Specifications 7390 svti hfutnZike- S FP52013- Uzro l5 American Security Alarms, Inc. RECEIVED 5411 SE McLoughlin Blvd., Portland, OR 97202 (503) 231 -0303 JAN 2 3 2013 a. PROPOSAL CITY OFTIGARD BUILDING DIVISION COMMERCIAL FIRE ALARM SYSTEM Attn: Dave Nichols January 17, 2013 Robinson Construction Hilltop Building 7340 SW Hunziker, Tigard, OR. Additions for 2nd Floor Suite #201 - Steele & Nannini LLP. 1. Install (1) Smoke Detector in Bream Room Area 2. Replace existing Office Smoke Detector with new Smoke Detector. 3. Install (1) new Smoke Detector in Hallway to Office Areas 4. Connect new Smoke Detectors to existing Fire Alarm Circuit. 5. Clean & Testing (5) existing Smoke Detectors for proper operation. $ 695.00 Installed, Labor & Materials $ 125.00 Electrical Permit $ 250.00 Fire Permit, Fire Permit Plan Submittal (estimated cost only) Includes a one year warranty on all parts and labor No warranty on customer's existing Sensors, Devices, wiring /cables, etc. American Security to Re -use existing Fire alarm Cables /wiring for new Fire Alarm System Fire Alarm Permit & Plan Submittal is estimated cost only, maybe additional cost Lift if required will be at additional cost Proposal is subject to approval of Authority having Jurisdiction. Customer is responsible for additional requirements made by Authority having Jurisdiction upon plan review or inspection. Approved: Date: 503 - 231 -0303 - Please call if you have any questions 503 - 230 -1044 - Fax - If you would like to proceed, please sign above and fax to our office. Upon receipt, our scheduler: Ken Schwander will contact you to set a time for the work James D. Liston Security /Fire Alarm Consultant THE SECURITY PROFESSIONALS...SINCE 1970 - GiobarNw . SILENT Project Named '11E...,. . 0 Standby Hours: I 24 KNIGI IT Project ID, Alarm Mins: 5 [ Prepared B J;,_•: . , , Derating Factor: 1.2 I SK -5208 Calculations Date'', • i 1 Voltage Drop Warning Version 02.26.09 '{ . , -` Threshold % : 10 Panel ID: (SK - 5208 I Model: SK -5208 Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: [off 1st floor restroom Volts: 24 VDC Max Panel Current: 6.0 Amps Ckt.# Circuit Name qty Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ % Drop Standby_ Alarm & Type 1000 Ft. One -Way Ohms EOL SK -5208 SK -5208 Main Control 1 0.140 0.550 SK -5217 ' SK -5217 Zone Expdr 0.000 0.000 SK -5235 SK -5235 LCD Remote 0.000 0.000 SK -5280 SK -5280 Display Mod 0.000 0.000 SK -5220 SK -5220 Dir Con Mod 0.000 0.000 SK -7181 SK -7181 Zn Cnvtr 0.000 0.000 IDC -1 Initiating Device Ckt 1 ,015 NA" IDC -2 Initiating Device Ckt 2 0.008 NA ** IDC -3 Initiating Device Ckt 3 0.008 NA" IDC -4 Initiating Device Ckt 4 0.000 NA" IDC -5 Initiating Device Ckt 5 0.000 NA ** IDC -6 Initiating Device Ckt 6 0.000 NA ** IDC -7 Initiating Device Ckt 7 0.000 NA ** IDC -8 Initiating Device Ckt 8 0.000 NA ** IDC -9 Initiating Device Ckt 9 0.000 NA *" IDC -10 Initiating Device Ckt 10 0.000 NA ** IDC -11 Inactive1i Add S 117 0.000 NA ** IDC -12 Iif; C live I Add S K ±f; 97; '. 0.000 NA** IDC -13 .Iiiaictiire;:Atd 44-014::i: 0.000 NA *" 100 -14 .inactive; Ap.dd >,;ffi • • •:i 0.000 NA ** IDC -15 InaetiVg *' a ii 0.000 NA" IDC -16 I .J` 0.000 NA "* IDC -17 Ifl tiv @;::Add $,, , 0.000 NA "' IDC -18 Iiidjiie; S KI 0.000 NA" IDC -19 Iriactive;':Add $i.O 't'• 0.000 NA ** IDC -20 l I i . k4 10 f 0.000 NA'* IDC -21 IiiaG(iti@ : r : :,j 1 0.000 NA ** IDC -22 Inactive ` '. • '• I : 4 , 0.000 NA'" IDC -23 Iii t , t 3`n ; Ctiue;a ,;.�a. -..t ;:-31 � 0.000 NA*" 100 -24 ;'J'. ' ail otiue; tea v 0.000 NA'* ," IDC -25 I;:: ': 0.000 NA'" IDC -26 Inctiv8;.4d ' Ei 0.000 NA ** IDC -27 Inactive i Add 6K=• r :I , 0.000 NA ** IDC -28 In#Cjive; iAdd SK l y 0.000 NA ** IDC -29 Ind Add S 52171 0.000 NA ** IDC - 30 Iri $}S?5217=- 0.000 NA ** NAC -1 Notification Appl Ckt 1 0.000 0.220 #16 Solid 4.02 250 2.01 19.96 2.17% NAC -2 Notification Appl Ckt 2 0.000 0.110 #16 Solid 4.02 250 2.01 20.18 1.08% NAC -3 Notification Appl Ckt 3 r 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% NAC -4 Notification Appl Ckt 4 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% Aux Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% Total Standby Current (Amps) 0.156 0.880 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 3.744 _ 0.073 Total Alarm AH Required Total Combined AH Required 3.82 Command Shortcuts Multiply By The Derating Factor 1.20 - ■ . Minimum Battery AmpHours Required 4.58 Configure Circuits Print Page i - J *` The SK -5208 and SK -5217 limits alarm current to 95mA per zone. The SK -5208 alarm current includes 10% of system zones in alarm, but in no case less than three zones per UL 864. SYSTEM SENSOR' , Photoelectric Smoke Detectors System Sensor's i "' series smoke detectors represent • significant advancement in conventional detection. The i family is founded on three principles: installation ease, intelligence, and instant inspection. Features Installation ease. The P line redefines installation ease with its • Plug-in detector line, mounting base included plug -in design. This allows an installer to pre -wire the bases included with the heads. The large wire entry port and in -line terminals • Large wire entry port provide ample room for neatly routing the wiring inside the base. • In -line terminals with SEMS screws The base accommodates a variety of back box mounting methods, • Mounts to octagonal and single -gang backboxes, 4- square as well as direct mounting with drywall anchors. To complete the backboxes, or direct to ceiling installation, P heads plug in to the base with a simple Stop Drop 'N Lock action. • Stop -Drop 'N Lock attachment to base • Removable detector cover and chamber Intelligence. i detectors offer a number of intelligent features • Built in remote maintenance signaling to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i line to minimize •Drift compensation and smoothing algorithms nuisance alarms. Two -wire i detectors needing cleaning can • Simplified sensitivity measurement generate a remote maintenance signal, when connected to the •Wide angle, dual color LED indication 2W -MOD2 loop test/maintenance module, or to a panel equipped • with the i protocol. This signal is indicated by LEDs located at the Loop testing via EZ Walk feature module and the panel. The SENS -RDR, a wireless device, displays the • Built -in test switch sensitivityof P detectors in terms of percent per- foot- obscuration. Instant inspection. The i series provides wide -angle red and green LED indicators for instant inspection of the detector's condition: normal standby, out -of- sensitivity, alarm, or freeze trouble. When connected to the 2W -MOD2 loop test /maintenance module or a panel with the i protocol, the EZ Walk loop test feature is available on two -wire P detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector. Agency Listings T ® MEA MSFM LISTED APPROVED 1' approved approved " :11 3011446 72 1209210 190 -01 -E 2093 • ( 6 Smoke Detector Specifications Architectural /Engineering Specifications Smoke detector shall be a System Sensor i Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The detector shall be a photoelectric type (Model 2W -B, 4W-B) or a combination photoelectric/thermal (Model 2WT -B, 4W1 -13) with thermal sensor rated at 135 °F • (57.2 °C). The detector shall include a mounting base for mounting to 31 -inch and 4 -inch octagonal, single gang, and 4 -inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wring connections shall be made by means of SEMS screws.lhe detector shall allow pre - wiring of the base and the head shall be a plug -in type.The detector shall have a nominal sensitivity of 2.5 percent- per -foot nominal as measured in the UL smoke box. The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dual color LED indication which blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT -B) conditions. When used in conjunction with the 2W -MOD2 module, 2 -wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel, and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24V non - polarized Minimum: 85V Maximum: 35V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2 -wire: 50 pA maximum average; 4 -wire: 50 pA maximum average Maximum Alarm Current 2 -wire: 130 mA limited by control panel; 4 -wire: 20 mA @121/ 23mA @ 24V Peak Standby Current 2 -wire: 100 pA; 4 -wire: n/a Alarm Contact Ratings 2 -wire: n /a; 4-wire: 0.5 A @ 30V AC/DC Physical Specifications Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz. (178 grams) Operating Temperature Range 2W -B and 4W -B: 32 °F -120 °F (0 °C- 49°C); 2W1 -B and 4W1-B: 327-100°F (0`C- 37.8 °C) Operating Humidity Range 0 to 95% RH non - condensing Thermal Sensor 135 °F (57.2 °C) fixed Freeze Trouble 2WT-B and 4WT-B only: 41°F (5 °C) Sensitivity 2.5%/ft. nominal Input Terminals 14-22 AWG Mounting 31/2-inch octagonal back box 4 -inch octagonal back box Single gang back box 4 -inch square back box with a plaster ring Direct mount to ceiling LED Modes Power Up Sequence equence for LED Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information Model Thermal Wiring Alarm Current 2W -B No 2 -wire 130 mA max. limited by control panel 2WT-B Yes 2 -wire 130 mA max. limited by control panel 4W -B No 4 -wire 20 mA @ 12V, 23mA @ 24V 4WT -B Yes 4 -wire 20 mA @ 12V, 23mA @ 24V Accessories 2W-MOD2 2 -wire loop test / maintenance module RT Removal / replacement tool SENS -RDR Sensitivity reader A77 -AB2 Retrofit adapter bracket, 6.6 in. (16.76cm) diameter ' \ SYSTEM 3825 Ohio Avenue • St. Charles, IL 60174 ``t`°'" SENSOR' r „r rKMx=uy . - � p . ,,.�. i t �,. :� Phone: 800-SENSOR2 • Fax: 630-377-6495 ^""^ a "' �'" �" u°= ' °, **�r•y���� z� -• Ans -03? 3 -715 nx; e 1A7:i [Page Too Large for OCR Processing]