Specifications Y i FIRE CONTROL ASD-PL SERIES INSTRUMENTS LOW PROFILE ANALOG ADDRESSABLE PHOTOELECTROMC SENSOR APPROVED DESCRIPTION The FCI Model ASD-PL Low Profile Analog Addressable Photoelectronic Sensor is 1.7-inches high when mounted in 'a standard base,thus presenting a very low profile suitable for installation where architectural requirements are a prime concern. The sensor is continually monitored to measure any change �;: -° • or,:g APP in its sensitivity due to the environment (dirt, smoke, , temperature, humidity, etc.). It can give an advance " indication to the control panel of the need for maintenance • and can be specific as to where the maintenance is needed.If local regulations permit, then selected maintenance may be performed as opposed to having to check the sensitivity of all sensors to assure overall performance when only a few may be dirty. FEATURES Designed to operate in conjunction with the FCI Analog Addressable Fire Alarm controls, the ASD-PL sensor • Compatible with FCI Analog transmits an analog value representative of the sensitivity that Addressable Control Panels can be used by the system to determine when maintenance is • Low Profile Construction required.Signal processing for alarm verification is built into the system to provide immunity to false alarms. • Easy plug-in of the Head to Base The sensor is of plug-in construction and is directly interchangeable in the same base with the ASD-IL analog • Built-in Signal Processing ionization and ATD/ATD-R thermal sensors.A wide variety • Built-in Tamper-Resistant Feature of bases,with sounder,relay,etc.,is available.Remote LED annunciator capability is also available as an optional • Remote Test Feature (From the Panel) accessory. • Built-in Test Switch The ASD-PL detector is Listed for use inside ducts up to a velocity of 4,000 FPM. • 360° View Angle of Dual Alarm LEDs The sensor may be tested from the control panel, or functional testing can be performed by applying a test magnet • Removable Insect Screen and Cover according to the test procedures. for Field Cleaning An optional isolator base,Model B224B1,is also available. • Sealed against Dirt, Insects,and Installation of two of these isolator bases allows Style 7 Back Pressure operation for all sensors located between the bases. • Optional Bases for Auxiliary Functions • Maximum Air Velocity 4,000 FPM TECHNICAL SPECIFICATIONS Operating Voltage 15-32 VDC Standby Current (Sensor) 230 uA(without communication) 330 uA(one communication every 5 sec. with LED enabled) Alarm Current (max.)(LED lit) .007 amp. Remote LED current .007 amp. Operating/Installation Temperature 32°F- 120°F(0°C-49°C) Operating Humidity 10%to 93%relative humidity(non condensing) Dimensions 1.7"H x 6.2"Dia.(In standard base) Weight 3.6 oz. 301 2nd Ave Waltham, MA 02451-1133 USA TEL:(781)487-0088 FAX:(781)370-4132 9020-0373Ner. 1.3 • Fire Control Instruments,Inc. -- - - - - - - - - - ------- SENSOR COVER INSTALLATION Place the sensor into the sensor base.Turn the sensor clockwise until the sensor locks into place. To use the tamper-proof feature,break the smaller tab a 0 0 Id' on the base as shown in the installation instructions. Install the sensor. To remove the sensor from the base COVER when using the tamper-proof feature,insert the blade of REMOVAL a small screwdriver into the hole on the side of the base TARS SCREEN L SCREEN • and push the plastic lever away from the detector head. ;�, This will allow the sensor to be rotated counterclockwise for removal.NOTE:The decorative ••••••• ''' '�'' T''�'�''• ring must be removed in order to remove the head when ` SCREEN SENSING using the tamper-proof feature. PC BOARD 1 CONTACTS CHAMBER CONTACT Refer to NFPA 72,Chapter 5-3"Smoke Sensing Fire Detectors" for spacing, location of sensors and other guidelines. I =EMI TESTING Mil — m Cl Sensors may be tested locally in the following ways: MAINTENANCE • A.Place a test magnet against the sensor housing per the installation instructions.The Cleaning programs should be adapted to the sensor should go into alarm within 30 seconds. individual environment in conformance with the National Fire Alarm Code, NFPA 72. We recommend, • B.Field metering of sensor sensitivity may be performed with the aid of a voltmeter and Test at the least,an annual cleaning of the unit. The sensor per, rm 119-9010N.with the aid For the voltmeter screen and cover assembly can be removed, revealing Kit,P/N refer to the or instructions ecomplete furnished the sensing chamber.A vacuum cleaner can be used to with each test kit. remove dust from the screen, cover and sensing chamber. For the complete procedure, refer to the • C.Aerosol Generator-The Gemini Model Installation and Maintenance Instructions furnished 501 aerosol generator may be used to perform with each sensor. a functional test.Follow instructions in the generator instruction manual. AGENCY APPROVALS • D.Sensor sensitivity may be tested and measured at the control unit.Refer to the UL(Std 268) S1913 control panel operating manual. ORDERING INFORMATION Part No. odel Description 110-90001 ASD-PL Low Profile Analog Photoelectronic Sensor 110-90005B-FL Standard plug-in sensor base with flange and decorative ring 110-90004 B224RB Plug-in sensor base with auxiliary relay,SPDT, rated 2 amps. @ 30 VDC(resistive) 110-90006 B224BI Plug-in sensor isolator base for Style 7 operation 130-3100G B501BH Plug-in sensor base with sounder 110-31A60 B501 Plug-in sensor base w/o flange 138-01005 RA-400Z Remote alarm indicator 119-9010N Detector sensitivity test kit. Specifications are provided for information only and are believed to be accurate.However,no responsibility is assumed by Fire Control Instruments.Inc.for their use. Spedflcations subled to change without notice. 0 1997 All Rights Reserved 2 of 2 9020-0373 Addressable Modules • \)A, 1 t, .ti ADDRESSABLE MONITOR MODULE ADDRESSABLE MONITOR MODULE • (AMM-4,AMM-4S) (AMM-2) The Addressable Monitor Module AMM-4 provides an The Addressable Monitor Module AMM-2 provides an address for a group of UL Listed normally open (N.O.) address for a group of UL Listed normally open (N.O.) initiating devices, such as heat detector, beam smoke initiating devices, such as heat detector, projected beam detector, 4-wire smoke detector, waterflow switch, manual smoke detector, 4-wire smoke detector, waterflow switch, station,etc. wired in a Class A,Style D or Class B,Style B manual station, etc. wired in a Class B, Style B initiating initiating circuit.The AMM-4S(non-FM)also allows the use circuit. of multiple, conventional 2-wire smoke detectors in the circuit. ir � a A r 4 , Yv_=_ v.;. x% ADDRESSABLE OUTPUT MODULE FAULT INDICATOR MODULE uw (AOM-2) (M500X) The Addressable Output Module connects to the same loop The optional M500X Fault Indicator Module is used to as the initiating devices and provides a form"C"relay output, protect the system against wire-to-wire short circuits on the or notification appliance circuit,which may be programmed signaling line circuits. The modules should be spaced to operate from either a trouble or alarm input from any between groups of sensors in a circuit to protect the rest of addressable device. An external 24 VDC power source is the circuit. In the event of a short circuit between any two required when the module is configured as a notification fault indicator modules, then both modules immediately appliance circuit module,which can be configured as Class switch to an open circuit condition and isolate any groups of B,Style Y or Class A,Style Z.The module contains an LED sensors between them.The remaining units on the circuit will which can be latched on by code command from the panel. continue to operate in a normal fashion.In a Style 4 circuit, the module is generally used at each "T-tap" branch. The module has an LED indicator that lights continuously during a short circuit condition. 9020-0348 3 of 4 f FIRE CONTROL INSTRUMENTS, Inc. • i TECHNICAL AND ORDERING INFORMATION Part No. Model Description Supervisory Alarm Current Current SENSORS 110-31060 ASD-1 Analog Ionization smoke sensor .00030 amp. .007 amp. 110-90002 ASD-IL Low Profile Analog Ion.smoke sensor .00030 amp. .007 amp. 110-3106J ASD-P Analog Photoelectronic smoke sensor .00015 amp. .007 amp. 110-90001 ASD-PL Low Profile Analog Photo.smoke sensor .00033 amp. .007 amp. 112-3219I 2551T Analog Photoelectronic smoke sensor with 135°F thermal unit .00015 amp. .007 amp. 114-22020 ATD Analog Thermal fixed temp. 135°F.sensor .00020 amp. .007 amp. 115-91120 ATD-R Analog Thermal combination fixed temp. 135°F.and Rate of Rise sensor .00020 amp. .007 amp. MODULES • 190-00002 AMM-2 Addressable Monitor Module • (N/O devices,Style B only) .0004 amp. .007 amp. 190-00003 AMM-4 Addressable Monitor Module (N/O devices,Style D or B) .0004 amp. .007 amp. 190-00013 AMM-4S Addressable Sub-Loop Monitor Module (2-wire detectors,Style D or B)(non-FM) .0004 amp. .043 amp. 190-00010 AOM-2 Addressable Output Module .0004 amp. .007 amp. 190-00100 M500X Fault Isolator Module .00045 amp. .005 amp. 252-90001 MB500 Module mounting bracket(Holds up to 8 AMM/AOM modules) BASES,ACCESSORIES-(ASD-I,ASD-P,ATD,ATD-R,2551T) 110-31A60 B-501 Plug-in base,4-inches diameter 112-31B60 ADB-F Plug-in base,flanged,6.2-inches diameter 130-3100G B501B Horn assembly unit(includes base) .0011 amp. .0115 amp. 110-3136K B524RB Plug-in base,flanged,with auxiliary relay, SPDT,rated 2 amps. @ 30 VDC(resistive) .0007 amp. 110-90015 B524BI Plug-in isolator base for Style 7 operation .0007 amp. .005 amp. 110-38060 DH500 w/rel* Duct housing with relays .026 amp. .087 amp. 119-A0300 DH500 w/o rel* Duct housing less relays .00015 amp. .006 amp. 138-01005 RA-400Z Remote alarm indicator(mounts on single gang box) .007 amp. 119-5310P RTS451** Remote test switch with Alarm LED .007 amp. 119-90018 RTS451KEY** Key operated test switch with Alarm LED .012 amp. .007 amp. *Use with ASD-I or ASD-P only **Requires 24 VDC external source of power BASES-(ASD-IL,ASD-PL) 110-90005 ADB-FL Plug-in base,flanged,with decorative ring 110-90004 B224RB Plug-in base with auxiliary relay, SPDT,rated 2 amps. @ 30 VDC(resistive) .0007 amp. 110-90006 B224BI Plug-in isolator base for Style 7 operation .0007 amp. .005 amp. NOTE:Low profile sensors ASD-IL and ASD-PL may be used with B501,B501 BH and RA-400Z. Specifications are provided for information only and are believed to be accurate.However,no responsibility is assumed by Fire Control Instruments,Inc.for their use. Specifications subject to change without notice. ©1997 All Rights Reserved 4 of 4 9020-0348 U 0 F 600 SERIES INSTRUMENTS NI FIXED TEMPERATURE AND RATE OF E RISE HEAT DETECTORS APPROVED DESCRIPTION The 600 series heat detectors provide reliable dual-action .detection in an attractive low-profile package that protrudes only 1 3/8" from the ceiling surface. Smooth, pleasing contours and an all white finish blend in with most ceiling ""^ designs.The rate of rise feature detects fires that grow rapidly s _ in intensity by quickly responding when the rate of temperature rise exceeds 15°F(9°C)per minute. The fixed temperature element operates independently of the rate of rise feature and uses a fusible alloy. When ; ' R , activated,the external heat collector drops away to provide quick visual confirmation that the element has operated. ' A patented reversible mounting plate is supplied with each detector. In one position it attaches to a 3 1/4 or 4-inch octagon box or a plaster ring.In the other position,it can be used for open wiring without junction boxes. The different models are marked with unique paint schemes on the heat collector. The detector is 4 9/16" diameter by 1 3/8" high flush mounted,and 1 9/16" high surface mounted. FEATURES APPROVALS • Attractive Low Silhouette Design U.L.(Std 521) File S2332 • Easy to Install F.M. Approved • Dual action - uses Two, Independent C.S.F.M. 7270-0061:005 Detection Methods NYC BS&A 6-87-SA • 2-circuit Models Available APPLICATION INFORMATION Model Description Max.spacing allowed Marking Code 601,621 Comb. FT+ROR, 135°F(57°C) 50 x 50 ft(IJL) 30 x 30 ft(FM) None 602,622 Comb. FT+ROR,200°F(93°C) 50 x 50 ft(UL) 30 x 30 ft(FM) Gray ring 603,623 Fixed temp.only, 135°F(57°C) 25 x 25 ft(UL) 20 x 20 ft(FM) Gray spot 604,624 Fixed temp.only,200°F(93°C) 15 x 15 ft(UL) 15 x 15 ft(FM) Gray spot&ring ORDERING INFORMATION AND SPECIFICATIONS Part No. Model Description Contact Type 115-1112C 601 Comb. 135°FT+ROR SPST 115-1122C 621 Comb. 135°FT+ROR DPST 115-1412C 602 Comb.200°FT+ROR SPST 115-1422C 622 Comb.200°FT+ROR DPST 115-111 .`3 ,.603 FT 135°only SPST 115-1124C # 623 FT 135°only DPST 115-1414C 604 FT 200°only SPST • 115-1424C 624 FT 200°only DPST All contacts rated 1.0 ampere @ 6-28 VDC(resistive) Spedficabons are provided for information only and are believed to be accurate.However,no responsibility Is assumed by Fire Control Instruments,Inc.for their use. Specifications subject to change without notice. 01997 All Rights Reserved 301 2nd Ave Waltham, MA 02451-1133 USA TEL:(781)487-0088 FAX: (781)370-4132 9020-0036Ner. 1.3 I C CONDUIT Z � CB CIRCUIT BREAKER Q Ct o CLG CEILING V N Q. a CT CURRENT TRANSFORMER Richard Martin CU COPPER OR SUPERVISORS: LIC. 2865—S E EMERGENCY 'I)/(E) EXISTING R� •',` 1•( ) F'�1GP EMT ELECTRICAL METALLIC TUBING 014 `� �;O f, 1 // W •coy eect f l� - GFI GROUND FAULT INTERRUPTER P0pc a\ o a��y fop a d �� .-t D GND GROUND Fo cp. O. o�� ' ,, iro ECM` Pet�°' Lka�'' 4 paw"/ Lli GRC GALVANIZED RIGID STEEL CONDUIT See�ek P ,� _ . Job Pdd�e55 U IG ISOLATED GROUND gy; 0„1A/- P4 u) 1MC INTERMEDIATE METAL CONDUIT \�� < V z MCA MINIMUM CIRCUIT AMPS w MOCP MAXIMUM OVERCURRENT PROTECTION Q 0 � z NC NORMALLY CLOSED V„ BUSHING NO NORMALLY OPEN (7 Z W w PH PHASE 0 0 PNL PANEL w —_I cr Q PVC POLY-VINYL-CHLORIDE CK O (, ,,.../. TELE TELEPHONE 0... - Cr H TTB TELEPHONE TERMINAL BOARD (, Q , ( U TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER U 0 TYP TYPICAL ~ - W UL UNDERWRITERS LABORATORIES W WIRE WP WEATHERPROOF BID# 3126 JOB #: 00016 SCALE:As Noted DATE: 5-16-00 DRAWN BY: RM • CHECKED BY:FVR REVISIONS: CIIDO pUWING R CAPITOL ELECTRIC COJNC.Noe ALL RICHTS RESERVE. I I THESE DRAWINGS ARE TIE PROPERTY Cf CAPITOL ELECTRIC CO..INC.ARC ARE NOT TO BE USED OR REPROOLICED IN ANY MANNER EXCEPT WIN THE PRIOR WRITTEN PERMISSION O.CAPITOL ELECTRIC C0.1NC. 1 SHEET El