Specifications
PRODUCT DATA FOR F eE PeOTECTI ON REM ODE L /.\ „41,4 9lio __d /l° i 6--- • m eo so Si/i 7 4-4 A e_ PENDENT, RECESSED PENDENT, AND UPRIGHT SPRINKLERS UNIVERSAL MODEL A STANDARD RESPONSE, 5mm BULB TYPE, 1/2" (15mm) ORIFICE, 1 /2" NPT ** SSU DEFLECTOR 6 ESCUTCHEON 1thY/ l� '� �1 �\'\ , :i�i,7!0'11a0 i " i `� PLATE SEATING i�� e- SURFACE i r — — 5 wREN FLAT 55,6mm ) i 2-3/16 � ( 4 2 � �i ` f� 3 M ODEL I/ 2-3/16 F700 NPT 4 (55� mm) 1-1 RECESSED ** (38,Imm) ESCUTCHEON �� SSP DEFLECTOR 2 -7/6" (73,0mm) DIA. . 7/16" (I I,Imm) MAKE -IN PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3- Gasketed 4 - Bulb 6- Deflector 2- Button Spring 5 - Compression Plate Screw ■ * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE A 1/2 INCH ORIFICE MODEL A PENDENT, RECESSED PENDENT, AND UPRIGHT SPRINKLERS ;; st; s,, :, ; design which allows installation of the installed and maintained in compli- GENERAL,DESCRIPTION sprinklers and pressure testing of the ance with this document, as well as fire protection system, prior to ceiling applicable standards of the National The 1/2 inch (15mm) orifice Universal construction and /or application of a fin- Fire Protection Association, in addi- Model A Pendent, Recessed Pendent, ish coat to the ceiling. They also permit tion to the standards of any other au- and Upright Sprinklers (Ref. Figure A) refinishing of a ceiling surface without thorities having jurisdiction. Failure are automatic sprinklers of the frangi- having to first shut down the fire pro- to do so may impair the integrity of ble bulb type. They are "standard re- tection system and remove the sprink- these devices. sponse - standard orifice spray sprink- lers. lers" intended for use in fire sprinkler The owner is responsible for main - systems designed in accordance with The adjustment provided by the F700 tailing their fire protection system the standard installation rules recog- substantially reduces the accuracy to and devices in proper operating con - nized by the applicable Listing or Ap- which the length of fixed pipe drops to dition. The installing contractor or proval agency (e.g., UL Listing is the sprinklers must be cut. Also, the manufacturer should be contacted rel- based on NFPA 13 requirements). The Closure has a 1/2 inch (12,7mm) wide ative to any questions. Pendent, Recessed Pendent, and Up- flange which provides ample clear - right Sprinklers all produce a hemi- ance for covering the mounting hole. Installation of Model A Pendent spherical water distribution pattern Sprinklers in recessed escutcheons below the deflector. other than the F700 will void all sprinkler warranties, as well as possi- The recessed versions of the Model A `•, bly void the sprinkler's Approvals Sprinkler are obtained by utilizing the iAPPROVALS AND ',STANDARDS.,- and /or Listings. Model A Pendent Sprinkler in combi- nation with the Model F700 Recessed Laboratory listings and approvals for Escutcheon (Ref. Figures A and C). the 1/2 inch (15mm) orifice Model A The F700 Recessed Escutcheon pro- Pendent, Recessed Pendent, and Up- TECHNICAL DATA vides 1/2 inch (12,7mm) of recessed right Sprinklers are given in Table A. adjustment or up to 3/4 inch (19,1 mm) The 1/2 inch (15mm) orifice Model A of adjustment from the flush pendent WARNING Pendent, Recessed Pendent, and Up- position. The 112 inch orifice ModelAPendent, right Sprinklers are rated for use at a Recessed Pendent, and Upright maximum service pressure of 175 psi • The F700 has a separable two - piece Sprinklers described herein must be (12,1 bar) and they are available in the Printed in U.S.A. 4 -94 TD516M 1 1 • SPRINKLER FINISH TYPE TEMPERATURE FRAME BULB NATURAL CHROME POLYESTER RATING COLOR LIQUID BRASS PLATED COATED CODE COLOR (All Colors) 135'F/57'C Unpainted Orange ) 155'F/68'C Unpainted Red PENDENT 175'F/79 •C White Yellow and 1, 2, 3, 5, 6 UPRIGHT 200'F/93'C White Green 286'F/141 °C Blue Blue 360 *F /182 °C Red Mauve 135 °F /57 °C Unpainted Orange RECESSED 155'F/68 °C Unpainted Red PENDENT' 1 , 2, 4, 6 1, 2, 6 175'F/79'C White Yellow 200'F/93 °C White Green NOTES: 1. Listed by Underwriters Laboratories, Inc. 2. Listed by Underwriters' Laboratories of Canada. 3. Approved by Factory Mutual Research Corporation. 4. Approved by Factory Mutual Research Corporation for use in Light Hazard and Ordinary Hazard (Groups 1 and 2) Occupancies.The FM Approvals for Ordinary Hazard Occupancies is limited to wet pipe sprinkler systems and preaction systems qualifying as wet pipe systems. 5. Approved by the Loss Prevention Council (United Kingdom). 6. Approved by the Scientific Services Laboratory (Australia). • Installed with 1/2" Model F700 Recessed Escutcheon. TABLE A LABORATORY LISTINGS AND APPROVALS DISCHARGE IN U.S. GALLONS PER MINUTE (GPM) temperature ratings and finishes indi- diameter frangible bulb. Table A indi- 10 15 20 25 30 35 cated in Table A. cates the bulb liquid color as a function 5° a� I, ■■ p ai :p;.i ! =■■■ of temperature rating. H ...... I II;11I. E l , Recessed versions of the Model A es ■ ■■■ ■■■ ■■ ■ ■■ ; e � PARTIAL CURVE ONLY pp � 3,0 a Sprinkler are obtained by utilizing the The F700 Recessed Escutcheon pro- = I MAX PRESSURE 175 PSI r Model A Pendent S rinkler in combi- vided for use with the Model A Pendent = p 2 4° ■ .......II .I..i..ierini nation with the Model F700 Recessed Sprinkler (Ref. Figure C) has a Closure w l� ( 9 ) 6 : e '_:; rasa rata 2.5 ■ ■ � ■ , Escutcheon. The F700 Escutcheons and Mounting Plate fabricated from D 35 1 i.. ■� I ' i ' X0 cc are available with a chrome plated fin- low carbon steel. The Mounting y ■ p ■ ■■ Plate k i ■ MO m ish or a coated finish in any color. prongs, which are compressed back W 30 �.I�I • ■ ■■' ' a m .al °' • • C•OO 2 0 _ I ■ Ip A- fi .aal r w into the Mountin Closure N UM I T. .. • -t 9 P P g Plate as the g 25 'B �I II'!EI ! . P ' 4 - - :1 66!1 :: H cc n The nominal dischar a curve lotted in is ushed over it, maintain a ti ht fric o r w Figure B represents the flow "Q" in tion fit between the two pieces. The 2 20 .I 1 I I.■..:.4 i_ 1,5 cc GPM (LPM) as determined by the fol- Mounting Plate and Closure can also W e � li- r .__ MID I lowing formula: swivel relative to each other and com t; ,5 . . ■• 1,0 pensate for minor non perpendicular H IIII II.�:1 - - - - - �0�� a • Q= K- cg. ity between the Model A Sprinkler and 10 I�III ■ PARTIAL CURVE ONLY the ceiling. '.p of 1 " MAX. PRESSURE 12,1 BAR 0,5 where the nominal discharge coeffi- 5 .LINIIIIlIILIIIIIIIII!!!! cient "K" equals 5.6 (80,7): s A5 1L0 PER 10 `I ( ) : and "p _ DISCHARGE IN LITRES PER MINUTTE equals the residual flowing pressure in , psi (bar). Listing standards permit the INSTALLATION FIGURE B actual value of "K" to vary from 5.3 to NOMINAL DISCHARGE CURVE 5.8 (76,4 to 83,6); however, for hydrau- NOTES lic calculations, a K- factor of 5.6 (80,7) Do not install any bulb type sprinkler is to be applied. if the bulb is cracked or there is a loss of liquid from the bulb. With the bly void the sprinkler's Approvals The Frame of the Model A Sprinkler sprinkler held horizontal, a small air and for Listings. (Ref. Figure A),.is bronze per ASTM bubble should be present. The diame- E3176 (C87800) or, a proprietary alloy ter of the air bubble is approximately The Model A Sprinklers must be in- designated as QM. The Button (bulb 1116 inch (1,6mm) for the stalled in accordance with the follow - retainer) is phospher bronze per 1357157 °C to 3/32 inch (2,4mm) for ing instructions. ASTM 8103 (C51000 or C52100). The the 36071182°C rating. (At higher Gasketed Spring Plate consists of a ambient 'temperatures, the bubble 1. Prior to installing pendent sprinklers Berylium Nickel (NO3360) disc spring may be barely perceptable for the and if applicable, verify that the face that is sealed on both its inside and lower temperature ratings.) of the sprinkler fitting is within the __ outside faces with a Teflont gasket. proper range of distance which can The Compression Screw is bronze per Installation of Model A Pendent be accommodated by the type of ASTM B140 (C31400) and the Deflec- Sprinklers in recessed escutcheons escutcheon being used. tor is brass per ASTM B152 (C11000). other than the F700 will void all The Model A Sprinklers utilize a 5mm sprinkler warranties, as well as possi- When installing a Model A Pendent t DuPont Registered Trademark i • / FULLY RECESSED DIMENSIONSf c - •N ) Up to 1/2 inch adjustment from 2 7�8" DIA P. minimum 1/4 inch to maximum (73,0mm) • 3/4 inch recessed position. S \ 7 Dim. Inches MM FACE -NI 2-1/4" DIA. ow OF (57,2mm) A - 5/8 ±1 /8tt 15,9 ±3,2 FITTING B -Min. 3/4 19,1 MOUNTING B -Nom. 1 25,4 i SURFACE B -Max. 11/4 31,8 -' C Min. 1/4 6,4 , — ;I I _ li /.//2 C -Max. 3/4 19,1 $l / t l -- - i HIGH ADJUSTMENT DIMENSIO i 1 8" — C 2b i (3,7mm) Up to 3/4 Inch adjustment from A 2 a r a the flush ceiling position to 3/4 I inch recessed position. —♦ %r= Dim. Inches MM t For best overall appearance. A - 1 /2±1 /4t1 12,7±6,4 ft Remaining 1/4 inch (6,4mm) of 1- Model A Pendent Sprinkler B -Min. 3/4 19,1 adjustment can be used to compensate 2 - Model F700 Recessed Escutcheon B Nom. 1-1/8 28 6 for variations in sprinkler make -in and a - Mounting Plate B-Max. 1 -1/2 38 1 fitting take -out. b - Closure C -Min. FLUSH — FIGURE C C - Max. 3/4 19,1 MODEL A RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE MODEL F700 RECESSED ESCUTCHEON N i Sprinkler with the F700 Recessed ler joint should be obtained with a combustion, but have not operated, Escutcheon, for best overall appear- torque of 7 to 14 ft.lbs. (9,5 to 19,0 should be replaced if they cannot be ante, use Dimension "A" indicated Nm). A maximum of 21 ft. lbs. completely cleaned by wiping the under the "Fully Recessed Dimen- (28,5 Nm) of torque is to be used to sprinkler with a cloth or by brushing it sions" heading of Figure C. Other- install the sprinklers. Higher lev- with a soft bristle brush. wise, use Dimension "A" under the els of torque may distort the "High Adjustment Dimensions" sprinkler inlet with consequent Care must be exercised to avoid dam- heading. In either case, the remain- leakage or impairment of the age to the sprinklers — both before ing adjustment can be used to com- sprinkler. and after installation. Sprinklers dam- pensate for the possible manufac- aged by dropping, striking, wrench turing variations in take -out of the Do not attempt to make -up for in- twist/slippage, or the like, must be re- fittting, as well as in the make -in of sufficient adjustment in the es- placed. Also, replace any sprinkler that the sprinklers (as permitted by ANSI cutcheon plate by under- or over- has a cracked bulb or that has lost B1.20.1). tightening the sprinkler: Readjust liquid from its bulb (ref. Installation the position of the sprinkler fitting Section Note). 2. After installing the F700 Mounting to suit. Plate (or other escutcheon, as appli- NOTES cable) over the sprinkler threads, 5. In recessed pendent sprinkler instal- Absence of an escutcheon, which is apply pipe thread sealant sparingly lations, after the ceiling has been used to cover a clearance hole, may to the sprinkler threads only. Use of installed or the finish coat has been delay the time to sprinkler operation a Teflont based pipe thread sealant applied, slide on the F700 Closure in a fire situation. is recommended. - over the Model A Sprinkler and push the Closure over the Mounting Plate Before closing a fire protection system 3. Hand tighten the sprinkler into the until its flange comes in contact with control valve for maintenance work on sprinkler fitting. the ceiling. the fire protection system which it con- . trols, permission to shut down the af- 4. Refer to Figure D and select the fected fire protection system must be appropriate Sprinkler Wrench for obtained from the proper authorities tightening the sprinkler into the CARE: AND MAINTENANCE and all personnel who may be affected sprinkler fitting. "' ' by this action must be notified. Automatic sprinklers must never be The F850 Sprinkler Wrench must be shipped or stored where their temper- It is recommended that automatic used for installing polyester coated atures will exceed 100 °F /38 °C and sprinkler systems be inspected guar- ) sprinklers, in order to prevent dam- they must never be painted, plated, terly by a qualified Inspection Service. age to the sprinkler finish. coated or otherwise altered after leav- ing the factory. Modified sprinklers NOTES must be replaced. Sprinklers that have A leak tight 112 inch NPT sprink- been exposed to corrosive products of ! SELECTION: mar . Select the appropriate wrench WARRANTY based on the ful!owing require - ments: _ 1 4v 0 Seller warrants for a period of one year / from the date of shipment (warranty A. Model A Sprinklers with a natu- L. I period) that the products furnished ! ral brass or chrome plated fin- ��� _ hereunder will be free from defects in ish and where the Wrench Flats III III material and workmanship. shown in Figure A are accessi- _._ ble, may be be installed using For further details on Warranty, see an 8 or 10 inc! adjustable Cres- .�- - Price List. cent type wrench or the Model F850 Sprinkler Wrench. ; I . - I B. Model A Sprinklers with a poly I i I i ORDERING PROCEDURE . ester coated finish must only be ` 1 J installed with the Model F850 1 1 A Product Symbol Number (PSN) is Sprinkler Wrench. WRENCH LUGS not specified when ordering polyester coated Model A Sprinklers with other C. Model A Recessed Pendent than a white color; when ordering color Sprinklers which are to be in- Model F850 Nylon Coated coated Model F700 Recessed Es- stalled after completion of a cutcheons with other than a white fixed ceiling Must only be in- S Wrench color; or, when ordering sprinklers with stalled with the Model F850 thread connections per ISO 7/1. It is Sprinkler Wrench. suggested that a color chip be pro- f vided when ordering special color fin - USE: ishes. Otherwise, responsibility for du- When using an 8 or 10 inch adjustable Crescent type wrench, the wrench is to be plication cannot be accepted. applied to the sprinkler wrench flats only (Ref. Figure A). Contact your local distributor for avail- To use the 30 Sprinkler Wrench, slip the Wrench opening over the Model A ability. I- W30 Sprinkler Deflector by passing the Sprinkler Wrench around the side of the Sprinkler Assemblies: Sprinkler as shown in the above illustration. Specify: 1/2" orifice, (specify tempera - A ture Using a 1/2 inch ratchet drive or by applying an 8 or 10 inch adjustable wrench to U right) ), Mon r (specify Pendent or the hex end of the Sprinkler Wrench, tighten the sprinkler into the fitting. The two or p s), PSN (specify from Table B). Sprinkler with (specify type of finish), lugs located on opposite sides of the Wrench indicate the orientation of the sprinkler frame arms. "Special Order" ! Sprinkler Assemblies with ISO 7/1 NOTE Push up on II; Sprinkler Wrench, while it i /inkler rench, wie t s being turned, to ensures that the Thread Connections: p p� g Specify: 1/2" orifice, (specify tempera - Wrench reces. z,tuys fully engaged with the sprinkler wrench flats. ture rating), Model A (specify Pendent or Upright) Sprinkler with (specify type Carefully removr - - the Sprinkler Wrench by disengaging it from the sprinkler wrench of finish) and with thread connection flats, and then 1,,,ssing it sideways over the sprinkler deflector. per ISO 7/1. FIGURE D .:SPRINKLER WRENCH SELECTION AND USE Recessed Escutcheon: Specify: 1/2" (15mm) Model F700 Re- cessed Escutcheon with (specify fin- . ish), PSN (specify). PSN V �/ 1/2" (15mm) F700 I PSN 57 - X X X - X - X X X Chrome Plated PSN 56- 701 -9 -010 1/2" (15mm) F700 I White Color TEMPERATURE Coated PSN 56-701-4-010 RATING Sprinkler Wrench: 135 135'F/57 °C Specify: Model F850 Sprinkler Wrench, PSN 56- 850 -4 -001. 155 155 °F /68'C SPRINKLER . FINISH 175 175 °F /79 °C - TYPE 1 NATURAL BRASS 200 200'F/93'C WEIGHT 571 PENDENT 4 WHITE POLYESTEll 286 286 °F /141'C The nominal weights are as follows. 1/2" Orifice Model A 570 UPRIGHT 9 CHROME PLATED 360 360 °F /182 °C Pendent Sprinkler 2.2ozs. (629) 1/2" Orifice Model A Upright Sprinkler 2.3 ozs. (66 g) TABLE B 1/2" PRODUCT SYMBOL NUMBER SELECTION Recessed Escutcheon 1.2 ozs. (35 g) 1/2 INCH ORIFICE MODEL A PENDENT AND UPRIGHT SPRINKLERS Model F850 WITH 1/2 INCH NPT CONNECTIONS Sprinkler Wrench 15.5 ozs. (440 g) ® Registered trademark of GRINNELL CORPORATION, 3 TYCO PARK, EXETER, NH 03833 NO l J THIS 15 71-1E* HEAD CUR2EN LY • ESE I N G- 0 SED TROD G-H OUT ® SC H OD L -. HORIZONTAL SIDEWALL SPRINKLER MODEL F950/Q -46 SOLDER TYPE, 1/2" ORIFICE GENERAL DESCRIPTION • _ 7/16 "(11 I)MAKE IN ry The 1/2 inch orifice Model F950/0.46 Horizontal Sidewall Sprinkler (Ref. Figure A), is an automatic sprinkler of p °" the fusible solder type. It is designed i -s /e" = a 1— I 11111 for installation along a wall or the side (41 3mm) - -- N w tD II= of a beam and just beneath a smooth g H `r ceiling. Horizontal sidewall sprinklers _ ''�i , t °� are generally used in lieu of pendent or Components: © —J upright sprinklers because of aesthetic, 1 -Frame building construction, or installation 2 -Strut — — — CENTERLINE • 3 -Hook TEMPERATURE OF WATERWAY economy considerations. 4- Deflector RATING APPROVALS AND STANDARDS 5- Collector 4 2 5 7 B • The Model F950/0-46 Horizontal 6 -Key 7- Button • Sidewall Sprinkler is listed by Under- � �-- �%'� ..., �� V 8- Gasket I !. writers Laboratories Inc. and Under- 9- Solder writers' Laboratories of Canada for use 35° � " ..�■ in Ordinary Hazard Occupancies. Fac- s /16' j I. 1 tory Mutual Research Corporation has (7.9mm) DEFLE M approved the F950/Q -46 for use in NOMINAL BOSS • v ' I/2" NPT Light Hazard Occupancies. The Tabora tory listings and approval only apply 3 9 6 I WALL PLATE to the temperature rating, finish and (soemmi • — ' sEAtrc coating combinations stated in Table SURFACE 5/8" _ 2-11/16" �) A, � (15 9mm) ° • (68 3mm) v The 1/2 inch orifice F950/Q -46 is FIGURE A, MODEL F950/Q -46 SPRINKLER ASSEMBLY approved by the New York City Board •■•=•.•' of Standards and Appeals under Calen- HORIZONTAL DISTANCE FROM DEFLECTOR BOSS,FEET dar Number 334- 79 —SA. 0 I 2 3 4 5 6 7 e 9 10 11 12 13 14 15 F 0 1..01 WARNING w e _ =o_.v■ ■■ ■ ■ ■■■■ ■ ■1 ■ ■ ■. -.■ ■.__ ■■ 1111 ■ The F950/Q - Horizontal Sidewall o t. I II111B■ ■ ■I IIiii ■i■■ ■ ■�._0 CCO C■�■C■■■ flied■■■■ Sprinklers described herein must be i .2, 4 : mum C C ■ ■ '■ �� �ei�C 11 installed and maintained in compliance W c t 2 IIIIIIICC� ��C Emig i4 amCa:I. =:i: ■■:CCC:i::r ji•: ■■ ■C•C with this document, as well as with the 2 1 , 2 • '■ ` ■ ■■■ ■'' ■�� ■■ PP IINI � I 9 fi C 1 ■■ a licable standards of the National C OIij i CC�� IIC Fire Protectioft Associatioft, if1 addi N LL 3 � 11 1 11111111111 M 11111111111111111111111111111111 lion to the standards of an y other ° ° mom 1 i, ■ y jurisdiction. Fa u _z 4 i■ ' authorities having _ii IIIIII IIII E� IIII _ ■I=IC■I■■ ,9 11 ure to do so may impair the into - Fir _� E� a : 1 �'� C d. ' �l�� C ii 111 C y of W1 5 €11 1 11111 6 11 11 111111•: :v : :a : : = ■ ■ =e111Cm -• •' : rit o this device. F The owner is responsible for maintain- 6 ing his fire protection system and (a.) RESIDUAL PRESSURE - 7.5 PSI (0.52 BARS) devices in proper operating condition. (b) RESIDUAL PRESSURE - 15 PSI (1.03 BARS) The installing contractor or manfljaC (c) RESIDUAL PRESSURE - 30 PSI (2 07 BARS) AND GREATER turer should be contacted relative to FIGURE B, UPPER LIMIT OF WATER SPRAY FOR THE F950/0 -46* any questions. `SEE TECHNICAL DATA AND WARRANTY SECTIONS TECHNICAL DATA The F950/Q -46 is available with natur- at brass or chrome plated finishes in CORROPROOF T EMPERATURE FRAME NATURAL CHROME COLO LEAD CORROPROOF WAX _ wax the 165F, 212F, 286F and 350F R SS PLATED c• - '0 0.4 temperature ratings. It is also available 1 165F / 74C PLAIN 1,2 i with Corroproof wax, lead, or Corro- • WHIT aialm�- — proof wax over lead coatings in the 286F/141C UE 1, 2 1.2 * * * 165F and 212F temperature ratings. 350F/ 177C RED I 1 * * * The F950/0 -46 is rated for use at a NOTES: maximum service pressure of 175 psi. I LISTED BY UNDERWRITERS LABORATORIES INC and UNDERWRITERS' LABORATORIES of CANADA Material specifications are the same as 2 APPROVED BY FACTORY MUTUAL RESEARCH CORP for the F950 upright and pendent *NOT AVAILABLE sprinklers described on TD517. TABLE A, LABORATORY LISTINGS AND APPROVAL Printed in U.S.A. 9 -87 TD536 , \ //. /\.).' \ 8 . HORIZONTAL SIDEWALL SPRINKLER, MODEL F950/Q -46, 1/2" ORIFICE The F950/Q-46 must be installed Soffits used for the installation of NOTE with a deflector to ceiling distance of Model F950/Q -46 Sprinklers are to be Before closing a fire protection me ance between 4 and 6 inches. To meet this a maximum of 6 inches wide (dis- main control valve for tance from wall). work on the fire protection system requirement, the centerline of the NOTE which it controls, pennission to shut sprinkler waterway (Ref. Figure A), Soffits wider than 6 inches are per- down the affected fire rotection sys- must be between 4 -5/16 and 6 - 5/16 mitred if additional sprinkler protec- tem must be obtained from the proper inches below the ceiling. Figure B illus- tion is provided for the area below authorities and all personnel who may trates the upper limit of the water the soffit. be affected by this action must be spray, as a function of residual pres- notified. sure. The sprinkler must be spaced The maximum left or right distance away from beams and other ceiling between the centerline of the F950/ It is recommended that automatic obstructions such that they will not Q -46 and an adjacent wall must be no - 'sprinkler systems be inspected quarter - interfere with the proper distribution more than one half the maximum mul- ly by a qualified Inspection Service. `tiple sprinkler spacing permitted for of water by the sprinkler. the particular occupancy classification WARRANTY NOTE and type of ceiling construction. The data provided in Figure B is not Ceiling obstructions must be spaced intended for use as a minimum water above the "Upper Limit of Water The nominal discharge curve plotted spray profile specification. Spray" which is associated with the in Figure C represents the flow "Q" in U.S. gallons per minute (GPM) as Seller warrants for a period of one maximum res pressure for single determined by the formula: Q =K 1rp; year from the date of shipment (war - • sprinkler operation. where the nominal sprinkler discharge ranty period) that the products fur- . . - . coefficient "K" = 5.55 and "p " = Wished hereunder will be free from DISCHARGE IN U.S. GALLONS PER MINUTE (CPU) ressure in n pounds per squ are Inch WO 15 .0 x5 30 J5 p si Listing standards permit the defects in material and workmanship. .... :...:.. .. • - -- (psi). ■ C.■ ■.. ■■ :• I el•�8 - - - .. of "K" t �■ .. .. ..� • ..0.. I actual value oo vary from 5.3 y , s •• ART L C •• mm m , For further details on Warranty, see - PAPL CURVE ONLY C • • Price List. d.0 to 5 - MAX % PRESSURE 175 PSI i 0 40 as = =L � '' - -•• ••iliblirwrim• '0 4 w ORDERING PROCEDURE • D :. • ■u. ■■ " A ti - INSTALLATION ■ T 0 ...0 =....1�•n•• •. ", "■ ■■ � ■ ■ e m The Model F950/Q-46 Sprinklers must Sprinkler Assemblies: i ao ■••• iii s be installed with the centerline of the Specify: 1/2" orifice, (specify tem- ..3..QO.......�=P' ■� ■ ■�C�■ ■■ � w waterway horizontal and perpendicu perature rating), Model F950/Q 46 ■■ a • • ' xs o � ■ ■ w lar to the back wall surface. The word , 5 Horizontal Sidewall Sprinkler with •o o ii■ ■■ e d TOP" on the deflector must face up (specify type of finish or coating), __ zD '•'• I - = ■_ ■■ e wards toward the ceiling. PSN (specify). ' ., ■ ■ 111•1111.1111 t.G Natural Brass Finish B .• - um. • = It is recommended that a light weight ': - e.10TIAL CURVE ONLY 165F/74C .PSN 50- 939 -1 -165 E tD= MAX PRESSURE 12 06 BARS spirit level (less than 1 pound), be used 165 PSN 50- 939 -1 -212 , • B I�C ■ ■ ■■ ■ ■■■ ■■ • c. to level the sprinkler fitting and the 286F/141C PSN 50- 939 -1 -286 M' I :: UM! !MU ==_= sprinkler Deflector Hat, as shown in 350F/I l7C PSN 50- 939 -1 -350 ' 50 75 100 125 150 Fj ure D. DISCH�tROE IN LITERS PER MINUTE 9 Chrome Plated Finish FIG C N OTE 165F/74C PSN 50- 939 -9 -165 NOMINAL DISCHARGE CURVE The Deflector Hat is angled forward- 212 F/100C PSN 5 0- 939 -9 -282 - _ - - : downward at a nominal angle of 3.5° . . Consequently, the spirit level must be 350F/177C PSN 50- 939 -9 -350 • SPRINKLER •- SPIRIT FITTING f f•, t \ LEVEL carefully positioned left -to -right, when Lead Coating ` - using it to level the Deflector Hat. 165F/74C PSN 50- 939 -7 -165 g r 212F/100C PSN 50- 939 -7 -212 16 ( Only use t Model F799 Offset Corroproof Wax Coating 6 OR LONGER Figure 165F/74C PSN 50- 939 -6 -165 CENTERLINE O F NIPPLE Wrench shown in Fi ure E for instal - ■ WATERWAY afion of natural brass, chrome plated 212F/100C PSN 50- 939 -6 -212 ••••. and lead coated sprinklers. Use an 8 or DEFLECTOR ��- �� 1 0 inch crescent wrench to install wax Corroproof Wax Over Lead Coating HAT S 165F/74C PSN 50- 939 -8 -165 p.,' — ■ and wax over lead coated sprinklers. 212F/t00C PSN 50- 939 -8 -212 � 1 - - — ' 'pie` — F950/0 -46 Separately Ordered Parts: FIGURE D CARE AND MAINTENANCE Specify: Model F799 Offset Sprinkler LEVELING OF Automatic sprinklers must never be Wrench, PSN 56-452-1-001. Offset SPRINKLER FITTING shipped or stored where their temper- atures will exceed 100F/38C and they CONVERSION FACTORS AND DEFLECTOR HAT must never be painted, plated, coated Parenthetical metric conversions cited here- . . or otherwise altered after leaving the in are approximate. f actory. Modified or over - heated 1 inch = 25.400 mm sprinklers must be replaced. 1 foot = 0.3048 m 1 psi 6.895 kPa E .(g9 Care must be exercised to avoid dam - 0.0689 bar* age to the sprinklers — both before = 0.0703 kg /cm and after installation. Sprinklers dam- 1 lb. = 0.4536 kg aged by dropping, striking, wrench 1 U.S.Gallon 3.785 dm FIGURE E twist /slippage, or the like, must be = 3.785litres OFFSET SPRINKLER WRENCH replaced. • Not recognized International System units "–,istered trademark of r- F'•NNELL cnr P'RATION, 3 TYCO PARK, EXETER, NH 03833 i 1 ! :, .• i., ... i SPECIFICATIONS .. .. 1 AND INSTALLATION •INSTRUCTIONS ::: ,,- < :Pr. t ~ .A,, l .,. I r ; e d 4 ( 2 tR a `r . +` R i. i a j Y f ttn.t ! Y t� y s ` � Y '�� � r . J a { e x J� 1 ! tI de 4‘ �f ly ? ' t l -, ' 4 ' • . A 5�i ( I i ', L>' P y ''',,,%. i I rI V , E » .. r � � : k N x ,47. e .a.� ? r , � 4,- , + ; �' :. iaa. ' 1 s . , „x . -1- '' ' ' ' '''.2 ' .� . '. i rrt 3 _ .te .z im .� ..,, r t r'' r _ 7 . 0 ` � 1 '�' '' 4 .. , �� t (,� Ft N�7T �� �`� t i �� c •,x , � �� C . ! ' o , f ' t .k t ! f , 7. 'i,: 4 w - : r. :',1';-': -, } h - - i m s 9 T, ti J k * � ,q - e``, , rdr .;.ir YY' 1 +! 4 a' ' ; S^ ^ 1 t Y ` . i • �� a � �, r i M fr e ra • t �' b ! r �I 4 r4� - : y , R _ .. - e , e 4 .. L{ r F.:x ?? -, , f , � ; , t'"`", ? " t t. e. 1 { , v 4 , t:'S� V c �pMt r ��+ '�� � . �� � � � z f t, y i NifJ LY r mi' ' • � r - r ; I i r i° a r i ,, . s A s, S K. L ,.:7 r, �, L . I s h y, { 1 ; f Ii V 1 y } # t sr+ ' s 7-+r,' , ., ,-,� �` y '' r y 5 f _ V e ' , I s . ., F �' � -. 1 . � C` Ya i y v�. 'I'r �# ?b S r v. ( � 5 , 1 l y 'L ,1 n k `,_/ M1 d d 1 ` T ,',4,:.1'..-'V'':.;:-.':'";:'''c.-,r..(!' d - j , .l.. , "S i J �. 'r }r r p r . `� r-rV Rd `h r R 'r ,+ V, y�Rti Y YTy �t y ; � P � , '1 n J •, .. 1 x. i #� t vy t ,y Y n t 3 ?F. "F5' .� F . 7 S .. - r� o - ' � r d'; T f '- r Y t "rl,,.. T S;. i rti� _d � r , a . C' s �r. a i r Pd f �� L :' ri „ .: r n .:` t �a c s' y 1 , �f F ', ,4.-',. , .� f t�1' t_.�:�T� Y a. ^ J 3 ( +_ ; i' ` � ,4- ':--.-;'.. ---,..., u F rz*: ' - --,1 , H-ID,) A -: : K : '.' -, •$: *E . ..izVI_ .;.- ..,,!,.. :-.--, ,,, ` (2,1z . .;,. 1 ,.. L .' : r ..„' -... , } a T o 4 '' .rr' b - 2 i . �,4 X 11 9 r a ''r r. 1 ` ' t 4a ''. 4 '� 4 aT, c • . • , r i . • p -4 ' 4 ' ';' - -"c,•: 11 :'• - •'•: , b I k i { LY L ' � / 1 � . 1 ] ' FS ,� { all l � I) r cn r b O r E ... < ��aa .. � Y t ' 1 I k' 1 Y �j�y1 I !' 4 r t b , I V:, . �� r � I h. , ... F �-�.:� % r , u p 0 .�A 3 a d MILWAUKEE VALVE COMPANY , INC. 2375 South BI- Irrell Sllcel f \A I.r:',IIIL .:,_:. VV!:,,•;,r�:,,ll ; :i : 'II i ' lt Telephone Area Code 414/744 -5240 • Fax -11.1/7'1-1 -58 Ii! - S::Ili;:, (_11l c o Fa.: '1141/4:1 - 4143 I / 1 SPECIFICATIONS - FOR SLOW CLOSE . SLOW CLOSE BUTTERBALL VALVE MONITOR POSITION SWITCH • VALVE ASSEMBLIES KITS AND BUILT -IN ASSEMBLIES PATENTED PATENTED 1. Provides slow opening and closing properties in 1. Available factory assembled or as a separate kit a quarter -turn valve. The purpose is to eliminate for field assembly. hydraulic shock and water hammer in fire 2. When mounted on the BB -SC100 Slow Close protection and other liquid systems. valves and wired up, the switch signals any 2. Economically replaces cumbersome O.S. & Y. movement of the valve disc from the full open ! gate valves. position. , 3. Compact, lightweight manual operator has 3 Valve position can be monitored at either one or scotch yoke design & visual position indicator. two locations because it houses two prewired Close coupled for positive direct drive. S.P D T micro switches. 4. Available with or without a built -in valve position 4. Switch Rating. monitor switch. 10 Amps /1 15 VAC - 60 H2 • 5. UL/FM rated at 175 psi. Also available at 350 psi 0.5 Arnps /28 VDC with N.Y.C. B.S.A approval. 5. Wire leads are 24' long. Consult factory for • '! special lengths. Factory / / �� 6. See hack page of this spec sheet for installation • e Mu l Approved l L (UM m L Gled instructions. , y el j For use with fire protection sprinkler systems 175 psi i I Approved by the New York City Board of Stcis. & !I Appeals under Calendar No. 996- 81 -SM, for both 1 175 and 350 psi. l 6. For indoor use only. i• C MODEL DESCRIPTION SIZES I BB - SC100 Valve Less Switch UIaFM 175 p si Threaded Ends NYC BSA 1', 1V,", 1V2" BB SCS02 Valve With Switch 2 ", 21' II Approved BBVSC100 Valve Less Switch UIJFM I BBVSCS02 Valve With Switch 175 psi - Grooved Ends NYC BSA 2 ", 21/2" Approved 1 1 BBHSC100 Valve Less Switch NYC BSA 1", 11/4', 11/2" l BBHSCS02 Valve With Switch 350 psi - Threaded Ends Approved 2 ", 2Y2' i BVHSC100 Valve Less Switch NYC BSA BVHSCS02 Valve With Switch 350 psi - Grooved Ends Approved 2 ", 2W 1 BB -SCK02 Valve Position Monitor Switch Fits All Valves MILWAUKEE VALVE COMPANY ! 2375 South Burrell Street Milwaukee, Wisconsin 53207 1 I; Valves built to take it . since 1 901 I 1 i . I • ".t:. 11'7. ,'. ,,:'- 1 I BUTTE.. RFLY VA LV ES . .. . .. _ _.„ .... VALVES LESS POSITION MONITOR SWITCH i 4' :: - 1 ' . , i 1 - di _ _ 0 --/-.-_-_--- ,--c- • ..---;),-- ` ‘,/ .), • E..f.F;_`. ' x' ,/./ Fit , _____ — • 1 •._ . ,. / i . , - , . - 1 1 :- -01,■,-- ! . 1 1 . BB-SC100 (Threaded Ends) BBVSC100 (Grooved Ends) Sizes 1", 1 1 2", 21/2" Sizes 2", 2 VALVES WITH BUILT-IN POSITION MONITOR SWITCH , - —` E ] I • I ® - I I j i \ 9. • f . ! t / ,IIIII ,,,. _,., • ___ 0 _.,,,_ 0, (11 ,_ © I -. - 6_0 ..,. (i) -1- \:,,I ,V! (3) I . 1 ....,____ ..__ I • _ L .__,__, _ 1 _, : _ (ci -__1 __ 1 i (--- 1 i------®--- _._ _-) _ THREADED ENDS GROOVED ENDS BB-SCS02 (2Valve w/Monitor Switch) BBVSCS02 (Valve w/Monitor Switch) DIMENSIONS - INCHES MATERIAL LIST SIZE 1 1 1/4 1 1/2 2 2 1/2 NO. PART MATERIAL SPECIFICATION A 2 1 a , 2 5.8 2 778 3 1/4 4 118 1 Indicator Sintered Iron F0008P B 5 1/18 5 13/32 5 21, 6 1.6 6 3.8 C 1 9/1e 1 15/16 2 :1/16 2 3/4 3 5/16 2 Housing Bronze ASTM 584 D 1 2332 2 1 8 2 as 3 1:16 3 12 3 Body Bronze ASTM 584 E — — — '5/18 15;16 4 I landle Brass F — — — 4 r2 5 Disc Stain. Stl. Type 304 H — — — 2 3/8 2 78 ' I 6 Disc Seal EPDM Elastomer W 13/45 1 1 / 4 1 1,2 1 7/16 2 ,, 4 L.10 2 25' 2 5' 3 25' 4 5 10 0' 7 Swan Housing Die Cast Aluminum i I W . s no wrencn make-up I enctri 1_40 • .s flow resistance expressed ,n egurvaJent lengln .7.f scr 40 poi .......1 MILWAUKEE VALVE COMPANY 2375 South Burrell Street Milwaukee, Wisconsin 53207 Valves built to take it . since 1901 I ‘ 1 , • it j VALVE AND POSITION I�ONI_ SWITCH INSTALLATION • j INSTALLATION -- USA BB-SC WI I Hnl, i A 1)()S11 ION MONITOR SWITCH A The BBSC can be installed in any orientation in a r - Ii piping system using standard National Pipe 1 hieu :I :3 Wrench should be used to hex on the end of valve - - - - j ii ueirlg threaded to pipe Pipe sealants should he li used sparingly I I r :I B The BBSC -SCK02 switch can be easily mounted c,i, ;I the valve in the field. (See special Installation - ;I instruction sheet provided with every switch kit) II 1' C If only one micro switch is required, simply cap 1rie: c .''; ,I '. ., 1. econd 3 wire lead set with wire nuts and tuck into �,i I, i . function box. ✓ I ' • D Make electrical connections in accordance with local I codes • INSTALLATION — (For Underwriters' Laboratories of BB �:CS Wl INtE GIott_ F'= c;:;ll ICaN MONITOR ;V ✓ITCH Canada) - I A Installation must provide upright orientation of valve r 1:c: _ . i' -'ti I I � II i 1 li B. Electrical connections as follows: "Bonding and ) grounding to be in compliance with the requirements I f ; - - -I r of the Canadian Electrical Code Part 1." I C. Conduit' The insertion depth of the threaded conduit I , must not exceed 1/8" into the sv,itch housing, and ..I I� .1 ,i _ I' the threaded conduit must fit tightly onto the switch "• . INSTALLATION FOR NEW YORK CITY VALVES '% � ' ' 1!1I ' C ;It I ;!! l; N Y.0 special valves [lave a large flow indicator whichI points in the direction of the valve disc, indicating ol)en \' _I� _ " "; or closed The valve should be installed in a position where the indicator is readily visible NOTE: DET;A.II_Er) INS I.AI.I F•. f ON INSTRt I;: TIC)N SHEETS • ARE I'FiC " \'I' %F =Ci \'JI!' I l -.kC:i i ygi_yE WIRING DIAGRAM j N.O. r�C.,;;l - riO J — -- Black i r..loNi i Di; 1/2 El ECTRICAL , ;'i Line-In :ii II CONDUIT N.0 Red ) — _ — , i Line -Out ' -, .. 1 1 1 Horn, i I .� I / • Bell, or i .. _ - I I.i.,i ' i. ii White Lem c:, ,i - -- '. - 1 -« 1 Q. - r n --- 1 1 . i - i ' I r r -. i . - :. � ...1 -¢ - li Switch Positic>� With Valve Full Open: � __ -i � . r , i l... ! �" a - •1 To Change 1`.';ririg From Normal Open To I 1 i I ii'‘iiii/ i. Normal Closed, Reverse Red and Black C\ - Switch Rating: 10 AMPS /115 VAC - 60 Hz -- ---1 I ' UI. LISTED ii . ;, .5 AMP /28 VDC c,-, � ',- --- JUNCTION ii BOX NOTE: Valves incorporating position monitoring switches are for iris oor use only is Not intended for connection to an alarm control unit 'l y r I'', 4 f _, /4 pP /d k _.. i r l „�,a I7;iac _ -\ /. n r • }r j 1 5 # y ,� r qa ' $ t tiR Sr`�' r aj �t i y " ' K. y , k . v . I r " ,, ` w �, . _ • n a;,, a t � , ,� a g �, n i n, ih ,�_ .,7„, eaeumr r �s "fi t 7 .a�,... �aafr. .e„a �{ g �,1 t t i c ti x - t " ' z ti CAS �'+ 'l a a at e ` ' �f' ` .,, , 1,-,, ti r . r �+ 4 r . �q, Y� .,, t 1 S y� Tw —y vf h�a + i Vl ,• �r i a; 1 r �s. r i • • A l j1? r . . !. �" 'n ' x ' i r ., '', e, k v'r . i 1 ik ' ': s a ' , : ° ' - r f �_'< � . �� a,, 1) fi y +.ti ��, r s ' a t „[ r n f'��� .' , " .f` � - ' ..! 4 4 l a ;. 4 r '! , r i [ v a, rk ? . ' , .... t. t i r,. <': t 1 r F . k ` y t ,.� $e1L�' ' ,L 5* t 4 i ,4 , v�� t :4 � 4 ri ti ' ° j:. , I l i . ,: e Pr-, q . - : Vi gk ' . , § A r s l. - a -'ii ' r F :, i" J., � Y � ti � r'r � N� ; .;,.3,.�' i� - „1 « ',� p��n a h- + ,� . , .�. .. � � . � F' P . +.. . .F' _. rr r; (s •. Wst� -tai, �'�... ,.�,+..w :� v� �� - y 1 h .•., ,. � a. r!„ . j.,.,. =34 ,.. ' „ �. s., ” „ ,. .., n9..r�,: � + Y�.:'� � - � ,. ,.. -. r.�.. , ... . ��., ,. „� - . it '.• MILWAUKEE VALVE COMPANY, INC. 2,37._, .;( - )lith Bi.irre'l . 1411'... - ,!!.. .... I' •; .'Ii . 'l•:l',;.);i(' ; i_,ii:it: —1 i -I,7. ;.1 .,.. li_i 0 - ,i , i;l. , .i ! I.: / .1 Ao HORIZONTAL SIDEWALL SPRINKLERS EC MODELS F950/Q -48 AND 1F950/Q-48, SOLDER TYPE, 1/2" ORIFICE 10 (USED WITH IF950/Q-46 ONLY) Components: 9 3 8 imi 5 I 1- Frame 2 - Strut 3 - Hook 4 - Heat `� '� 1\������ 4 J O g ,. 5 K ey Collector 1-1/2" I z � h.,- . y . 6-Button (3B.1mm) I r co.. - co '��t r, m 7 - Gasket I v \ �_ 8 - Solder xN O 'MX ` 9 - Deflector "`" 10 -Fin w 4 6 T CENTERLINE OF WATERWAY 7/16 "(I I.Imm)MAKE – IN - _':• - ' -`ter. PREFIX 1 I /2 "NPT ^'�� "� ." -j— A _ _. .._,..,..,,,...., ,, - ;; - *;:s 0 k ' ') r :,, ". DESIGNATES ` �'� "�'� — WITH FIN (10) 50 ' =�" P a l k I II I W OM DEFLECTOR BOSS ` �' 6 (II1mm) TEMPERATURE RATING WALL �•� , PLATE NOMINAL— 2 -1 /B" SEATING •% (54.0mm) SURFACE 9/16 2- 13/16 (14.3mm) (71 4 mm) FIGURE A 1/2 INCH ORIFICE MODEL F950/Q-48 AND 1F950/Q-48 EC HORIZONTAL SIDEWALL SPRINKLERS GENERAL DESCRIPTION APPROVALS AND STANDARDS manufacturer should be contacted The 1/2 inch orifice, Model F950/Q -48 The 1/2 inch orifice, Model F950/Q -48 relative to any questions. and 1 F950/Q -48 EC Horizontal and 1 F950/Q -48 EC Horizontal Side - Sidewall Sprinklers (Ref. Figure A) are wall Sprinklers are listed by Under - automatic sprinklers of the fusible writers Laboratories Inc. and Un- TECHNICAL DATA solder type. They are intended to be derwriters' Laboratories of Canada. Sprinkler Assemblies: used in light hazard, extended The listings only apply to the service coverage (EC) automatic sprinkler conditions indicated in the Technical The 1/2 inch orifice, Model F950/Q -48 system applications per NFPA 13. Data and Installation /Usage sections. and 1F950/0-48 Horizontal Sidewall Sprinklers are available in a 165F/74C WARNING temperature rating with either natural They are designed for installation The F950/Q -48 and 1F950/Q -48 EC brass or chrome plated finishes. The along a wall or the side of a beam and Horizontal Sidewall Sprinklers sprinklers are rated for use at a maxi - just beneath a smooth and level ceil- described herein must be installed mum service pressure of 175 psi. ing. Horizontal sidewall sprinklers are and maintained in compliance with generally used in lieu of pendent or this document, as well as with the ap- The nominal discharge curve plotted in upright sprinklers because of aes plicable standards of the National Figure B represents the flow "Q" in thetic, building construction, or instal- Fire Protection Association, in addi- U.S. gallons per minute (GPM) as lation economy considerations. tion to the standards of any other determined by the formula: 0 = K,r1S authorities having jurisdiction. where the nominal sprinkler discharge Failure to do so may impair the in- coefficient "K" = 5.6, and "p" = pres- The Model 1 F950/Q -48 Sprinkler has tegrity of these devices. sure in pounds per square inch (psi). a Fin added to the fusible link, in order Listing standards permit the actual to provide the thermal response The owner is responsible for main- value of "K" to vary from 5.3 to 5.8. characteristic necessary for use with tam ing their fire protection system coverage areas of up to 16 feet wide and devices in proper operating con- The Fin which is utilized with the by 20 feet long. • dition. The installing contractor or 1F950/Q-48 is copper per ASTM B152 Printed in U S A 7 -89 TD546 MIN. MIN. • DISCHARGE IN U S GALLONS PER MINUTE (GPM) W x L TEMP FLOW PRESSURE A B 500 :5 20 25 30 35 ■_ APPLICATION FTxFT 'F GPM PSI INCHES FEET . a PARTIAL CURVE ONLY _ - 3 0 EC 16 x 18 165 29 2(% 8 4 to 12 8 = MAX. PRESSURE 175 PSI i . ■ 11 EC ") 1 6 x 20 165 36 41 3 4 to 12 8 W 40 C■■ _ - t-i.:ii-i- - I EC' ') 18 x 16 165 29 21; is 4 to 12 9 a 35 111110 � � "��- � �> , ■ � _l I_ 2.5 a F„ 11 p■�J li ■ ___ _ ;' _A .^ ■ i m CENTERLINE OF W 00 i ' � - - ■� • � Y.p� w SPRINKLER WATERWAY _` C 20 _ u■ ■ ■ ■■ - - w _ W Z 25 ■ ■■ ■ ■■ O 2 _ _ _ _ - - 1 i■■e ■ ■ 2 1.5 I B I '1 Z 2 0 ■iii ■■u■■■■ �. -- r I I m ■ C ■ ■ ■ � ■ ■. 1 o NO D 17 FEET �— B— -- g C- 14 FEET �6�io8 �, ' • _ • I � - LIMIT MINIMUM MINIMUM ■ �I P ARTIAL CURVE ONLY - --- _L___ ____ _ _____ I a 10 p i MAX, PRESSURE 12 07 BARS - _ - t ■ ■P EWE - _ _ _ - 5 VA! IIIL - U!! :. 50 75 100 125 150 /' - - - DISCHARGE IN LITERS PER MINUTE LIMITS OF SINGLE *DEFLECTOR -TO- FIGURE B SPRINKLER COVERAGE `` CEILING DISTANCE NOMINAL DISCHARGE CURVE NOTES: (C11000). The sprinkler frame is (a) Light Hazard Occupancy automatic sprinkler system applications per NFPA 13. bronze either per ASTM B176 (b) The 1F950/Q-48 must be used for maximum sprinkler coverage lengths of more than 18 (C87800) or ASTM B584 (C83600 or feet The F950/Q -48 may be Used with maximum sprinkler coverage lengths of up to 18 '- C84400). The Strut is silicone bronze feet. per ASTM B97 (C65500), the Deflec- tor is brass per ASTM B36 (C22000), (c) Renllirement is based on minimum flow in GPM from dach sprinkler. The indicated and the Hook is phosphor bronze per rest„ lal pressures are based on the nominal K - factor. ASTM B159 (C51000). The Heat Col- lector and Key are copper per ASTM (d) To meet this requirement, the centerline of the waterway (Ref. Fig. A) must be Installed B152 (C10200), the Button is brass per betwoun 4 -7/16 and 12 -7/16 Inches below the ceiling. ASTM B36 (C23000), and the Gasket is copper per ASTM B152 (C11000). TABLE A INSTALLATION CRITERIA FOR 1/2 INCH ORIFICE Escutcheon Plates: MODEL F950/Q - 48 AND 1F950/0 EC HORIZONTAL SIDEWALL Figure D illustrates a typical installa- SPRINKLERS tion of an F950/Q -48 Sprinkler using a standard one -piece escutcheon plate like that described in Technical Data mum flows required for typical NOTE Sheet TD805. TD805 also describes a coverage areas. Soffits wider than 8 inches are per - flush two -piece escutcheon plate that milted if additional sprinkler protec- may be used with the 1/2 inch orifice NOTE tion is provided for the area below the F950/Q -48 or 1 F950/Q -48. For coverage area dimensions less soffit. than or between those indicated in NOTES Table A, it is necessary to use the min- Only use escutcheon plates that will imum required flow for the next INSTALLATION provide a deflector-to-mounting sur- highest width (W) and length (L) for The 1/2 inch orifice', Mbdei•F950 /Q -48 face distance of 2 to 6 inches (Ref which installation criteria are stated. and 1 F950/Q -48 EC Horizontal Figure D). Sidewall Sprinklers must be installed Ceiling mounted obstructions such as in accordance with the following in- Only use escutcheon plates which con- heating or air conditioning diffusers, structions. sist of metallic materials that will not overhangs, and light fixtures must be deform or dislodge at a temperature of located above an elevation, as shown 1. Prior to installing each sprinkler, less than 1200F/649C and /or which in Figure G, where they will not inter- verify that the outer face of the have been listed by Underwriters fere with the proper distribution of mating fitting is within the proper Laboratories Inc. for fire protection water by the sprinkler. range of distance from the wall service. which can be accomodated by the NOTE particular type of escutcheon plate The F950 / Q-48 and 1F950/Q -48 being used and that the deflector -to- Sprinklers must NOT be used with mounting surface distance will be EC beams, joists, or ducts located within from 2 to 6 inches (Ref. Figure D). INSTALLATION /USAGE CRITERIA the sprinkler coverage area. They may The 1/2 inch orifice Model F950/Q -48 be located along the boundaries 2. The F950/Q -48 and 1 F950/Q -48 and 1 F950/Q -48 Horizontal Sidewall separating adjacent sprinkler must be installed with the centerline Sprinklers must only be installed and coverage areas. utilized in Light Hazard Occupancies of the waterway horizontal and per - under smooth and level ceilings, and Soffits used for the installation of pendicular to the back wall surface. in accordance with the criteria given in F950/Q -48 and 1 F950/O -48 Sprinklers Table A. The nominal wetting patterns are to be a maximum Of 8 inches wide NOTE are illustrated in Figure C for the mini- (distance from wall). It is recommended that a spirit level DEFLECTOR -TO- CEILING: 4 INCHES \�� \ \ \ \\ ` . \\ 0' s BACK WALL FAR WALL 0' • CEILING ,Ilt4 4' DEFLECTOR -TO- $' SIDEWALL $' CEILING DISTANCE. 110 11111111111111111111.- REFER TO TABLE A 2 `11 , 11111 2' ESCUTCHEON 11e ©e®® ee eee PLATE 4' ®1111111 ■ee® me . e 29 GPM FLOW l� eee 1� ' 4' DEFLE CTOR SPRINKLER 11111111111111111.1. . ■■eee111 11 �-1._.�_ - ' 11 M ME N E EM e ®i1i 1 no 11� , �11 ra- - -� 6 11 ®e ® 6 ( \ � CENTERLINE '� ' : : �r �7/l6 �- - OF SPRINKLER WATERWAY r 0' 4' 8' 12' 16' 18' CENTERLINE OF 16' X 18' COVERAGE AREA MOUNTING SURFACE 2 to 6 INCHES DEFLECTOR -TO- CEILING 4 INCHES 0' s 4, BACK WALL FAR WALL 4 ' 0' FIGURE D ( 4141 SIDEWALL , 11111�o11®e - I 2 F950/O -48 AND 1 F950/Q -48 TYPICAL 2 1� _®_ 1 ® 111 ® ® USING 4' SPRINKLEALLATION ®�tei S® ®e® 36 GPM FLOW i mCe ®® ®1111 _�� a 1� 1 4 ' A STANDARD ESCUTCHEON � ®1 111 ® ® = =Ce ® ® ®e ■e ee11 1 6' ��� N11.e®ee®®e®e®e UN eee l U = 1 6' 1 ®e®®®®M ® ®e®®® eeE ih in -7 ., SPRINKLER SPIRIT 0' 4 ' � 8' 12' 16' 20' FIT1IN G %� LEVEL CENTERLINE OF 16' X 20' COVERAGE AREA f , e1 CENTERLINE OF6 OR LONGER NIPPLE WATERWAY .._ DEFLECTOR r=-'/_ � DEFLECTOR -TO- CEILING: 4 INCHES _ � �` ■'t / 0 , BACK WALL FAR WALL 0 r / _j " y - - -- 5' SIDEWALL 5' 9 ' N 9 ' 2' II I t -' -' ' -' - 2' priarn FIGURE E 1 1 11 ee_ ®e e ■ a `1 O hm LEVELING OF ®® 4' e 29 GP FL 1 4' SPRINKLER FITTING ®®1iIIII 1�®-_ _. - AND DEFLECTOR Or111oIeee®® ®e ®e =UUU ee11, 6' /® 1,1e® ® ®® ® ®e®® ee ee � III 6' . 6 poe�vloom! mm ®® ®A®®e® ®e I 1p 0. ' q 0' 4' 6' 12' 16' CENTERLINE OF 18' X 16' COVERAGE AREA F19� ►j NOTES: 1. Patterns shown with no ceiling mounted obstructions. ' 2. See Warranty Section. FIGURE C .NOMINAL WETTING PATTERNS AT MINIMUM REQUIRED FLOWS FIGURE F FOR EC APPLICATIONS OFFSET SPRINKLER WRENCH SIDEWALL • k WARRANTY • The data provided in Figure C is not in- 9' — 20 � ; tended for use as a minimum wetting 8' ' - u I I pa ttern specification. - 0 Seller warrants for a period of one year 6'' I 8 . � ' from the date of shipment (warranty 4. — 8 roducts furnished I I_. - - -. -- '• - - I . period) that the P hereunder will be free from defects in 2 j I I I i --- i i.4 I material and workmanship. +4 : I I i 0, +4 „ j . _. I For further details on Warranty, see 0' . _ 4" 8' , r0' 2' 14' 16' 18' 20' Price List. • SPRINKLER I CENICRLI51 OF COVERAGE AREA PLAN VIEW NOTES: ORDERING PROCEDURE 1. For a given position within the coverage area, ceiling mounted obstructions must not hang below the elevation dimension given in the graph. Sprinkler Assemblies: Specify: 1/2 inch orifice, 165F, Model 2. Elevation dimensions are with respect to the top of the Deflector Hat (ref. Fig. A), where (specify F950/Q -48 or 1F950/0-48) positive ( +) dimensions are above the Deflector Hal and negative ( -) dimensions are EC Horizontal Sidewall Sprinkler with below. (Reference: the Deflector Hat is 7/16 abovr' ti.a sprinkler centerline of waterway.) (specify type of finish), PSN (specify). FIGURE G Model F95010 -a8 ALLOWABLE ELEVATION FOR CEILING MOUNTED OBSTRUCTIONS Natural Brass Finish .. ... PSN 50- 957 -1 -165 SUCH AS HEATING OR AIR CONDITIONING DIFFUSERS, OVERHANGS Chrome Plat. I s Finish .. .... ....PSN 50- 957 -9 -165 AND LIGHT FIXTURES Model 1F950/Q -48 Natural Brass Finish ... ....PSN 50- 959 -1 -165 Chrome Plated • be used to level the sprinkler fitting Do not attempt to make -up for insuf Finish PSN 50-959-9-165 as shown in Figure E and that a ficient adjustment in an escutcheon square be used to clie. - .lr perpen- pl'r /.? by under- or over- tightening Separately Ordered Parts: dicularity of the waterway center- the ;prinklet: Readjust the position Specify: Model F799 Offset Sprinkler line to the mounting surface. of r ?:e sprinkler fitting to suit. Wrench, PSN 56- 452 -1 -001. 3. Use only a non - hardening type of Teflont based pipe joint sealant or PATENTS Teflonttape and apply it sparingly to The following patents are applicable to the male pipe thl :gads only. CARE AND MAINTENANCE the Model F950/Q -48 and 1 F950/Q -48 4. Hand tighten the sprinkler Into the Autonii tic sprinklers must never be EC Horizontal Sidewall Sprinklers: sprinkler fitting. shippe:I or stored where their tempera- CO INTRY PATENT NO. tures will exceed 100F /38C and they U S A . . . . . . . . . . . . . . 4,296,815 5. Use only the Model F799 Offset must never be painted, plated, coated U.S A. ... 4 296,816 y or otherwise altered after leaving the United Kingdom . .... . Sprinkler Wrench shown in Figure F dom .. 2,103,48 P 9 factory. Modified or over - heated !Jolted Kingdom ... ..2,103,481 1 to tighten the sprinkler into the fitting. sprinkler” must be replaced. The word "TOP" on the Deflector must face upwards toward the cell- Care must be exercised to avoid CONVERSION FACTORS ing. damage to the sprinklers - both before Parenthetical metric conversions cited herein are and after instaliatior:. Sprinklers apv.».im.a Ms recommcrtded that a torque Of 7 damaged by dropping, striking, to 14 ft. lbs. be used to obtain a . • wrench twist /slippage, or the like, must 1 inch = 25 400mm be r e laced. 1 foot - 0.3048 m inch NPT sprinkler joint. A radial p 1 psi = 6895kPa force of 10 to 20 lbs. applied to the = 0 0689 bar F799 wrench will exert a torque of 7 NOTE = 0.0703 kg /cm Before closing a fire protection system 1 lb. = 0 4536 kg B l to 14 ft. lbs. 1 U.S. gallon = 3.785 dm main control valve for maintenance 3.785 litres' NOTES work on the fire protection system which it controls, permission to shut 'Not recognized International System units. A maximum of 21 ft. lbs. of torque is down the affected fire protection sys- to be used to install the sprinkler t,:m must be obtained from the proper Higher levels of torque may distort authorities and all personnel who WEIGHT the sprinkler orifice seat with conse- ma be, affected by this action must f.':. 9 The nominal weight of the 1/2 inch quent leakage. ttotfied. orifice, Model F950/Q -48 and It is recommended that automatic 1F950/10 EC Horizontal Sidewall it isrecomr ,; that a spirit level sprinkler systems be inspected Sprtnkler is 0.20 pounds be used to leoel the Deflector Hat, as quarterly by a qualified Inspection Ser- shown in Figure E. The Deflector vice. Hat has a raised portion at the front. Consequently, the spirit level must be carefully positioned on the rear - flat portion of the Deflector Hat. n Registered trademark of GRINNELL CORPORATION, 3 TYCO PARK, EXETER NH 03833 r DuPont Registered Trademark