Correspondence City of Tigard, Oregon • 13125 SWWHall Blvd. • Tigard, OR 97223
September 29, 2008
RE: FIRE ALARM SYSTEM , P,T GAR1N
Project Information }`iu *b
Building Permit: BUP2008 -00327 Construction Type: 2B
Tenant Name: Sanrio Occupancy Type: M
Address: 9585 SW Washington Sq. Required: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC), 2007 edition the Oregon Fire Code 2007 edition and 2002 edition of NFPA 72.
The submitted plans are approved subject to the following.
General Requirements
A separate low- voltage electrical permit is required for installation and inspection of
alarm wiring.
A completed inspection and testing form is required at the time of final inspection
containing the information as outlined in NFPA section 10.6.2.3.
TESTING — NFPA 72 Chapter 10, OFC 901.2.1, 901.5, 903.5
1. Upon completion of the installation, a satisfactory test of the entire system
shall be made in the presence of the building inspector. All functions of the
system or alteration shall be tested.
2. A record of completion in accordance with NFPD 72 verifying that the system has
been installed in accordance with the approved plans and specifications shall be
provided.
VISUAL ALARMS — NFPA 72 - 5.14.5, 7.5.4, OSSC chapter 9 & 11
3. When required; Visual alarms shall be located not less than 80 inches and not more
than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be
mounted within the dimensions stated above and at least 6 inches below the ceiling. No
place in a room shall be more than 50 feet from a visual signal. In corridors spacing
between devices shall be no more than 100 Ft. and no more than 15 Ft. from the end.
MANUAL ALARM - 1109.2.3.5, 1109.2.3.6 OSSC
4. Manual Fire Alarm activation devices when installed shall be mounted in the following
reach ranges:
• Forward Reach -15 inches to 48 inches above the floor.
• Side Reach — 9 inches to 54 inches above the floor.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
ALARM SIGNALS — OFC 903.4
5. Alarm, supervisory and trouble signals shall be distinctly different and shall be
automatically transmitted to an approved central station, remote supervising station or
proprietary supervising station as defined in NFPA 72 or, when approved by the fire
code official, shall sound an audible signal at a constantly attended location.
6. Duct smoke detectors shall be connected to the building's fire alarm control
panel when a fire alarm system is provided. Activation of a duct smoke detector
shall initiate a visible and audible supervisory signal at a constantly attended
location. Duct smoke detectors shall not be used as a substitute for required
open -area detection.
7. Automatic fire - extinguishing systems shall be connected to the building fire
alarm system where a fire alarm system is required by another section of this
code or is otherwise installed. OSSC 907.13
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.3.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respec ully,
AA
an N - Ison
Senior Plans Examiner
(503) 718 -2436
dann@tigard-or.gov