Plans[Page Too Large for OCR Processing]
[Page Too Large for OCR Processing]
FP52®I3- COO 3o
975q &,S
SIEMENS
Siemens Infrastructure & Cities
15201 NW Greenbrier Pkwy, Suite A4
Beaverton, OR 97006
Phone: (503) 207 -1900
Fax: (503) 207 -1901
Siemens Infrastructure & Cities
Fire Alarm System Contractor
Horizon Retail Construction
General Contractor
FIRE ALARM SUBMITTAL
Washington Square
The Art of Shaving
Suite D05
Siemens Job Number
5200330609
Siemens Project Manager
Charles Hughes
Submittal Version Date Siemens Project Engineer
Charles Hughes
Issued For PemtiVConstrucbon 03103/13
Proprietary document for approval only
Table of Contents SIEMENS
1 BILL OF MATERIAL &
COMPONENT SPECIFICATIONS
BILL OF MATERIALS SIEMENS
Washington Square
The Art of Shaving
Fire Alarm System
Item Part # Qty Mfg Description
1 FP -11 2 Siemens Photo -Smoke Detector
2 DB -11 2 Siemens Detector Base
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1 313/2013
SIEMENS Catalog Sheet
Fire Safety & Security Products
MXL, MXL -IQ and MXLV Panels
Intelligent FirePrint Detector
Model FP -11
ARCHITECT AND ENGINEER SPECIFICATIONS
• Most Sophisticated "Detector Intelligence" available in the Fire / Life Safety market
• Multi- criteria fire detection for the price of a photoelectric detector
• FirePrintTM' technology to distinguish between deceptive
phenomena and an actual fire _
• Easily programmed to match specific hazard profiles
from the fire -alarm control panel (FACP)
• Pre -Alarm reporting based upon fire profile selected
• Remote - sensitivity- measurement capability
• System -logic activation based upon any of three (3) .
inputs from the detector (smoke, heat or neural network) •
• Field- cleanable chamber with replaceable chamber parts �.
• Compatible with field programmer / tester (Model DPU) •.;
or FPI -32 Upgrade Kit
• Supports software - based, automatic environmental
compensation (EnviroLINK) • Multi- color, detector - status LED
• Backward compatible with older MXL systems
(Rev. 2 and above) • (2) Two -wire operation
• • Optional fully programmable relay base, audible base • OUL and OULC Listed;
and duct housing FM, CSFM & NYMEA Approved
Product Overview
The Intelligent Fire Detector (Model FP -11) provides methods and reduces in and service costs by
the most highly evolved detection system — electronically programming and testing the detector
including the most sophisticated level of protection; prior to installation.
as well as nuisance -alarm immunity — currently
available in the Fire I Life Safety market. Specifications
Model FP -11 utilizes advanced detection Model FP -11 is a plug -in, two -wire, multi- sensor
technology that allows the detector to distinguish detector with photoelectric and thermal inputs that is
non - threatening deceptive phenomena (i.e. - compatible with the MXL family of FACPs. Each
cigarette smoke) from actual fire hazards, while detector consists of a dust - resistant, field - cleanable
optimizing detection for the area of its intended photo chamber; a solid- state, non - mechanical thermal
zone. Model FP -11 uses state -of- the -art sensor, and microprocessor -based electronics with a
microprocessor circuitry with error check, detector low- profile plastic cover and base.
self- diagnostics and supervision programs. Model FP -11 utilizes state -of- the -art ASIC and surface -
Model FP -11 is compatible with the Siemens mount technology for maximum reliability. Every
Industry, Inc. — Fire Safety division's FPI -32 upgrade Model FP -11 fire detector is shipped with a protective
kit or Siemens' field - programmer I tester (Model dust cover. Model FP -11 fire detector utilizes an
DPU), which is a compact, portable and menu- infrared light- emitting diode (IRLED), and light sensing
driven accessory for efficiently programming and photodiode. Under normal conditions, light transmitted
testing detectors electronically. Model DPU or by the LED is directed away from the photodiode and
FPI -32 upgrade kit eliminates the need for scattered through the smoke chamber in a controlled
• cumbersome, unreliable mechanical programming pattern.
Intelligent FirePrint Detector 6175
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued)
The smoke chamber is designed to manage light sophisticated mathematical formulas or algorithms —
dissipation and extraneous reflections from dust comparing this input to characteristics of both
particles or other non -smoke airborne contaminants threatening fires and deceptive phenomena that would
in such a way as to maintain stable, consistent deceive any ordinary detector. This technology was
detector operation. When smoke enters the developed over years of research and reviewing the
detector chamber, light emitted from the IRLED results of over 20 years of fire -test data in one of the
is scattered by the smoke particles, and is received world's most advanced fire research centers. The
by the photodiode. results of this research are the mathematical models
Model FP 11 also utilizes a modern, accurate and that form the algorithms used in FirePrint. No other fire
shock - resistant thermistor to sense temperature detector has this level of intelligence or this amount of
changes. The 'on- board' FirePrint technology research and development supporting its design.
allows the detector to gather smoke and thermal The software of the microprocessor can identify and
data, analyzing this data in the detector's 'neural disregard false input caused by radio frequency (RFI)
network.' By comparing data received with the and electromagnetic (EMI) interference, and validates
common characteristics of fires, or fire fingerprints, all trouble conditions before annunciating or reporting
Model FP -11 can compare these 'fire prints' to to the control panel. The microprocessor for Model FP-
those of deceptive phenomena that cause other 11 uses an integral EEPROM to store the detector's
detectors to alarm. The advanced FirePrint address and other critical operating parameters, which
technology allows the Model FP -11 to accurately include the assigned program values for alarm and
determine a true fire hazard from non - threatening, trouble thresholds.
deceptive phenomena — without the need to use Communications within the detector; between Model
alarm delaying verification and confirmation FP -11 and the FACP; or with the field programmer I
techniques, which can increase the probability tester (Model DPU), are supervised and safeguarded
of losses due to fire. against disruption by reliable, microprocessor -based
Model FP -11 provides the highest level of detector error checking routines. Additionally, the
intelligence available today with a detector I microprocessor supervises all EEPROM memory
control -panel link that allows the user to program locations and provides a high degree of EEPROM failure
the detector for the specific hazard profile. fault tolerance.
Detectors are optimized by selecting one (1) of In MXL 1(V) applications, Model FP -11 determines its
the following applications: operating status to be in normal, alarm, or trouble
• Office I Retail mode, depending on the difference between the alarm
• Lobby threshold values stored in the detector's memory and
• Computer room the detector's latest analog measurement. The detector
• Dormitory then communicates changes in its status to the FACP.
• Healthcare facility In addition, the MXL 1(V) FACP will sample the value of
• Parking garage the analog signal for Model FP -11 over a period of time,
• Utility I transformer room
• Hostile environment in order to determine if those values indicate excessive
• Precious storage buildup in the photo chamber. In the event of
• Air duct excessive buildup, the MXL 1(V) FACP will accurately
• warehouse I light manufacturing indicate which detector shall require maintenance.
Once programmed, the software does the rest — Model FP -11 is listed as a self- testing device. The LED
no guessing on detector sensitivities or alarm for Model FP -11 flashes GREEN every four (4) seconds,
verification — the FACP programs Model FP -11 for indicating communication with the FACP, and that it
the protected area without any confirmation delays. has passed its self -test. Should the detector sense a
Once optimized for the hazards in the protected fault or failure within its systems, the LED will flash
area, Model FP -11 provides the utmost means in AMBER, and the detector will transmit that data to the
detection. Should the operator or installer forget FACP. A quick visual inspection is sufficient to indicate
to program the detector, Model FP -11 will revert the condition of the detector at any time. If more
to a default setting that, in turn, allows operation detailed information is required, a printed report can be
as a standard photoelectric or photothermal provided from the MXL panel, indicating the status and
detector. settings assigned to each individual detector.
The FP -11's FirePrint technology for Model FP -11 When Model FP -11 moves to the alarm mode, it will
monitors input from the photo chamber and the flash AMBER, and will transmit that data to the FACP.
thermal sensor, evaluating this information with When the MXL I (V) confirms the condition of the
detector, the FACP will instruct Model FP -11 to flash
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued)
RED — and to continue flashing RED, until the detector locks, as well as an installation tool, preventing
system is reset manually at the FACP. At that same unauthorized removal of the detector head. Model
time, any user - defined system alarm functions DB -11 has integral, decorative plugs to cover the outer
programmed into the system are activated. Each mounting screw holes.
Model FP -11 detector can operate one (1) remote Model FP -11 is electrically compatible with existing
alarm indicator; one (1) auxiliary relay, or one (1) MXL- detector accessories, including relays, remote
audible base. lamps, duct housings and audible bases. With duct
Detector sensitivity, calibration and identification housings, a base adapter and new detector housing
are dynamically supervised by the FACP. Detector cover are required (order AD -11 UK upgrade kit). To use
sensitivity and pre -alarm levels are a function of the existing Model DB -3S base or audible base, Model FP -11
application chosen at the FACP, and are controlled requires a base adapter (Model DB- ADPT).
by the panel. If an alternate, non - FirePrint mode is All Model FP -11 detectors are approved for operation
selected, then the sensitivity can be changed from within the ®UL- specified temperature range of 32 °F
the FACP. (0 °C) to 100 °F (38 °C).
The Program I Test unit (Model DPU) or FPI -32
upgrade kit is used to program and verify the Application Data
detector's address. The technician selects the Installation of the Model FP -11 series of fire detectors
accessory's program mode to enter the desired requires a (2) two -wire circuit of 18 AWG (minimum)
address. In turn, Model DPU or FPI -32 automatically thermoplastic fixture wire enclosed in conduit, or 18
sets I verifies the address, and tests the detector. AWG (American Wire Gauge) limited energy, shielded
Model DPU also allows the user to change the cable without conduit, if permitted by local codes. Field
device ID from that of a Model FP -11 detector to an wiring should conform to local and national electric
older detector ID (such as: ILP -1, ILPT -1, ILP -2, ID- codes and the control panel wiring specifications.
60P or ID -60PT) to allow for easy replacement of
older detectors without the need of reprogramming 'T- tapping" is permitted only for Style 4 (Class B) wiring.
the FACP. Model FP -11 fire detectors can be applied within the
The FPI -32 upgrade kit operates on AC power or maximum 30 -foot center spacing (900 sq. ft. areas), as
rechargeable batteries, providing flexibility and referenced in NFPA 72. This applications guideline is
convenience in programming and testing based upon ideal conditions — specifically — smooth
equipment from almost any location. When in test ceiling surfaces, minimal air movement, and no physical
mode, Model DPU or FPI -32 upgrade kit will perform obstructions between potential fire sources and the
a series of diagnostic tests without altering the detector. Do not mount detectors in close proximity to
address or other stored data, allowing technicians ventilation or heating and air - conditioning outlets.
to determine if the detector is operating properly. Exposed joints or beamed ceilings may also affect safe
Model FP -11 may be installed on the same initiating spacing limitations for detectors. Should questions arise
circuit with IL or ID series detectors (Photoelectric, regarding detector placement, observe National Fire
thermal, or ionization), MSI- series manual stations, Protection Association (NFPA) 72 guidelines.
TRI- series interfaces, ICP output control devices, or
CZM series of addressable, conventional -zone Dimensions
modules.
Diameter Base
All Model FP -11 detectors can be cleaned in the 6 " '
field — when required — by simply removing the
detector cover and unsnapping the photo chamber. T
There is also the option of cleaning the interior of
Overall
the detector with a clean, soft cloth or brush, or Height
replacing the labyrinth and bug screen included in 2.3" _f: "; ;: °'n ■
the detector maintenance kit, Model DMK -11. r�l�Jl
Model FP -11 uses the low- profile, surface - mounting
base, Model DB -11. This base mounts on a 4 -inch
octagon, square, or a single -gang electrical box.
The base utilizes screw -clamp contacts for electrical
• connections and self - wiping contacts for increased
reliability. The base can be used with the optional
Model LK -11 detector locking kit, which contains 50
SIEMENS Industry, Inc.
Building Technologies Division
Technical Data Details for Ordering
Environmental Model Part
Temperature: 32 °F (0 °C) to 100 °F (38 °C) Number Number Description
Humidity: Up to 93% RH, non - condensing
Air Pressure: No effect FP -11 500 -095112 Addressable FirePrint Detector
Alarm Temperature: 135 °F (57 °C) Detector Mounting Base
DB-11 500-094151 For Series 11 Intelligent Detectors
Electrical DB -11 E 500-094151E Detector Base (Small)
Voltage: 16 -27 VDC Air -Duct Housing (for use with Models
Ripple: 3V peak -to -peak AD2 -P 500- 649706 FP -11, HFP -11,
Supervisory Current: 110pA max •
HFPO -11 and PE -11 Detectors)
Air -Duct Housing (for use with Models
Alarm Current: 33 -50 mA AD2 -XHR 500- 649708 FP -11, HFP -11,
HFPO -11 Detectors with Relay)
ADBX -11 500 - 096181 Audible Base
DB -X11 RS 500 -096125 Relay Base for Series 11
Intelligent Detectors
RLI -1 500-390673 Remote Alarm Indicator:
4" Octagon Box Mount, Red
RLI-2 500-390674 Remote Alarm Indicator:
Single -Gang Mount, Red
DMK-11 500 - 695338 Series 11 Maintenance Kit (replacement
labyrinth and bug screen)
DB -ADPT 500 -094187 Base Adapter to Model DB -3S Base
LK -11 500 - 695350 Base Locking Kit for Series 11 Detectors
•
In Canada, please order:
Model Part Description
Number Number
135 °F Fixed Temperature, Plug -In
FP-11C 500 -095112C Detector Addressable FirePrintTM
Detector [ULC Listed]
Detector Mounting Base
DB -11C 500 - 095687 For Series 11 Intelligent Detectors
[@IJLC Listed]
AD -11 PC 500 -095984 Air -Duct Housing [60ULC Listed]
DB X11 RSC 500-093125C Relay Base for Series 11 Intelligent
Detectors [®ULC Listed]
ADBX 11C 500-096181C Audible Base for Series 11 Intelligent
Detectors [OULC Listed]
•
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up -to -date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Building Technologies Division Tel: (973) 593 -2600 sn.rs L6T 5E4 / Canada Supersedes gus �
20110
FAX: (908) 547 - 6877 Printed in U.S.A. Tel: (905) 799 -9937 (Rev.1)
URL: www.SBT.Siemens.com /FIS FAX: (905) 799 -9858