Plans 4.
FPs o ,, to - cr—o 1
q
LI S 3 iN ) c a-- . St . Ro(
tqcci I Fire & Building a
Products
p � , ! i i,
FEB 112010
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 CITY OF TIGABD
BUILDING DIVISION
Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli- -^
Description cable approval agencies, the testing is - - rte
not representative of all possible cor- -- .,
The Series TY -FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it j
8.0 K- factor, Upright and Pendent is recommended that the end user be lit f I ilit Sprinklers described in this data sheet consulted with respect to the suitability I are i
are quick response - standard cover- of these coatings for any given corro-
age, decorative 3 mm glass bulb type sive environment. The effects of ambi-
spray sprinklers designed for use in ent temperature, concentration of -" •
light or ordinary hazard, commercial chemicals, and gas /chemical velocity, _
occupancies such as banks, hotels, should be considered, as a minimum, `" -- - ' '�
shopping malls, etc. along with the corrosive nature of the
The recessed version of the Series chemical to which the sprinklers will be
TY-FRB Pendent Sprinkler, where ap- exposed. �`
plicable, is intended for use in areas An intermediate level versions of the
with a finished ceiling. It uses either a Series TY-FRB Pendent Sprinklers are -.
two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet , 1
Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de-
(' Style with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the WARNINGS /
flush pendent position, or a two -piece The Series TY -FRB Sprinklers de- t.,
Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and `"‹ .
inch NPT) Recessed Escutcheon with maintained in compliance with this - -i.i'
1 /4 inch (6,4 mm) of recessed adjust- document, as well as with the applica-
ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro - TY3231 - Pendent 5.6K
total adjustment from the flush pen- tection Association, in addition to the en ,1/2 "NPT
dent position. The adjustment provided standards of any other authorities hay- TY4131 - Upright 8.0K, 3/4 "NPT
by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may TY4231 - Pendent 8.0K, 3/4 "NPT
the accuracy to which the fixed pipe impair the performance of these de-
drops to the sprinklers must be cut. vices. Technical
Corrosion resistant coatings, where The owner is responsible for maintain- Data
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler Approvals
tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed.
with any questions. FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
IMPORTANT information including corrosion resis-
Always refer to Technical Data tant status.)
Sheet TFP700 for the "INSTALLER Model /Sprinkler Maximum Working Pressure
WARNING" that provides cautions
with respect to handling and instal- Identification 175 psi (12,1 bar)
lation of sprinkler systems and com- Discharge Coefficient
ponents. Improper handling and in- Numbers K = 2.8 GPM /psi (40,3 LPM /bar
stallation can permanently damage K = 4.2 GPM /psili (60,5 LPM /barli
a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2"NPT K = 5.6 GPM /psi (80,6 LPM/barl /
- nents and cause the sprinkler to fail TY1231 - Pendent 2.8K,1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /bar
to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings
it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B
TY3131 - Upright 5.6K, 1/2 "NPT
I Page 1 of 8 JULY, 2004 TFP171
Y
Page 2 of 8 TFP1 71
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
• PLATE SEATING ** NOMINAL RECESSED SSU*
SURFACE
1/2' T MAKE -IN ESCUTCHEON DEFLECTOR •
=� m r �- — -� i n1,� 6
r �
7/16" �m' 5
i� �l
2 -1/4" ,�G � (11,1 mm) I 4
(57,2 mm) f MUM � I NOMINAL I I
t iI I MAKE -IN 2
1 9/16" I (39,7 mm) I (55,6 mm) ,A
i 11
F LATS — �} 1
7
SSP DEFLECTOR * f- 2 -7/8" (73,0 mm) DIA. I 1/2° NPT f
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2° ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
IUJL 7/16° d' 5
2 -3/16°
(11,1 mm
(55,6 mm) tin' � - NOMINAL II 4
MAKE -IN
(38,1 / mm) I �IP WRENCH (#1141 i 2- 3/16° �p o 2
(55 mm) !�
i - -- 1 . - II -- F LATS — I 3
1
SSP DEFLECTOR * -.— 2 -7/8° (73,0 mm) DIA. 1/2° NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
c
Finishes Bulb Glass m
Sprinkler: Refer to Table A and B Compression Screw Bronze Operation
Recessed Escutcheon: White Coated, Deflector .. . . . Copper /Bronze ►-
Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which e
expands when exposed to heat. When m
the rated temperature is reached, the 0)
Physical Characteristics fluid expands sufficiently to shatter the ¢
. Frame Bronze glass Bulb, allowing the sprinkler to E
Button Brass /Copper activate and water to flow. a
Sealing Assembly
rE
Beryllium Nickel w/Teflont
. 4—
TFP171 Page 3 of 8
ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20
• PLATE SEATING 1/2° ,t,, NOMINAL RECESSED SSU*
SURFACE NPT "IN ESCUTCHEON DEFLECTOR
t ,— ___..
Mil , arfilitILIP
2 -3/16" ��f� 7/16" t �� 5
(11,1 mm)
(55,6 mm) I Ill - - NOMINAL i 4
�� ` MAKE -IN
1 1/2° I kit � 2-3/16" r 2
WRENCH
(38,1 mm) 1
, i -,...-J-IL-----. IR FLATS (55,6 mm) ; V
SSP DEFLECTOR * — 2 -7/8° (73,0 mm) DIA. 1/2° NPT t
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb. 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2° (12,7 mm) STYLE 30 or 40
PLATE SEATING 3/4 ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
6
2 -5/16° ,7 2 ° (�' 5
gm=--_-_- -�� (12,7 mm)
(58,7 mm) �= � ��— I NOMINAL I i 4
1 1 � MAKE -IN
1 -9/16° `_� 2-1/4° p 4 - 1 2
(39,7 mm) j ii. WRENCH I (57,2 mm
. FLATS i ) � SSP DFLECTOR * f 2 -7/8° (73,0 mm) DIA. 3/4° NPT ** Ol 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw .* *Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Listing is based on the requirements of
Design NFPA 13, and FM Approval is based Installation
Criteria on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style The Series TY-FRB Sprinklers must be
10, 20, 30, or 40 Recessed Escutch installed in accordance with the follow -
The Series TY Pendent and Up- eon, as applicable, is to be used for ing instructions:
right Sprinklers are intended for fire recessed pendent installations.
protection systems designed in ac- NOTES
cordance with the standard installation Do not install any bulb type sprinkler if
rules recognized by the applicable the bulb is cracked or there is a loss of
Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler
e.
Page 4 of 8 TFP171
' SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob-
K TYPE TEMP. BULB NATURAL CHROME WHITE*** tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
LIQUID BRASS PLATED POLYESTER ft.lbs. (40,7 Nm) of torque is to be used
135 °F /57 °C Orange to install sprinklers with 3/4 NPT con -
PENDENT nections. Higher levels of torque may
(TY1231) 155 °F /68 °C Red distort the sprinkler inlet and cause
and 175 °Fl79 °C Yellow 1, 2, 3, 5 leakage or impairment of the sprinkler.
UPRIGHT Do not attempt to make -up for insuffi-
1131 UPRIGHT 200 °F /93 °C Green cient adjustment in the escutcheon
2.8 ) 286 °F /141 °C Blue plate by under- or over - tightening the
1/2° sprinkler. Readjust the position of the
NPT 135 °F /57 °C Orange sprinkler fitting to suit.
RECESSED 155 °F /68 °C Red
The Series TY - FRB Pendent and Up
PENDENT
(TY1231)• 175 °F /79 °C Yellow right Sprinklers must be installed in
• accordance with the following instruc-
Figure 5 200 °F /93 °C Green 1; 2, 5 tions. g
135 °F /57 °C Orange Step 1. Pendent sprinklers are to be
RECESSED 155 °F /68 °C Red installed in the pendent position, and
PENDENT upright sprinklers are to be installed in
(TY1231)** 175 °F /79 °C Yellow the upright position.
Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap-
135 °F /57 °C Orange plied to the pipe threads, hand tighten
PENDENT the sprinkler into the sprinkler fitting.
(TY2231) 155 °F /68 °C Red
and 175 °F /7s °C Yellow Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W -Type
UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13).
a 2 (TY2131) With reference to Figures 1, 2, 3, and
286 °F /141 °C Blue 4, the W-Type 6 Sprinkler Wrench is to
NPT 135 °F /57 °C Orange 1 2 be applied to the sprinkler wrench
RECESSED flats.
PENDENT 155 F /68 °C Red
(TY2231)• 175 °F /79°C Yellow The Series TY -FRB Recessed Pen -
Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in
accordance with the following instruc-
135°F/57°C Orange tions.
RECESSED 155 °F /68 °C Red Step A. After installing the Style 10.
PENDENT 20, 30, or 40 Mounting Plate, as a li
(TY2231)•• 175 °F /79 °C Yellow cable, over the sprinkler threads and
Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES: kler into the sprinkler fitting.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W
Sprinklers. P 9 9 Y YP
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- 7 Recessed Sprinkler Wrench (Ref.
klers. Figure 14). With reference
W -Type 7 Recessed
5. Approved by the City of New York under MEA 354 -01 -E. 2, and 4, the ssed
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in-
Recessed Escutcheon, as applicable. stalled or the finish coat has b
•• Installed with Style 20 (1/2" NPT) or Style 30 (3/4° NPT) 1/2° Total Adjustment been a p
Recessed Escutcheon, as applicable. plied, slide on the Style 10, 20, 30, or
••" Frame and Deflector only. Listings and approvals apply to color (Special Order). 40 Closure over the Series TY
N /A: Not Available Sprinkler and push the Closure over
the Mounting Plate until its flange
TABLE A comes in contact with the ceiling.
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi -
(1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with
temperature ratings. 1/2 NPT connections. A leak tight 3/4
TFP171 Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
•
PENDENT 155 °F /68 °C Red
(TY3231) 1,2,3,4,5,6,7
and 175 °F /79 °C Yellow 1, 2, 3, 5
UPRIGHT 200 °F /93 °C Green
5.6 (TY3131)
286 °F /141 °C Blue
1/2°
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5
(TY3231)• 175 °F /79 °C Yellow N/A
•
Figure 9 200 °F /93 °C Green
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231) ** 175 °F /79 °C Yellow
Figure 10 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY4231)
and 175 °F /79 °C Yellow 1, 2, 5
1,2,3,4,5,6,7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4" •
NPT 135 °F /57 °C Green
•
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)• 175 °F /79 °C Red
Figure 11 200 °F /93 °C Yellow •
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5
(TY4231)" 175 ° F /79 ° C Yellow N/A
Figure 12 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
• Installed with Style 10 (1/2° NPT) or Style 40 (3/4° NPT) 3/4° Total Adjustment Recessed Escutcheon, as applicable.
• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2° Total Adjustment Recessed Escutcheon, as applicable.
°°' Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
Page 6 of 8 TFP1 71
2 -7/8" DIA. _ 2 -7/8° DIA.
° 5/8 ±1/4' (73,0 mm) 3/4° (19,1 mm) (73,0 mm)
1/2±1/8' 1/2° (12,7 mm)
(15,9±6,4 mm) 2 -1/4" DIA. 1 1/4° (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4° (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
SPRINKLER PLATE SPRINKLER MOUNTING
PLATE
FITTING FITTING
1/8' 1/8°
•T' (3,2 mm) •� 3,2 mm
\ �: SOURFACE V'
MOUNTING
SURFACE ir•`�o
,-9 row.
CLOSURE SERIES 1 -5/16° (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm)
TY -FRB 13/16° (20,6 mm) TY-FRB 1 -1/16' (27,0 mm)
FIGURE 5 FIGURE 6
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8° DIA. 2 -7/8° DIA. _
5/8 ±1/4' (73,0 mm) 3/4' (19,1 mm) 1/2±1/8° (73,0 mm) 1/2' (12,7 mm)
(15,9±6,4 mm) 2 -1/4° DIA. 1/4° (6,4 mm) (12,7±3,2 mm) 2 -114° DIA. 1/4° (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
SPRINKLER PLATE SPRINKLER MOUNTING
FITTING PLATE
FITTING
1/8'
• (3,2 mm) •� (3,2 mm
pi, ill. A lglf . �,�lgll, _ ,� (, I )
MOUNTING VP f
MOUNTING � : f SURFACE
SURFACE ..
CLOSURE SERIES 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm)
TY-FRB 3/4' (19,1 mm) TY -FRB 1° (25,4 mm)
FIGURE 7 FIGURE 8
SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
- WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
. STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may and after installation. Sprinklers dam -
Care and delay the time to sprinkler operation in aged by dropping, striking, wrench
a fire situation. twist/slippage, or the like, must be re-
Maintenance Sprinklers that are found to be leaking has a cracked p bulb or has lost
The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced. Section).
ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec-
painted, plated, coated or otherwise
NOTES altered after leaving the factory. Modi ommended to be initially performed for
Before closinga fire protection system fied sprinklers must be replaced. corrosion resistant coated sprinklers,
main control valve for maintenance Sprinklers that have been exposed to after the installation has been com-
work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor-
it controls, permission to shutdown the have not operated, should be replaced rosion resistant coating. Thereafter,
affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25
obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of in-
and all personnel who may be affected by brushing it with a soft bristle brush. specting from the floor level, a random
by this action must be notified. sampling of close -up visual inspec-
Care must be exercised to avoid dam- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
TFP171 Page 7 of 8
2 -7/8' DIA 2 -7/8' DIA
• 5/8±1/4' (73,0 mm) 3/4' (19,1 mm) (73,0 mm)
(15,9±6,4 mm) 1/4' (6,4 mm) 1/2±1/8' 1/2' (12,7 mm)
2 -1/4' DIA ( ) (12,7x3,2 mm) 2 -1/4' DIA 1/4' (6,4 mm)
FACE OF (57,2 mm) (57,2 mm)
MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER
FITTING PLATE
FITTING
1/8' 1/8'
= AC ( mm) 111 (3,2 mm)
- - .� _J I I f AZIM-
MOUNTING II/
MOUNTING SURFACE
Nil
SURFACE _ _,� _.
CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm)
TY -FRB 3/4' (19,1 mm) TY -FRB 1' (25,4 mm)
FIGURE 9 FIGURE 10
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8' DIA 2 -7/8' DIA
5/8±1/4' (73,0 mm) 3/4' (19,1 mm)
1/2±1/8' (73,0 mm) 1/2' (12,7 mm)
(15,91-6,4 mm) 2 -1/4' DIA 1 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4' DIA 1/4' (6,4 mm)
FACE OF (57,2 mm) MOUNTING (57,2 mm)
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8' 1/8'
(3 2 mm) A 3 + ,2 mm) A
.may _ 1 r } � ' % ■
MOUNTING li =la MOUNTING �I I SURFACE
SURFACE �- i . ,
CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm)
• TY -FRB 13/16' (20,6 mm) TY -FRB 1 -1/16' (27,0 mm)
FIGURE 11 FIGURE 12
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may WRENCH
be affected by the corrosive conditions L ' RECESS
present.
WRENCH RECESS
ll , Th e owner is responsible for the in- (END °A° USED FOR 4 spection, testing, and maintenance of 1/2° NPT MODELS) / .
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable H RECESS
standards of the National Fire Protec- (END WRENCH
USED FOR PUSH WRENCH
tion Association (e.g., NFPA 25), in
3 /4° NPT MODELS) IN TO ENSURE
addition to the standards of any other ENGAGEMENT
authorities having jurisdiction. The in- WITH SPRINKLER
stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA
facturer should be contacted relative to W -TYPE 6 SPRINKLER
any questions. WRENCH
It is recommended that automatic FIGURE 14
sprinkler systems be inspected, local requirements and /or national W-TYPE 7 RECESSED
tested, and maintained by a qualified codes. SPRINKLER WRENCH
Inspection Service in accordance with
Page 8 of 8 TFP171
P/N 57 - XXX - X - XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER -
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4 2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)' 200 200 °F /93 °C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon:
Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es-
DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N
Warranty LIMITED TO LABOR CHARGES, RE (specify).
GARDLESS OF WHETHER TYCO
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2• (15 mm)
Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10
original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated ... P/N56- 701 -9 -010
against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010
manship when paid for and properly ABILITY EXCEED AN AMOUNT White Plated 0' P/N 56- 701 -3 -010
installed and maintained under normal EQUAL TO THE SALES PRICE. B rass Pl P/N 56- 701 -2 -010
use and service. This warranty will ex- 112• (15 mm THE FOREGOING WARRANTY IS 1
pire ten (10) years from date of ship- Style 20 )
' ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND ALL Chrome Plated P/N 56- 705 -9 -010
ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56-705-4-010
components manufactured by compa- INCLUDING WARRANTIES White RAL9010* P/N 56 -705 -3 -010
nies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Brass Plated P/N 56- 705 -2 -010
Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR 3/4• (20 mm)
components which have been subject POSE Style 30
to misuse, improper installation, corro- Chrome Plated P/N 56- 705 -9 -011
sion, or which have not been installed, White Coated P/N 56- 705 -4 -011
maintained, modified or repaired in ac- Ordering White RAL9010' P/N 56 -705 -3 -011
cordance with applicable Standards of ng Brass Plated . ... P/N 56- 705 -2 -011
the National Fire Protection Associa- Procedure 3/4' (20 mm)
tion, and /or the standards of any other Style 40
Authorities Having Jurisdiction. Mate- earfitaistryigun local distributor for avail- Chrome Plated ..... .... P/N 56- 700 -9 -010
rials found by Tyco Fire Products to be abr , indicate the White Coated .... .... P/N 56- 700 -4 -010
defective shall be either repaired or ful product White RAL9010' P/N 56- 700 -3 -010
replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56-700-2-010
option. Tyco Fire Products neither as- the Pnce List for
complete listing ' Eastern Hemisphere sales only
sumes, nor authorizes any person to of Part Numbers.
assume for it, any other obligation in Sprinkler Wrench:
connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench,
parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387.
shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick
system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench,
incomplete information supplied by temperature rating), Series TY-FRB P/N 56-850-4-001.
Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler
IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating),
PRODUCTS BE LIABLE, IN CON P/N (specify from Table C).
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE -
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqcci Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series RFII — 5.6 K- factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
General Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the Aft
Description sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro- _ _ -
_
The Series RFII Quick Response tective Cap can also be used to mark
~
( 3 mm bulb ) & Standard ( 5 the center of the ceiling hole into p Response - -- P onse ��. : - ;;
mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently ) „.7.-. -- �"~:N
I I" Concealed Pendent Sprinklers are pushing the ceiling product against the =� ' °'
decorative sprinklers featuring a flat Protective Cap. When the ceiling in- _�
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed.
lobbies, office buildings, churches,
and restaurants. As an option, the Series RFII Standard � -- -- --
Response (5 mm bulb) "Royal Flush II"
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM.
The separable two -piece design of the intended for sensitive areas where it is
Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical
blies allows installation of the sprin- through the cover plate from the area
klers and pressure testing of the fire above the ceiling.
protection system prior to installation WARNINGS Data
of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII
of the finish coating to a fixed ceiling. PP
They also permit removal of sus Sprinklers described herein must be UL and C -UL Listed. FM Approved.
pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353 -01 -E. LPCB (Ref.
• building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for
having to first shut down the fire pro- with the applicable standards of the TY3531) Approved.
tection system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv-
Also, the separable two piece design in addition to the standards of any ice conditions indicated in the Design
o
f the tee Spr wo -pe for ign other authorities having jurisdiction. Criteria section and maximum pres-
inch a th mm) o o de ju for 1/2 Failure to do so may impair the per- sure ratings indicated in the
formance of these devices. Model/Sprinkler Identification Num-
to reduce the accuracy to which the The owner is responsible for maintain- bers section.
length of fixed pipe drops to the sprin- P
klers must be cut. m g their fire protection system and de- Approvals for Air & Dust Seal
The Series RFII Sprinklers are vices in proper operating condition. (Part #10908100)
shipped with a Disposable Protecare The installing contractor or sprinkler UL and C -UL Listed for use with the
manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate
Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate
WARNING" that provides cautions Identification Discharge Coefficient
with respect to handling and instal- K = 5.6 GPM /ps i 1 ' (80,6 LPM /bar
lation of sprinkler systems and corn- Numbers Adjustment
ponents. Improper handling and in- 1/2 inch (12,7 mm)
stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm F
a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass
nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC.
to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm Plated, or White Painted (Custom paint
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by matches and colors other than white
are available on request.)
Page 1 of 4 JULY, 2004 TFP181
Page 2 of 4 TFP181
Physical Characteristics 1/2• NPT i / SEALING
• Frame Bronze ASSEMBLY
Support Cup . Chrome Plated Steel
Guide Pins Stainless Steel
Deflector Bronze FR AME j� `� �Q
Compression Screw Brass 1'4.--*-- �/ CAP
Bulb Glass i
Cap Bronze or Copper SUPPORT Sealing Assembly CUP WITH BULB
Beryllium Nickel w/Teflon• ROLL FORMED Cover Plate Brass
THREADS - I 1 b Retainer Brass � COMPRESSION
Ejection Spring . . . . Stainless Steel GUIDE 1= 0 x,1111 E SCREW
.% I
Patents PINS (2) �� / =% �j
U.S.A. 4,014,388 I I -
1 _ _ DEFLECTOR
, . , (DROPPED
Operation DEFLECTOR ■ i �i `� POSITION)
G _
When exposed to heat from a fire, the SPRINKLER/SUPPORT CUP
Cover Plate, which is normally sol I ASSEMBLY
dered to the Retainer at three points,
falls away to expose the Sprinkler As THREAD INTO I RETAINER
sembly. At this point the Deflector sup SUPPORT CUP j WITH THREAD
ported by the Guide Pins drops down UNTIL SURFACE I MOUNTING 0 J DIMPLES
P Y P SURFACE IS
to its operational position. FLUSH WITH EJECTION
The glass Bulb contains a fluid that CEILING SPRING
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the �_�- _ MMEMIMME:17
glass Bulb, activating the sprinkler and
allowing water to flow. SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE
Design ASSEMBLY
FIGURE 1
Criteria SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
The RFII (TY3551 & TY3504), 5 mm
• Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be
- klers are UL and C -UL Listed as stand- Installation installed in the pendent position and
and response - standard spray sprin- with the centerline of the sprinkler per-
• klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface.
current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap.
Approved as standard response - tions:
standard spray sprinklers for use in NOTES Step 3. With pipe thread sealant ap-
accordance with the current FM Loss plied to the pipe threads, hand tighten
Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting.
The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler
Th Type, Concealed Pendent Sprin-
mm liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench
klers are UL and C-UL Listed as quick held horizontally, a small air bubble ( Ref. Figure 3). The RFII Sprinkler
response - standard spray sprinklers should be present. The diameter of the W rench i s to be applied to the Spnn-
air bubble is approximately 1/16 inch i
for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 kler as shown n Figure 3.
NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tern- Step 5. Replace the Protective Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards
and spray sprinklers for use in accord- A leak ti ht 1/2 inch NPT s nnkler joint until it bottoms out against the Support
ance with the current FM Loss s hould be obtained with a torque of 7 Cup. The Protective Cap helps prevent
Prevention Data Sheets. q damage to the Deflector and Arms dur-
The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- ing ceiling installation and /or during
Sprinklers are only listed and ap- mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the
proved with the Series RFII Concealed is to be used to install sprinklers. ceiling. It may also be used to locate
Cover Plates having a metallic or white Higher levels of torque may distort the the center of the clearance hole by
painted finish. sprinkler inlet with consequent leak- gently pushing the ceiling material up
age or impairment of the sprinkler. against the center point of the Protec-
The Se RFll where must not b used in Do not attempt to compensate for in- tive Cap. p
sufficient adjustment in the Sprinkler
- above the ceiling is greater than that Assembly by under- or over - tightening NOTE
- below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. A.s long as the Protective Cap remains
port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to
tion in a fire situation. fitting to suit. be "Out of Service ".
Registered Trademark of DuPont
TFP181 Page 3 of 4
FACE OF CLEARANCE HOLE CLEARANCE
•
SPRINKLER L DIAMETER - HOLE
FITTING L DIMENSION C
immora
SPRINKLER I
SUPPORT CUP \ r-- ,
ASSEMBLY I ]
1/2° (12,7 mm) `-� 1
P I ■i
THREADED II_
D ADJUSTMENT
FACE OF CEILING o
RETAINING RING FIGURE 4
MOUNTING
O. DISPOSABLE PROTECTIVE CAP
SURFACE
\ il / I 1 I 1 / Step 6. After the ceiling has been corn-
pleted with the 2-1/2 inch (63,5 mm)
- -- -= -- 11 diameter clearance hole and in p�epa
\
V ration for installing the Cover Plate As
I I sembly, remove and discard the Pro-
T - -` tective Cap, and verify that the
3/16° to 11/16° MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE 3/32° (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE kler assembly. Do not attempt to mod-
- PROFILE DEPTH DIAMETER �- ify or repair a damaged sprinkler.
DIMENSION B DIMENSION A Step 7. When installing an Air and .
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
A: 3 -1/4° (82,6 mm) C: 2 -3/8" to 2 -5/8° (60,3 to 66,7 mm) Dust Seal, verify the angle of the out -
B: 3/16" (4,8 mm) D: 1 -3/4° to 2 -1/4° (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
FIGURE 2 the Retainer in the grooved slot of the
SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around
INSTALLATION DIMENSIONS Dust Seal retainer until the entire Air and
Dust Seal is engaged.
` NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
--- %l =t'- FRAME J► =l , _ _ tainer.
111 ARM i(� I• Step 8. Screw on the Cover Plate /Re-
• I tainer Assembly until the Retainer -
' % j If Figure 2 (or Air and Dust Seal - Figure
SUPPOR i 5) contacts with the ceiling. Do not
I i CUP ; ; continue to screw on the Cover
Plate /Retainer Assembly such that it
W ' �01�11 ' lifts a ceiling panel out of its normal •
� � position. If the Cover Plate /Retainer
I■I � i As sembl c n be engaged w i t h t
7/8' (23 mm) tainer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN dl Care and
J `, ARROWS WITH � � FRAMEARMS OE Maintenance
ACCEPTS -... � � The Series RFII must be maintained
�
0 1/2° SOCKET — and serviced in accordance with the
DRIVE following instructions:
NOTES
FIGURE 3 Absence of the Cover Plate Assembly
RFII SPRINKLER WRENCH • may delay sprinkler operation in a fire
situation.
Page4of4 TFP181
When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT
• nominal 3/32 inch (2,4 mm) air gap CUP / CEILING SEAL
between the lip of the Cover Plate and , BEVEL AS
the ceiling, as shown in Figure 2. This �_�` 1 COVER .,G% /p SHOWN
air gap is necessary for proper opera- I PLATE �/•
tion of the sprinkler. If the ceiling is to ` - RETAINER -
be repainted after the installation of )) � ASSEMBLY
k
the Sprinkler, care must be exercised � _ .../
to ensure that the new paint does NOT ' _
seal off any of the air gap. 4I ! E n + CLEAN
% ' „�, .4 ROOM
Factory painted Cover Plates MUST 1.1- . LIP OF COVER SEAL
NOT be repainted. They should be re — — RETAINER PLATE
placed, if necessary, by factory
painted units. FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result.
Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI-
work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT
it controls, permission to shut down the EQUAL TO THE SALES PRICE.
affected fire protection system must be THE FOREGOING WARRANTY IS
obtained from the proper authorities MADE IN LIEU OF ANY AND ALL
and all personnel who may be OTHER WARRANTIES EXPRESS OF{
by this action must be notified. arrant IMPLIED. INCLUDING WARRANTIES
Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT -
or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR-
must be replaced. Products are warranted solely to the POSE.
Automatic sprinklers must never be original Buyer for ten (10) years
t against defects in material and work-
Au painted, plated, sprinklers must never be
manship when paid for and properly Ordering
altered after leaving the factory. Modi- installed and maintained under normal
fied sprinklers must be replaced. use and service. This warranty will ex- Procedure
Sprinklers that have been exposed to pire ten (10) years from date of ship -
corrosive products of combustion, but ment by Tyco Fire Products. No war- When lacin an order, indicate the full
have not operated, should be replaced rant is given for products
if they cannot be completely cleaned Y product name. Contact your local dis
g P or P g
components manufactured by compa- tributor for availability.
by wiping the sprinkler with a cloth or tY
Hies not affiliated by ownership with
by brushing it with a soft bristle brush. Tyco Fire Products or for products and Sprinkler Assembly:
Care must be exercised to avoid dam- components which have been subject Specify: (SIN), (specify temperature
age to the sprinklers - before, during, to misuse, improper installation, corro- rating) Series RFII Concealed Pen
dent Sprinkler, P/N (specify).
- and after installation. Sprinklers dam- sion, or which have not been installed,
aged by dropping, striking, wrench maintained, modified or repaired in ac-
twist/slippage, or the like, must be re- cordance with applicable Standards of 17 - 1-1 2790 - 1-2
• placed. Also, replace any sprinkler that PP TY35 51-790-1-155 51-790-1-200
P P Y P the National Fire Protection Associa- TY350 4 51- 796-1-155 51- 796-1 -200
has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51 -792 -1 -200
liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate:
reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in
mediately. connection with the sale of products or 135F/57C(a) 165F/74C•(b)
parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165
P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165
The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56- 792 -9 -165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome - .-- --
their fire protection system and de- incomplete information supplied by White 56 56- 792 7928
-0 -135 135 56 56- 792 792 -0 8 -165 165
p y P pp y White (RAL9010)' 56- 792 -3 -135 56- 792 -3 -165
vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165
ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off Wh 56- 792 -5 -135 56- 792 -5 -165
standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Clack 56-792-6-135 56-792-6-165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR custom 56- 792 -X•135 56-792-X-165
addition to the standards of any other UNDER ANY OTHER LEGAL THE- (a) For use with 155F/68C sprinklers.
jurisdiction. The in- (b) For use emi 200F/93C sales spn ly. ers
authorities having 1 ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only.
stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56- 000 -1 -075.
sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
• P/N 56- 908 -1 -001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
•
[Page Too Large for OCR Processing]