Correspondence ,A\
r
April 2, 2003 CITY OF TIGARD
Jackie Hancock OREGON
Delta Fire, Inc.
14795 SW 72 Avenue
Portland, OR 97223
RE: STANDPIPE FOR OPEN PARKING GARAGE
Building Permit: BUP2004 -00100 Occupancy Type: S-4
Tenant Name: Washington Square Construction Type: II-FR
Address: 9585 SW Washington Square Road Occupant Load: 976
Area: 194,720 Sq Ft Stories: 4
Standpipe: Class I
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
• Guard post shall be provided to protect the standpipes from vehicle damage. See
construction requirements attached to plans. Section 903.4.3 TVFR99 -01.
• The Class I standpipe system is approved provided it is located as required for Class 2
per footnote 4, Table 1004 -A TVFR99 -01. See plans.
• Clearances shall be provided around all piping extending through walls, floors, and
foundations. Minimum clearance for pipes 4 inches and larger shall be 2 inches.
Standard 9 -1, section 4- 5.4.3.4 Exception, flexible couplings provided within 1 foot
of each side of the floor or wall.
Approved Plans: I set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processi •1 the documents.
Respectfull
rian Bl. ock,
Senior Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772