Correspondence ?30o uht 4A , Sz .5- - ,e /
BLOODWORTH, ELLIS, SEDER, McNAMARA i ARCHITECTS, P.C.
February 3, 1989
ACCEiVaD
Mr. Chris Hampson FEB 1 M39
Meier & Frank Co.
621 S.W. Fifth Snell* Onelopmert
Portland, Oregon 97204
Re: Washington Square
Mechanical Room Relocation
Job No. 88 -49
Dear Chris:
I filed plans with the City of Tigard this morning for review for building
permit. Before the plans can be reviewed they will need a plan check fee.
The fee is as follows:
City of Tigard Plan Review: $ 1,581.45
Washington County Fire
District No. 1 Fire and
Life Safety Review: $ 973.20
TOTAL: $ 2,554.65
This fee is base upon their evaluation of the work of $500,000.00.
Please send the fee by check to:
City of Tigard
P.O. Box 23397
Tigard, Oregon 97223
Attn: Nancy
RE: Plan Check No. 1 -46C
The earlier they receive the fee the faster plans can be reviewed.
Thank you.
Yours truly,
C CAOW 4 4/(A 14 /C4 - q?V` r--°
Darrel O.W. Kraxberger, A.I.A.
Architect
DWK:jr
5200 SW MACADAM, SUITE 370 • PORTLAND, OREGON 97201 • (503) 223 -6963
ggov /24 jijp s'Io 4/5
CITY OF TINA RD
OREGON
March 9, 1989
Darrel O. W. Rraxberger
_ Bloodworth, Ellis, Seder, McNamara /Architects, P.C.
5200 S. W. Macadam, Suite 370
Portland, OR 97201
Project: Meier & Frank Mechanical System
Dear Mr. Rraxberger:
Building plans for this project have been reviewed for conformity with
applicable codes, and are approved, subject to clarification or incluision
of the following items.
1. Provide 42 in. high guardrail inside Door 4. No landing
is indicated on exterior side.
2. Provide control details for the automatic smoke detector
shutdown of the air handling equipment.
The mechanical and plumbing systems are also approved, and separate
permits are required for that work. You may get all of the permits for
this project at your convenience. If you have any questions, or if we
may be of assistance, please contact us at any time.
Sincerely,
Jim Ja
Plans Examiner
13125 SW Hall Blvd., P.O. Box 23397, Tigard, Oregon 97223 (503) 639 -4171
• )//4/89
FIRE MARSHALS OFFICE U 41 7 041 5
Q`P` y Washington County Fire District No.1
W � O
d `� 1 . City of Beaverton Fire Department 83 tAks Rc4
Tualatin Rural Fire Protection District
c ..
; r' ' 4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, Oregon 97076 • Phone (503) 526 -2469
1#
February 27, 1989
Bloodworth /Ellis
5200 S.W. Macadam Avenue
Portland, Oregon 97201
RE: Mechanical Penthouse
Meier & Frank
Washington Square
Gentlemen:
The plans submitted to this office on February 21, 1989 have been reviewed
and approved, subject to the following requirements and /or comments:
1. Exit Door Hardware: All doors shown on the drawings must be openable
from the inside for immediate exit at all times without the use of a
key, special knowledge, or effort. UBC Sec. 3304
2. Landings at Doors: There must he a floor or landing on each side of
all doors. The floor or landing must not be more than one -inch lower
than the threshold of the doorway unless serving access for the
physically handicapped. UBC Sec. 3304(h)
3. Fire Extinguisher Required: A fire extinguisher having a minimum
rating of 2A10B:C must he placed in an accessible location within
plain view. UFC Sec. 10.301(a)
4. Approved Plans on Job Site: One set of approved plans hearing the
stamps of the Tigard Building Department and this office must he
maintained on the project site throughout all phases of construction
and must be made available to building and fire inspectors for
reference during required construction inspections. UBC Sec. 303
5. Certificate of Occupancy Required: Prior to the use and occupancy of
the project (space), a certificate of occupancy or other written
instrument of approval must be obtained from the City of Tigard
Building Department. UBC Sec. 307
•
Bloodworth /Ellis
February 27, 1989
Page 2
6. Exit Ways /Temporary Walls: During construction and relocation of the
new penthouse mechanical room, special care should be taken that no
exit ways on either floor (1st or 2nd) become obstructed or blocked
due to the new construction of this project. Further, temporary
walls to be constructed in the 2nd level training and accessory
rooms, as rioted on the plans, shall provide easy access to the exit
ways. At no time should access be obstructed by these walls.
It shall be further noted that fire protection for the penthouse
shall be done as prescribed on page FP -1, thus the alteration of the
sprinkler system and the alarm system shall meet the intent of all
applicable codes.
SPECIAL NOTICE:
DEVIATIONS FROM THE SUBMITTED AND HEREBY CONDITIONALLY APPROVED PLANS
DURING THE COURSE OF CONSTRUCTION, EXCLUSIVE OF THOSE NECESSARY TO
- COMPLY WITH FIRE SAFETY REQUIREMENTS AS LISTED HEREIN, ARE PROHIBITED
WITHOUT THE WRITTEN AUTHORIZATION OF THE WASHINGTON COUNTY BUILDING
DEPARTMENT AND THIS OFFICE.
APPROVAL OF SUBMITTED PLANS IS NOT AN APPROVAL OF OMISSIONS OR
OVERSIGHTS BY THIS OFFICE OR OF NON- COMPLIANCE WITH ANY APPLICABLE
REGULATIONS OF LOCAL GOVERNMENT.
If I can be of any further assistance to you, please feel free to contact
me at 526 -2501.
S ely ,
• / ,' \4 '
• ^✓
Bert •arker
Fire Marshal
BP:kw /
cc: Tigard Building Department t/
NOTE TO INSPECTOR:
These plans are for the construction of a new penthouse on the top of the
Meier & Frank /May Company, located at Washington Square. This new
penthouse shall become the housing unit for the air conditioning and air
handling for this occupancy. Two new air handling units are to be
installed and at the end of this project the old penthouse is to be
demolished and the units therein removed from the site project.
ii