Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
$- zO13- Qacy- l b O S� v S • tLjco Fire & Building RECEIVED Products APR 0 2 2013 CITY OFTIGARD Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 BUILDING DIVISION Series EC -8 — 8.0 K- factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General tant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is r Description not representative of all possible cor- rosive atmospheres. Consequently, it The Series EC -8 Extended Coverage is recommended that the end user be Pendent Sprinklers are decorative consulted with respect to the suitability iir i <> glass bulb sprinklers designed for use of these corrosion resistant coatings " - s in light hazard occupancies. They are for any given corrosive environment. intended for use in automatic sprinkler The effects of ambient temperature, systems designed in accordance with concentration of chemicals, and standard installation rules (e.g., NFPA gas /chemical velocity, should be con - 13) for a maximum coverage area of sidered, as a minimum, along with the 400 ft (37,2 m as compared to the corrosive nature of the chemical to maximum coverage area of 225 ft2 which the sprinklers will be exposed. (20,6 m for standard coverage sprin- klers used in light hazard occupancies. WARNINGS The recessed version of the EC 8, in- The Series EC -8 Extended Coverage Sprinklers described herein must be • tended for use in areas with a finished p ceiling, uses either the two -piece Style installed and maintained in compli- 30 or 40 Recessed Escutcheon. The ance with this document, as well as ;> with the applicable standards of the Style 30 Recessed Escutcheon pro- pp • vides up to 1/2 inch (12,7 mm) of total National Fire Protection Association, y>' - . adjustment from the flush pendent po in addition to the standards of any 0‹, f< sition, whereas, the Style 40 provides other authorities having jurisdiction. / 3/4 inch (19,1 mm) of vertical adjust- Failure to do so may impair the per- - - ment from the flush pendent position. formance of these devices. The adjustment provided by the Re- The owner is responsible for maintain- - cessed Escutcheons reduces the ac- ing their fire protection system and de- ` curacy to which the fixed pipe drops to vices in proper operating condition. the sprinklers must be cut. The installing contractor or sprinkler Corrosion resistant coatings, where manufacturer should be contacted applicable, are utilized to extend the with any questions. life of copper alloy sprinklers beyond Technical that which would otherwise be ob- Model /Sprinkler tained when exposed to corrosive at- Data mospheres. Although corrosion resis- Identification Approvals Number UL and C -UL Listed. FM and NYC Ap- proved. (Refer to Table A for complete IMPORTANT TY4232 - Pendent, 8.0K approval information including corro- Always refer to Technical Data sion resistant status. The approvals Sheet TFP700 for the 'INSTALLER TY4232 is a redesignation for C4232. apply to the service conditions indi- WARNiNG" that provides cautions cated in the Design Criteria section.) with respect to handling and instal- lation of sprinkler systems and com- Maximum Working Pressure ponents. Improper handling and in- 175 psi (12,1 bar) stallation can permanently damage Pipe Thread Connection • a sprinkler system or its compo- 3/4 inch NPT nents and cause the sprinkler to fail to operate in a fire situation or cause Discharge Coefficients it to operate prematurely. K = 8.0 GPM /psili (115,2 LPM /bar / Page 1 of 6 MARCH, 2007 TFP223 Page 2 of 6 TFP223 Components: 3/4" " ESCUTCHEON PLATE 1 1 - Frame 4 NPT SEATING SURFACE 2 - Button 3 - Sealing Assembly 4 - Bulb 2 / pr .___________ 5 Compression � >) 2 -1/8" / Screw 3 �; =, " , — , (54,0 mm) 6 - Deflector* 1/ * Temperature rating is 4 t NOMINAL 1 -7/16" indicated on Deflector. I ■ 1 MAKE -IN =r (36,5 mm) ** Pipe thread 5 o * • , connections per ISO - -- '-�' – 7/1 can be provided 6 on special request. FIGURE 1 SERIES EC -8 (TY4232) EXTENDED COVERAGE PENDENT SPRINKLERS SPRINKLER FINISH (See Note 4) HAZARD TYPE TEMP. BULB NATURAL CHROME WHITE* LIQUID BRASS PLATED POLYESTER LIGHT PENDENT 135 °F /57 °C Orange Refer to Table B for UL and C -UL 155 °F /68 °C Red 1. 2, 3, 5 Sensitivity Rating REC. PENDENT 135 °F /57 °C Orange and w/ Style 30 Esc. 155 °F /68 °C Red 1 , 2, 3, 5 Refer to Table C for FM Sensitivity Rating REC. PENDENT 135 °F /57 °C Orange w/ Style 40 Esc. 155 °F /68 °C Red 1 , 2. 5 NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL). 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL). 3. Approved by Factory Mutual Research Corporation (FM). 4. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. 5. Approved by the City of New York under MEA 113 -04 -E. *Frame and Deflector only. Listings and approvals apply to color (Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS (Refer to the Design Criteria Section) Temperature Ratings recessed installation, as applicable 135 °F /57 °C and 155 °F /68 °C Operation (Ref. Table A, B, and C). Finish The glass bulb contains a fluid that UL and C -UL Listing Sprinkler: Refer to Table A expands when exposed to heat. When Requirements Recessed Escutcheon: White Coated, the rated temperature is reached, the Chrome Plated, and Brass Plated fluid expands sufficiently to shatter the 1. The Series EC -8 Sprinklers may be glass bulb, allowing the sprinkler to used for the coverage areas shown Physical Characteristics activate and flow water. in Table D, based on maintaining the Frame Bronze minimum specified flow rate as a Button Bronze function of coverage area and haz- Sealing Assembly Design and group for all of the sprinklers in Beryllium Nickel w /Teflont the design area. Bulb Glass (3 mm dia.) Criteria Compression Screw 2. With respect to heat sensitivity, the Bronze The Series EC -8 Extended Coverage Series EC -8 Sprinklers can be used Deflector Brass Pendent Sprinklers must only be in- with unobstructed construction con - stalled in accordance with the applica- sisting of flat, smooth ceilings (in- • t Registered trademark of DuPont ble UL and C -UL Listing or FM Ap- cluding bar joists) with a maximum proval requirements as indicated pitch of one in six as defined and below. Only the Style 30 or 40 Re- permitted by NFPA 13. cessed Escutcheon is to be used for 3. The minimum allowable spacing be- TFP223 Page 3 of 6 135 °F 155 °F Installation AREA STYLE The Series EC -8 Sprinklers must be installed in accordance with the follow- ing instructions: 16 x 16 Pendent QR QR 16 x 16 Style 30 Recessed QR QR NOTES 16 x 16 Style 40 Recessed OR OR Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of 18 x 18 Pendent QR QR liquid from the bulb. With the sprinkler 18 x 18 Style 30 Recessed QR SR held horizontally, a small air bubble 18 x 18 Style 40 Recessed QR SR should be present. The diameter of the air bubble is approximately 1/16 inch 20 x 20 Pendent QR SR (1,6 mm). 20 x 20 Style 30 Recessed QR SR A leak tight 3/4 inch NPT sprinkler joint 20 x 20 Style 40 Recessed SR SR should be obtained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi - OR Quick Response mum of 30 ft.lbs. (40,7 Nm) of torque SR: Standard Response is to be used to install sprinklers. N /A: Not Applicable Higher levels of torque may distort the sprinkler inlet with consequent leak - TABLE B age or impairment of the sprinkler. SENSITIVITY RATING FOR UL AND C -UL LISTING Do not attempt to compensate for in- OF SERIES EC -8 SPRINKLERS sufficient adjustment of an Escutcheon Plate by under- or over - tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. 135 °F 155 °F Step 1. The sprinkler must be installed with the deflector parallel to the mount- ing surface. Pendent sprinklers must AREA STYLE be installed in the pendent position. Step 2. After installing the Style 30 or 16 x 16 Pendent QR QR 40 mounting plate (or other escutch- 16 x 16 Style 30 Recessed QR N/A eon, as applicable) over the sprinkler 16 x 16 Style 40 Recessed N/A N/A pipe threads, and with pipe thread sealant applied to the pipe threads, 18 x 18 Pendent QR QR hand tighten the sprinkler into the 18 x 18 Style 30 Recessed QR N/A sprinkler fitting. 18 x 18 Style 30 Recessed N/A N/A Step 3. Wrench tighten pendent sprin- klers using only the W -Type 3 (End A) 20 x 20 Pendent OR OR Sprinkler Wrench. Wrench tighten the 20 x 20 Style 30 Recessed QR N/A recessed pendent sprinklers using 20 x 20 Style 40 Recessed N/A N/A only the W -Type 23 Sprinkler Wrench. The wrench recess of the applicable QR: Quick Response sprinkler wrench (Ref. Figure 4 and 5) SR: Standard Response is to be applied to the sprinkler wrench N /A: Not Applicable flats (Ref. Figure 1). TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC -8 SPRINKLERS tween the Series EC -8 Sprinklers, to FM Approval prevent cold soldering, is 8 feet (2,4 Requirements m). The Series EC -8 Extended Coverage Sprinklers are to be installed in accord - 4. The Series EC -8 Sprinklers are to be ance with the applicable Factory Mu- installed in accordance with all other tual Loss Prevention Data Sheet. Infor- requirements of NFPA 13 for ex- mat ion provided in the FM Loss tended coverage pendent sprin- Prevention Data Sheets relate to, but klers. are not limited to, hydraulic design, ceiling slope and obstructions, mini- mum and maximum allowable spac- ing, and deflector -to ceiling distance. Page 4 of 6 TFP223 "FITTING SIDE" TOWARDS SPRINKLER FITTING • DESCRIPTION AREA GPM PSI TY4232 (K =8.0) PENDENT 16 x 16 26 10.6 _ / G 18 x 18 33 17.0 20 x 20 40 25.0 1 ft. = 0.3048 m WRENCH 1 ft = 0.093 m2 RECESS 1 gpm = 3.785 Ipm ^ (END "A ") 1 psi = 0.06895 bar 1 gpm/ft = 40.74 mm/min FIGURE 4 TABLE D W -TYPE 3 SPRINKLER FLOW CRITERIA FOR UL AND C -UL LISTING WRENCH OF SERIES EC -8 SPRINKLERS WRENCH 2 -7/8" DIA. RECESS 1/211/8" (73,0 mm) 1/2" (12,7 mm) / (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) C S C SPRINKLER 1/8 — i '� FITTING (3,2 mm) 4 �� A �. ■ ® CEO iii f \ .........; , MOUNTING SURFACE VI MOUNTING 11111 PLATE CLOSURE - — = FIGURE 5 1 - 1/4" (31,8 mm) W -TYPE 23 RECESSED 1^ (25,4 mm) SPRINKLER WRENCH FIGURE 2 SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT Care and STYLE 30 RECESSED ESCUTCHEON Maintenance 2 - 7/8" DIA. The Series EC -8 Sprinklers must be 9/16 ±1 /4" (73,0 mm) 3/4" (19,1 mm) maintained and serviced in accord - (14,3±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) ance with the following instructions: FACE OF (57,2 mm) SPRINKLER 1/8" NOTE FITTING (3,2 mm) Before closing a fire protection system main control valve for maintenance work on the fire protection system that � _ f it controls, permission to shut down Jl ■� the affected fire protection systems i , must be obtained from the proper MOUNTING authorities and all personnel who may fl SURFACE MOUNTING be affected by this action must be no- oll PLATE tified. CLOSURE _ = Sprinklers that are found to be leaking 1 - 5/16" (33,3 mm) or exhibiting visible signs of corrosion 13/16" (20,6 mm) must be replaced. FIGURE 3 Automatic sprinklers must never be • SERIES EC -8 RECESSED PENDENT SPRINKLER ASSEMBLY painted, plated, coated, or otherwise WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT altered after leaving the factory. Modi- STYLE 40 RECESSED ESCUTCHEON fled sprinklers must be replaced. Sprinklers that have been exposed to TFP223 Page 5 of 6 corrosive products of combustion, but Limited Ordering have not operated, should be replaced if they cannot be completely cleaned - by wiping the sprinkler with a cloth or Warranty Procedure by brushing it with a soft bristle brush. Care must be exercised to avoid dam- Products manufactured by Tyco Fire & When placing an order, indicate the age to the sprinklers before, during- Building Products (TFBP) are war- full product name. Please specify the and after installation. Sprinklers dam- ranted solely to the original Buyer for Sprinkler Identification Number (SIN), ten (10) years against defects in mate- quantity, and temperature rating. Re- ands e aged twist/slippage, dropping, striking, wrench h rial and workmanship when paid for fer to the Price List for complete listing p ag e, or the like, replaceanysmu must st be that and properly installed and maintained of Part Numbers. placed. has a cracked bulb or that has lost under normal use and service. This Contact your local distributor for avail - liquid from its bulb. (Ref. Installation warranty will expire ten (10) years ability. from date of shipment by TFBP. No Section). warranty is given for products or corn- Frequent visual inspections are rec- ponents manufactured by companies Sprinkler Assemblies with NPT ommended to be initially performed for not affiliated by ownership with TFBP Thread Connections: corrosion resistant coated sprinklers, or for products and components which Specify: ), Exte , (specify tempera after the installation has been corn- have been subject to misuse, improper tune rating), Extended Coverage Pen pleted, to verify the integrity of the cor- installation, corrosion, or which have dent Sprinkler with (specify finish), P/N rosion resistant coating. Thereafter, not been installed, maintained, modi- (specify). annual inspections per NFPA 25 fied or repaired in accordance with ap- 135 °F /57°c should suffice; however, instead of in- plicable Standards of the National Fire Natural Brass PSN 50 -801 - -135 specting from the floor level, a random Protection Association, and /or the White Coated ) PSN 50-801-4-135 P 9 White (RAL9010' PSN 50- 801 -3 -135 sampling of close -up visual inspec- standards of any other Authorities Chrome Plated PSN 50- 801 -9 -135 tions should be made, so as to better Having Jurisdiction. Materials found 155 °F /68 °C determine the exact sprinkler condi- by TFBP to be defective shall be either Natural Brass PSN 50 -801 -1 -155 tion and the long term integrity of the repaired or replaced, at TFBP's sole White Coated PSN 50-801-4-155 corrosion resistant coating, as it may option. TFBP neither assumes, nor wn to (RALSO1o) PSN 50- 801 -3 -155 be affected by the corrosive conditions authorizes any person to assume for it, Chrome Plated PSN 50- 801 -9 -155 present. any other obligation in connection with 'Eastern Hemisphere sales only the sale of products or parts of prod - The owner is responsible for the in- ucts. TFBP shall not be responsible for Recessed Escutcheon: spection, testing, and maintenance of sprinkler system design errors or inac- Specify: Style (30 or 40) Recessed their fire protection system and de- curate or incomplete information sup- Escutcheon with (specify finish), P/N vices in compliance with this docu- plied by Buyer or Buyer's repre- (specify). ment, as well as with the applicable sentatives. standards of the National Fire Protec- Style 30 Recessed Escutcheon, tion Association e. NFPA 25 , in In no event shall TFBP be liable, in Chrome Plated PSN 56- 705 -9 -011 • ( g., ) contract, tort, strict liability or under White Color Coated PSN 56- 705 -4 -011 addition to the standards of any other White (RAL9010)' PSN 56- 705 -3 -011 authorities having jurisdiction. The in- any other legal theory, for incidental, Brass Plated PSN 56- 705 -2 -011 indirect, special or consequential dam - stalling contractor or sprinkler manu- ages, including but not limited to labor Style 40 Recessed Escutcheon facturer should be contacted relative charges, re Chrome Plated PSN 56 -700 -9 -010 , gardless of whether TFBP White Color Coated PSN 56- 700 -4 -010 to any questions. was informed about the possibility of White (RAL9010)' PSN 56- 700 -3 -010 It is recommended that automatic such damages, and in no event shall Brass Plated PSN 56- 700 -2 -010 sprinkler systems be inspected, TFBP's liability exceed an amount tested, and maintained by a qualified equal to the sales price. *Eastern Hemisphere sales only. Inspection Service in accordance with The foregoing warranty is made in lieu Sprinkler Wrench: local requirements and /or national of any and all other warranties. ex- Specify: W-Te codes. press or implied. including warranties P/N 56 895 - 1-0013 Sprinkler Wrench, of merchantability and fitness for a par- ticular purpose, Specify: W -Type 23 Recessed Sprin- kler Wrench, P/N 56- 000 -6 -838. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. tLjCO Fire Suppression RECEIVED & B uilding Products NR 0 2 2013 CITY OFTIGARD Technical Services 800 -381 -9312 I +1- 401 -781 -8220 BUILDING DIVISION www.tyco - fire.com Series TY -FRB — 2.8 4.2,1 ' - Factor 6, and 8.0 K-Factor Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage G eneral Corrosion- resistant coatings, where applicable, are utilized to extend the - _ - Description life of copper alloy sprinklers beyond '� -'r" "+�' that which would otherwise be obtained The TYCO Series TY -FRB, 2.8, 4.2, 5.6, when exposed to corrosive atmo R and 8.0 K- factor, Upright and Pendent spheres. Although corrosion - resistant ; ' Sprinklers described in this data sheet coated sprinklers have passed the are quick response, standard coverage, standard corrosion tests of the appli- decorative 3 mm glass bulb -type spray cable approval agencies, the testing is i 4 sprinklers designed for use in light or not representative of all possible cor- ordinary hazard, commercial occupan- rosive atmospheres. Consequently, +' : ties such as banks, hotels, and shop- it is recommended that the end user ping malls. be consulted with respect to the suit- ability of these coatings for any given The recessed version of the Series TY corrosive environment. The effects of FRB Pendent Sprinkler, where applica- ambient temperature, concentration of ble, is intended for use in areas with a chemicals, and gas /chemical velocity, finished ceiling. This recessed pendent should be considered, as a minimum, sprinkler uses one of the following, along with the corrosive nature of the • A two-piece Style 10 (1/2 inch NPT) chemical to which the sprinklers will be / xts '� or Style 40 (3/4 inch NPT) Recessed 12,7 mm) exposed. ;-. ., Escutcheon with 1/2 inch w {� ( ) of An intermediate level of the Series TY- recessed adjustment or up to 3/4 inch FRB Pendent Sprinklers is detailed (19,1 mm) of total adjustment from the in Technical Data Sheet TFP356, and ";•+� flush pendent position, or a Sprinkler Guards are detailed in Tech- • A two -piece Style 20 (1/2 inch NPT) nical Data Sheet TFP780. or Style 30 (3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of NOTICE recessed adjustment or up to 1/2 inch The Series TY -FRB Concealed Pendent Model /Sprinkler (12,7 mm) of total adjustment from the Sprinklers described herein must be flush pendent position. installed and maintained in compliance Identification Number (SIN) adjustment provided by the with this document and with the appli Recessed Escutcheon reduces the cable standards of the National Fire accuracy to which the fixed pipe drops Protection Association, in addition to to the sprinklers must be cut. the standards of any authorities having TY1131: Upright 2.8K, 1/2 "'NPT jurisdiction. F ailure to do so may impair TY1231: Pendent 2.8K, 1/2 "" NPT the perform of these devices. TY2131: Upright 4.2K, 1/2" NPT Owners are r esponsible for maintaining TY2231: Pendent 4.2K, 1/2 "" NPT their fire protection system and devices TY3131: Upright 5.6K, 1/2 NPT in proper operating condition. The TY3231: Pendent 5.6K, 1/2" "NPT !�— TY4131: Upright 8.0K, 3/4" NPT TY4231: Pendent 8.0K, 3/4° NPT TY4831: Upright" 8.0K, 1/2" "NPT TY4931: Pendent* 8.0K, 1/2 "NPT •Eastern Hemisphere Sates Only IMPORTANT installing contractor or sprinkler manu- Always refer to Technical Data facturer should be contacted with any Sheet TFP700 for the "INSTALLER questions. WARNING" that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 JULY 2010 TFP171 I, TFP171 Page 2 of 10 7/16" (11,1 mm) ESCUTCHEON STYLE 10 or 20 * NOMINAL PLATE SEATING RECESSED SSU 1/2" MAKE -IN SURFACE ESCUTCHEON DEFLECTOR NPT ' 'Ir = I T 5 �: � �, 7/16" i 4 (11,1 mm) 2 -1/4" IN 2 1, I I NOMINAL MAKE -IN A II (57,2 mm) �� � �- -- 3 J 4` (5 mm) i I I 1-9/16" 4i0 Y WRENCH (39,7 mm) 1 a!� FLATS 7 y� = /�/'l, -,,. j , / rf!�\N 1/2 NPT SSP DEFLECTOR -..— 2 -7/8" (73,0 mm) DIA. —.-1 CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly - Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Com 7 - Bushing orifice seat on frame. Screw FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT 7/16" (11,1 mm) ESCUTCHEON STYLE 10 or 20 SSU* NOMINAL PLATE SEATING RECESSED SSU 1/2" MAKE -IN SURFACE ESCUTCHEON • DEFLECTOR NPT t 6* 5 7/16' r (11,1 mm) 2 -3 /16" ��1 4 I NOMINAL I,= (55,6 mm) �—_ MAKE -IN f IN fr 2/ I Irmo I 1- 1/2" � Pi 2 3/16' (55,6 mm) } � WRENCH (38,1 mm) 3 FLATS i 1 _ =,.._=,_.,,..... ._ 1 1 -- -.. 1/2" NPT SSP DEFLECTOR !— -- 2 -7/8" (73.0 mm) DIA. • --- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly ' Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT ir TFP171 Page 3 of 10 7/16" (11,1 mm) ESCUTCHEON STYLE 10 or 20 * NOMINAL PLATE SEATING RECESSED • SSU MAKE -IN 1/2" SURFACE ESCUTCHEON DEFLECTOR NPT 1 i 6 ` — _...._.. - -- 1 I 5 - -_ ;�, 7/16" — I ►► (11,1 mm) f " 1 4 ` NOMINAL I r (55,6 mm2 -3/16) i-_ i Fr MAKE -IN 1 2 -3/16" 1 1/2" 2 5,6 mm) WRENCH (38,1 mm) 3 f I _ FLATS — — — — — + _— 1 1 1/2" NPT SSP DEFLECTOR 2 -7/8° (73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - A s ling Deflector -Bulb 6 - Deflact • Temperature rating is indicated on deflector or adjacent to y 5 - Compression orifice seat on frame. 2 - Button Screw FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT 1/2' (12,7 mm) ESCUTCHEON STYLE 30 or 40 SSU * NOMINAL 3/4" PLATE SEATING RECESSED MAKE -IN SURFACE ESCUTCHEON DEFLECTOR NPT 6* I o ,07 try rrr - - ' . 5- - - try I 5 — 1/2" 14 { -- � 4 I ` (NOMINAL I 58,� '� ..,,, 1 MAKE -IN 111 ' ri o ( i 2 II A i / ?� p 2-1 m ' r= 9, 7 m Si �I� � � (57,2 mm) + (39,7 9/ 39,7mm) if 3/4" NPT SSP DEFLECTOR * — 2 -7/8" (73,0 mm) DIA. - -.- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly 5 - Compression ' Temperature rating is indicated on deflector or adjacent to 2 - Button Screw orifice seat on frame. QUICK RESPONSE SERIES TY-FRB 8 ° 0 K FACT UPRIGHT FIGURE 4 (TY4131) 3/4 INCH AND NP P ENDENT (TY4231) SPRINKLERS , T f. TFP171 Page 4 of 10 7/16" (11,1 mm) SSU NOMINAL DEFLECTOR MAKE -IN 1/2 • NPT 6 :'� %a'r', � /TIC`\ / /•i --- ,-�'c� =s 5 — 7/16" I (11.1 mm) I f 2-1/4" ' 4 NOMINAL anim -1 (57,2 mm) MAKE -IN — 2 Ft V ri 2 -3/16" 1110 1 -9/16" 3 (55,6 mm) _ f WRENCH (39.7 mm) FLATS II 1 SSP * CROSS 1/2" NPT DEFLECTOR SECTION UPRIGHT PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly ' Temperature rating is indicated on deflector or adjacent to 2 -Button 5 - Compression orifice seat on frame. Screw FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT Technical Operation inch (1,6 mm) for the 135 °F /57 °C and l" 3/32 inch (2,4 mm) for the 286 °F /141 °C Data The glass Bulb contains a fluid that temperature ratings. expands when exposed to heat. When Obtain a leak -tight 1/2 inch NPT sprin- Approvals the rated temperature is reached, the kler joint by applying a minimum to UL and C -UL Listed fluid expands sufficiently to shatter the maximum torque of 7 to 14 ft.lbs. (9,5 FM, LPCB, and NYC Approved glass Bulb, allowing the sprinkler to to 19,0 Nm). Higher levels of torque Refer to Table A and B for complete activate and water to flow. can distort the sprinkler Inlet with con - approval information including Sequent leakage or impairment of the corrosion - resistant status. Design sprinkler. Maximum Working Pressure Do not attempt to compensate for Criteria insufficient adjustment in the Escutch- Refer to Table C. eon Plate by under- or over - tightening Discharge Coefficient The TYCO Series TY -FRB Pendent the sprinkler. Re- adjust the position of 2) and Upright Sprinklers are intended the sprinkler fitting to suit. K =2.8 GPM /psi (40,3 LPM /bait / for fire protection systems designed in K =4.2 GPM /psis / (60,5 LPM /bart/ The Series TY -FRB Pendent and K =5.6 GPM/ sit /2 , accordance with the standard installa- p (80,6 LPM /bar ) tion rules recognized by the applicable Upright Sprinklers must be installed K =8.0 GPM /psis /2 (115,2 LPM /bar1/2) Listing or Approval agency (such as, UL in accordance with the following Listing is based on the requirements of instructions. Temperature Rating NFPA 13, and FM Approval is based on 1. Install Pendent sprinklers in the Refer to Table A and B. the requirements of FM's Loss Preven- pendent position. Install upright Finishes tion Data Sheets). Only the Style 10, sprinklers in the upright position. Sprinkler: Refer to Table A and B. 20, 30, or 40 Recessed Escutcheon, as 2. With pipe thread sealant applied to Recessed Escutcheon: White Coated, applicable, is to be used for recessed Chrome Plated, or Brass Plated. pendent installations. the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Physical Characteristics Installation 3. Tighten the sprinkler into the sprin- Frame Bronze kler fitting using only the W -Type 6 Button Brass /Copper The TYCO Series TY -FRB Sprinklers Sprinkler Wrench (Figure 14). With Sealing Assembly Beryllium must be installed in accordance with reference to Figures 1 through Nickel w/Teflont the following instructions. 5, apply the W-Type 6 Sprinkler . Bulb Glass Wrench to the sprinkler wrench Compression Screw Bronze NOTICE flats. Deflector Copper /Bronze Bushing (K =2.8) Bronze Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter t Registered Trademark of Dupont of the air bubble is approximately 1/16 r TFP171 Page 5 of 10 SPRINKLER FINISH (See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE*'* FACTOR COLOR BRASS PLATED POLYESTER 135 °F /57°C Orange PENDENT 155 °F /68 °C Red (TY1231) and 175'F/79'C Yellow 1, 2, 3, 4 UPRIGHT (TY1131) 200'F/93 °C Green 286 "F /141 °C Blue 135'F/57'C Orange 2.8 RECESSED 155`F/68`C Red 1/2" NPT PENDENT (TY1231)* 175'F/79 °C Yellow Figure 6 200'F/93 °C Green 1.2,4 135 °F /57 °C Orange RECESSED PENDENT 155F/68°C Red (TY1231)** 175'F/79'C Yellow Figure 7 200'F/93 °C Green 135 °F /57 °C Orange PENDENT 155'F/68 °C Red (TY2231) and 175'F/79'C Yellow UPRIGHT (TY2131) 200'F/93'C Green 286'F/141 °C Blue 135'F/57°C Orange 4.2 RECESSED 1/2" NPT PENDENT 155'F/68`C Red 1, 2 (TY2231)* 175'F/79°C Yellow Figure 8 200 °F /93'C Green 135'F/57'C Orange RECESSED • PENDENT 155`F/68 "C Red (TY2231)** 175 °F /79'C Yellow Figure 9 200'F/93°C Green NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354 -01 -E. 5. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C - Listed as Corrosion- Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "` Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K- FACTOR SPRINKLERS TFP171 Page 6 of 10 SPRINKLER FINISH (See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE*** LEAD FACTOR COLOR BRASS PLATED POLYESTER COATED 135`F/57'C Orange PENDENT (TY3231) 155 °F /68 °C Red and 175 °F /79'C Yellow 1, 2, 3, 4. 5, 6, 7 1 2. 3. 5 UPRIGHT 200'F/93'C Green (TY3131) 286'F/141 °C Blue 135 °F /57 "C Orange RECESSED 155"F/68°C Red 5.6 PENDENT 175 °F /79'C Yellow 1, 2, 4. 5 N'A. 1/2" NPT (TY3231)' • Figure 10 200F/93°C Green 286'F/141 °C Blue 135 "F /57'C Orange RECESSED 155`F/68`C Red PENDENT 175 °F /79'C Yellow 1, 2, 3. 4, 5 N/A (TY3231)** Figure 11 200 "F /93'C Green 286'F/141 °C Blue 135`F/57'C Orange PENDENT 155'F/68 °C Red (TY4231) and 175'F/79°C Yellow 1, 2. 3, 4, 5, 6. 7 1, 2, 5 UPRIGHT 200`F/93 "C Green (TY4131) 286 "F /141 °C Blue 135'F/57 °C Orange RECESSED 155'F/68 °C Red 8.0 PENDENT 175 "F /79'C Yellow 1, 2. 5 N A 3/4" NPT (TY4231)' Figure 12 200'F/93'C Green 286 °F /141 °C Blue 135 °F /57'C Orange RECESSED 155 °F /68 °C Red PENDENT 175 °F /79'C Yellow 1, 2. 3, 5 N.A (TY4231)" Figure 13 200 °F /93'C Green 286'F/141 °C Blue • 135'F/57 "C Orange PENDENT 155 "F /68 "C Red 8 0 (TY4931) 1/2 "NPT and 175'F/79'C Yellow 1, 2, 4. 5, 6 1. 2 5 UPRIGHT 200'F/93 "C Green (TY4831) 286'F/141`C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C - UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428- 3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead - Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion - Resistant Sprinklers. Where Lead - Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion- Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. • "' Frame and Deflector only. Listings and approvals apply to color (Special Order), N /A: Not Available • TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K- FACTOR SPRINKLERS v TFP171 Page 7 of 10 SPRINKLER FINISH • K TYPE NATURAL CHROME WHITE LEAD FACTOR BRASS PLATED POLYESTER COATED PENDENT (TY1231) and 2.8 UPRIGHT (TY1131) 1/2" NPT 175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY1231) PENDENT (TY2231) and 4.2 UPRIGHT (TY2131) 1/2" NPT 175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY2231) PENDENT (TY3231) 175 PSI and (12,1 BAR) 5.6 UPRIGHT (TY3131 250 PSI (17,2 BAR) 1/2" NPT OR 175 PSI (12,1 BAR) RECESSED (SEE NOTE 1) N/A PENDENT (TY3231) PENDENT (TY4231) 175 PSI and (12.1 BAR) $ 0 UPRIGHT (TY4131) 3/4" NPT 175 PSI (12,1 BAR) - RECESSED N/A PENDENT (TY4231) 8 0 PENDENT (TY4931) 175 PSI 1/2" NPT a n d 175 PSI (12,1 BAR (12,1 BAR) UPRIGHT (TY4831) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL): the Listing by Underwriters Laboratories, Inc. for use in Canada (C - UL); and, the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE The Series TY -FRB Recessed Pendent Care and Exercise care to avoid damage to Sprinklers must be installed in accor- sprinklers before, during, and after dance with the following instructions. Maintenance installation. Never paint, plate, coat, 1. After installing the Style 10, 20, 30, or otherwise alter automatic sprinklers or 40 Mounting Plate, as applica- The TYCO Series TY -FRB must be after they leave the factory. ble, over the sprinkler threads and maintained and serviced in accordance Replace sprinklers that: with pipe- thread sealant applied to with the following instructions. • were modified or over - heated. the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. NOTICE • were damaged by dropping, striking, wrench twisting, wrench slippage, or 2. Tighten the sprinkler into the sprin- B efore closing a fire protection system the like. kler fitting using only the W -Type 7 main control valve for maintenance Recessed Sprinkler Wrench (Fig - work on the fire protection system • are leaking or exhibiting visible signs ure 15). With reference to Figures 1 that it controls, obtain permission to of corrosion. to 4, apply the W -Type 7 Recessed shut down the affected fire protection • were exposed to corrosive products Sprinkler Wrench to the sprinkler systems from the proper authorities of combustion but have not oper- wrench flats. and notify all personnel who may be ated, if you cannot easily remove 3. After ceiling installation and finish- affected by this action. combustion by- products with a cloth, ing, slide on the Style 10, 20, 30, or Absence of the outer piece of an • have a cracked bulb or have lost liq- 40 Closure over the Series TY -FRB escutcheon, which is used to cover uid from the bulb. Refer to the Instal- • Sprinkler and push the Closure over a clearance hole, can delay sprinkler lation section in this data sheet. the Mounting Plate until its flange operation in a fire situation. comes in contact with the ceiling. TFP171 Page 8 of 10 2 -7/8° DIA. 2 -7/8" DIA. 5/8±1/4" (73.0 mm) 3/4° (19,1 mm) 1/211/8" _ (73,0 mm) 1/2" (12,7 mm) " (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12.7±3,2 mm) 2 -1/4" DIA f__ 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER I PLATE FITTING FITTING _l___;__-- 1/8" / / 1/8" q, (3,2 mm) _ sa (3,2 mm) 611111 1 r �l ai . I 1 - { \ - � \ 4 MOUNTING IV MOUNTING , 1'J I SURFACE SURFACE Al iifeti�� moire ___ CLOSURE SERIES 1-5/16" (33,3 mm) CLOSURE SERIES 1 -5/16" {33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm) FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. 2 -7/8" DIA. _ 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (15,9 ±6,4 mm) 2 1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) - FACE OF (57,2 mm) MOUNTING MOUNTING SPRINKLER - PLATE SPRINKLER PLATE FITTING FITTING 1/8" / JAM I (3,2 mm) .7:. 'S ri 1 , 1/8" �. (3,2 mm) � � � l• , 1J MOUNTING / MOUNTING SURFACE SURFACE - ■ - -- / ...- N .. - _ - SERIES 1 -1/4" (31,8 mm) SERIES 1 -1/4" (31,8 mm) CLOSURE CLOSURE TY-FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Initial and frequent visual inspections of Responsibility lies with the owner for Care must be exercised to avoid dam - random samples are recommended for the inspection, testing, and mainte- age to the sprinklers - before, during, corrosion - resistant sprinklers to verify nance of their fire protection system and after installation. Sprinklers dam - the integrity of the corrosion - resistant and devices in compliance with this aged by dropping, striking, wrench material of construction. Thereafter, document, as well as with the appli- twist /slippage, or the like, must be annual inspections per NFPA 25 should cable standards of the National Fire replaced. Also, replace any sprinkler suffice. Protection Association (for example, that has a cracked bulb or that has lost Inspections of corrosion resistant NFPA 25), in addition to the standards liquid from its bulb. (Ref. Installation sprinklers are recommended at close of any other authorities having jurisdic- Section). tion. Contact the installing contractor or range, instead of from the floor level sprinkler manufacturer regarding any Initial and frequent visual inspections of per NFPA. Inspection at close range random samples are recommended for can better determine the exact sprin- questions. corrosion- resistant sprinklers to verify kler condition and the long -term integ- Automatic sprinkler systems are rec- the integrity of the corrosion - resistant rity of the corrosion - resistant material, ommended to be inspected, tested, material of construction. Thereafter, which can be affected by the corrosive and maintained by a qualified Inspec- annual inspections per NFPA 25 should conditions present. tion Service in accordance with local suffice. requirements and /or national codes. TFP171 • Page 10 of 10 P/N 57 - XXX - X - XXX I I MODEL /SIN SPRINKLER TEMPERATURE FINISH RATINGS 330 2.8K UPRIGHT (1/2 "NPT) TY1131 1 NATURAL BRASS 135 135 °F (57 °C) 331 2.8K PENDENT (1/2 "NPT) TY1231 4 WHITE POLYESTER 155 155 ° F (68 °C) 340 4.2K UPRIGHT (1/2 "NPT) TY2131 3 WHITE (RAL9010)' 175 175 °F (79 °C) 341 4.2K PENDENT (1/2 "NPT) TY2231 9 CHROME PLATED 200 200 °F (93 °C) 370 5.6K UPRIGHT (1/2 "NPT) TY3131 7 LEAD COATED 286 286 °F (141 °C) 371 5.6K PENDENT (1/2 "NPT) TY3231 390 8.0K UPRIGHT (3/4 "NPT) TY4131 391 8.0K PENDENT (3/4 "NPT) TY4231 360 8.0K UPRIGHT (1/2 "NPT) TY4831" * Eastern Hemisphere sales only. 361 8.0K PENDENT (1/2 "NPT) TY4931" TABLE D PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS Limited responsible for sprinkler system design Ordering errors or inaccurate or incomplete infor- Warranty mation supplied by Buyer or Buyer's Procedure representatives. Products manufactured by Tyco Fire In no event shall TFSBP be liable, in Contact your local distributor for Suppression & Building Products contract, tort, strict liability or under availability. When placing an order, (TFSBP) are warranted solely to the any other legal theory, for incidental, indicate the full product name and Part original Buyer for ten (10) years against indirect, special or consequential dam- Number (P /N). defects in material and workmanship ages, including but not limited to labor when paid for and properly installed charges, regardless of whether TFSBP Sprinkler Assemblies with NPT and maintained under normal use and was informed about the possibility of Thread Connections service. This warranty will expire ten such damages, and in no event shall (10) years from date of shipment by TFSBP's liability exceed an amount Specify: (Specify Moo), (specify Quick TFSBP. No warranty is given for prod- y t Response, rating), , fa t Seri er s ), (specify ucts or components manufactured by equal to the sales price. temperature rating), Series TY-FRB companies not affiliated by ownership The foregoing warranty is made in lieu (specify Pendent or Upright) Sprinkler with TFSBP or for products and corn- of any and all other warranties, express with (specify type of finish or coating). ponents which have been subject to or implied, including warranties of mer- P/N (specify from Table D). misuse, improper installation, corro- chantability and fitness for a particular Recessed Escutcheon: sion, or which have not been installed, purpose. Specify: Style (10, 20, 30, or 40) maintained, modified or repaired in This limited warranty sets forth the Recessed Escutcheon with (specify') accordance with applicable Standards exclusive remedy for claims based on finish, P/N (specify *). of the National Fire Protection Associa- failure of or defect in products, materi- tion, and /or the standards of any other als or components, whether the claim is Sprinkler Wrench Authorities Having Jurisdiction. Mate- made in contract, tort, strict liability or Specify: W -Type 6 Sprinkler Wrench, rials found by TFSBP to be defective any other legal theory. P/N 56- 000 -6 -387. shall be either repaired or replaced, at TFSBP's sole option. TFSBP neither This warranty will apply to the full Specify: W -Type 7 Sprinkler Wrench, assumes, nor authorizes any person extent permitted by law. The invalidity, P/N 56- 850 -4 -001. • to assume for it, any other obligation in in whole or part, of any portion of this - Refer to Technical Data Sheet TFP770. connection with the sale of products or warranty will not affect the remainder. parts of products. TFSBP shall not be Copyright © 2007 -2010 Tyco Fire Suppression & Building Products. All rights reserved.