Correspondence /® g'
Afi
AleC 9,3 - oo/35
• TUALA TIN VALLEY FIRE & RESCUE
7 20665 S.W. Blanton St. • Aloha, OR 97007 • 503/649 -8577 • FAX 642 -4814
&.RE0
July 9, 1993
Dimensional Fabricators
9538 S.W. Tigard Street
Tigard, Oregon 97223
Re: Clean Room
Dimensional Fabricators
9538 S.W. Tigard Street
6089A- 221 -004
Gentlemen:
This is a Fire and Life Safety Plan Review and is based on
the 1991 editions of the Uniform Fire Code (UFC) and those
sections of the Uniform Building Code (UBC) and Uniform
Mechanical Code (UMC) specifically referencing the fire
department, and other local ordinances and regulations.
Plans are conditionally approved subject to Tigard
Building Department requirements and the following items:
1. The tenant space number must be prominently displayed
on the street front where it is readily visible to
drivers and officers of responding fire apparatus and
other emergency vehicles. UFC Sec. 10.208
2. Not less than one (1) approved fire extinguisher(s)
with a rating of not less than ( *) shall be provided
for each ( * *) square foot of floor area or fraction
thereof. The travel distance to an extinguisher from
any portion of the building, shall not exceed 75
feet. UFC Sec. 10.303
( *) 2A10B:C - Light and Ordinary Hazard
4A10B:C - Extra Hazard
( * *) 3,000 - Light Hazard
1,500 - Ordinary Hazard
1,000 - Extra Hazard
"Working" Smoke Detectors Save Lives
Dimensional Fabricators
July 9, 1993
Page 2
Note: Where flammable or combustible liquids are
used, "B" ratings of extinguishers may need to be
higher and travel distances shorter. See
requirements in National Fire Protection Association
Standard 10 -1.
3. Plans referred to and examined by this office contain
no provisions for the alteration or installation of
automatic sprinkler system. Not less than three sets
of ,plans for the installation shall be submitted to
this office for approval prior to installation. UBC
302 (b)
Approval of submitted plans is not an approval of
omissions or oversights by this office or of non-
compliance with any applicable regulations of local
government.
If I can be of any further assistance to you, please feel
free to contact me at 562 -2469.
Sincerely,
Bradley N. Wanamaker
Deputy Fire Marshal
BNW:kw
cc: Tigard Building Department