Correspondence 9'3 -- av /3 2. <9.--Or q3
IN)
{ J 11tt1 TUALATIN VALLEY FIRE & RESCUE
AND
`ce` l BEAVERTON FIRE DEPARTMENT
w n(;
'� , J 1, 4755 S.W. Griffith Drive • P.O. Box 4755 • Beaverton, OR 97076 • (503) 526 -2469 • FAX 526 -2538
� RF AR - ES -. /'
August 5, 1993
David Udkow
15425 N. Greenway- Hayden Lp.
Scottsdale, Arizona 85260
Re: Lady Footlocker
Washington Square Mall
9640 S.W. Wash Sq Rd
5889C- 060 -068
Dear Mr. Udkow:
This is a Fire and Life Safety Plan Review and is based
on the 1991 editions of the Uniform Fire Code (UFC) and
those sections of the Uniform Building Code (UBC) and
Uniform Mechanical Code (UMC) specifically referencing
the fire department, and other local ordinances and
regulations.
Plans are conditionally approved subject to Tigard
Building Department requirements and the following
items:
1. The tenant space number must be prominently
displayed on the street front where it is readily
visible to drivers and officers of responding fire
apparatus and other emergency vehicles. UFC Sec.
10.208
2. Not less than one (1) approved fire
extinguisher(s) with a rating of not less than ( *)
shall be provided for each ( * *) square foot of
floor area or fraction thereof. The travel
distance to an extinguisher from any portion of
the building, shall not exceed 75 feet. UFC Sec.
10.505
( *) 2A10B:C - Light and Ordinary Hazard
4A10B:C - Extra Hazard
"Working" Smoke Detectors Save Lives
David Udkow
y August 5, 1993
Page 2
( * *) 3,000 - Light Hazard
1,500 - Ordinary Hazard
1,000 - Extra Hazard
Note: Where flammable or combustible liquids
are used, "B" ratings of extinguishers may
need to be higher and travel distances
shorter. See requirements in National Fire
Protection Association Standard 10 -1.
3. Plans referred to and examined by this office
contain no provisions for the alteration or
installation of automatic sprinkler system. Not
less than three sets of plans for the installation
shall be submitted to this office for approval
prior to installation. UBC 302(b)
Approval of submitted plans is not an approval of
omissions or oversights by this office or of non-
compliance with any applicable regulations of local
government.
If I can be of any further assistance to you, please
feel free to contact me at 562 -2469.
Sincerely,
Bradley N. Wanamaker
Deputy Fire Marshal
BNW:kw /