Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
August 26, 2008
i I
RE: MECHANICAL REFRIGERATION
Project Information --'
Building Permit: MEC2008 -00430 Construction Type: 2 -B
Tenant Name: Winco Occupancy Type: M
Address: 7501 SW Dartmouth St. Occupant Load: NA
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition.
1) Prefabricated refrigeration panels installed in Oregon shall bear one Oregon
insignia of compliance located on the exterior side of the panel located nearest
the door prior to final inspection.
2) Every refrigerant- containing part of every system that is erected on the premises
shall be tested and proved tight after complete installation, and before operation.
Tests shall include both the high and low- pressure sides of each system and
shall not be pressured down until verification of the City of Tigard Building
Inspector.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
0)1/40 '.
Dan Nelson,
Senior Plans Examiner
(503)718 -2436
dann @tigard- or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772