7341 SW BRIDGEPORT RD .
PROJECT: SINJU SUSHI RESTAURANT 05.25.05
PERMIT #: 05 -3898
ADDRESS: 7341 BRIDGEPORT ROAD
BRIDGEPORT VILLAGE
BLDG. RI
ATTN: CITY OF TUALITIN - PERMIT REVIEW
RE: RESPONSE TO PERMIT REQUIREMENTS (REVISION 1)
Item # Sheet Description
1. A1.0 1. project team updated, added contractor R &H Construction
2. deferred submittal
3. project address is updated
2. A1.1 1. restrooms to remain (2) unisex restrooms. Occupant load re-
calculated to be 149. as per table 2901.1, required fixtures =
1 water closet per 75 male, 1 water closet per 75 female, 1
lavatory per 200 occupants. As per OSSC 2902.1.1 "fixtures
located within unisex toilet bathing rooms complying with chapter
11 are permitted to be included in determining the minimum
required number of fixtures for assembly and mercantile
occupancies.
2. opening force for door 105 to meet min. standards stated in
OSSC 1109.9.9 of 5 pounds- force.
3. note was added giving detailed description of 2 hour rated wall
(OSSC table 720.1)
4. note was added reference OSSC for min. locks and latches
requirement (OSSC 1008.1.8.3)
5. panic hardware (see item 3, number 1 below)
3. A1.2 1. note added to all exterior egress doors stating "lock and latch
to satisfy landlord requirement & OSSC 1008.1.8.3 & fitted with
panic hardware as described in 1008.1.9.
2. existing door on drawings provided by the landlord was marked
by the City of Tualitin to include panic hardware. Door is existing,
panic hardware should be covered under a separate permit. If
not, landlord to provide panic hardware.
3. lavatories removed from restrooms and relocated directly
adjacent to restrooms, thus allowing all maneuverability
requirements required by code.
4. A3.1 1. storefront design manufacturer to meet requirements stated
in OSSC 2404, 1609, ASCE 7 section 9.6.2.10. note added to
sheet. (see revised struct.)
T:503.525.9315 SW Alch:r 5C, Ponuand. Oregon 97205 » www.skylabdesign,;um » r 503.525.93151221
7314 5f--/ 6- gyni;# m DC 3$1
5 A5.5 1. drawings have been updated to show code required dimensions
in accordance with OSSC 1109.2.3.5, 1109.10.5.5, 1109.10.8
6. A5.6, A7.1 1. wood interior finishes to be sealed and finished with clear
intumescent coating as suggested by the manufacturer, note is
added to the finish schedule on sheet A7.1.
7. A5.9 1. dispensers dimensioned per OSSC 1109.10.5.5.
2. handrail included on both sides of stair in accordance with
OSSC 1109.11.
3. handrails to include extensions in accordance with OSSC
109.1 1.5
4. stair treads and risers meet code per the following
information: OSSC 1009.10.2 treads of alternating tread devices
- Exeption: "alternating tread devices used as an element of a
means of egress in buildings from a mezzanine area not more
than 250 square feet in area which serves not more than 5
occupants shall have a minimum projected tread of of 8.5 inches
with a minimum tread depth of 10.5 inches."
This has been noted on the drawings. The mezzanine is shown to
qualify both by size and occupancy in the drawings.
8. A8.6 1. all floor underlayment has been changed to fire retardant.
9. S2.1,S2.2,S2.3 1. see revised structural drawings
10. A1.1, A5.9 1. added fire extinguisher cabinets
11. project man. 1. Energy forms summary has been added to the front of the
drawings in 8 1/2 x 11 format.
12. M2.1 1. approved RTU zone has been show.
T:503.525.9315 SW Airier St., Portland, Oregon 97205 » www.skylabdesign.com » F:503.525.93151221
yy z y •
y': •
4 �' 11 fiYY yi -ir, . 1
Form 5a _ Project Name: SINJU SUSHI RESTRAUNT Page: 1
LIGHTING - GENERAL
1. Interior Exceptions (Section 1313.1)
❑ No Interior Lighting. The building plans and specifications do not call for new or altered interior lighting.
Skip to item 5, Exterior building Lighting - General, below.
Exceptions ❑ Exceptions. 1. The building or part of the building qualifies for an exception from code lighting
Discussion of qualifying requirements. Applicable code exception is number:
exceptions in instructions
section. 2. Lighting equipment that qualifies for an exception - in addition to general lighting and is separately
controlled. Applicable code exception is number:
Areas of the building and equipment that qualify for any exceptions:
Plans/ Specs
Show compliance by including a
drawing sheet, detail number,
and/or specification section and
subparagraph. 2. Local Shut -off controls (Section 1313.3.1.1)
o Complies. At least one local snut -ott lighting control for every 'L,uuu square feet of
lighted floor area and for all spaces enclosed by walls or ceiling height partitions.
This control(s) is detailed in the building plans on drawing number: E2
O Exception. The building or part of the building qualifies for an exception.
Applicable code exception is Section 1313.3.1.1, Exception:
Portions of the building that qualify:
3. Automatic Shutoff Controls (Section 1313.3.1.2)
o Not Applicable. Office floor area is not over 2,000 square feet of contiguous office floor area or
permitted space is not over 5,000 square feet. No offices less than 300 square feet, meeting
or conference rooms, or school classrooms.
❑ Complies. All interior lighting systems are equipped with a separate automatic control to shut off lighting
during unoccupied periods. Offices less than 300 square feet, meeting and conference rooms, and school
classrooms shall be equipped with occupancy sensors that comply with Section 1313.3.1.2.1.
Compliance details in plans /specs:
❑ Exception. I he building or part of the buuoing qualities for an exception. t he
applicable code exception is Section 1313.3.1,2, Exception:
Portions of the building that qualify:
4. Daylighting Controls (1313.3.1.3)
•
o No classrooms or atriums with skylights or window to wall ratio greater than 50 %.
❑ Complies. All classrooms and atriums with window to wall ratio greater than 50% and /or skylights are
equipped with automatic daylight sensing controls, as required by Section 1313.3.1.3.1 and Section
1313.3.1.3.2. The daylight sensors specified comply with Section 1313.3.1.3.3.
Compliance details in plans /specs:
., Exterior Build - ing 5. Exterior Lighting (Section 1313.5)
Lighting ❑ Complies. The plans do not call for use of incandescent or mercury vapor lamps for use on building exterior.
is lighting directed to illuminate o Exception. The building plans indicate luminaires with incandescent or mercury vapor lamps, but are
the exterior of the building and specified for use in or around swimming pools, water features, or other locations subject to requirements
adjacent walkways and loading of Article 680 of the 2002 National Electrical Code.
areas with or without canopies.
Clock Switches
shall be astronomic (seasonal 6. Exterior and Canopy Lighting Controls (Section 1313.3.2)
correcting) type with separate 0 Complies. The building plans and specifications include photoelectric and/or clock switches on all exterior
programs for each day of the lighting systems which are designed and programmed to extinguish lights when daylight is present, as
week and shall store energy to required by Section 1313.3.2.
maintain timekeeping during
power outages.
7. Interior Connected Lighting Power (Section 1313.4)
YES Complies. The interior lighting power does not exceed the interior power allowance established
in either the Tenant Space Method (Form 5b) or the Space -by -Space Method (Form 5c).
+' s i • El Tenant Space Method (Form 5b) ❑Space-by-Space Method (Form 5c)
r4
5-1
Paf It. 0 5 — 3 31 g- 3A-ig 91- 19 b-r.. k-gt '
Compliance with OSSC. effective 01/01/05
,�, . e , -
i
Form 5b Project Name: SINJU SUSHI RESTRAUNT Page:
INTERIOR LIGHTING POWER - Tenant Space Method
Lighting ( (b) (c) (d)
•
Budget
Occupancy/ Tenant or Building Type Floor Area Max Power Lighting Power
Use Types able -13G • (sq ft) Density (Wlft Budget (W)
See instructions for desc a ��. r . � +� ,,
Ewa - t , 3,259 1.3 4,237
notion of occupancy types to . • a ,.- 1 .. F ,
Lighting Power 1. Total interior Lighting Power Budget (Watts) for Building. 4,237
Budget
Track Lighting 2. Total length of track lighting (ft) -
Power
3. Linen multiplied by 37.5 Watts /ft
4. Total amperage of circuit breaker(s) serving track lighting (amps)
5. Voltage of circuit breaker serving track lighting (volts)
6. Maximum wattage of track lighting (multiply line 4 by line 5)
7. Track Lighting Power (lesser value of line 3 or line 6)
8. Track Lighting Power (line 7)
9. Total Interior Lighting Power from Worksheet 5b - 1 (Sum of Column (m)) + 3,588
Building's 10. Total Adjusted Lighting Power (line 8 + line 9) = 3,588
Lighting Power
11. Does design meet budget? Line 10 must be no greater than line 1. YES
t'Z:ik et l3
5
Compliance with OSSC. effective 01/01/05
WorkE Project Name: SINJU SUSHI RESTRAUNT Page 5
LIGHTING SCHEDULE •
( (b) (c) (d) (e) (0
Lum Luminaire Is Luminaire
ID Luminaire Lamp Ballasts Power From -
Type A Description No. Description No. Description (watts) Table 5c
A I Fluorescent T8 - 4 foot 2- F32T8 /30ES -ELECT NO -54W J 2 F32T8 /30ES 1 Electronic Normal Output. IS 54 YES
— 13 - 1 Compact Fluorescent Quad ■ 1- CFQ26W /G24q -3- ELECT -26W 1 CFQ26W /G24q -3 1 Electronic 26 YES
C I User Defined ■ 1 -30W R20 J 1 30W R20 N/A 30 NO
-- User Defined ■ 1 -100W A19 1 100W A19 N/A 100 NO
F 12 Volt Tungsten Halogen Lamps ■ 1 -35 watt lamp - EPS -38W ji 1 35 watt lamp 1 Electronic Power Supply 38 YES
1 12 Volt Tungsten Halogen Lamps - 1 -35 watt lamp- EPS -38W A 1 35 watt lamp 1 Electronic Power Supply 38 _ YES
K 12 Volt Tungsten Halogen Lamps 1 -35 watt lamp- EPS -38W 1 35 watt lamp 1 Electronic Power Supply 38 YES
L 12 Volt Tungsten Halogen Lamps ∎ --.J 1 -50 watt lamp- EPS -54W 1 50 watt lamp 1 Electronic Power Supply 54 YES
N Fluorescent Rapid Start T8 - 2 foot ■ 2 -F17T8 -ELECT NO -33W J 2 F17T8 1 Electronic Normal Output. RS _ 33 YES
p Fluorescent Circline 1- FC12T9 MAG STD -45W 1 FC12T9 1 Magnetic Standard. RS 45 YES
Q Fluorescent T8 - 4 foot ■ 1- F32T8 /30ES -ELECT NO -29W - 1 F32T8/30ES 1 Electronic Normal Output. IS _ 29 YES
R Fluorescent Rapid Start T8 - 2 foot ■ 1 -F17T8 -ELECT NO -22W 1 F17T8 1 Electronic Normal Output. RS 22 YES
s Fluorescent T8 - 4 foot zi 1- F32T8 /30ES -ELECT NO -29W J 1 F32T8 /30ES 1 Electronic Normal Output. IS 29 YES
�
Si Fluorescent Rapid Start T8 - 3 foot - 1- F25T8ES -ELECT NO -27W .�J 1 F25T8ES 1 Electronic Normal Output. RS 27 YES
T 12 Volt Tungsten Halogen Lamps ■ 1 -35 watt lamp- EPS -38W 1 35 watt lamp 1 Electronic Power Supply 38 YES
BB Fluorescent T8 - 4 foot - 1- F32T8 /30ES -ELECT NO -29W J 1 F32T8 /30ES 1 Electronic Normal Output. IS 29 YES
BB1 Fluorescent Rapid Start T8 - 3 foot - J i 1- F25T8ES -ELECT NO -27W �- 1 F25T8ES 1 Electronic Normal Output. RS 27 YES
foot BB2 ( Fluorescent Rapid Start T8 - 2 ■ 1 -F17T8 -ELECT NO -22W :i 1 F17T8 1 Electronic Normal Output. RS 22 YES
FF I Fluorescent T8 - 4 foot 2- F32T8 /30ES -ELECT NO -54W 2 F32T8 /30ES 1 Electronic Normal Output. IS 54 YES
J
■
A
A J
J -I
J -1
J
_ - - -- I - I
LightingForms- V2.3.xls
5 sv+„::t. lc , .r - i n,: «,..+u ;u igjir ....raai3O4m i • f t o r • ?
• I
Worksheet 5b-1 Project Name: SINJU SUSHI RESTRAUNT Page
INTERIOR LIGHTING POWER
Space -by -Space Method Only
Skip to cokem 4 it using the Tenant Space Method ii
(!) 7 3r„ 4 "- -' ..,717 - ,.,, a - � • (d) (e) LLR1 (Q) Q) (t) (.1) (k)
;s� a .y -;y,� n from Ouanttyof
Room ID (do Space Type Space Lighting Power Wtxksttest Luminaires (or Ltsrtikars Lighting Room ,
not leave any Area -,,(Table 13-H) Type Budget 5a Cokam Snare f . for track Power Exempt Power Total Ltg.
blanks) (It) jN1(K1pa type only once per room) LPD (b) x (d) a fig Ing) (Watts) Fixtures (g) x (h) Power
Each room - „ we- 7 54 ❑ 378 -
must be - - ".`. #' 2 26 ❑ 52 -
identified. - -- - • , pg s 3 30 ❑ 00 -
Daseriba . 5 100 ❑ 500 --
luminaires for each
individual room in _ •'0 Fill 4 38 ❑ 152 -
plans.
- - .1 - 3 38 ❑ 114 -
• - ti is 28 38 ❑ 1,064 -
- _ u., ,. 7 54 ❑ 378 -
For track fighting - -- 046 1 33 '❑ 33 -
enter lineal feet in -- - Par 2 45 ❑ 90 --
column column (g) . . '
- - O _ 1 29 ❑ 29 -
- - R ' - +i l 3 22 ❑ 66 --
Column (k), enter
sum of column (j) - -• S -.-'- '.• [ 52 - ❑ - -
for each room only - - St :-:,? 1.1 2 27 ❑ 54 --
once at cast entry
for the room . See 1 - TVA 4 '1 2 38 ❑ 76 -
axamplein - - =ea k• l. 2 29 ❑ Se -
instructiwls.
- - 881 2 27 ❑ 54 -
- - a82,wt 1 22 ❑ 22 --
- - I FF gk I:el 7 54 0 378 -
- '- ...-6,,, - C - --
, _ . - ❑ - --
I _ .. -- ..., - 0 - -
- - -:'• - ❑ - . -
-- - - C - --
- -- . - C - --
-- - . - C --
- ❑ - -
-- . - ❑ --
-- I -- • - C - --
- I -- • - C - --
-- I - • - C - --
- - . C - -
-- - ".. - C - -
- -- .. . - C - --
- . - ❑ --
I - -- - ❑ - -
-- -- - ❑ - --
i - - - ❑ I - -
- -1 - •( - ❑ I -
- Worksheet 55 -1 Total Budget I Wksht 5b -1 Total Lighting Power (excluding exemptttrack fixtures) 3,588 t
Other Pages Total Number of Additional Worksheet 5b l' ii:j. -
List the additional
worksheets nece-
ssary to catalog all
luminaires in (I) (m) (n)
building Lighting Power Budget: Space Proposed Eluding Lighting
by -Space only (Total of Power (Total of column (k), Area Sqft. (not required
Worksheet Number column (e)) excluding exempt/track) for Tenant Method)
5b -1 - 3.588 -
5b -2
5b -3
Sum of additional 5b worksheets
Total Budget (of all worksheets 3,588
Ce..,-
J a
Nat f7
5
Comptonce with OSSC. effective 01,01/05 •
•