Final Inspection Report
Inspection Date:
Builder: Marnella Homes LLC
Subdivision: Barrows Road
Lot#: 21
Address: 11316 SW Hallmark Terrace
City: Tigard
Certifications: Energy Star/Earth Advantage
Solar Elements:
Re-inspection Required: No
Required Action: Earth Advantage final inspection has been approved. ENERGY STAR HVAC
and Water Management checklists and register flow measurements are required for certification.
The attached TEC is for your records.
Final Inspection Results
Insulation Inspection: Pass
Thermal Enclosure Checklist: Pass
Energy Star Measures: Corrections Needed
1
Earth Advantage Measures: Pass
Blower Door Test Results
Maximum Allowed ACH: 5.0 (for Earth Advantage) /4.0 (for ENERGY STAR)
Actual CFM: 824
ACH: 3
To better serve you, we measure and report the actual air flow of bathroom exhaust fans and the
ventilation system's intake air (when feasible). These flows serve as an indicator of the quality
of duct installation and to ensure that all equipment is capable of meeting ASHRAE 62.2.
Bath Fan Test Results
First Floor CFM: NA
2nd Floor CFM: 72
Master CFM: 84
To meet ASHRAE 62.2, all bathroom fans must be capable of exhausting at least 50 CFM. This
requirement only pertains to bathrooms with showers, tubs, spas, or similar sources of moisture
(not half baths or rooms with toilets only).
Ventilation Test Results
Required Continuous CFM: 48
Measured Continuous CFM: 70
Controller Setting: Honeywell set to 3 beds, 1900sf, 70cfm