Firestop Company
9384 S.W. Tigard Street
Tigard, Oregon 97223
Re: Wood Energy
Oregon Business Park Bldg. #4
16350 S.W. 72nd
6290B- 042 -005
Gentlemen:
This is a Fire and Life Safety Plan Review and is based on
the 1991 editions of the Uniform Fire Code (UFC) and those
sections of the Uniform Building Code (UBC) and Uniform
Mechanical Code (UMC) specifically referencing the fire
department, and other local ordinances and regulations.
This review covers the minor modifications to an existing
sprinkler system in the above noted occupancy. The
proposed modification is approved as submitted.
Call this office for inspection of installed equipment
while the installer is still on the job. Please notify
this office 24 hours prior to anticipated completion for
field verification of compliance of altered equipment.
NFPA 13 Sec. 1 -11
An approved set of plans shall be available to the
inspector at the job site at all times during construction.
Approval of submitted plans is not an approval of omissions
or oversights by this office or of non - compliance with any
applicable regulations of local government.
If you desire a conference regarding this plan review or if
you have questions, please feel free to contact me at (503)
526 -2469.
Sincerely,
y can :� ei to
Deputy Fire Ma al
DEF:kw
"Working" Smoke Detectors Save Lives
99- 00
-
d ,J
17.1
,L
—;� \ _ , , TUALATIN VALLEY FIRE & RESCUE
� " AND
'�' A BEAVERTON FIRE DEPARTMENT
/R S 4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, OR 97076 • (503) 526 -2469 • FAX 526 -2538
RE .
February 7, 1994
John H. Romish
2216 S.E. 24th Avenue
Portland, Oregon 97214
Re: Spec Office Space
16350 S.W. 72nd
6290B- 042 -005
Dear John:
This is a Fire and Life Safety Plan Review and is based on
the 1991 editions of the Uniform Fire Code (UFC) and those
sections of the Uniform Building Code (UBC) and Uniform
Mechanical, Code (UMC) specifically referencing the fire.
department, and other local'ordinances -and regulations.
Plans received for the above noted project have_been
reviewed and are. conditionally approved subject to the.
following:
1. Automatic Sprinkler Plans: Plans referred to and
examined by this office contain no provisions for the
alteration or installation of automatic sprinkler
system. Not less than three sets of plans for the
installation shall be submitted to this office for
approval prior to installation. UBC 302(b)
2. Address Required: The tenant space number must be
prominently displayed on the street front where it is
readily visible to drivers and officers of responding
fire apparatus and other emergency vehicles. UFC Sec.
10.208
3. Fire Extinguisher Requirements: Not less than one (1)
approved . fire extinguisher(s). with a rating of'not
less than ( *) shall be provided for each ( * *) square
..foot . of floor area .or fraction thereof.. The .
,.distance to-an-extinguisher from any portion _ ofd the
- building shall not exceed 75 feet. UFC Sec'. '10.505
"Working" Smoke Detectors Save Lives
John H. Romish
February 7, 1994
Page 2
( *) 2A10B:C, - Light and Ordinary Hazard
4A10B:C - Extra Hazard
•
( * *) 3 000 - Light Hazard
1,500 - Ordinary Hazard
1,000 - Extra Hazard
Note: Where flammable or combustible liquids are
used, "B" ratings of extinguishers may need to be
higher and travel distances shorter. See
requirements in National Fire Protection
Association Standard 10 -1.
Approval of submitted plans is not an approval of omissions
or oversights by this office or of non - compliance with any
applicable regulations of local government.
If I can be of any further'assistance to you, please feel
free to contact me at 526 -2502.
Sincerely,
Gene Birchill, DFM
Plans Examiner
GB:kw
cc: City of Tigard Building Department
6 -1,(7L - /- ' frg
',
C �% '� �, TUALATIN VALLEY FIRE & RESCUE
v'� ?� �) ; AND
c BEAV 9',�fl y�f `
ERTON FIRE DEPARTMENT
'A U C, J� ` / 4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, OR 97076 • (503) 526 -2469 • FAX 526 -2538
,
F & RES `
August 12, 1993
John H. Romish
2216 S.E. 24th Avenue
Portland, Oregon 97214
Re: Spec Office Space
Oregon Business Park 1
16350 S.W. 72nd
6290B- 042 -005
Dear Mr. Romish:
This is a Fire and Life Safety Plan Review and is based on
the 1991 editions of the Uniform Fire Code (UFC) and those
sections of the Uniform Building Code (UBC) and Uniform
Mechanical Code (UMC) specifically referencing the fire
department, and other local ordinances and regulations.
Plans are conditionally approved subject to Tigard Building
Department requirements and the following items:
1. The tenant space number must be prominently displayed
on the street front where it is readily visible to
drivers and officers of responding fire apparatus and
other emergency vehicles. UFC Sec. 10.208
2. Not less than one (1) approved fire extinguisher(s)
with a rating of not less than ( *) shall be provided
for each ( * *) square foot of floor area or fraction
thereof. The travel distance to an extinguisher from
any portion of the building, shall not exceed 75 feet.
UFC Sec. 10.303
( *) 2A10B:C - Light and Ordinary Hazard
4A10B:C - Extra Hazard
i
( * *) 3,000 - Light Hazard
1,500 - Ordinary Hazard
1,000 - Extra Hazard
"Working" Smoke Detectors Save Lives
John H. Romish
August 12, 1993
Page 2
Note: Where flammable or combustible liquids are used,
"B" ratings of extinguishers may need to be higher and
travel distances shorter. See requirements in National
Fire Protection Association Standard 10 -1.
3. Plans referred to and examined by this office contain
no provisions for the alteration or installation of
automatic sprinkler system. Not less than three sets
of plans for the installation shall be submitted to
this office for approval prior to installation. UBC
302(b)
Approval of submitted plans is not an approval of omissions
or oversights by this office or of non - compliance with any
applicable regulations of local government.
If I can be of any further assistance to you, please feel
free to contact me at 526 -2469.
Sincerely,
ex-
R ald W. Tobias
Deputy Fire Marshal
RWT:kw
cc: Tigard Building Department
✓
g 9 P
H.L. Green Company