Correspondence •
January 5, 2005
CITY OF TIGARD
OREGON
Howard S Wright
425 NW 10 Avenue, Suite 700
Portland, OR 97209
RE: SITE WORK FOR MALL EXPANSION
Project Information
Site Permit: SIT2004 -00027 Construction Type: II -B
Tenant Name: Washington Square Occupancy Type: M/S2
Address: 9585 SW Washington Square road Occupant Load: NA
Area: 131,404 Sq Ft Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
EROSION
• Erosion control measures shall be in place prior to excavation or grading.
FIRE
• The private fire service main shall be at least 30 inches below grade.
• The private fire service main shall be flushed thoroughly before connection to the
system riser in order to remove foreign materials that might have entered the main
during the course the installation. The flow rate shall not be less than the water
demand rate of the system.
• All piping shall be inspected prior to backfill.
ACCESSIBILITY
• Accessible walkways and routes shall not exceed a running slope of 1 unit vertical in
20 units horizontal (5% slope). Cross slopes shall not exceed 1 unit vertical in 50
units horizontal (2% slope).
• Accessible parking spaces and access aisles shall be located on a surface with a slope
not to exceed 1 unit vertical in 50 units horizontal in all directions. 1104.4.3 OSSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
' be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
- American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully, t