July 1, 1991
Pacific Mobile Leasing
P.O. Box 1404
Chehalis, Washington 98532
Re: Portable Classroom
Fowler Junior High
10865 S.W. Walnut
6088B- 016 -000
Gentlemen:
This is a Fire and Life Safety Plan Review and is based on the
1988 editions of the Fire and Life Safety Code (UBC),
Mechanical Fire and Life Safety Code (UMC), Uniform Fire Code
(UFC), and other local ordinances and regulations.
Plans are conditionally approved as submitted subject to the
following items:
1. Fire Extinguisher Requirements: Not less than one (1)
approved fire extinguisher(s) with a rating of not less
than ( *) shall be provided for each ( * *) square feet of
floor area or fraction thereof. The travel distance to
an extinguisher from any of the building shall
not exceed 75 feet. UFC Sec. 10.303
( *) 2A10B:C - Light and Ordinary Hazard
4A10B:C - Extra Hazard
( * *) 3,000 - Light Hazard
1,500 - Ordinary Hazard
1,000 - Extra Hazard
Note: Where flammable or combustible liquids are used,
"B" ratings of extinguishers may need to be higher and
travel distances shorter. See requirements in National
Fire Protection Association Standard 10 -1.
"Working" Smoke Detectors Save Lives
I 1
Pacific Mobile Leasing
July 1, 1991
Page 2
2. Approved Plans on Job Site: One set of approved plans
bearing the stamps of the building department issuing
the construction permit and this office must be
maintained on the project site throughout all phases of
construction and must be made available to building and
fire inspectors for reference during required
construction inspections. UBC Sec. 303
3. Required Occupancy Certificate: Prior to the use and
occupancy of the project (space), a certificate of
occupancy or other written instrument of approval must
be obtained from the building department issuing the
construction permit. UBC Sec. 307
If I can be of any further assistance to you, please feel free
to contact me at 526 -2502.
Sincerely,
---/Z.
Gene Birc ill
Deputy Fire Marshal
GB:kw /
cc: Tigard Building Department ✓