Permit CITY OF TIGARD BUILDING PERMIT
PERMIT #: BUP2005 -00609
A
DEVELOPMENT SERVICES DATE ISSUED: 12/14/2005
13125 SW Hall Blvd., Tigard, OR 97223 503 - 639 -4171
PARCEL: 1S12600-00300
SITE ADDRESS: 09393 SW WASHINGTON SQUARE RD ZONING: C -G
SUBDIVISION: WASHINGTON SQUARE LOT: JURISDICTION: TIG
Project Description: T.I. (3,200 sq ft area)
REISSUE: FLOOR AREAS EXTERIOR WALL CONSTRUCTION
CLASS OF WORK: ALT FIRST: sf N: S: E: W:
TYPE OF USE: COM SECOND: sf PROJECT OPENINGS?
TYPE OF CONST: 2N : sf N: S: E: W:
OCCUPANCY GRP: M TOTAL AREA: 0 sf ROOF CONST: FIRE RET?
OCCUPANCY LOAD: 107 BASEMENT: sf AREA SEP. RATED:
STOR: 1 HT: ft GARAGE: sf OCCU SEP. RATED:
BSMT ?: MEZZ ?: REQD SETBACKS REQUIRED
FLOOR LOAD: psf LEFT: ft RGHT: ft FIR SPKL: Y SMOK DET:Y
DWELLING UNITS: FRNT: ft REAR: ft FIR ALRM : Y HNDICP ACC:Y
BEDRMS: BATHS: IMP SURFACE: PRO CORR: PARKING:
VALUE: $ 350,000.00
Owner: Contractor:
WASHINGTON SQUARE LLC ROYAL SEAL CONSTRUCTION
BY THE MACERICH COMPANY 124 MCMAKIN RD
9585 SW WASHINGTON SQUARE RD BARTONVILLE, TX 76226
TIGARD, OR 97223
Phone: Contact #: PRI 817 - 491 -6400
FEES Reg #: LIC 78744
Description Date Amount REQUIRED ITEMS AND REPORTS
[BUPPLN] Pln Rv 11/21/200: $1,114.30
[FLS] FLS Pln Rv 11/21/200E $685.72
[BUILD] P jmit Fee 12/14/200: $1,714.30
[TAX] 8% State Surchari 12/14/200E $137.14
Total $3,651.46
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes
and all other applicable law. All work will be done in accordance with approved plans. This permit will expire if work is
not started within 180 days of issuance, or if work is suspended for more than 180 days. ATTENTION: e.regon law
requires you to follow the rules adopted by the Oregon Utility Notification Center. Those rules are set orth in OAR
952 - 001 -0010 through OAR 952 - 001 -0100. You may obtain a copy of these rules or direct questio ;'to OUNC by
calling 503 - 246 -6699 0 1- 800 - 332 -2344.
Issued By: _ -e Permittee Signature:
Call 503 -639 -4175 by 7:00 a.m. for an inspection that business day.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
,t'' Wasit 1 vi s b-
Building Permit Applicati u'' I T1 t a5 ' FOR OFFICE USE ONLY •
City of Tigard � / Da /13 � /� PennitNo13�?25, 6 q
NO V "
13125 SW flail Blvd., Tigard, OR 97223 N1 4 ,,� I . Plan Review
Phone: 503.639.4171 Fat: 503.598.1960 c• �(i Date/By: / ^,J/ � Other Permit:
Inspection Line: 503.639.4175 CITY Date Ready /By! Loris: ) 0 See Attached Checklist for
Internet: www.ci.tigard.nr. OF TI
r 'D Notilied/Method:42 - 5 ay' T! U / Supplemental Information
BUILDING DIVISION L.WI M S� e h e, �,
,.._..,;:.. :., TYPE; OF W'ORK.. ,.,... .
„. r,�,...: � ... ::(: :, ::::;:..�... ........ .. :; ; :- „:, .,D,...... , . R FQUIR :�1
. I)2 F'aM1•IILY ....... ;..�
ED DATA , DWE .
® New construction ❑ Demolition Permit fees* are based on the value of the work performed.
— Indicate the value (rounded to the nearest dollar) of all
❑ Addition /alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
work indicated on this application.
n cac
aPP
:..: : ...::,.: CA'TEGORY OF";CONSTRUCTIOV
El I- and 2- family dwelling Valuation: $
b ®Commercial /industrial
111 Accessory building 111 Multi-family Number of bedrooms:
111 Master builder El Other:
Number of bathrooms:
Total number of floors: .. .39
JOB:SITF. INFORMATION AND LOCATION ':
Job site addressJ9585 Washington Square Rd. New dwelling area: square feet
City /State /ZIP: Tigard, Oregon 97223 Garage /carport area: square feet
Suite/bldg. /apt. no.: S -11 Project name: abercrombie #134 1� Covered porch area: square feet
Cross street/directions to job site: Washington Square Mall Deck area: square feet
Other structure area: square feet
REQUIRED 1DATA : =11SE. CHECKLIST.
Subdivision: t Lot no.: Permit fees* are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
fax map /parcel no.: equipment, materials, labor, overhead, and the profit for the
sDESCRIPTION OF WORK :,;!:=,;:!:::: " :.:.... work indicated on this application.
Tenant Build Out. First and partial second floor. Valuation: $$350,000.00
Existing building area: ' square feet
New building area: �L1;69tr e
soar feet
:1. :PROPER. OW' : /. . ►1 TENANT ,.. Number of stories: 2 3f91.14 _
Name: Abercrombie & Fitch - Store Planning Type of construction: 2B
Address: 6301 Fitch Path Occupancy groups:
City /State /ZIP: New Albany, Ohio 43054 Existing: Merchanlile inl aJ w
Phone: (614)283 -6541 Fax: (614)283 -8541 New: Merchantile
(� �/�•
_ ..... ❑ APPLICANT. : ” ' ®!'CONTACT PERSON: „ : :f
r
Business name: Feinknopf Macioce Schappa Architects Inc. (FMS Architects) All contractors and subcontractors are required to be
Contact name: George Pack — l .,(. S��e h M‘ licensed with the Oregon Construction Contractors Board
under ORS 701 and may be required to be licensed in the
Address: 1020 Dennison Ave Suite 300 1 -0 1 7 e "i Q \ \ (` � ' S jurisdiction in which work is being performed. If the
_ / applicant is exempt from licensing, the following reasons
City /State /ZIP: Columbus, Ohio 43201
11 S/9 l 11 vac) apply:
Phone: (614) 297 -1020 Fax: : (614) 291-1020
E -mail: gpackl(afmsarchitects.com
,... ON "I'R.1CT0
w. A :
Business name: TBI 4 2C Q T ; : .'- .Ji ~
O l Pf\ P t v�.S�YIi.C� 0 vim-/ � BtiILDINGI?ERi1•IIT.�FGES% ;'•;,F
Address: (c�� � ��� ^ 1 ek,. Please refer to fee schedule.
City /State /ZIP: — g c , r N- t,,..� t i, \� � 7x x, . 6
— — Fees due upon application $0.00
Phone: ( 39 — 6 77 i Fax:
y 7 / Y / � Amount received
CCB lie.:
Date received:
Authorized signature: This permit application expires if a permit is not obtained
within 180 days after it has been accepted as complete.
Print name: George Pack Date: 10 -21 -05 * Fee methodology set by Tri- Count Building Industry
Service Board.
i \ Building \Permits\BUP- PennitApp.doe 12/03 440- 4613T(1 t /02 /('OMAVEB)
ott Pavos no 6 09
l,, Form 5a .Project Name: abercrombie #134 Page: 1
LIGHTING - GENERAL
1. Interior Exceptions (Section 1313.1)
❑ No Interior Lighting. The building plans and specifications do not call for new or altered interior lighting.
Skip to item 5, Exterior building Lighting - General, below.
Exceptions ❑ Exceptions. 1. The building or part of the building qualifies for an exception from code lighting
Discussion of qualifying requirements. Applicable code exception is number:
exceptions in instructions
section. 2. Lighting equipment that qualifies for an exception - in addition to general lighting and is separately
controlled. Applicable code exception is number:
Areas of the building and equipment that qualify for any exceptions:
Plans /Specs
Show compliance by including a
drawing sheet, detail number,
and/or specification section and
subparagraph. 2. Local Shut -off controls (Section 1313.3.1.1)
p Complies. At least one local shut -off lighting control for every 2,000 square feet of
lighted floor area and for all spaces enclosed by walls or ceiling height partitions.
D �y (�e a control(s) is detailed in the building plans on drawing number: E2.1 and E2.2
L'ai eption. The building or part of the building qualifies for an exception.
NOV 2005 Applicable code exception is Section 1313.3.1.1, Exception: 4
U
Portions of the building that qualify: Sales Area
CITY OF TIGeoz
BUILDING DWISI
�- A utomatic Shutoff Controls (Section 1313.3.1.2)
❑ Not Applicable. Office floor area is not over 2,000 square feet of contiguous office floor area or
permitted space is not over 5,000 square feet. No offices less than 300 square feet, meeting
or conference rooms, or school classrooms.
O Complies. All interior lighting systems are equipped with a separate automatic control to shut off lighting
during unoccupied periods. Offices less than 300 square feet, meeting and conference rooms, and school
classrooms shall be equipped with occupancy sensors that comply with Section 1313.3.1.2.1.
Compliance details in plans /specs: E2.1 and E2.2
El Exception. The building or part of the building qualities for an exception. The
applicable code exception is Section 1313.3.1,2, Exception: 3 and 7
Portions of the building that qualify: Sales Area and Mechanical /Electrical Rooms
4. Daylighting Controls (1313.3.1.3)
O No classrooms or atriums with skylights or window to wall ratio greater than 50 %.
' �, ❑ Complies. All classrooms and atriums with window to wall ratio greater than 50% and /or skylights are
•
equipped with automatic daylight sensing controls, as required by Section 1313.3.1.3.1 and Section
1313.3.1.3.2. The daylight sensors specified comply with Section 1313.3.1.3.3.
Compliance details in plans /specs:
Exterior Build 5. Exterior Lighting (Section 1313.5)
ing Lighting o Complies. The plans do not call for use of incandescent or mercury vapor lamps for use on building exterior.
is lighting directed to illuminate ❑ Exception. The building plans indicate luminaires with incandescent or mercury vapor lamps, but are
the exterior of the building and specified for use in or around swimming pools, water features, or other locations subject to requirements
adjacent walkways and of Article 680 of the 2002 National Electrical Code.
loading areas with or without
canopies.
Clock Switches 6. Exterior and Canopy Lighting Controls (Section 1313.3.2)
shall be astronomic (seasonal O Complies. The building plans and specifications include photoelectric and /or clock switches on all exterior
correcting) type with separate lighting systems which are designed and programmed to extinguish lights when daylight is present, as
programs for each day of the required by Section 1313.3.2.
week and shall store energy to
maintain timekeeping during
power outages.
7. Interior Connected Lighting Power (Section 1313.4)
(YES(Complies. The interior lighting power does not exceed the interior power allowance established
oar in either the Tenant Space Method (Form 5b) or the Space -by -Space Method (Form 5c).
r Tenant Space Method (Form 5b) IT Space -by -Space Method (Form 5c)
5 -1
Compliance with OSSC, effective 01/01/05
Form 5c Project Name: abercrombie #134 Page: 2
INTERIOR LIGHTING POWER - Space -by -Space Method
Lighting 1. Total Interior Lighting Power Budget from Worksheet 5b -1 (Sum of Column (I)) 6,880
Power Budget
2. Total length of track lighting (ft) - 197
Track Lighting
Power 3. Line 2 multiplied by 37.5 Watts /ft 7,388
4. Total amperage of circuit breaker(s) serving track lighting (amps) 40
5. Voltage of circuit breaker serving track lighting (volts) 120
6. Maximum wattage of track lighting (multiply line 4 by line 5) 4,800
7. Track Lighting Power (lesser value of line 3 or line 6) 4,800
8. Total Interior Lighting Power from Worksheet 5b -1 (Sum of Column (m)) + 2,041
Building's 9. Total Adjusted Lighting Power (line 7 + line 8) = 6,841
Lighting Power
10. Does design meet budget? Line 9 must be no greater than line 1. YES
5-3
Compliance with OSSC, effective 01/01/05
• - -
. •-. .
....:. ‘_. .: ,.
. .
• ,
. Work: :Project Name: abercrombie #134 Page: .3 P
LIGHTINd SCHEDULE •
... .
. .
- :: -, i.'-' - '•.•.; • .'.-.- :- --• :•••:'.-.---': r'''.;• • '':; '•:, : • •:(d) .(9), '::,
• .
., .
ID :: . ..•.::.:.:•....: . : .. : -=. : -..;Luminaiie- ,,:•-•-;.• ' 1. :=„:„ E •:. . Lamp • ' : : . Ballasts?: . " r • • Power.7 From
i• • '. :•::- '''. •• . • : • •.; -• ,..!
Type ..: • ..:: :....--, •:? DescriptiOn : ; :•'Description i 7 , No .-,:- : Description " .! (walls) ', Table 5c ff
H I User Defined - 1-23 watt lamp-Compact Fluorescent 1..: '.:, .,i• 23 Watt?larnp, •:••2 1 ' •• Self Ballasted . '. '. .; : •23:' ' '• •-, .',. ':NO
L I 12 Volt Tungsten Halogen Lamps ..±1 1-3 wattlamp-EPS-38W • ::1 -:. 35'matt!taiiiii:.'.- !: :••1 •:' :- ' .Electronic Power..:SAiPtii.:''' ::.. ".,. 38 ::-.''' ''' : YES -
Ni User Defined .■ 1-30 watt lamp R20 • !:1; ::'::•:, '30 wattllamp - '• 30 • NO
. . ., : .
.... .
U Fluorescent T8 - 4 foot
1-F32T8/30ES-ELECT NO-29W 17 :(1:' ..;..4F02T8/80ES: ., - 1 :: , Electronic Normal 0O113u1: ;!::. :.:29... .. 2 - i - .ritp . r :
,/- .1 TiTaCK Lighting Track Lighting
, . . .
:I 12 Vok Tungsten Halogen Lamps •;i 1-35 watt lamp-EPS-38W 7 f:1;; , ' :• : ":1 •Electronic Power:Supply 38 YES
ii Track Lighting .. Track Lighting ■ ..!;:::: !;' -4,-. . " — , • 37.5 •-: . YES
_________I .. • . • .. - .
—1 - • • .
I • . . . . . .
' • • • .
-- i , ,:::::,:::-,.. ...--• ' :: ' ' . ' '1 ' " : . •
. I ______ j ------------- ., .: ;; • . •-,:' :-.; :, - -.. : . ), .: l_ .
_I ...._„___________A . , ■ , , .._•.. • _ ,• , „ . •
..,:t :_ • . • .
I. . A _ ", :.: • •• . • ..
. .
1 "
-. .
.. ...., -
. . .
r A
-I •.:
-I , . - • .-.... • -..
I ,7
_ . • - - ; - '
w , • .
' ..
. • ■ . , -
I .
. ■ . '
- I . . . . A -•
•
. .
• .
.-. -• -- ..- • -. •
• • . . ..
. . .
. . .L
•
2005-0690_Energy_Oregon-V2.3.xls
. . .
. . '
W PB
Form 2a Project Name: tC 3f cUM tat - K it D$ Page:
SUMMARY
Project 1: Project Name 1V-c f f l E
2. Project Address: /311'JC 1M' 6GtaAe(,1AtL
3: Cityrrown TrC4 Y / t/eC Go4' 5..County .
4. Building, Gross Area (ft2) 6: No of Floors l
7. Construction Site Elevation Above 2,000 ft? ❑ YES ❑ NO
Attached Chapter Type ID Description Attach
Forms and Building Envelope Form 3a Building Envelope - General El
3b Prescriptive Path - All Climate Zones ❑
Worksheets * CodeComp Report for Simplified Trade -off El
* In lieu of 3b * Floppy disc with .occ CodeComp file ❑
Check boxes to Worksheet 3a Wall U- factor U
indicate attached 3b Roof U- factor ❑
forms and 3c Floor U- factor ❑
worksheets 3d Window /Skylight Schedule El
Systems Form 4a Systems - General
4b Complex Systems El
1 p P
f ° ?;l C Worksheet 4a Unitary Air Conditioners - Air Cooled El
4b Unitary Air Cond. - Water & Evap Cooled ❑
NU 1 4 2ta6 4c Unitary Heat Pump - Air Cooled ❑
4d Unitary Heat Pump - Water Cooled El
4e Packaged Terminal KC. - Air Cooled
CITY OF 'WARD ❑
BUILDING D ., ,SpON 4f Packaged Terminal Heat Pump - Air Cooled
4g Water Chilling Pkgs - Water & Air Cooled
4h Heat Rejection Equipment ❑
4i Boiler - Gas -Fired and Oil -Fired ❑
4j Furnace & Unit Heaters - Gas and Oil -Fired El
4k Simultaneous Heating and Cooling ❑
41 Air Transport Energy El
4m Natural Ventilation ❑
Lighting Form 5a Lighting - General ❑
5b Interior Lighting Power - Tenant Method El
5c Int. Ltng. Power - Space -by -Space Method El
Worksheet 5a Lighting Schedule El
5b Interior Lighting Power El
Applicant 7. Name 10.,Telephone
8. Company :. 11. Date
9. 6ignature
Attached No of Pages ; . Description of Documentation ;::
Document- 6 A N U GGC 6 e 5
ation
- i.ompnance witn uoou, errecuve u uu iiuo
Form 4a Project Name: A 85R. G R 'M 13' C Page:
SYSTEMS - GENERAL
Applicability Plans /Specs
Discussion of qualifying Show compliance by including a drawing sheet, detail number,
exceptions on page 4 -25 specification section and subparagraph.
1. Applicablity (Section 1317)
Is this form required?
E l Form Required. Complete form if a new HVAC system is being installed, or components of an
existing HVAC system are being replaced (I.e., equipment, controls, ductwork, and insulation.)
El Exception. The building or part of the building qualifies for an exception from HVAC code
requirements. Applicable code exception is Section 1317.1. Portions of the building that
qualify:
Area: Exception ❑ - ❑ -2 ❑ -3
Area: Exception 1:1 - ❑ -2 ❑ -3
Area: Exception ❑ - El -2 CI -3
❑ Form Not Required. This project does not contain work required to comply with code.
2, Simple or Complex Systems (Section 1317.9 or 1317.10)
lg Simple System. Building contains only Simple HVAC System(s). Complete this form (4a) and
equipment efficiency worksheets as required. Form 4b is not required.
El Complex System. Project includes a Complex System. Complete this form (4a), form 4b and
equipment efficiency worksheets as required.
3. Equipment Performance (Section 1317.5)
❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment,
ombustion heating equipment, or heat - operated cooling equipment.
101Complies. All new HVAC equipment have efficiencies not less than those required by code.
Th following equipment efficient 'worksheets are attached:
-4a ❑ -4b ❑ -4c ❑ -4d ❑ -4e El -4f -4g El -4h ❑ -4i ❑ -4
4. Duct Insulation and Sealing (Sections 1317.7 & 1317.8)
E l No Ducts. The building plans and specifications do not call for new HVAC ducts or plenums.
dComplies. The plans and specifications call for all air - handling ducts and plenums to be
insulated and sealed as reauired by Sections 1317.7 &1317.8.
5. Distribution Transformers (Section 1316.1)
E l No Distribution Transformers. The plans /specs do not call for new distribution transformers.
❑ Complies. All new distribution transformers comply with efficiency, testing, and labeling
requirements of Section 1316.1.1.
El Exception. The project qualifies for an exception per Section 1316.1.1, Exceptiion:
0 -1 0 -2 0 -3 0 -4 0 -5 ❑ -s 0 -7 0 -8 0 -9 CI 0 - 1 CI -12 ❑ -13 El -14
Attach relevant documentation for appropriate exception. The plans /specs show compliance in the
".� following locations:
4 • - April 2005 -
Compliance with OSSC, effective 01/01/05
Form 4a ' Project Name: , A Bet C Rd/M 3r a Page:
SYSTEMS - GENERAL
•
6. HVAC Controls (Section 1317.4)
6.1 System Thermostat /Zone Controls (Section 1317.4.1)
❑ Complies. All new HVAC systems include at least one temperature control device responding to
temperatures within the zones.
❑ Exception. HVAC system qualifies for an exception from zone control requirements.
The applicable code exception is Section 1317.4.2, Exception 0-1 0 -2
Portions of the building that qualify:
The plans /specs show compliance in the following locations:
/ 6.2 Off - hour Controls - Auto Setback or Shutdown (Section 1317.4.3)
® Complies. Systems must have at least one of the following features:
fif Control Setback Complies. Each system is equipped with automatic control capable of reducing
energy through control setback during periods of non -use or alternate use of spaces served.
,energy
Equipment Shutdown Complies. Each system is equipped with controls capable of reducing
energyj.ise through automatic shutdown during periods of non -use or alternate use of spaces.
1 HVAC systems with equipment shutdown are equipped with at least one of the following:
gi Programmable controls (1317.4.3.1 (1))
❑ Occupant sensor (1317.4.3.1 (2))
❑ Interlocked to a security system (1317.4.3.1 (3))
❑ Manually activated timers with 2 -hour operation max (1317.4.3.1 (4))
❑ Exception. The building qualifies for an exception to the requirement for automatic setback or
shutdown controls. The applicable code exception is Section 1317.4.3
Exception 0-1 0
The plans /specs show compliance in the following locations:
6.3 Control Capabilities (Sec. 1317.4.2.1)
❑ Complies. Zone thermostats are capable of being set to the temperatures described in Sec.
• 1317.4.2.1. Where used to control both heating and cooling, zone controls shall be capable of
providing a temperature range or deadband of at least 5 degrees F within which the supply of
heating and cooling energy to the zone is shut off or reduced to a minimum.
❑ Exception. The building qualifies for an exception to the deadband requirements.
The applicable code exception is Section 1317.4.2.1 Exception 0-1 0
Portions of the building that qualify:
The plans /specs show compliance in the following locations:
6.4 Optimum Start Controls (Section 1317.4.3.2)
❑ Complies. Separate HVAC systems have controls capable of varying start-up time of system to
ust meet temperature set point at time of occupancy.
Exception. HVAC systems have a design supply air capacity not exceeding 10,000 cfm.
The plans /specs show compliance in the following locations:
hu -1
/6.5 Heat Pump Controls (Section 1317.4.4) ..
• No Heat Pump. The plans /specs do not call for a new heat pump
❑ Complies. All new heat pumps equipped with supplementary heaters are controlled to minimize
the use of supplemental heat as defined in Section 1317.4.4.
The plans /specs show compliance in the following locations:
4 -2 April 2005
Compliance with OSSC, effective 01/01/05
pp
Form 4a Project Name: if l3Eh ....p.m ex C G
Page:
SYSTEMS - GENERAL
7. Economizer Cooling (Section 1317.3)
❑ No Cooling. The building plans do not call for a new fan system with mechanical cooling.
El Complies. Each new fan system has an air economizer capable of modulating outside -air and
return -air dampers to provide up to 100 percent of the design supply air as outside air.
❑ Exception At least one new fan system qualifies for an exception. The applicable code exception
is Section 1317.3, Exception ❑ - ❑ -2 ❑ -3 ❑ -4 ❑ -5 ❑ -6
If Exception 3 is selected complete the following:
• (a) Total cooling capacity of exempt units (Btu /hr)
(b) Total installed building cooling capacity (Btu /hr)
❑ Complies. Sum of exempt units rated at less than 54,000 Btu /hr is <240,000 Btu /hr or a/b
< 0.10 (10% of total building cooling capacity).
Unit Identifier of exempt units:
The plans /specs show compliance in the following locations:
8. Economizer Pressure Relief & Integration (Section 1317.3.1 and 1317.3.2)
❑ No Economizers Required. Project does not contain a new fan system requiring economizers.
SI Overpressurization Complies. The drawings specifically identify a pressure relief mechanism for
each fan system that will relieve the extra air introduced by the economizer.
• Integration Complies. Economizer is capable of providing partial cooling even when additional
mechanical cooling is required to meet the remainder of the cooling load.
❑ Exception. The applicable exception is Section 1317.3.2, Exception ❑ -1 ❑ -2
The plans /specs show compliance in the following locations:
9 Hot Gas Bypass (Section 1317.5)
NI No Hot Gas Bypass
❑ Complies. See allowable amount of hot gas bypass as a percentage of total cooling capacity in
table below.
Unit ID Rated Cooling Capacity Hot Gas Bypass Capacity
. ::: ' ' :::;.;:: Allowable Hot Gas BYpass : :.:;:: >:::::::::..::.....
i Rated Cooling' Capacity :;.; ::` Max:Hot Gas Bypass ' <240,000 Btu /hr 50%
>240,000 Btu /hr 25%
❑ Exception. Unitary packaged system with cooling capacity no greater than 90,000 Btu /h
4 -3 April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: A fER L ROM 13L E Page:
SYSTEMS - GENERAL
10. Shutoff Dampers (1317.4.3.3)
❑blot Required. Shutoff dampers are not required on this project.
Mr Complies. Each outdoor air supply & exhaust system shall be equipped with motorized dampers.
❑ Exception. The building qualifies for an exception to the motorized damper requirement. The
applicable code exception is Section 1317.4.3.3 Exception ❑ - CI ❑ -3 ❑ - ❑ - ❑ -
The plans /specs show compliance in the following locations:
lh I- 10
/10.1. Shutoff Damper Controls (Section 1317.4.3.3.1)
11 Complies. Outdoor air supply and exhaust systems shall be provided dampers that automatically
shut when systems or spaces served are not in use or during building warm -up, cooldown, or
setback.
❑ Complies. Stair and shaft vents are capable of being automatically closed during normal building
operation and interlocked to open as required by fire and smoke detection systems.
The plans /specs show compliance in the following locations:
11 0.2. Motorized Damper Leakage (1317.4.3.3.2)
C omplies. Motorized outdoor air supply and exhaust air dampers have a maximum leakage rate
of 4 cfm /ft2 at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998.
❑ Exception. Packaged HVAC equipment may have maximum leakage rate of 20 cfm /ft at 1.0 in
w.g. when tested in accordance with AMCA Standard 500 -1998.
The plans /specs show compliance in the following locations:
11. Piping Insulation (Section 1314)
❑ No New Piping. The building plans and specifications do not call for new piping serving a
J heating or cooling system or part of a circulating service water heating system.
85 Complies. All new piping serving a heating or cooling system or part of a circulating service
water heating system complies with the requirements of the Code, Section 1314.1.
❑ Exception. New piping qualifies for exception: Section 1314.1, Exception ❑ - ❑ -2
1?. Occupancy Ventilation
Complies. Mechanical ventilation systems provide the required amount of ventilation is indicated
in plans /specifications as specified in Chapter 4 of the Oregon Mechanical Specialty Code.
❑ Complies. Natural ventilation systems provide required amount of ventilation as certified by a reg-
istered architect or engineer as specified by Section1203.4.1, Exception. Attach worksheet 4m.
The plans /specs show compliance in
the following locations:
The plans /specs show compliance
-a -. on the following pages: _
4 -4 April 2005
Compliance with OSSC, effective 01/01/05
t.
Form 4a Project Name: At R. � R � . O 3 ��
J7 Page:
SYSTEMS - GENERAL
13. High Occupancy Ventilation (Section 1317.2.2)
❑ Complies. HVAC systems with ventilation air capacities of 1,500 CFM or greater that serve areas
having an average occupant load of 20 square feet per person or less from Table 1004.1.2 have a
means to automatically reduce outside air intake.
Identify applicable systems:
Plans /specs indicate where equipment (i.e. carbon dioxide sensor) and sequence is specified:
El Exception. HVAC systems are equipped with an energy recovery device with at least 50%
/ recovery effectiveness.
® No High Occupancy Systems. Project does not contain an HVAC system as described above.
14. Exhaust Air Heat Recovery (Section 1318.3)
d Not Regulated. HVAC system does not have: 1) design supply air cap. of >10,000 cfm, and 2)
min. outside air supply >70 %, and 3) at least 1 exhaust fan rated at 75% of min outside air supply.
❑ Complies. Heat recovery system increases outside air temperature by 20 °F (Climte Zone 1) or
30 °F (Zone 2) and has provision to provide bypass during air economizer mode.
❑ Exception. An HVAC system qualifies for an exception to this requirement. Applicable exception
from Section 1318.3 Exception❑ -1 0-2 0-3 0-4 0-5 0-6 0-7
The plans /specs show compliance in the following
locations:
1 Large Volume Fan Systems (Section 1318.4.2.4)
ril Not Regulated. The building plans or specifications do not call for fan systems over 15,000 CFM
that serve a single zone and function for the purpose of temperature control.
❑ Complies. Fan systems are equipped with variable frequency drive or two speed motor to reduce
airflow as required by Section 1318.4.2.3.
The plans /specs show compliance in the following
locations:
10. Variable Speed Drives (Section 1317.10.3.1)
Not Regulated. The building plans or specifications do not call for fan and pump motors 10
horsepower and greater that serve variable -flow air or liquid systems.
❑ Complies. All fan and pump motors 10 hp and greater which serve variable -flow air or liquid
systems are controlled by a variable -speed drive.
❑ Exception. The building qualifies for an exception to the variable -speed drive requirement.
Portions of the building that qualify:
Applicable code exception is Section 1317.10.3.1, Exception
The plans /specs show compliance in the following
locations:
17. Service Water Heating (Sec. 1315)
❑ No New Water Heating. The building plans and specifications do not call for new water heaters,
p ot water storage tanks or service hot water distribution systems.
C omplies. All new water heaters, hot water storage tanks or service hot water distribution
systems comply with the requirements of the Section 1315.
❑ Exception. The applicable code exception is Section: Exception:
Portions of the building that qualify:
. The plans /specs show compliance in the following locations:
4 -5 April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: A 6 ER C. RGM I = l- Page:
SYSTEMS - GENERAL
1$. Swimming Pools, Spas and Hot Tubs (Section 1315.5)
Ni No New Pools. The building plans and specifications do not call for new, swimming pools, spas
or hot tubs.
❑ On /Off Controls Complies. Spa and hot tub heaters are equipped with a readily accessible
ON /OFF switch as required by Section 1315.5.1.
E l Ventilation Controls Complies. Pool ventilation system is controlled based on humidity.
E l Cover Complies. All heated pools, hot tubs and spas are equipped with a cover.
❑ Heat Recovery Complies. Pools, Spas, and hot tubs, over 200 ft utilize recovered heat as
required by Section 1315.5.3.
El Exception. Heat recovery is not necessary as pool is heated by renewable energy or
waste heat recovery sources capable of providing at least 70 percent of the heating
energy required over an operating season.
1?. Fume Hoods (Section 1317.2.1.)
No Fume Hoods. The building plans do not call for fume hood systems that have a total exhaust
rate greater than 15,000 cfm.
❑ Complies. Fume hood systems have at least one of the following features:
El Variable air volume hood exhaust and room supply systems capable of reducing exhaust
and makeup air volume to 50% or less of design values.
❑ Direct makeup (auxiliary) air supply equal to at least 75% of the exhaust rate, heated no
warmer than 2° F below room set point, cooled no cooler than 3° F above room set point,
no humidification added, and no simultaneous heating and cooling used for
dehumidification control.
❑ Heat recovery systems to precondition makeup air from fume hood exhaust in accordance
with 1318.3 - Exhaust Air Energy Recovery, without using any exception.
The plans /specs show compliance in the following locations:
2p. Parking Garage Ventilation (Section 1317.2.3)
It No Enclosed Garages. The building plans and specifications do not call for enclosed Group S -2
parking garages with a ventilation exhaust rate greater than 30,000 CFM.
El Complies. The plans and specifications call for carbon monoxide sensing devices as required by
Section 1317.2.3.
E l Exception. Open parking garages.
2 Kitchen Hoods (Section 1317.11)
pJ Not Regulated. The plans /specs do not call for any new kitchen hoods with exhaust capacity
greater than 5,000 cfm each.
El Complies. All new kitchen hoods with a total exhaust capacity greater than 5,000 cfm have at
least 50 percent of the required makeup air; (a) unheated or heated to no more than 60 °F; and (b)
uncooled or evaporatively cooled.
The plans /specs show compliance in the following locations:
2?. Outside Heating Systems (Section 1317.12)
No Outside Heating Systems. The plans /specs do not call for new permanently installed heating
systems outside the building.
❑ Complies. All new permanently installed outside heating systems are radiant gas fired systems
controlled by an occupancy sensor or timer switch as required by Section 1317.12.
4 -6 April 2005
Compliance with OSSC, effective 01/01/05
•
• •
__, •
- • .... _
• • Worksheet 4g • project Name: Ag tz:-.014 gir
Page:
WATER CHILLING PKGS. - & AIR COOLED
. .
Equipment _ _ _
:" (b) I: s ( (0): (f)
Proposed :
Discussion of equipment : " : s i Cooling :Steady Proposed Compliance
- -
ratings and equipment CapaCity State - Part Load Schedule
definitions on page 4
Equip. ID Model Designation (Btu/hr) COP IPLV (A- I)
A WU- 1 1=PC 44. lo 1:- 01 L 1 , 2 -2 1.66" c'.
;-,
, Required Indicate source of information
Document- ARI Unitary Directory, Section AC, page:
ation
RI Applied Products directory, Section ULE, Page:
Product data (Attach data furnished by the equipment supplier, I.e., "cut sheets")
Code : Minimum Rating
Compliance Schedule Equipment Type Cooling Capacity (Tons) COP _ IPLV
Required Air Cooled, With Condenser, Electrically
A Capacities Efficiencies Operated All Capac . 2.80 2.80
Air Cooled, Without Condenser,
' 3.10
This schedule of equip- Electrically Operated All Capacities . 3.10
ment efficiencies was
Water Cooled, Electrically Operated,
reformatted from code, C All Capacities 4.20 4.66
Table 13 Positive Displacement (Reciprocating)
Water CoOled, Electrically Operated, < 150 tons 4.45 : 4.50
Positive Displacement (Rotary, Screw and >150, <300 tons 4.90 4.95
Scroll) >300 tons 5.50 5.60
E < tons
Water Cooled, Electrically Operated,
>150 , <300 tons 5.50 _ 5.50
'
Centrifugal "
>300 tons ' 6.10
41.1111:* F : Air Cooled Absorption; Single Effect • All Capacities 0.60 ?.
r 4.1 G Water Cooled Absorption ; Single Effect All Capacities 0.70 : -
Absorption Double Effect. Indirect Fired All Capacities " 1.00 1..05
Absorption Double Effect Direct Fired All Capacities 1.00 1.00
4-17
Compliance with OSSC, effective 01/01/05
CITY. OF TIGARD , -,,.. g•UP
BUILDING DIVISION
A PERMIT #: 2401;110c
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED:
Phone: (503) 639-4171 . 44 :14411 ,
•
Inspection Requests (24 Hrs.): (503) 639-4175 ...„!4- s"!.!..
I
INSPECTION WORKSHEET FOR DATE: .151 it) 1 64 TIME: PAGE:
SITE ADDRESS: eicits oto sisk CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE: . 1
PROJECT NAME:
DESCRIPTION: . 63tieR c k i ms ati r r, t
OWNER: PHONE #:
CONTRACTOR: PHONE #:
Inspection Request Scheduled For: Date: Pour Time:
Code # Inspection Description Confirm # Contact # Message
Corrections/Comments/Instructions:
r ------ ,
-0
C C ,
w IP
I .
T
ASS 0 PARTIAL APPROVAL 111 CANCEL 111 NO ACCESS
E] FAIL IN CA L FOR NSPECTION 0 ADDITIO AL F ES ASSESSED
■ 0/
I V
Inspector: ,i Date: Phone #: (503) 718-
CITY. OF.TIGARD
BUILDING DIVISION • PERMIT #: BUP200 -00609
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12! 42.005
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175 I I..
INSPECTION WORKSHEET FOR DATE: 518 /2006 TIME: 7:07AM PAGE: 139
SITE ADDRESS: 09393 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE KIDS
DESCRIPTION: T.I. (3,200 sq ft area)
OWNER: WASHINGTON SQUARE LL.C, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION. PHONE #: 817 - 491 - 6400
Inspection Request Scheduled For: Date: 502006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
2.99 I'Inal inspection 029421 -01 972 X49.6895 N
Corrections /Comments /Instructions:
� V) S . 1 -012 ejW - 4 ,7 (i
?
•
•
•
[-PAS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
AIL ❑ CALL FOR IN 'ECTION ❑ ADDITI• A EES ASSESSED
Inspector: 41111M_ Date: _I Phone #: (503) 718 - 2A2'..
CITY. OF TIGARD
BUILDING DIVISION PERMIT #: 13UP2005-
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 121142005
Phone: (503) 639 -4171 th
Inspection Requests (24 Hrs.): (503) 639 -4175
INSPECTION WORKSHEET FOR DATE: 5/2/2006 TIME: 7:01AM PAGE: 69
SITE ADDRESS: 09393 SWWASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE KIDS
DESCRIPTION: T.I. (3,200 sq ft area
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: 817 - 491 - 6400
Inspection Request Scheduled For: Date: 5/2J2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
299 Final inspection 029061 -01 972 -249 -6895 Y
Corrections /Comments /Instructions:
cck Lott TUPsc) ay A m /3o�A ✓cs
— ( ov <<. ELK 264 — Ociac
� 00lRZ -CG S
PRawt [ E z c -
❑
PASS. 0 PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
Fq1/_ ❑ CALL FOR INSPECTION ❑ ADDITIO AL FEES ASSESSED
Inspector:/ ft Date: leX Phone #: (503) 718 - Z4cz
CITY. OF.TIGARD , ` ••
BUILDING DIVISION PERMIT #: I3UP2005 -0() )9
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/14/2005
Phone: (503) 639 -4171 i
Inspection Requests (24 Hrs.): (503) 639 -4175 - --
INSPECTION WORKSHEET FOR DATE: 2/21 2006 TIME: 7:07AM PAGE: 76
SITE ADDRESS: (09393 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE KIDS
DESCRIPTION: T .I. (3,200 t -.q ft area)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
' CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: 817. 491-6°400
Inspection Request Scheduled For: Date: 2/21'2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
23/ Suspended ceiling 026123-01 1;03- 519.9132 N •
Corrections /Comments/ Instructions:
i
V7 ( L/ (` r ,!i
•
. PASS ❑ PARTIAL APPROVAL ❑ CANCEL • ❑ NO ACCESS
❑ FAIL • CALL FO" INSPECTION ❑ ADDITI AL FEES ASSESSED
• Inspector: i �I�� Date: _ ®� Phone #: (503) 718 - 7- 4 6—i ---3
IP' ► I
CITY. OF' TIGARD • •
BUILDING DIVISION PERMIT #: I3UP7005.00609
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: (3
Phone: (503) 639 -4171 I�Ih
Inspection Requests (24 Hrs.): (503) 639-4175
INSPECTION WORKSHEET FOR DATE: 1 /20/2006 TIME: 7 :00AM PAGE: 23
SITE ADDRESS: 09383 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE KIDS
DESCRIPTION: T.I. (3,200 sq ft area)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: 817 - 491 - 1400
Inspection Request Scheduled For: Date: 1120/2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
287 Suspended ceiling 026383 -02 503. 518.9132 N
Corrections/Comments/Instructions:
C f l (�C 6 *
❑ PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL - LL FOR I PECTION ❑ ADDITI • NAL FEES ASSESSED
Inspector: r Date: Phone #: (503) 718 -
CITY OF.TIGARD . •
BUILDING DIVISION PERMIT #: F3()P2(()()5.00509
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/14/200
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175 'IL.
INSPECTION WORKSHEET FOR DATE: 1/20/2006 TIME: 7 :00AM PAGE: 24
SITE ADDRESS: 09393 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE KIDS
DESCRIPTION: T.I. (3,200 sq Ft area)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION • PHONE #: 817- 491 -CA00
Inspection Request Scheduled For: Date: 1/2012006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
275 Framing 02536'3.01 503 -519 -9132 N
Corrections /Comments /Instructions:
•
r lr. l
�� �1 . waI
❑ PASS ARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL NI CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED " ZO Inspector: Date: Phone #: (503) 718-
CITY OF.TIGARD
BUILDING DIVISION PERMIT #60drac'8d
13125 SW Hall Blvd., Tigard, OR 97223 D ATE ISSUED:
Phone: (503) 639 -4171 a I nspection Requests (24 Hrs.): (503) 639 -4175 - ..
INSPECTION WORKSHEET FOR DATE: TIME: PAGE:
,t�►% W s4 56
SITE ADDRESS: `;' it CLASS OF WORK:
SUBDIVISION: 013 ) LOT #: TYPE OF USE:
PROJECT NAME:
DESCRIPTION: f r (C ^ ,n J 1
OWNER: PHONE #:
CONTRACTOR: PHONE #:
Inspection Request Scheduled For: Date: Pour Time:
Code # Inspection Description Confirm # Contact # Message
ig 1 ` ovt 3e9-0
Corrections /Com J AI'V)tL
nt s /Instructions:
k2 ,14 f �,�- > --,
„0_,,, , 5- "� i' ;� 1 / �/,re% 4 ai
❑ PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
Inspector: Date:
I V1 /-0 Phone #: (503) 718-
•
CITY • OF.TIGARD
BUILDING DIVISION PERMIT #: BUP2005 -00609
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12114/2005
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639-4175
INSPECTION WORKSHEET FOR DATE: 1212212005 TIME: 7:03AM PAGE: 56
SITE ADDRESS: 09393 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE KIDS
DESCRIPTION: 1.1 (3,200 sq ft area)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: 817-491-6400
Inspection Request Scheduled For: Date: 12/22/2005 Pour Time:
Code # Inspection Description Confirm # Contact # Message
275 Framing 023882 -01 972-249-6895 N
Corrections/Comments/Instructions:
vapsr - • jr- ;v4-'
r
[11 PASS RTIAL APPROVAL CANCEL 111 NO ACCESS
❑ FAIL ❑ CAL FOR INSPECTION El ADDITI NAL EES ASSESSED
i�'
\ Z ( 22 fr Inspector: Date: Phone #: (503) 718-