Specifications 3u P o -0 3 8'/ • g g 1 5 SW O'VVLO V ck RECEIVED NOV 2 5 2008 CITY OF TIGARD A PROFESSIONAL FIRE SYSTEMS BUILDING DIVISION 17272 S. STEINER ROAD BEAVERCREEK,OR 97004 HYDRAULIC CALCULATIONS FOR Tigard Senior Center Garden Room Addition Room DATE: NOV 18, 2008 - DESIGN DATA - OCCUPANCY CLASSIFICATION: Light Hazard DENSITY: .1 gpm /sq. ft. AREA OF APPLICATION: Largest Room plus 1 Head Flow COVERAGE PER SPRINKLER: 225 sq.ft. Max. NUMBER OF SPRINKLERS CALCULATED: 5 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 133.0 gpm TOTAL WATER REQUIRED (including hose): 133.0 gpm FLOW AND PRESSURE (@ BOR): 133.0 gpm @ 47.7 psi SPRINKLER ORIFICE SIZE: K 5.6 NAME OF CONTRACTOR: A Professional Fire Systems Co. DESIGN /LAYOUT BY: R. Berry AUTHORITY HAVING JURISDICTION: City of Tigard CONTRACTOR CERTIFICATION NUMBER: 41650 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16061181 ) HRS SYSTEMS, INC. TUCKER, GA 30084 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 11/18/2008 C: \RICK'S CALC FILES \TIGARD SENIOR CTR \ROOM.SDF JOB TITLE: Tigard Sr. Center/ Garden Room WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) 10 77.2 77.2 432.7 77.2 133.0 47.7 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 133.0 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 133.0 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 8.0 • K= 5.45 17.0 22.5 2 8.0 K= 5.45 19.1 23.8 3 8.0 - - - - 20.7 - - - 4 8.0 K= 5.45 26.9 28.3 5 8.0 K= 5.45 27.9 28.8 6 8.0 K= 5.45 29.4 29.5 7 8.0 - - - - 29.5 - - - 8 8.0 - - - - 43.1 - - - 9 8.3 - - - - 44.5 - - - 10 1.5 SOURCE 47.7 133.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 11/18/2008 C: \RICK'S CALC FILES \TIGARD SENIOR CTR \ROOM.SDF JOB TITLE: Tigard Sr. Center/ Garden Room PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 1 -22.5 1.049 PL 13.00 PF 2.1 1 8.0 5.5 17.0 22.5 8.4 120 FTG - - -- PE 0.0 2 8.0 5.5 19.1 23.8 0.162 TL 13.00 PV Pipe: 2 -46.3 1.049 PL 0.50 PF 1.5 2 8.0 .5.5 19.1 23.8 17.2 120 FTG E PE 0.0 3 8.0 0.0 20.7 0.0 0.616 TL 2.50 PV Pipe: 3 -46.3 1.049 PL 9.33 PF 8.8 3 8.0 0.0 20.7 0.0 17.2 120 FTG T PE 0.0 7 8.0 0.0 29.5 0.0 0.616 TL 14.33 PV Pipe: 4 -28.3 1.380 PL 9.96 PF 1.0 4 8.0 5.5 26.9 28.3 6.1 120 FTG 2E PE 0.0 5 8.0 5.5 27.9 28.8 0.065 TL 15.96 PV Pipe: 5 -57.1 1.610 PL 13.00 PF 1.5 5 8.0 5.5 27.9 28.8 9.0 120 FTG - - -- PE 0.0 6 8.0 5.5 29.4 29.5 0.112 TL 13.00 PV Pipe: 6 -86.6 1.610 PL 0.50 PF 0.1 6 8.0 5.5 29.4 29.5 13.7 120 FTG - - -- PE 0.0 7 8.0 0.0 29.5 0.0 0.243 TL 0.50 PV Pipe: 7 -133.0 2.067 PL 55.08 PF 13.5 7 8.0 0.0 29.5 0.0 12.7 120 FTG 4ET PE 0.0 8 8.0 0.0 43.1 0.0 0.159 TL 85.08 PV Pipe: 8 -133.0 3.260 PL 66.25 PF 1.6 8 8.0 0.0 43.1 0.0 5.1 120 FTG 2ET2L PE -0.1 9 8.3 0.0 44.5 0.0 0.017 TL 94.45 PV Pipe: 9 -133.0 3.260 PL 6.83 PF 0.2 9 8.3 0.0 44.5 0.0 5.1 120 FTG E PE 3.0 10 1.5 SRCE 47.7 (N /A) 0.017 TL 11.83 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 16061181 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 11/18/2008 C: \RICK'S CALC FILES \TIGARD SENIOR CTR \ROOM.SDF JOB TITLE: Tigard Sr. Center/ Garden Room (2) The system has been calculated to provide an average • imbalance at each node of 0.012 gpm and a maximum imbalance at any node of 0.111 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 17.2 ft /sec at pipe 3. (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD.PIP PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 5.00 1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 10.00 10.00 8.00 2.067 5.00 10.00 3.00 11.00 6.00 1.00 10.00 10.00 10.00 PAGE: B MATERIAL: THNWL HWC: 120 Diameter Equivalent Fitting Lengths in Feet - (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee - 3.260 5.00 13.00 2.60 22.00 14.00 1.00 18.00 18.00 20.00 - O > W tTi WATER SUPPLY ANALYSIS H •• 100.0 Static: 77.23 psi Resid: 77.20 psi Flow: 432.7 gpm y LEGEND r I tam Available pressure 1-■ m 1 77.23 psi @ 133.0 gpm H Required pressure ~' N G 2 47.71 psi @ 133.0 gpm W o A 80.0 A. Source Supply Curve °D B. System Demand Curve U 0 m G • ▪ m ro E n 70 a) I a z rt x 8 60.0 nnm � 70 E o m m S a 1-11-< 2 o x y m - tJ U m 3 840.0 0 > K E o r • n m ( H r p r H th n S m i20.0 y z o � K m m v H m m tJ z 0.0 B 0 m n H -14.7 I I I I I I I I o 200 300 400 500 600 700 800 900 1000 0 FLOW (GPM) �n m ro • � SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 11/18/2008 C: \RICK'S CALC FILES \TIGARD SENIOR CTR \ROOM.SDF JOB TITLE: Tigard Sr. Center/ Garden Room WATER SUPPLY CURVE 84+ 77 * \0 \ \ \ \ \ \ \ \ \ \ \* < -77.2 psi @ 433 gpm Flow Test Point 70+ 63+ P 56+ R I E I S I S 49+ U I X R I E I 42+ ( I P I S I I 35+ I 28+ 21+ • 14+ LEGEND I If I X = Required Water Supply 47.71 psi @ 133.0 gpm 7+ I 0 = Available Water Supply " I 77.23 psi @ 133.0 gpm I! I " 0 + +- +--- + - - - -+ + + + + + + SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 11/18/2008 C: \RICK'S CALC FILES \TIGARD SENIOR CTR \ROOM.SDF JOB TITLE: Tigard Sr. Center/ Garden Room 200 300 400 500 600 700 800 900 1000 FLOW (GPM) ti,co Fire & Building 1 VE� Products RE CE 8 AD OV Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 CO "a -1 % v $1 0IN Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General tamed when exposed to corrosive at- mospheres. Although corrosion resis- ;-_;... tant coated sprinklers have passed the . " A•r >, Description standard corrosion tests of the appli- _ �': tea '' cable approval agencies, the testing is ;J-- - #*•+.,,.k eilii The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor- 5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it ', .- . dent Sprinklers described in this data is recommended that the end user be sheet are quick response - standard consulted with respect to the suitability coverage, decorative 3 mm glass bulb of these coatings for any given corro- type spray sprinklers designed for use sive environment. The effects of ambi- = in light or ordinary hazard, commercial ent temperature, concentration of occupancies such as banks, hotels, chemicals, and gas /chemical velocity, shopping malls, etc. should be considered, as a minimum, The recessed version of the Series along with the corrosive nature of the TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be plicable, is intended for use in areas exposed. ... ( , with a finished ceiling. It uses either a An intermediate level versions of the two-piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet - '� cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 .., � • (19,1 mm) of total adjustment from the • flush pendent position, or a two-piece WARNINGS Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers d N.,..„.. _ ' inch NPT) Recessed Escutcheon with scribed herein must be installed and � '., ' - 1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica- total adjustment from the flush pen- ble standards of the National Fire Pro- dent position. The adjustment pro- tection Association, in addition to the vided by the Recessed Escutcheon re- standards of any other authorities hay- Model/Sprinkler duces the accuracy to which the fixed ing jurisdiction. Failure to do so may pipe drops to the sprinklers must be impair the performance of these de- Identification cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain- Numbers applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT manufacturer should be contacted TY2131 - Upright 4.2K, 112 "NPT IMPORTANT with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT TY3131 - Upright 5.6K, 1/2 "NPT Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT Sheet TFP700 for the °INSTALLER TY4131 - Upright 8.0K, 3/4 "NPT WARNING that provides cautions TY4231 - Pendent 8.0K, 3/4 "NPT with respect to handling and instal - TY4831- Upright 8.0K, 1/2 "NPT lation of sprinkler systems and corn- TY4931- Pendent 8.0K, 1/2"NPT ponents. Improper handling and in- - stallation can permanently damage a sprinkler system or its compo- , nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.