Correspondence jt/AM, 752_ 4/6/99 I
FIRE MARSHALS OFFICE
WQ .`'- ' ° Q y,. Washington County Fire District No. 1
; -, City of Beaverton Fire Department
� Tualatin Rural Fire Protection District
'
4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, Oregon 97076 • Phone (5031 526 -2469
•
•
April 4, 1989
Dennis Woods
Mackenzie /Saito
P.O. Box 69039
Portland, Oregon 97201 -0039
RE: 15800 S.W Upper Boones Ferry Rd.
Oregon Bu siness Park II Bldg. A
Dear Dennis:
A fire and life safety plan review was conducted on the above captioned
project for compliance with the 1985 editions of the Uniform Building Code
(UBC), Uniform Mechanical Code (UMC), and the Uniform Fire Code (UFC), as
amended by Washington County Fire District No. l's Ordinance 86 -1.
Plans are conditionally approved as submitted subject to the following
items:
1. Automatic Sprinkler Plans: Plans referred to and examined by this
office contain no provisions for the alteration or installation of
automatic sprinkler system. Not less than three sets of plans for
the installation shall be submitted to this office for approval prior
to installation. UBC 302(b)
2. Fire Extinguisher Requirements: Not less than one (1) approved fire
extinguisher(s) with rating of not less than 2A10B:C shall be
provided for each 1,500 square feet of floor area or fraction
thereof. The travel distance to an extinguisher from any portion of
the building shall not exceed 75 feet. UFC Standard 10 -1
3. Approved Plans on Job Site: One set of approved plans bearing the
stamps of the Tigard Building Department and this office must be
maintained on the project site throughout all phases of construction
and must be made available to building and fire inspectors for
reference during required construction inspections. UBC Sec. 303
4. Inspections Required: Inspection and approval of construction by a
representative of this office is required: (a) prior to the cover of
any new framing elements following the installation of all utility
runs which will be concealed within wall and partition cavities; (b)
upon completion of construction and prior to occupancy of the tenant
space. UBC Sec. 305
Dennis Woods
April 4, 1989
Page 2
5. Certificate of Occupancy Required: Prior to the use and occupancy of
the project (space), a certificate of occupancy or other written
instrument of approval must be obtained from the City of Tigard
Building Department. UBC Sec. 307
SPECIAL NOTICE:
DEVIATIONS FROM THE SUBMITTED AND HEREBY CONDITIONALLY APPROVED PLANS
DURING THE COURSE OF CONSTRUCTION, EXCLUSIVE OF THOSE NECESSARY TO
COMPLY WITH FIRE SAFETY REQUIREMENTS AS LISTED HEREIN, ARE PROHIBITED
WITHOUT THE WRITTEN AUTHORIZATION OF THE WASHINGTON COUNTY BUILDING
DEPARTMENT AND THIS OFFICE.
APPROVAL OF SUBMITTED PLANS IS NOT AN APPROVAL OF OMISSIONS OR
OVERSIGHTS BY THIS OFFICE OR OF NON - COMPLIANCE WITH ANY APPLICABLE
REGULATIONS OF LOCAL GOVERNMENT.
If I can be of any further assistance to you, please feel free to contact
me at 526 -2502.
Sincerely,
Gene Birchill
Deputy Fire Marshal
GB:kw
cc: Tigard Building Department