the ing instructions. sprinkler fitting using only the W-Type wax coating. Before wrench tighten- 6 Sprinkler Wrench(Figure 4). For wax- ing the sprinkler, adjust the jaws of the TFP161 Page 3 of 6 *Temperature ** Pipe thread 1 - Frame 4 - Bulb 7 - Ejection fal rating is connections 2 - Button 5 - Compression Spring indicated on per ISO 7-1 can 3 - Sealing Screw . Deflector. be provided on Assembly 6 - Deflector* / WRENCH RECESS special request. (END"A"USED FOR 1/2" NPT MODELS) ARROW MUST POINT AWAY - 7/16" FROM AND BE FIGURE 4 ESCUTCHEON (11,1 mm) PERPENDICULAR O W TYPE 6 PLATE SEATING NOMINAL TO THE BACK SURFACE NPT** MAKE-IN WALL SURFACE / SPRINKLER WRENCH L 6* WRENCH I i_-_ --�= �� I «�9'`�\ RECESS _ FLOW 1° 5 2-3/16") a Ab ' 2-3/16" 4 �� A, (55,6 mm —\ (55,6 mm) 1 1 C 1-1/2" I g (38,1 mm) WRENCH/ � V ; 2 } 1 �u � FLATS 7 I 1 3 �-�� ¢ 1 PUSH WRENCH IN TO ENSURE SHOWN SHOWN CROSS ENGAGEMENT PENDENT UPRIGHT SECTION WITH SPRINKLER WRENCHING AREA FIGURE 2 FIGURE 5 SERIES TY-B VERTICAL SIDEWALL(TY3451)SPRINKLERS W-TYPE 7 RECESSED 5.6 K-FACTOR, STANDARD RESPONSE SPRINKLER WRENCH __ 5/8±1/4" wrench to contact only the sprinkler (15,9±6,4 mm) wrench flats. After wrench tightening the sprinkler, loosen the wrench jaws MOUNTING FACE OF before removing the wrench. SURFACE '�- SPRINKLER FITTING After installation, inspect the sprinkler A wrench flats and frame arms and re- touch(repair)the wax coating whenev- CLOSURE - T er the coating has been damaged and bare metal is exposed.Retouch the wax coating on the wrench flats by gently �_ 2-7/8"DIA. applying a heated 1/8 inch diameter SERIES —rill� (73,0 mm) steel rod to the damaged areas of wax TY-B l� il ,III) 2-1/4"DIA. to smooth it back over areas where bare =11` (57,2 mm) metal is exposed. MOUNTING I NOTICE PLATE Ir Only retouching of the wax coating ap- 4 plied to the wrench flats and frame arms is permitted,and the retouching is to be performed only at the time of the initial 1/8" sprinkler installation. (3,2 mm) The steel rod should be heated only to 1-1/4°(31,8 mm) 3/4"(19,1 mm) the point at which it can begin to melt + y the wax, and appropriate precautions 3/4"(19,1 mm) 1/4"(6,4 mm) need to be taken when handling the I heated rod in order to prevent the in- FIGURE 3 staller from being burned. SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY Continued on Page 4 WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON, 5.6 K-FACTOR, 1/2 INCH NPT TFP161 Page 4 of 6 SPRINKLER FINISH(See Note 10) K TYPE TEMP. BULB LIQUID NATURAL CHROME WHITE"' LEAD WAX COATED WAX OVER BRASS PLATED POLYESTER COATED LEAD COATED 135'F(57°C) Orange 155°F(68°C) Red 1 HORIZONTAL 1,2,3,9 SIDEWALL 175"F(79°C) Yellow 1. 2.3.=1. 9 1, 2.3. 9 (TY3351) 1, 2.3.9 Figure 1 200°F(93°C) Green 5.6 286"F(141°C) Blue 1/2- NPT 360°F(182°C) Mauve 1,2,4,9 1. 9 N/A RECESSED 135°F(57°C) Orange HORIZONTAL 155°F(68°C) Red SIDEWALL 175°F(79°C) Yellow 1,2,3,9 N/A (TY3351)' Figure 3 200°F(93°C) Green 135°F(57°C) Orange VERTICAL SIDEWALL 155°F(68°C) Red 5. 6.7. 9 5.6 (TY3451) 175°F(79`C) Yellow 4,5,6,7,8,9 1/2" PENDENT 5,6, 7,9 NPT or 200°F(93°C) Green UPRIGHT Figure 2 286°F(141°C) Blue 5",6",7",9" 360°F(182°C) Mauve 4,5,6,8,9 N/A NOTES 1. Listed by Underwriters Laboratories,Inc.(UL)for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL)for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation(FM)for use in Light Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceil- ing distance. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05&007k/03)at a 4 to 6 inch(100 to 150 mm)deflector to ceiling distance 5. Listed by Underwriters Laboratories,Inc.(UL)for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL:)for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation(FM)for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05&007k/03). 9. Approved by the City of New York under MEA 354-01-E. 10. Where Polyester Coated,Lead Coated,Wax Coated,and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.Where Lead Coated,Wax Coated,and Wax over Lead Coated Sprinklers are noted to be FM Ap- proved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. ' Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4-Total Adjustment Recessed Escutcheon,as applicable. 150°F(66°C)Maximum Ceiling Temperature. Frame and deflector only.Listings and approvals apply to color(Special Order). TABLE A SERIES TY-8 HORIZONTAL AND VERTICAL SPRINKLERS LABORATORY LISTINGS AND APPROVALS Horizontal Sidewall Sprinklers 5).With reference to Figure 1,apply the The TYCO Series TY-B Recessed Hori- W-Type 7 Recessed Sprinkler Wrench zontal Sidewall Sprinklers must be in- to the sprinkler wrench flats. stalled in accordance with the following Step D.After the ceiling is installed or instructions. the finish coat is applied, slide on the Step A. Install recessed horizontal Style 10 Closure over the Series TY-B sidewall sprinklers in the horizontal Sprinkler and push the Closure over the position with their centerline of water- Mounting Plate until its flange comes in way perpendicular to the back wall and contact with the ceiling. parallel to the ceiling.The word"TOP" on the Deflector is to face towards the ceiling. Step B. After installing the Style 10 Mounting Plate over the sprinkler threads,hand-tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure TFP161 Page 5 of 6 • SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD WAX WAX OVER LEAD BRASS PLATED POLYESTER COATED COATED COATED HORIZONTAL SIDEWALL (TY3351) 250 PSI(17,2 BAR) 175 PSI(12,1 BAR) OR 5.6 175 PSI(12,1 BAR) 1/2". RECESSED HORIZONTAL (SEE NOTE 1) N/A NPT SIDEWALL(TY3351) VERTICAL SIDEWALL N/A (TY3451) NOTE 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS MAXIMUM WORKING PRESSURE Care and aged by dropping, striking, wrench twist/slippage,or the like,must be re- Maintenance placed.Also,replace any sprinkler that has a cracked bulb or that has lost The TYCO Series TY-B, 5.6 K-factor, liquid from its bulb. (Ref. Installation Horizontal and Vertical Sidewall Sprin- Section.) klers must be maintained and serviced The owner is responsible for the in- in accordance with this section. spection,testing,and maintenance of Before closing a fire protection system their fire protection system and devices main control valve for maintenance in compliance with this document,as work on the fire protection system that well as with the applicable standards of it controls, obtain permission to shut the National Fire Protection Association down the affected fire protection sys- (for example, NFPA 25), in addition to tern from the proper authorities and no- the standards of any other authorities tify all personnel who may be affected having jurisdiction.Contact the install- by this action. ing contractor or sprinkler manufacturer The owners must ensure that sprinklers regarding any questions. are not used for hanging any objects. Automatic sprinklers are recommended Otherwise,non-operation in the event to be inspected,tested,and maintained of a fire or inadvertent operation may by a qualified Inspection Service in ac- result. cordance with local requirements and/ or national codes. Absence of an escutcheon, which is used to cover a clearance, may delay the time to sprinkler operation in a fire situation. Sprinklers which are found to be leak- ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory.Modi- fied sprinklers must be replaced.Sprin- klers that have been exposed to corro- sive products of combustion,but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam- age to the sprinklers- before,during, and after installation.Sprinklers dam- TFP161 Page 6 of 6 P/N 57 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 578 HORIZONTAL SIDEWALL TY3351 1 NATURAL BRASS 135 135°F(57°C) 575 VERTICAL SIDEWALL TY3451 3 PURE WHITE(RAL9010)' 155 155°F(68°C) 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) X Jet Black(RAL9005)" 200 200°F(93°C) 6 WAX COATED 286 286°F(141°C) 286°F(141°C)MAX 7 LEAD COATED 360 360°F(182°C) 8 WAX OVER LEAD 286°F(141°C)MAX 9 CHROME PLATED Eastern Hemisphere sales only. Available only for 155°F(68°C) or 200°F(93°C)temperature rated sprinklers TABLE C SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS PART NUMBER SELECTION Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-B (specify SIN), (specify K-factor), (specify Horizontal or Vertical Sidewall ) Sprinklers with (specify) temperature rating, (specify) finish or coating, P/N(Refer to Table C). Recessed Escutcheon Specify:Style 10 Recessed Escutcheon with(specify)finish, P/N(specify*). •Refer to Technical Data Sheet TFP770. Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, PIN 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. tyco TEFLON is trademark of The DuPont Corporation. • CO Worldwide ldwide Co www.tyco-fire.com Series TY-B — 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General be consulted with respect to the suit- ability of these coatings for any given ,/ Description corrosive environment. The effects of ;r-� ambient temperature, concentration of ' -" • The TYCO Series TY-B, 2.8, 5.6, and chemicals, and gas/chemical velocity, - 8.0 K-factor, Upright and Pendent should be considered,as a minimum, Sprinklers described in this data sheet along with the corrosive nature of the are standard response - standard chemical to which the sprinklers will be coverage,decorative 5 mm glass bulb exposed. type spray sprinklers designed for use An intermediate level version of the ``-"~� in light,ordinary,or extra hazard,corn- Series TY-B Pendent Sprinkler can be ... 4_, mercial occupancies such as banks, obtained by utilizing the Series TY-B hotels, shopping malls, factories, Pendent Sprinkler in combination with refineries,and chemical plants. the Model S2 Shield. The recessed version of the Series Wiz`--_. TY-B Pendent Sprinkler, where appli- NOTICE cable,is intended for use in areas with The TYCO Series TY-B Sprinklers .,_ ■-,N a finished ceiling. It uses a two-piece described herein must be installed Style 10(1/2 inch NPT)or Style 40 (3/4 and maintained in compliance with inch NPT) Recessed Escutcheon.The this document, as well as with the (1N. Recessed Escutcheon provides 1/2 applicable standards of the National • inch(12,7 mm)of recessed adjustment Fire Protection Association, in addition or up to 3/4 inch (19,1 mm) of total to the standards of any other authori- 4. ,: i / adjustment from the flush pendent ties having jurisdiction. Failure to do so �' position. The adjustment provided by may impair the performance of these "—� the Recessed Escutcheon reduces the devices. 14. accuracy to which the fixed pipe drops _,_p-r ` to the sprinklers must be cut. The owner is responsible for maintain- ing their fire protection system and Corrosion resistant coatings, where devices in proper operating condition. applicable, are utilized to extend the The installing contractor or sprinkler life of copper alloy sprinklers beyond manufacturer should be contacted with that which would otherwise be obtained any questions. when exposed to corrosive atmo- spheres.Although corrosion resistant Sprinkler coated sprinklers have passed the p standard able a rp corrosion tests of the sting Identification cable approval agencies, the testing is not representative of all possible corrosive atmospheres.Consequently, Numbers it is recommended that the end user TY1151 Upright 2.8K, 1/2" NPT TY1251 . . . . Pendent 2.8K, 1/2""NPT TY3151 Upright 5.6K, 1/2""NPT IMPORTANT TY3251 .. . . Pendent 5.6K, 1/2-NPT Always refer to Technical Data TY4151 Upright 8.0K, 3/4-NPT Sheet TFP700 for the "INSTALLER TY4251 . . . . Pendent 8.0K, 3/4""NPT WARNING" that provides cautions TY4851 Upright 8.0K, 1/2-NPT with respect to handling and TY4951 .. . . Pendent 8.0K, 1/2""NPT installation of sprinkler systems and components. Improper handling and • installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it • to operate prematurely. Page 1 of S MARCH 2013 TFP151 TFP151 Page 2 of 8 CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 7 3 - Sealing 6 - Deflector* irf?=r'}ri=1'.Fie. _ I �$ Assembly 7 - Bushing 1 e 1 4 - Bulb (1 7/1 mm) s— 2 1/4„ AA 3 NOMINAL (57,2 mm) a7' % Jr ` r. MAKE-IN 2 *Temperature rating is 1 1 2-3/16" I 1-9/16" 4 indicated on Deflector. (55,6 mm) (39,7 mm) L 5 ** Pipe thread connections per ISO 7-1 can be - • •°"''...R'... 6* provided on special 1/2" NPT** t WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 1 SERIES TY-B UPRIGHT(TY1151)AND PENDENT(TY1251)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE ----- 1 / iiiiii - 7/16" ���r� A / 3' (11,1 mm) /' NOMINAL �/ �� / 2 MAKE-IN 2 3/16 II(55,6 mm) Ijr'— I f 4 - II II i (55,6/mm) I Ii 1-1/2" ��f (38,1 mm) 1 5 6* 1/2" NPT** t WRENCH STYLE 10 I 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 SERIES TY-B UPRIGHT(TY3151)AND PENDENT(TY3251)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE TFP151 Page 3 of 8 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE IIITTITTM 1/2" � 3 g14 (12,7 mm) � �� A NOMINAL 2-5/16" �� %� . 44=, MAKIE-IN (58,7 mm) ` — ` li $ (57,2/mm) I li (1-9/mm) ��� 4 • . �RJ 5 3/4" NPT t WRENCH STYLE 40 I —~~+�`~_ 6* ** 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 SERIES TY-B UPRIGHT(TY4151)AND PENDENT(TY4251)SPRINKLERS 8.0 K-FACTOR, 3/4 INCH NPT, STANDARD RESPONSE CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 3 - Sealing 6 - Deflector* s•r•�-, -,- _ f Assembly 4 - Bulb 7/16" 21 3 gil (11,1 mm) 2-1/4" NOMINAL 1 1 1 (57,2 mm) /! .!1 2 — MAKE-IN + *Temperature rating is —M 2 3/16„ ' 1 9/16" 4 indicated on Deflector. (55,6 mm) i (39,7 mm) A i °��—5 ** Pipe thread connections _� -- - �,la. 6* per ISO 7-1 can be provided on special 1/2" NPT** t WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 4 SERIES TY-B UPRIGHT(TY4851)AND PENDENT(TY4951)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE TFP151 Page 4 of 8 SPRINKLER FINISH(See Note 8) K TYPE TEMP. BULB LIQUID NATURAL CHROME WHITE*** LEAD WAX WAX OVER BRASS PLATED POLYESTER COATED COATED LEAD COATED 135`F(57°C) Orange UPRIGHT 155°F(68°C) Red 2.8 (Tand 1) 175°F(79°C) Yellow 1,2,3 1/2" NPT PENDENT 200°F(93°C) Green N/A (TY1251) Figure 1 286°F(141°C) Blue 360°F(182°C) Mauve 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY3151) 1,2,3,5 1,2,3,5 175°F 79'C and ( ) Yellow 1,2,3,4,5,6,7 1,2,3,5 PENDENT 200°F(93°C) Green (TY3251) Figure 2 286°F(141°C) Blue 5.6 1/2" 360'F(182°C) Mauve N/A NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 1,2,3,4,5 (TY3251)* 175°F(79°C) Yellow N/A Figure 5 200°F(93°C) Green 286°F(141°C) Blue 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red 1,2,3,5 1,2,5 (T and 1) 175°F(79°C) Yellow PENDENT 1,2,3,4,5,6,7 1,2,5 (TY4251) 200°F(93°C) Green Figure 3 286°F(141°C) Blue 8.0• 3/4" 360°F(182°C) Mauve N/A NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 1,2,3,4,5 (TY4251)* 175°F(79°C) Yellow N/A Figure 6 200°F(93°C) Green 286°F(141°C) Blue 1,2 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red 8.0 (T and 1) 175°F(79°C) Yellow 1/2 PNT ( 1,2,3,4,5,6 N/A ENDE NPT ENDS 1) 200°F(93°C) Green Figure 4 286°F(141°C) Blue 360°F(182°C) Mauve NOTES 1. Listed by Underwriters Laboratories,Inc.(UL) 2. Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL) 3. Approved by Factory Mutual Research Corporation(FM) 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/03) 5. Approved by the City of New York under MEA 354-01-E 6. VdS Approved(For details contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/05) 8. Where Polyester Coated,Lead Coated,Wax Coated,and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.Where Lead Coated,Wax Coated,and Wax over Lead Coated Sprinklers are noted to be FM Ap- proved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. • Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable 150°F(66°C)Maximum Ceiling Temperature •" Frame and deflector only.Listings and approvals apply to color(Special Order) TABLE A SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS LABORATORY LISTINGS AND APPROVALS TFP151 Page 5 of 8 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD WAX WAX OVER LEAD BRASS PLATED POLYESTER COATED COATED COATED 2.8 UPRIGHT(TY1151) 1/2" and 175 PSI(12,1 BAR) N/A NPT PENDENT(TY1251) UPRIGHT(TY3151) and 175 PSI(12,1 BAR) 5.6 PENDENT(TY3251) 250 PSI(17,2 BAR) 1/2" OR — NPT 175 PSI(12,1 BAR) RECESSED PENDENT (SEE NOTE 1) (TY3251) N/A UPRIGHT(TY4151) and 175 PSI(12,1 BAR) 8.0 PENDENT(TY4251) 3/4" NPT RECESSED PENDENT 175 PSI(12,1 BAR) N/A (TY4251) 8.0 UPRIGHT(TY4851) 1/2" and 175 PSI(12,1 BAR) NPT PENDENT(TY4951) NOTE 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL):and,the Approval by the City of New York TABLE B SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS MAXIMUM WORKING PRESSURE Technical Physical Characteristics Design Frame Bronze Data Button Brass/Copper Criteria Sealing Assembly. . . Beryllium Nickel Approvals w/TEFLON The TYCO Series TY-B, 2.8, 5.6, UL and C-UL Listed Bulb Glass and 8.0 K-factor, Upright and Pen- FM, LPCB, VdS, and NYC Approved Compression Screw Bronze dent Sprinklers are intended for (Refer to Table A for complete approval Deflector Copper fire protection systems designed information including corrosion resis- Bushing(K=2.8) Bronze in accordance with the standard tant status.) installation rules recognized by the applicable Listing or Approval Maximum Working Pressure Operation agency (for example, UL Listing is Refer to Table B The glass bulb contains a fluid which based on the requirements of NFPA ands when exposed to heat.When 13, and FM Approval is based on the Tx Discharge Coefficient p p requirements of the FM Loss Prevention K = 2.8 GPM/psiv2 (40,3 LPM/bar1/2) the rated temperature is reached,the Data Sheets). Only the Style 10 or 40 K = 5.6 GPM/psi-I/2 (80,6 LPM/bar1/2) fluid expands sufficiently to shatter the Recessed Escutcheon,as applicable, K=8.0 GPM/psi112 (115,2 LPM/bar1/2) glass bulb, allowing the sprinkler to is to be used for recessed pendent activate and water to flow. installations. Temperature Ratings Refer to Table A Finishes Sprinkler:Refer to Table A Recessed Escutcheon:Signal or Pure White, Jet Black, Chrome Plated, or Natural Brass TFP151 Page 6 of 8 2-7/8"DIA. C-10, 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) _ (15,9±6,4 mm) 1/4"(6,4 mm) . 2-1/4"DIA. WRENCH RECESS FACE OF (57,2 mm) MOUNTING (END"A" USED FOR SPRINKLER 1/2" NPT MODELS) FITTING PLATE / 1/8" (3,2 mm) WRENCH RECESS mil (END"B"USED FOR I j j 3/4" NPT MODELS) \ t1 } FIGURE 7 MOUNTING W-TYPE 6 SURFACE A SPRINKLER WRENCH CLOSURE SERIES 1-1/4"(31,8 mm) TY-B 3/4"(19,1 mm) WRENCH RECESS FIGURE 5 ��f SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY D�° WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT i 2-7/8"DIA. (73,0 mm) 3/4"(19,1 mm) ."�� _ 5/8±1/4" PUSH WRENCH (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) IN TO ENSURE (57,2 mm) ' ENGAGEMENT FACE OF MOUNTING WITH SPRINKLER SPRINKLER PLATE WRENCHING AREA FITTING / 1/8" FIGURE 8 1 14 (3,2 mm) W-TYPE 7 RECESSED \ �far SPRINKLER WRENCH ,i , Installation MOUNTING �� The TYCO Series TY-B, 2.8, 5.6, and SURFACE , -z---•-• 8.0 K-factor, Upright and Pendent CLOSURE SERIES 1-5/16"(33,3 mm) Sprinklers must be installed in accor- TY-B 13/16"(20,6 mm) dance with this section. NOTICE FIGURE 6 Do not install any bulb type sprinkler if SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY the bulb is cracked or there is a loss of WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT liquid from the bulb. With the sprinkler STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 INCH NPT held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F(57°C) to 3/32 inch (2,4 mm) for the 360°F (182°C) temperature ratings. A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Obtain a leak-tight 3/4 inch NPT sprinkler joint by applying a minimum to maximum torque of 10 to 20 ft.-lbs. (13,4 to 26,8 Nm). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. TFP151 Page 7 of 8 Do not attempt to make-up for insuf- Recessed Pendent Sprinklers replaced. Also, replace any sprinkler ficient adjustment in the escutcheon The Series TY-B Recessed Pendent that has a cracked bulb or that has lost plate by under-or over-tightening the Sprinklers must be installed in accor- liquid from its bulb. (Ref. Installation sprinkler. Readjust the position of the dance with the following instructions. Section.) sprinkler fitting to suit. Step A. After installing the Style 10 The owner is responsible for the Upright and Pendent Sprinklers or 40 Mounting Plate, as applicable, inspection,testing,and maintenance of The Series TY-B Upright and Pendent over the sprinkler threads and with their fire protection system and devices Sprinklers must be installed in accor- pipe-thread sealant applied to the pipe in compliance with this document, as dance with the following instructions. threads,hand-tighten the sprinkler into well as with the applicable standards of the sprinkler fitting. the National Fire Protection Association Step 1. Install pendent sprinklers in the pendent position; install upright Step B. Tighten the sprinkler into the (for example, NFPA 25), in addition to the standards of any other authorities sprinklers in the upright position. sprinkler fittin g usin g only the W-Type i ihavng jurisdiction. Contact the install- 7 Recessed Sprinkler Wrench (Figure Step 2. With pipe-thread sealant 8). With reference to Figure 3 or 4,the ing contractor or sprinkler manufacturer applied to the pipe threads, hand- W-Type 7 Recessed Sprinkler Wrench regarding any questions. tighten the sprinkler into the sprinkler to the sprinkler wrench flats. Automatic sprinklers are recommended fitting. to be inspected,tested,and maintained Step 3. Tighten the sprinkler into the Step C.After cathe applied,is installed the by a qualified Inspection Service in sprinkler fitting using only the W-Type the e 10 or 40 is Closure slide Series ies accordance with local requirements Style 10 or 40 Closure over the Series 6 Sprinkler Wrench (Figure 7). For TY-B Sprinkler and push the Closure and/or national codes. wax-coated sprinklers, use an 8 or over the Mounting Plate until its flange 10 inch adjustable Crescent wrench. contacts the ceiling. With reference to Figures 1 through 4, apply the W-Type 7 Sprinkler Wrench Care and or the adjustable Crescent wrench, as applicable is to be applied to the Mai wrench wrench flats. When installing wax-coated sprinklers The TYCO Series TY-B, 2.8, 5.6, and with the adjustable Crescent wrench, 8.0 K-factor, Upright and Pendent exercise care to prevent damage to the Sprinklers must be maintained and ser- wax coating on the sprinkler wrench viced in accordance with this section. flats or frame arms and,consequently, exposure of bare metal to the corrosive Before closing a fire protection system environment. Open the jaws of the main control valve for maintenance wrench sufficiently wide to pass over work on the fire protection system the wrench flats without damaging the that it controls, obtain permission to wax coating. Before wrench tightening shut down the affected fire protection ' the sprinkler, adjust the jaws of the system from the proper authorities wrench to contact only the sprinkler and notify all personnel who may be wrench flats. After wrench tightening affected by this action. the sprinkler, loosen the wrench jaws Owners must ensure that sprinklers before removing the wrench. are not used for hanging any objects. After installation,inspect the sprinkler Otherwise, non-operation in the event wrench flats and frame arms and of a fire or inadvertent operation may retouch(repair)the wax coating when- result. ever the coating has been damaged Absence of an escutcheon, which is and bare metal is exposed. Retouch used to cover a clearance,may delay the wax coating on the wrench flats the time to sprinkler operation in a fire by gently applying a heated 1/8 inch situation. diameter steel rod to the damaged areas of wax, to smooth it back over Sprinklers which are found to be leak- areas where bare metal is exposed. ing or exhibiting visible signs of corro- sion must be replaced. NOTICE Automatic sprinklers must never be Only retouching of the wax coating painted, plated, coated, or otherwise applied to the wrench flats and frame altered after leaving the factory. arms is permitted, and the retouching Modified sprinklers must be replaced. is to be performed only at the time of Sprinklers that have been exposed to the initial sprinkler installation. corrosive products of combustion, but have not operated, should be replaced The steel rod should be heated only to if they cannot be completely cleaned the point at which it can begin to melt by wiping the sprinkler with a cloth or the wax, and appropriate precautions by brushing it with a soft bristle brush. ' need to be taken when handling the Care must be exercised to avoid dam heated rod in order to prevent the age to the sprinklers exercised before, Burin installer from being burned. and after installation.Sprinklers dam- ' aged by dropping, striking, wrench twist/slippage, or the like, must be TFP151 Page 8 of 8 P/N 57 - XXX - X - XXX • I I SIN SPRINKLER TEMPERATURE FINISH RATINGS 530 2.8K UPRIGHT(1/2-NPT) TY1151 1 NATURAL BRASS 135 135°F(57°C) 531 2.8K PENDENT(1/2"NPT) TY1251 3 PURE WHITE(RAL9010)• 155 155°F(68°C) 570 5.6K UPRIGHT(1/7 NPT) TY3151 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) 571 5.6K PENDENT(1/2"NPT) TY3251 X JET BLACK(RAL9005)°° 200 200°F(93°C) 590 8.0K UPRIGHT(3/4"NPT) TY4151 6 WAX COATED 286 286°F(141°C) 286°F(141°C)MAX 591 8.0K PENDENT(3/4 NPT) TY4251 7 LEAD COATED 360 360°F(182°C) 560 8.0K UPRIGHT(1/7 NPT) TY4851 8 WAX OVER LEAD 286°F(141°C)MAX 561 8.0K PENDENT(1/7 NPT) TY4951 9 CHROME PLATED •Eastern Hemisphere sales only. Available in only 8.0K,155°F(68°C) or 200°F(93°C);requires lead time to manufacture. TABLE C SERIES TY-8 UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-B (specify SIN), (specify K-factor), (specify Upright or Pendent) Sprinkler with (specify) temperature rating, (specify) finish or coating, P/N(Refer to Table C). Recessed Escutcheon Specify: Style (10 or 40) Recessed Escutcheon with(specify)finish,P/N°. 'Refer to Technical Data Sheet TFP770. Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387. Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 1 Telephone+1-215-362-0700 Copyright®2013 Tyco Fire Products,LP. All rights reserved. TEFLON Is trademark of The DuPont Corporation.